InspectAPedia.com InspectAPedia®
Google
InspectAPedia
 

Free Encyclopedia of Building & Environmental Inspection, Testing, Diagnosis, Repair

Ask a Question or Search InspectAPedia

  • HOME
  • AIR CONDITIONING
  • ELECTRICAL
  • EXTERIORS
  • HEATING
  • HOME INSPECTION
  • INTERIORS
  • PLUMBING
  • ROOFING
  • SEPTIC SYSTEMS
  • STRUCTURE
  • WATER SUPPLY
  • ENERGY SAVINGS
  • ENVIRONMENT
  • INDOOR AIR IAQ
  • INSULATION
  • MOLD INSPECT TEST REMOVE
  • NOISE
  • ODORS
  • SOLAR ENERGY
  • VENTILATION
  • EXPERTS DIRECTORY
  • CONTACT US



Mobile Phone/PDA website viewMobile View
BUILDING INTERIORS

ACOUSTICAL SEALANT CHOICES
AGE of a BUILDING - how to determine
AIR POLLUTANTS, COMMON INDOOR
AIR SEALING STRATEGIES
ANIMAL ALLERGENS
ANTI SCALD VALVES
APPLIANCE EFFICIENCY RATINGS
ARCHITECTURE & BUILDING COMPONENT ID
ASBESTOS IDENTIFICATION IN buildings
ATTIC LEAKS, CONDENSATION & MOLD
ATTIC VENTILATION

BASEMENT CEILING VAPOR BARRIER
BASEMENT HEAT LOSS
BASEMENT WATERPROOFING
BATH & KITCHEN DESIGN GUIDE
  Bath & Kitchen Associations, Product Sources
  BATHROOM DESIGN
  Bathroom Design, Accessible
  Bathroom Ventilation
  CABINETS & COUNTERTOP DEFECTS
  CABINET CHOICES, Bath / Kitchen
  CEMENT BACKERBOARD Installation
  COUNTERTOPS, KITCHEN
  FAUCETS, Kitchen & Bathroom
  FLOOR DESIGN, Kitchen & Bathroom
  FLOOR ENGINEERED WOOD & LAMINATES
  FLOOR FRAMING & SUBFLOOR for TILE
  Floor, Stone, Granite, Marble, Agglomer
  Floor Tile, Ceramic for K & B
  Floor Tile Sealers, Ceramic/Stone
  Floor Tile Over Concrete Slabs
  Floor Tile Setting Compounds
  GROUT Installation, Tile
  KITCHEN CABINET DESIGN Guide
  KITCHEN DESIGN Principles
  Kitchen Design, Accessible
  KITCHEN LAYOUTS, Typical
  Kitchen Ventilation
  PLUMBING FIXTURES
  SCALD PROTECTION
  SHOWER PANS
  SPAS, Whirlpools, Soaking & Jetted Tubs
  Spa, Whirlpool, Soaking & Jetted Tub Installation
  TILE INSTALLATION DETAILS
  TOILET TYPES, Design Choices
  Toilet Installation Procedures
  TUBS & Tub/Shower Units
BATHROOM VENTILATION
BEST CONSTRUCTION PRACTICES GUIDE
Best Interior Finish Practices
BLOWER DOORS & AIR INFILTRATION
BLOWN-IN INSULATION
BOOKSTORE - INTERIORS
BRICK LINED WALLS
BRICK VENEER WALL INSULATION
BRICK VENEER WALL Loose, Bulged
BRICK WALL DRAINAGE WEEP HOLES
BUCKLED FOUNDATIONS due to INSULATION?
BUILDING SAFETY HAZARDS GUIDE
BUILDING NOISE DIAGNOSIS & CURE

CABINETS & COUNTERTOPS
CARPETING & INDOOR AIR QUALITY
CARPETING, SELECTION & INSTALLATION
CASEWORK, CABINETS, SHELVING INSTALLATION
CATHEDRAL CEILING INSULATION
CATHEDRAL CEILING VENTILATION
CEILING FINISHES INTERIOR
CEILINGS, DROP or SUSPENDED PANEL
CEILINGS, PLASTER TYPES
CERAMIC TILE FLOOR, WALL
CERAMIC TILE, ASBESTOS in?
CHIMNEY INSPECTION DIAGNOSIS & REPAIR
CHINESE DRYWALL HAZARDS
CLOGGED DRAIN DIAGNOSIS & REPAIR
COMBUSTION AIR for TIGHT buildings
CONDENSATION or SWEATING PIPES, TANKS
COOLING LOAD REDUCTION by ROOF VENTS
CRAWL SPACES

