Mobile ViewBUILDING INTERIORS ACOUSTICAL SEALANT CHOICES AGE of a BUILDING - how to determine AGE of PLUMBING MATERIALS & FIXTURES AGE of AIR CONDITIONERS & HEAT PUMPS AGE of HEATERS, BOILERS, FURNACES AGE of WATER HEATERS AIR BYPASS LEAKS AIR LEAK DETECTION TOOLS AIR LEAK MINIMIZATION AIR POLLUTANTS, COMMON INDOOR AIR LEAK SEALING PROCEDURE AIR SEALING STRATEGIES ANIMAL ALLERGENS ANTI SCALD VALVES APPLIANCE EFFICIENCY RATINGS ARCHITECTURE & BUILDING COMPONENT ID ASBESTOS IDENTIFICATION IN buildings ATTIC LEAKS, CONDENSATION & MOLD ATTIC VENTILATION BASEMENT CEILING VAPOR BARRIER BASEMENT HEAT LOSS BASEMENT LEAKS, INSPECT FOR BASEMENT WATERPROOFING BATH & KITCHEN DESIGN GUIDE BATHROOM VENTILATION BEST CONSTRUCTION PRACTICES GUIDE BLOWER DOORS & AIR INFILTRATION BLOWER FAN CONTINUOUS OPERATION BLOWER FAN OPERATION & TESTING BLOWN-IN INSULATION BOOKSTORE BRICK LINED WALLS BRICK VENEER WALL INSULATION BRICK VENEER WALL Loose, Bulged BRICK WALL DRAINAGE WEEP HOLES BUCKLED FOUNDATIONS due to INSULATION? BUILDING SAFETY HAZARDS GUIDE BUILDING NOISE DIAGNOSIS & CURE CACTUS FUNGI / MOLD CAR MOLD CONTAMINATION CARPET DUST IDENTIFICATION CARPET MOLD CONTAMINATION CARPET PADDING ASBESTOS, MOLD, ODORS CARPET STAIN DIAGNOSIS CARPET & other STAIN TESTS CARPET TEST PROCEDURE CABINETS & COUNTERTOPS CARPETING & INDOOR AIR QUALITY CARPETING, SELECTION & INSTALLATION CASEWORK, CABINETS, SHELVING INSTALLATION CATHEDRAL CEILING INSULATION CATHEDRAL CEILING VENTILATION CEILING FINISHES INTERIOR CEILINGS, DROP or SUSPENDED PANEL CEILINGS, PLASTER TYPES CERAMIC TILE FLOOR, WALL CERAMIC TILE, ASBESTOS in? CHIMNEY INSPECTION DIAGNOSIS & REPAIR CHINESE DRYWALL HAZARDS CLOGGED DRAIN DIAGNOSIS & REPAIR COMBUSTION AIR for TIGHT buildings CONDENSATION or SWEATING PIPES, TANKS COOLING LOAD REDUCTION by ROOF VENTS CRAWL SPACES DEW POINT CALCULATION for WALLS DEW POINT TABLE - CONDENSATION POINT GUIDE DOORS, INTERIOR DRYWALL HAZARDS, CHINESE DRYWALL INSTALLATION Best Practices DRYWALL MOLD DRYWALL MOLD RESISTANT EARTHQUAKE DAMAGED FOUNDATIONS EFFLORESCENCE, Salts & White / Brown Deposits ELDERLY & VETERANS HOME SAFETY ELECTRICAL INSPECTION, DIAGNOSIS, REPAIR ENERGY SAVINGS in buildings ENGINEERED WOOD Flooring ENGINEERED WOOD Products EXTERIOR WALL SIDING TRIM & FINISHES FIBERGLASS INSULATION FIBERGLASS HAZARDS FIBERGLASS INSULATION MOLD FLAT ROOF MOISTURE & CONDENSATION FLOOD DAMAGE ASSESSMENT, SAFETY & CLEANUP FLOODS IN buildings-mold FLOOR, CERAMIC TILE FLOOR, CONCRETE SLAB CHOICES FLOOR, CONCRETE SLAB POURED FINISH FLOOR DAMAGE DIAGNOSIS FLOOR, ENGINEERED WOOD & LAMINATES FLOOR FRAMING & SUBFLOOR for TILE FLOOR, KITCHEN & BATH OPTIONS FLOOR, LAMINATE PLASTIC FLOOR RADIANT HEAT Mistakes to Avoid FLOOR, RESILIENT VINYL or CORK FLOOR, STONE, GRANITE, MARBLE, AGGLOMER FLOOR & SUBFLOOR MOLD, HIDDEN FLOOR TYPES & DEFECTS FLOOR TILE ASBESTOS IDENTIFICATION FLOOR TILE HISTORY & INGREDIENTS FLOOR TILE INSTALLATION DETAILS FLOOR WOOD AGE TYPES HISTORY FLOOR WOOD, DAMAGE DIAGNOSIS ; FLOOR, WOOD ENGINEERED, LAMINATE, INSTALL FLOOR, WOOD FINISHES FLOOR, WOOD INSTALLATION GUIDE FLOOR, WOOD MOISTURE FLOOR, WOOD RADIANT HEAT FLOOR, WOOD SOLID STRIP, PLANK FLOOR, WOOD TYPES FLOORING MATERIALS, Age, Types FORMALDEHYDE HAZARDS FOUNDATION BULGE or LEAN MEASUREMENTS FOOTING & FOUNDATION DRAINS FOUNDATION CRACKS & DAMAGE GUIDE FOUNDATION WATERPROOFING FRAMING DAMAGE, INSPECTION, REPAIR FRAMING DETAILS for BETTER INSULATION FREEZE-PROOF A BUILDING FROST HEAVES, FOUNDATION, SLAB FUNGICIDAL SPRAY & SEALANT USE GUIDE GAS DETECTION & MEASUREMENT GAS EXPOSURE EFFECTS, TOXIC GAS EXPOSURE LIMITS & STANDARDS GAS TEST PROCEDURES HEAT LOSS in buildings HEAT LOSS DETECTION TOOLS HEAT LOSS INDICATORS HEAT LOSS PREVENTION PRIORITIES HEAT LOSS R U & K VALUE CALCULATION HEAT TAPES & CABLES on Roofs for Ice Dams HEATING COST SAVINGS METHODS HOT ROOF DESIGNS: Un-Vented Roof Solutions HOT WATER HEATERS HOUSEWRAP AIR & VAPOR BARRIERS HOUSE DOCTOR, how-to be HUMIDITY LEVEL TARGET ICE DAM PREVENTION Ice Dams: Comparing Two Houses INDOOR AIR QUALITY & HOUSE TIGHTNESS INDOOR AIR QUALITY IMPROVEMENT GUIDE INSULATION CHOICES INSULATION FACT SHEET- DOE INSULATION for GREENHOUSE or SOLARIUM INSULATION IDENTIFICATION GUIDE INSULATION INSPECTION & IMPROVEMENT INSULATION LOCATION - WHERE TO PUT IT INSULATION MOLD INSULATION R-Values & Properties INTERIOR FINISHES: BEST PRACTICES INTERIOR FINISHES: DRYWALL KIT HOMES, Aladdin, Sears, Wards, Others KITCHEN & BATH DESIGN GUIDE LIGHTING, EXTERIOR GUIDE LIGHTING, INTERIOR GUIDE LOG HOME GUIDE METAL LATH, PLASTER & STUCCO MIXING / ANTI-SCALD VALVES MOBILE HOME INSPECTIONS MOISTURE CONTROL in BUILDINGS MOLD in FOAM INSULATION, RESISTANCE MOLD INFORMATION CENTER Nanomaterials Hazards NOISE / SOUND DIAGNOSIS & CURE NOISE, AIR CONDITIONER COMPRESSOR NOISE, DUCT VIBRATION DAMPENERS NOISE CONTROL for HEATING SYSTEMS NOISE CONTROL for FLOORS NOISE CONTROL for PLUMBING NOISE CONTROL for ROOFS NOISE, PLUMBING DRAIN DIAGNOSIS NOISE, PLUMBING DRAIN REPAIR NOISE, PLUMBING CHECKLIST NOISE, WATER HEATER NOISES, WATER PUMP ODORS & SMELLS DIAGNOSIS & CURE PASCAL CALCULATIONS PAINT FALURE, DIAGNOSIS, CURE, PREVENTION PLASTER PLASTER & BEAVERBOARD & DRYWALL PLASTER BULGES & PILLOWS PLASTER LATH, METAL PLASTER, LOOSE FALL HAZARDS PLASTER TYPE IDENTIFICATION PLASTER VENEER Best Practices PLASTER VENEER Best Practices RADIANT HEAT RADIANT HEAT Floor Mistakes to Avoid RADIANT HEAT TEMPERATURES RADIANT SLAB FLOORING CHOICES RADIANT SLAB TUBING & FLUID CHOICES ROOF VENTILATION SPECIFICATIONS ROT, FUNGUS, TERMITES ROT, TIMBER FRAME SAFETY HAZARDS & INSPECTIONS SAFETY: Elderly & Veterans Home Safety SAFETY for ELECTRICAL INSPECTORS SEARS KIT HOUSES SINKHOLES, WARNING SIGNS SINKING BUILDINGS SLAB CRACK EVALUATION SOUND CONTROL in buildings Splits in Structural Wood Beams STAIN DIAGNOSIS on BUILDING EXTERIORS STAIN DIAGNOSIS on BUILDING INTERIORS STAINS & FINISHES, INTERIOR STAIRS, RAILINGS, LANDINGS, RAMPS STONE CLEANING METHODS STRESS SKIN INSULATED PANELS STUCCO WAll FAILURES DUE TO WEATHER STUCCO WALL METHODS & INSTALLATION STUCCO OVER FOAM INSULATION STUCCO PAINT FAILURES SUMP PUMPS GUIDE SWEATING (CONDENSATION) on PIPES, TANKS THERMAL EXPANSION of MATERIALS THERMAL MASS in buildings THERMAL TRACKING Indicates Heat Loss TILE INSTALLATION DETAILS TRIM, INTERIOR INSTALLATION TRUSS UPLIFT, ROOF TRUSSES, Floor & Roof VAPOR BARRIERS & CONDENSATION in BUILDINGS VENTILATION in buildings VINYL Siding or PLASTIC Window ODORS in buildings VINYL CHLORIDE HEALTH INFO WALL SIDING TRIM & FINISHES WALL FINISHES INTERIOR WATER BARRIERS, EXTERIOR BUILDING WATER ENTRY in buildings WINDOWS & DOORS WINTERIZE A BUILDING WOOD Burning Heaters Fireplaces Stoves WOOD FLOOR DAMAGE More Information |