DEW POINT CALCULATION for WALLS
DOORS, INTERIOR
DRYWALL HAZARDS, CHINESE
DRYWALL INSTALLATION Best Practices
DRYWALL MOLD
DRYWALL MOLD RESISTANT

EARTHQUAKE DAMAGED FOUNDATIONS
EFFLORESCENCE, Salts & White / Brown Deposits
ELDERLY & VETERANS HOME SAFETY
ELECTRICAL INSPECTION, DIAGNOSIS, REPAIR
ENERGY SAVINGS in buildings
ENGINEERED WOOD Flooring
ENGINEERED WOOD Products
EXTERIOR WALL SIDING TRIM & FINISHES

FIBERGLASS INSULATION
FIBERGLASS HAZARDS
FLAT ROOF MOISTURE & CONDENSATION
FLOOD DAMAGE ASSESSMENT, SAFETY & CLEANUP
FLOOR TYPES & DEFECTS
FORMALDEHYDE HAZARDS
FOOTING & FOUNDATION DRAINS
FOUNDATION CRACKS & DAMAGE GUIDE
FOUNDATION WATERPROOFING
FRENCH DRAINS
FRAMING DETAILS for BETTER INSULATION
FREEZE-PROOF A BUILDING
FROST HEAVES, FOUNDATION, SLAB
FUNGICIDAL SPRAY & SEALANT USE GUIDE

GAS EXPOSURE LIMITS & STANDARDS

HEAT LOSS in buildings
HEATING COST SAVINGS METHODS
HOT ROOF DESIGNS: Un-Vented Roof Solutions
HOT WATER HEATERS
HOUSEWRAP AIR & VAPOR BARRIERS
HOUSE DOCTOR, how-to be
HUMIDITY LEVEL TARGET

ICE DAM PREVENTION
INDOOR AIR QUALITY & HOUSE TIGHTNESS
INDOOR AIR QUALITY IMPROVEMENT GUIDE
INSULATION INSPECTION & IMPROVEMENT

KIT HOMES, Aladdin, Sears, Wards, Others
KITCHEN & BATH DESIGN GUIDE

LIGHTING, EXTERIOR GUIDE
LIGHTING, INTERIOR GUIDE
LIGHTNING PROTECTION SYSTEMS
LOW VOLTAGE BUILDING WIRING
LOG HOME GUIDE

METAL LATH, PLASTER & STUCCO
MIXING / ANTI-SCALD VALVES
MOBILE HOME INSPECTIONS
MOISTURE CONTROL in BUILDINGS
MOLD INFORMATION CENTER

NOISE / SOUND DIAGNOSIS & CURE
NOISE CONTROL for FLOORS
NOISE CONTROL for PLUMBING
NOISE, PLUMBING DRAIN DIAGNOSIS
NOISE, PLUMBING DRAIN REPAIR
NOISE, WATER HEATER
NOISES, WATER PUMP

ODORS GASES SMELLS, DIAGNOSIS & CURE
ODORS IN WATER
ODORS, SEPTIC or SEWER
ODORS, SULPHUR SMELL SOURCES
ODORS, URINE REMOVAL
OIL FIRED WATER HEATERS
OUTHOUSES & LATRINES

PAINT FALURE, DIAGNOSIS, CURE, PREVENTION
PIPING IN buildings, Clogs Leaks Types
PLASTER & BEAVERBOARD & DRYWALL
PLASTER BULGES & PILLOWS
PLASTER LATH, METAL
PLASTER TYPE IDENTIFICATION
PLASTER VENEER Best Practices
PLUMBING FIXTURES, KITCHEN, BATH
Plumbing Materials & Fixtures, Age, Types
PLASTIC HEATER VENT
PLASTIC PIPING
PUMPS & WELLS

RADIANT BARRIERS
RADIANT HEAT
RANGE BOILERS
RELIEF VALVES - TP Valves on Boilers
RELIEF VALVES - STEAM TP VALVES
RELIEF VALVES - Water Heaters
RELIEF VALVES - Water Tanks
ROOF VENTILATION SPECIFICATIONS
ROT, FUNGUS, TERMITES