This article discusses choices of materials to use for building interior cabinets and shelving: casework, and describes best practices for building these components. This article series discusses and provides a best construction practices guide to the selection and installation of building interior surface materials, carpeting, doors, drywall, trim, flooring, lighting, plaster, materials, finishes, and sound control materials. InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers nor with topics or services discussed at this website.© Copyright 2012 InspectAPedia.com, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use page top links to major topics or use links at the left of each page to navigate within topics and documents at this website. Green links show where you are in a document series or at this website. Casework: Guide to Selecting Materials for Built-In Cabinets & ShelvingThis article includes excerpts or adaptations from Best Practices Guide to Residential Construction, by Steven Bliss, courtesy of Wiley & Sons. Our page top photo shows site-built casework in a Poughkeepsie, NY home constructed in 1900 (DJF). Also see INTERIORS of buildings, our home page for information about all topics relating to building interiors. As described in the book, Best Practices Guide to Residential Construction Chapter 5, Interior Finish: For shelving, built-ins, and other casework, contractors can choose from a wide array of panel products. The most widely used are veneer-core plywood, MDF, and particleboard. MDF and particleboard are available either unfinished or with a wood veneer or melamine facing. Medium density overlay (MDO) is a good option for cabinets exposed to very high humidity or exterior uses. Using Veneer-Core Plywood For Built-In Casework: Cabinets & ShelvingCabinet-grade plywood typically has five inner plies (more for better grades), plus the face veneers, and in most cases uses phenol-formaldehyde adhesive, which has negligible off-gassing. Plywood is strong and dimensionally stable. For paint-grade cabinets, birch plywood remains an excellent choice. Baltic birch plywood uses all birch for the inner plies, is free of voids, and can be edge sanded, making it ideal for drawer sides and similar applications. For stain-grade work, hardwood plywood can be special ordered with matched veneers. Where screwing into edges is required, 7-ply material is less likely to split. Using MDF (Medium Density Fiberboard) For Built-In Casework: Cabinets & ShelvingMedium-density fiberboard is a fine composite material made from fine wood fibers and resin, usually urea-formaldehyde (see description on page 184). MDF is available as both a paint-grade panel or faced with wood veneer or melamine. Because of its competitive pricing and good workability, MDF is now the dominant panel product in many markets. In paint-grade work, the edges need to be sealed or banded due to high absorption of paint. Concerns about off-gassing of formaldehyde could be a concern to customers with allergies or chemical sensitivities. However, if laminated on all faces with an impervious facing, such as melamine, or finished with two or more coats of varnish or an oil-based paint (or paint rated as a vapor barrier) on all faces, the off-gassing will be minimized. Guide to using Particleboard For Built-In Casework: Cabinets & ShelvingParticleboard is similar to MDF, but with larger fibers, so it doesn’t machine to a crisp edge and leaves a noticeable texture when painted. Also, edges and corners are more prone to chipping than with MDF. Like MDF, it off-gasses urea-formaldehyde. Sealing all surfaces will minimize the problem. Guide to using MDO (Medium Density Overlay) For Built-In Casework: Cabinets & ShelvingMedium-density overlay is an exterior grade plywood with a durable resin-treated paper facing that takes paint exceptionally well. It is widely used for sign making as well as concrete forms. Though not typically used in casework, it is an ideal material for cabinets