SAFETY HAZARDS & INSPECTIONS
SAFETY: Elderly & Veterans Home Safety
SEARS KIT HOUSES
SEPTIC SYSTEM INSPECT DIAGNOSE REPAIR
SEPTIC METHANE GAS
SEPTIC ODORS
SEPTIC PUMPS
SEPTIC SYSTEM ODORS
SEPTIC & CESSPOOL SAFETY
SEWAGE BACKUP, WHAT TO DO
SEWAGE BACKUP PREVENTION
SEWAGE CONTAMINATION in buildings
SEWAGE EJECTOR / GRINDER PUMPS
SEWAGE PUMPS
SEWER GAS ODORS
SEWER LINE REPLACEMENT
SULPHUR & SEWER GAS SMELL SOURCES
SLAB CRACK EVALUATION
SOUND CONTROL in buildings
STAIN DIAGNOSIS on BUILDING EXTERIORS
STAIN DIAGNOSIS on BUILDING INTERIORS
STAINS & FINISHES, INTERIOR
STAIRS, RAILINGS, LANDINGS, RAMPS
STUCCO WALL METHODS & INSTALLATION
SUMP PUMPS GUIDE
SWEATING (CONDENSATION) on PIPES, TANKS

THERMAL MASS in buildings
THERMAL TRACKING Indicates Heat Loss
TOILETS, INSPECT, INSTALL, REPAIR
TOILET ALTERNATIVES
TOILET FLUSHOMETER VALVES
TOILET INSTALLATION PROCEDURE
TOILET OVERFLOW EMERGENCY
TOILET PLUGS, SEWER BACKUP
TOILET REPAIR GUIDE
TOILET TISSUE CHOICES
TOILET TISSUE TEST
TOILET TYPES
Toilet Types, Flush Methods
TOILETS, DON'T FLUSH LIST
TRAPS on PLUMBING FIXTURES
TRIM, EXTERIOR CHOICES, INSTALLATION
TRIM, INTERIOR
TRIM, INTERIOR INSTALLATION

VAPOR BARRIERS & CONDENSATION in BUILDINGS
VENTILATION in buildings
VINYL Siding or PLASTIC Window ODORS in buildings
VINYL CHLORIDE HEALTH INFO

WALL SIDING TRIM & FINISHES
WALL FINISHES INTERIOR
WATER BARRIERS, EXTERIOR BUILDING
WATER ENTRY in buildings
WATER HEATERS
WATER PRESSURE & FLOW MEASUREMENT
WATER PRESSURE GAUGE ACCURACY
WATER PRESSURE LOSS DIAGNOSIS & REPAIR
WATER PRESSURE PROBLEM DIAGNOSIS TABLE
WATER PRESSURE REPAIRS & COSTS
WATER PUMPS, TANKS, TESTS, WELLS, REPAIRS
WATER PUMPS, TANKS, WELLS - BASICS
WATER PUMP TYPES & LIFE EXPECTANCY
WATER PURIFIERS
WATER QUALITY TESTS, CONTAMINANTS, TREATMENT
WATER QUANTITY IMPROVEMENT
WATER QUANTITY USAGE GUIDE
WATER SOFTENERS & CONDITIONERS
WATER SUPPLY & DRAIN PIPING
WATER TANK TYPES: WATER, OIL, EXPANSION, ALL
WATER TANK AIR, HOW TO ADD
WATER TANK REPAIRS
WATER TESTS, CONTAMINANTS, TREATMENT
WATER ODORS, CAUSE CURE
WATER PUMPS & WELLS
WATER SOFTENERS & CONDITIONERS
WATER TREATMENT EQUIPMENT CHOICES
WELLS CISTERNS & SPRINGS
WINTERIZE A BUILDING
WOOD Burning Heaters Fireplaces Stoves

More Information

Figure 6-13: Clear Floor Space required in kitchens (C) J Wiley, S Bliss Kitchen Layout & Design Principles
InspectAPedia®  -      

  • Kitchen Design & Layout Guidelines: best practices
  • List of types of work centers in kitchens
  • Space and clearance requirements for kitchen work centers & activities: dishwasher, sink, food prep, recycling, cooktop, oven landing area, microwave, refrigerator work areas.
  • Clearances for kitchen walkways, work aisles
  • Kitchen cabinet frontage recommendations
  • Layout of the kitchen work triangle, two-cook kitchen layout
  • Kitchen counter size, layout specifications
  • Kitchen lighting, natural
  • Questions & answers about principles of kitchen layout & design

Kitchen layout & design principles: this article explains the basic principles of kitchen layout and design, including the layout and clearances for different types of kitchen activities or work centers, and kitchen layouts for one and two-cook kitchens. This article series discusses current best design practices for kitchens and bathrooms, including layout, clearances, work space, and accessible kitchen and bathroom layout, clearances, turning space, grab bars, controls, etc. We include advice on choosing and installing kitchen countertops, cabinets, and kitchen or bathroom flooring, sinks, and other plumbing fixtures and fixture controls such as faucets. A list of kitchen and bath product manufactures and sources is included.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers nor with topics or services discussed at this website.

© Copyright 2012 InspectAPedia.com, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use page top links to major topics or use links at the left of each page to navigate within topics and documents at this website. Green links show where you are in a document series or at this website.

Kitchen and Bath Best Design Practices

As detailed in Chapter 6 of Best Practices Guide to Residential Construction:

Kitchen Design Basics

Whether designing a small galley kitchen or an expansive space for multiple cooks and entertaining, the same rules apply regarding clearances and relationships between key work centers so that work in the kitchen flows smoothly and efficiently.

While the traditional American kitchen developed around three main appliances—the sink, range, and refrigerator—today’s kitchen may have many more centers of activity, including the following list adapted from the National Kitchen and Bath Association (NKBA):

  • Primary clean-up center: Includes the main sink, dishwasher, recycling center, and waste disposer.
  • Secondary sink center: May also serve cleanup functions. Often associated with the food preparation center.
  • Food preparation center: A clear space at least 16x36 inches typically located between the sink and cooktop or sink and refrigerator. A two-cook kitchen requires two such spaces.
  • Cooking center: Revolves around the cooktop and may also include a separate built-in oven or microwave.
  • Microwave center: Because of its frequent use, this should be near the main activity areas.
  • Pantry center: Tall storage cabinets work well to store food and cooking supplies near the preparation area. Tall cabinets may also store dishes in the serving or dining area.
  • Serving center: This area stores dishes and other serving items and may be in the kitchen or closer to the dining area.
  • Dining center: Many kitchens include either an eating counter or a separate dining area.
  • Socializing center: A casual seating area adjacent to the kitchen work space allows other family members or friends to visit and socialize with the cook.
  • Home office center: A space for the telephone, mail, household records, and cookbooks is often incorporated into the kitchen. Concealing the desktop visually from the kitchen is appreciated by many clients. (List adapted with permission from John Wiley & Sons from Essential Kitchen Design Guide, © NKBA, 1996.)

Kitchen Design Guidelines

In 1992, the National Kitchen and Bath Association (NKBA) introduced new design guidelines based on research conducted at the University of Minnesota. These have been expanded and revised over time to reflect the continuing evolution of kitchen design and usage.

The key kitchen design rules are shown below. Accessibility recommendations are listed separately here, but they are now incorporated into all NKBA guidelines.

Kitchen Walkways and Kitchen Work Aisles

Figure 6-1: Kitchen & Bath Design (C) J Wiley S Bliss


Kitchen work aisles with counters or appliances on both sides should be at least 42 inches wide for a one-cook kitchen and 48 inches wide for a two-cook kitchen.

Walkways in kitchens, which may have a work counter on one side, should be at least 36 inches wide and should not cross the work triangle (see Figure 6-1).

[Click any image or table to see an enlarged version with additional detail, commentary & source citation.]

Kitchen Work Triangle Specifications

The shortest walking distance between the refrigerator, primary sink, and primary cooktop should be 26 feet or less, as shown in Figure 6-1 above. Each leg of the triangle should range from 4 to 9 feet long. No major walkway should pass though the triangle, and no corner of an island or peninsula should intersect the triangle by more than 12 inches.

Two-Cook Kitchen Work Triangles

Figure 6-1: Kitchen & Bath Design (C) J Wiley S Bliss

 

In a two-cook kitchen, each person should have his or her own work triangle of less than 26 feet.

The two kitchen work triangles may share a leg, but they should not cross one another (Figure 6-2).

Conflicting Kitchen Entry, Appliance, Cabinet Doors

All entry doors, appliance doors, and cabinet doors should swing freely without interfering with another door.

Kitchen Cabinet Frontage Recommendations

Figure 6-1: Kitchen & Bath Design (C) J Wiley S Bliss

Provide the minimum cabinet frontage shown in Table 6-1 at left.

Do not count difficult-to-reach wall cabinets over hoods or refrigerators unless special access is provided.

A pie-cut lazy Susan base counts as 30 inches.