that will be exposed to extreme moisture or exposed to weather on porches, patios, or other outdoor locations. Recommendations for Constructing Built-in ShelvingTypical shelf spans for simple shelves sitting on cleats at both ends are shown in Table 5-11 below. These assume a load of heavy books and minimal deflection, although long-term deflection under a constant load may be greater. -- Adapted with permission from Best Practices Guide to Residential Construction. Resources: Manufacturers, Industry Associations, & Sources of Indoor Wall Materials, Flooring, Carpeting, Lighting, Sound Control MaterialsDrywall Trims and AccessoriesClinch-On Products, A Deitrich Metal Framing Company www.dietrichindustries.com Nail-on and clinch-on galvanized metal corner beads Con-Form International/Strait Flex www.straitflex.com Strait-Flex fiber-composite mud-on corner bead for inside and outside off-90 degree angles Drywall Systems International www.no-coat.com No-Coat prefinished drywall tapes for inside and outside corners, off angles and bullnose trims Flex-Ability Concepts www.flexc.com Curved metal top and bottom plates for curved wood or metal stud walls Grabber Construction Products www.grabberman.com Drywall screws, corner clips, and fiberglass mesh tapes Insta Arch Corp. www.instaarch.com Galvanized steel preformed and custom arches for drywall National Gypsum Co. www.nationalgypsum.com ProForm tapes and finishing compounds Pla-Cor www.pla-cor.com ABS corner trims, bullnose, 3-way corner caps, and flexible arches Phillips Manufacturing Co. www.phillipsmfg.com Metal and vinyl corner beads, bullnose trim, and flexible bullnose and angled arch trim Trim-Tex www.trim-tex.com Vinyl drywall beads, flexible arch beads, and finishing accessories U.S. Gypsum Beadex and Sheetrock-brand tape-on metal corner beads and trims. Complete line of drywall finishing compounds Vinyl Corp., A Deitrich Metal Framing Company www.vinylcorp.com Full line of vinyl beads and trim Prefinished Wood FlooringAlloc Inc. www.alloc.com Snap-together, no-glue long-strip and single-strip laminated flooring Anderson Hardwood Floors www.andersonfloors.com Laminated strip, nail, glue, and floating Armstrong World Industries www.armstrong.com Bruce, Hartco, and Robbins prefinished plank and engineered strip BHK of America www.bhkuniclic.com Snap-together, no-glue laminated wood flooring Columbia Wood Flooring www.columbiaflooring.com Prefinished solid strip Duro-Design www.duro-design.com Floating click-lock oak flooring Gammapar www.gammapar.com Engineered wood strip with oil, UV-cured urethane, or acrylic-impregnated finish Junkers Hardwood www.junkershardwood.com Floating solid strip with metal clip installation Kahrs www.kahrs.com Laminated strip with UV-cured acrylic urethane, nail, glue, or floating Lauzon www.lauzonltd.com Prefinished strip, laminated strip, and click-lock laminated plank Mannington Mills www.mannington.com Laminated strip and plank with polyurethane and aluminum-oxide finish Medallion Hardwood Flooring www.medallionhardwood.com Prefinished solid hardwood strip and plank with aluminum-oxide finish Tarkett Wood Floors www.harris-tarkett.com Prefinished solid hardwood, laminated, and long-strip flooring MercierWood Flooring www.mercierdurable.com Prefinished solid strip and laminated strip with aluminum-oxide finish PermaGrain Hardwood Flooring www.permagrain.com Acrylic-impregnated laminated strip and plank Zickgraf Hardwood Flooring www.zickgraf.com Prefinished solid strip with UV-cured urethane with diamond and aluminum oxide Bamboo Flooring