Tall cabinets 72 inches or higher can count as either base or wall cabinets as follows: for 12-inch-deep cabinets, multiply frontage by one to count as base cabinets and by 2 to count as wall cabinets.

Double these amounts for 21- to 24-inch-deep tall cabinets.

Kitchen Counter Heights and Edge Specifications

Provide at least two counter heights in the kitchen with one 28 to 36 inches high and the other 36 to 45 inches high. Varied heights create work spaces for various tasks and for cooks of different heights, including seated cooks. Also, clip or round over countertop corners and edges to eliminate sharp edges.

Dishwasher Work Center Location

Figure 6-1: Kitchen & Bath Design (C) J Wiley S Bliss

 

Locate the dishwasher within 36 inches of the sink and allow at least 21 inches of clearance between the dishwasher and any counters, cabinets, or appliances placed at a right angle to the dishwasher.

If possible, allow 30 inches of clear floor space on each side of the dishwasher so two people can work at the same time (Figure 6-3).

Kitchen Sink Work Center Location

Locate the primary sink between or across from the cooking surface, food preparation area, or refrigerator (Figure 6-4).

Figure 6-1: Kitchen & Bath Design (C) J Wiley S Bliss
  • Counter space: Allow 24 inches on one side of the sink and 18 inches on the other.

    If the sink is within 3 to 18 inches of a corner, provide at least 21 inches of additional space on the return counter.
  • Cabinet space: Provide at least 60 inches of wall cabinet frontage within 72 inches of the primary sink centerline.

    Alternate: Use one tall cabinet within 72 inches of the sink.
  • Floor space: A 30x48–inch floor space centered in front of the sink will make it wheelchair accessible. Secondary Sinks.

    Provide a minimum of 3 inches of countertop frontage on one side of a secondary sink and at least 18 inches on the other side.

Food Preparation Area Specifications

Figure 6-1: Kitchen & Bath Design (C) J Wiley S Bliss

 

Provide 36 inches of continuous countertop, at least 16 inches deep, immediately adjacent to a sink.

For a two-cook kitchen, provide either two separate 36-inch spaces or one 72-inch space adjacent to a sink (see Figure 6-5).

Recycling Center Area Specifications for Kitchens

Unless provided elsewhere in the plan, provide at least two waste receptacles in the kitchen, one for garbage and one for recyclables.

Cooktop Work Center Design Specifications

Figure 6-1: Kitchen & Bath Design (C) J Wiley S Bliss
  • Counter space: Provide 15 inches on one side of the cooktop and 9 inches on the other. Or if placed against an end wall, leave at least 3 inches of clearance to the wall and cover it with a flame-retardant material. Where there is no backsplash, as in an island or peninsula, provide a minimum of 9 inches behind the cooktop for safety reasons (Figure 6-6).
  • Clearances: Allow at least 24 inches of clearance between a cooking surface and a protected surface above, such as a range hood, or 30 inches to an unprotected surface.
  • Ventilation: Ventilate all major appliance cooking surfaces with a minimum 150 cfm exhaust fan. Gas appliances must vent to the exterior.

Oven Landing Space Needed in Kitchens

Provide at least 15 inches of landing space, a minimum of 16 inches deep, next to or above the oven. If the oven does not open into a traffic area, the landing space can be directly across from the oven by no more than 48 inches.

Microwave Work Center Measurements

Locate stand-alone microwave ovens so that the bottom of the appliance is 24 to 48 inches above the floor. Provide at least 15 inches of landing space, a minimum of 16 inches deep above, below, or to the side of the microwave oven.

Refrigerator Work Center Specifications

Figure 6-1: Kitchen & Bath Design (C) J Wiley S Bliss

 

Provide at least 15 inches of counter space as a “landing area” adjacent to the handle side of the refrigerator or on both sides of a sideby- side refrigerator.

Alternately, provide 15 inches of countertop directly across from the refrigerator and no more than 48 inches away.

With a side-by-side unit, provide easy access to a counter from the fresh food side (Figure 6-7).

Overlapping Work Centers

Where countertop areas of two work centers (e.g., sink, refrigerator, food preparation) overlap, the minimum counter frontage between the centers should equal the longest of the required two lengths plus 12 inches.

Tall Cabinets Between Work Centers

Do not separate two primary work centers (primary sink, refrigerator, preparation area, or cooking center) by a full-height, fulldepth tower such as an oven cabinet, pantry cabinet, or refrigerator. One exception is a corner-recessed tall tower if knee space is planned to one side.

Kitchen Eating Area Design Specifications

Figure 6-1: Kitchen & Bath Design (C) J Wiley S Bliss
  • Eating counter heights. Heights and capacities for tables, eating counters, and bars are shown in Figure 6-8.
  • Seating widths have been increased to 30 inches in the 30-inch-high seating area to accommodate wheelchairs.

Figure 6-1: Kitchen & Bath Design (C) J Wiley S Bliss
  • Clearances to walls. Allow a minimum clearance of 36 inches from the edge of a counter or table to a wall or obstruction. Increase this to 65 inches if the space also serves as a walkway (Figure 6-9).

Figure 6-1: Kitchen & Bath Design (C) J Wiley S Bliss
  • Table sizes. Many kitchens feature small or full-size dining tables (Table 6-1).
  • When selecting a table, pay close attention to whether leg placement will interfere with the number of chairs planned.

Kitchen Wiring for Use of Electrical Devices

Install ground-fault circuit interrupters (GFCIs) on all receptacles within the kitchen. Locate wall-mounted room controls, including electrical receptacles, switches, thermostats, telephones, and intercoms, between 15 to 48 inches above the finished floor.

Home Kitchen Fire Protection Advice

A fire extinguisher should be visibly located in the kitchen away from cooking equipment and 15 to 48 inches above the floor. Smoke alarms should be installed near the kitchen.

Natural Lighting for Kitchens

The combined area of windows and skylights should equal at least 10% of the square footage of the kitchen. Also, every work surface should be well illuminated by appropriate task or general lighting. (see Kitchen Lighting Requirements).

Kitchen and Bath Product Manufacturers, Sources, Associations

Association of Home Appliance Manufacturers(AHAM) www.aham.org

National Kitchen and Bath Association (NKBA) www.nkba.org

Ceramic Tile Institute of America www.ctioa.org

Home Ventilation Institute (HVI) www.hvi.org

Marble Institute of America www.marble-institute.com Porcelain Enamel Institute (PEI) www.porcelainenamel.com

Tile Council of America (TCA) www.tileusa.com

-- Adapted with permission from Best Practices Guide to Residential Construction.

Questions & Answers regarding this article

Questions & answers about principles of kitchen & bathroom design.

Ask a Question or Search InspectAPedia

HTML Comment Box is loading comments...

Recommend / Share this Article            

...

Technical Reviewers & References

  • InspectAPedia.com® - Daniel Friedman - Publisher & Editor.
  • Steven Bliss served as editorial director and co-publisher of The Journal of Light Construction for 16 years and previously as building technology editor for Progressive Builder and Solar Age magazines. He worked in the building trades as a carpenter and design/build contractor for more than ten years and holds a masters degree from the Harvard Graduate School of Education. Excerpts from his recent book, Best Practices Guide to Residential Construction, Wiley (November 18, 2005) ISBN-10: 0471648361, ISBN-13: 978-0471648369, appear throughout this website, with permission and courtesy of Wiley & Sons. Best Practices Guide is available from the publisher, J. Wiley & Sons, and also at Amazon.com.
  • InspectAPedia Bookstore lists recommended books, organized by topic & available for purchase. Most of our articles also include a list of recommended books for the specific article topic as well as other references, and information sources.
  • Critique, contributions wanted: Contact Us to suggest corrections or additions to articles at this website, and if you wish, to receive online listing and credit as a contributor. Particular thanks are due to the many experts and also consumers who read and critique technical articles at InspectAPedia.com.
  • Additional technical contributors & reference sources for this article are listed below.

Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

BATH & KITCHEN DESIGN GUIDE - see detailed links at page left

  • Best Practices Guide to Residential Construction, by Steven Bliss. John Wiley & Sons, 2006. ISBN-10: 0471648361, ISBN-13: 978-0471648369, Hardcover: 320 pages, available from Amazon.com and also Wiley.com. See our book review of this publication.