Producers & SourcesBamtex (a division of Wood Flooring International) www.bamtex.com Laminated bamboo and palm flooring Duro-Design www.duro-design.com Laminated bamboo flooring with durable water-based finish Gammapar www.gammapar.com Acrylic-impregnated bamboo flooring Hawa Bamboo Flooring www.hawabamboo.com Prefinished bamboo flooring with aluminum-oxide finish Natural Cork www.naturalcork.com Prefinished glue-down or nail-down 3-ply bamboo planks with aluminum-oxide finish Resilient Flooring Manufacturers ListCongoleum www.congoleum.com Vinyl sheet flooring and tiles Domco (division of Domco Tarkett Group) www.domco.com Vinyl sheet flooring and tiles Forbo www.forbo-flooring.com Linoleum sheet and tiles Mannington Mills www.mannington.com Vinyl sheet flooring and tiles Nova Distinctive Floors www.novafloorings.com Laminated linoleum surface over fiberboard and cork planks, floating installation Tarkett www.tarkettna.com Vinyl sheet flooring and tiles Cork Flooring Manufacturers & SourcesAmerican Cork Products Co. www.amcork.com Prefinished parquet tiles and floating floor planks Amorim Revestimentos (formerly Ipocork) www.wicanders.com Floating or glue-down laminated cork tiles with UV-acrylic or oil finish BHK of America www.bhkuniclic.com Snap-together, no-glue, laminated cork flooring with UV-acrylic finish Expanko Cork Inc. www.expanko.com Cork tiles with wax or polyurethane finish Korq Inc. (212) 758-2593 Natural Cork www.naturalcork.com Glue-down cork tiles and floating laminated planks with UV-cured acrylic finish Nova Distinctive Floors www.novafloorings.com Laminated cork planks with glue-down and floating click-lock installation WECork www.wecork.com Cork tiles, sheets, and floating floors Polymer (Urethane), MDF, and Vinyl Trim Producers & SourcesBurton Mouldings www.burton-mouldings.com MDF(medium-density fiberboard), polymer, flex, and wood Fypon www.fypon.com Polymer moldings and components Nu-Wood www.nu-wood.com Polymer moldings and components Outwater Plastics www.outwater.com Polymer moldings and components RAS Industries www.rasindustries.com Polymer moldings and components Royal Mouldings (formerly Marley Mouldings) www.royalmouldings.com Polymer, polystyrene, expanded-PVC, CPVC, and acrylic molding profiles and components Flexible Trim Manufacturers & SourcesFlex Trim www.flextrim.com Flexible polymer moldings Resin Art www.resinart.com Flexible polymer moldings Industry & Trade Associations for Carpeting, Lighting, Finishes, Wood Products, Flooring, Painting & DecoratingAmerican Lighting Association www.americanlightingassoc.com Association of the Wall and Ceiling Industries www.awci.org Carpet and Rug Institute (CRI) www.carpet-rug.org Drywall Finishing Council www.dwfc.org Forest Stewardship Program www.fscus.org FloorFacts www.floorfacts.com The Gypsum Association www.gypsum.org National Oak Flooring Manufacturers Association (NOFMA) www.nofma.com National Wood Flooring Association www.woodfloors.org Painting and Decorating Contractors of America www.pdca.org Smartwood/Rainforest Alliance www.smartwood.org -- Adapted with permission from Best Practices Guide to Residential Construction. Questions & Answers regarding this articleQuestions & answers about building casework, cabinets, shelving - best practices guide. Ask a Question or Search InspectAPediaHTML Comment Box is loading comments...
Recommend / Share this Article
... Technical Reviewers & References
Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website. INTERIORS of buildings Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair
|