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.
  • Best Practices Guide to Residential Construction, by Steven Bliss. John Wiley & Sons, 2006. ISBN-10: 0471648361, ISBN-13: 978-0471648369, Hardcover: 320 pages, available from Amazon.com and also Wiley.com. See our book review of this publication.
  • Home Reference Book - Carson Dunlop The Home Reference Book - the Encyclopedia of Homes, Carson Dunlop & Associates, Toronto, Ontario, 2010, $69.00 U.S., is available from Carson Dunlop, and from the InspectAPedia bookstore. The 2010 edition of the Home Reference Book is a bound volume of more than 450 illustrated pages that assist home inspectors and home owners in the inspection and detection of problems on buildings. The text is intended as a reference guide to help building owners operate and maintain their home effectively. InspectAPedia.com ® author/editor Daniel Friedman is a contributing author. Field inspection worksheets are included at the back of the volume.
  • "The Elimination of Unsafe Guardrails, a Progress Report," Elliott O. Stephenson, Building Standards, March-April 1993
  • "Are Functional Handrails Within Our Grasp" Jake Pauls, Building Standards, January-February 1991
  • Access Ramp building codes:
    • UBC 1003.3.4.3
    • BOCA 1016.3
    • ADA 4.8.2
    • IBC 1010.2
  • Access Ramp Standards:
    • ADA (Americans with Disabilities Act), Public Law 101-336. 7/26/90 is very often cited by other sources for good design of stairs and ramps etc. even where disabled individuals are not the design target.
    • ANSI A117.4 Accessible and Usable buildings and Facilities (earlier version was incorporated into the ADA)
    • ASTM F 1637, Standard Practice for Safe Walking Surfaces, (Similar to the above standards)
  • America's Favorite Homes, mail-order catalogues as a guide to popular early 20th-century houses, Robert Schweitzer, Michael W.R. Davis, 1990, Wayne State University Press ISBN 0814320066 (may be available from Wayne State University Press)
  • American Plywood Association, APA, "Portland Manufacturing Company, No. 1, a series of monographs on the history of plywood manufacturing",Plywood Pioneers Association, 31 March, 1967, www.apawood.org
  • ASHRAE resource on dew point and wall condensation - see the ASHRAE Fundamentals Handbook, available in many libraries. The following three ASHRAE Handbooks are also available at the InspectAPedia bookstore in the third page of our Insulate-Ventilate section:
    • 2005 ASHRAE Handbook : Fundamentals : Inch-Pound Edition (2005 ASHRAE HANDBOOK : Fundamentals : I-P Edition) (Hardcover), Thomas H. Kuehn (Contributor), R. J. Couvillion (Contributor), John W. Coleman (Contributor), Narasipur Suryanarayana (Contributor), Zahid Ayub (Contributor), Robert Parsons (Author), ISBN-10: 1931862702 or ISBN-13: 978-1931862707
    • 2004 ASHRAE Handbook : Heating, Ventilating, and Air-Conditioning: Systems and Equipment : Inch-Pound Edition (2004 ASHRAE Handbook : HVAC Systems and Equipment : I-P Edition) (Hardcover)
      by American Society of Heating, ISBN-10: 1931862478 or ISBN-13: 978-1931862479
      "2004 ASHRAE Handbook - HVAC Systems and Equipment The 2004 ASHRAE HandbookHVAC Systems and Equipment discusses various common systems and the equipment (components or assemblies) that comprise them, and describes features and differences. This information helps system designers and operators in selecting and using equipment. Major sections include Air-Conditioning and Heating Systems (chapters on system analysis and selection, air distribution, in-room terminal systems, centralized and decentralized systems, heat pumps, panel heating and cooling, cogeneration and engine-driven systems, heat recovery, steam and hydronic systems, district systems, small forced-air systems, infrared radiant heating, and water heating); Air-Handling Equipment (chapters on duct construction, air distribution, fans, coils, evaporative air-coolers, humidifiers, mechanical and desiccant dehumidification, air cleaners, industrial gas cleaning and air pollution control); Heating Equipment (chapters on automatic fuel-burning equipment, boilers, furnaces, in-space heaters, chimneys and flue vent systems, unit heaters, makeup air units, radiators, and solar equipment); General Components (chapters on compressors, condensers, cooling towers, liquid coolers, liquid-chilling systems, centrifugal pumps, motors and drives, pipes and fittings, valves, heat exchangers, and energy recovery equipment); and Unitary Equipment (chapters on air conditioners and heat pumps, room air conditioners and packaged terminal equipment, and a new chapter on mechanical dehumidifiers and heat pipes)."
    • 1996 Ashrae Handbook Heating, Ventilating, and Air-Conditioning Systems and Equipment: Inch-Pound Edition (Hardcover), ISBN-10: 1883413346 or ISBN-13: 978-1883413347 ,
      "The 1996 HVAC Systems and Equipment Handbook is the result of ASHRAE's continuing effort to update, expand and reorganize the Handbook Series. Over a third of the book has been revised and augmented with new chapters on hydronic heating and cooling systems design; fans; unit ventilator; unit heaters; and makeup air units. Extensive changes have been added to chapters on panel heating and cooling; cogeneration systems and engine and turbine drives; applied heat pump and heat recovery systems; humidifiers; desiccant dehumidification and pressure drying equipment, air-heating coils; chimney, gas vent, fireplace systems; cooling towers; centrifugal pumps; and air-to-air energy recovery. Separate I-P and SI editions."
    • Principles of Heating, Ventilating, And Air Conditioning: A textbook with Design Data Based on 2005 AShrae Handbook - Fundamentals (Hardcover), Harry J., Jr. Sauer (Author), Ronald H. Howell, ISBN-10: 1931862923 or ISBN-13: 978-1931862929
  • Best Practices Guide to Residential Construction, by Steven Bliss. John Wiley & Sons, 2006. ISBN-10: 0471648361, ISBN-13: 978-0471648369, Hardcover: 320 pages, available from Amazon.com and also Wiley.com. See our book review of this publication.
  • Building Research Council, BRC, nee Small Homes Council, SHC, School of Architecture, University of Illinois at Urbana-Champaign, brc.arch.uiuc.edu. "The Small Homes Council (our original name) was organized in 1944 during the war at the request of the President of the University of Illinois to consider the role of the university in meeting the demand for housing in the United States. Soldiers would be coming home after the war and would be needing good low-cost housing. ...  In 1993, the Council became part of the School of Architecture, and since then has been known as the School of Architecture-Building Research Council. ... The Council's researchers answered many critical questions that would affect the quality of the nation's housing stock.
    • How could homes be designed and built more efficiently?
    • What kinds of construction and production techniques worked well and which did not?
    • How did people use different kinds of spaces in their homes?
    • What roles did community planning, zoning, and interior design play in how neighborhoods worked
  • The Circular Staircase, Mary Roberts Rinehart
  • Energy Savers: Whole House Systems Approach to Energy Efficient Home Design [copy on file as /interiors/Whole_House_Energy_Efficiency_DOE.pdf ] - U.S. Department of Energy
  • "Energy Savers: Whole-House Supply Ventilation Systems [copy on file as /interiors/Energy_Savers_Whole-House_Supply_Vent.pdf ] - ", U.S. Department of Energy energysavers.gov/your_home/insulation_airsealing/index.cfm/mytopic=11880?print
  • "Energy Savers: Whole-House Exhaust Ventilation Systems [copy on file as /interiors/Energy_Savers_Whole-House_Exhaust.pdf ] - ", U.S. Department of Energy energysavers.gov/your_home/insulation_airsealing/index.cfm/mytopic=11870
  • "Energy Savers: Ventilation [copy on file as /interiors/Energy_Savers_Ventilation.pdf ] - ", U.S. Department of Energy
  • "Energy Savers: Natural Ventilation [copy on file as /interiors/Energy_Savers_Natural_Ventilation.pdf ] - ", U.S. Department of Energy
  • "Energy Savers: Energy Recovery Ventilation Systems [copy on file as /interiors/Energy_Savers_Energy_Recovery_Venting.pdf ] - ", U.S. Department of Energy energysavers.gov/your_home/insulation_airsealing/index.cfm/mytopic=11900
  • "Energy Savers: Detecting Air Leaks [copy on file as /interiors/Energy_Savers_Detect_Air_Leaks.pdf ] - ", U.S. Department of Energy
  • "Energy Savers: Air Sealing [copy on file as /interiors/Energy_Savers_Air_Sealing_1.pdf ] - ", U.S. Department of Energy
  • Gypsum Construction Guide, National Gypsum Corporation
  • Gypsum Construction Handbook [purchase at Amazon.com] H17, Technical Folder SA920 and PM2, PM3 and PM4, United States Gypsum Company, 125 South Franklin ST., PO Box 806278, Chicago, IL 60680-4124,
  • Humidity: What indoor humidity should we maintain in order to avoid a mold problem?
  • Ice Dam Leaks in building attics and roof cavities, how to inspect for evidence of leaks, identify causes, and
  • What Style Is It?: A Guide to American Architecture, Rev., John C. Poppeliers, S. Allen Chambers, Wiley; Rev Sub edition (October 6, 2003), ISBN-10: 0471250368, ISBN-13: 978-0471250364
  • ...

Home About Us Accuracy Contact Us Content Use Policy Printing Tips Privacy Website Description © 2012 Copyright InspectAPedia.com