InspectAPedia ® Home STRUCTURAL INSPECTIONS & DEFECTS ADVANCED INSPECTION METHODS AGE of a BUILDING - how to determine ARCHITECTURE & BUILDING COMPONENT ID BARK SIDE UP on DECKS & STEPS BASEMENT WATERPROOFING BEST CONSTRUCTION PRACTICES GUIDE BRICK FOUNDATIONS & WALLS BRICK STRUCTURAL WALL Loose Bulged BRICK WALL THERMAL EXPANSION CRACKS BRICK VENEER WALL Loose, Bulged BRICK WALL DRAINAGE WEEP HOLES BUCKLED FOUNDATIONS due to INSULATION? BUILDING DAMAGE ASSESSMENT & REPAIR BUILDING SAFETY HAZARDS GUIDE BUILDING SETTLEMENT CARPENTER ANTS CARPENTER BEES CHIMNEY INSPECTION DIAGNOSIS REPAIR COLD POUR JOINTS, CONCRETE COLUMNS & POSTS, DEFECTS CONCRETE FOUNDATIONS CONCRETE FOUNDATIONS, PRE-CAST CONNECTORS, FASTENERS, TIES Cracks, Checking or Splitting Beams & Log Homes CRAWL SPACES DECK & PORCH CONSTRUCTION DECK CONSTRUCTION BEST PRACTICES BARK SIDE UP on DECKS & STEPS Deck Beams & Girders Deck Piers & Posts Deck & Porch Connections: Ledger Boards Deck Framing Tables, Spans Deck Flashing at Building DECK FLOOR & STEP CUPPING Deck Board Gaps, Spacing Guide Deck & Porch Steps or Stairs Deck & Porch Railings Deck & Porch Products, Manufacturers Fasteners, Nails, Screws, Hidden, for Decks Fasteners/Connectors, Ties, Structural Porch Construction & Porch Screening Preservative-Treated Framing Lumber Rooftop Deck Construction ROT-RESISTANT Deck Lumber & Flooring STRUCTURAL DAMAGE PROBING Synthetic Deck Lumber: Composite, Plastic, Vinyl DECK COLLAPSE Case Study DECK FINISHES COATINGS PRESERVATIVES DECK FLASHING LEAKS, ROT Case Study DECKS, ROOFTOP CONSTRUCTION DECK CONSTRUCTION BEST PRACTICES DEBRIS STAINING on ROOFS DEFINITIONS of Mobile Home, Doublewide, Modular, Panelized DEFINITIONS of ENGINEERED WOOD OSB LVL etc DEW POINT CALCULATION for WALLS DEW POINT TABLE - CONDENSATION POINT GUIDE DISASTER BUILDING INSPECTION & REPAIR EARTHQUAKE DAMAGED FOUNDATIONS EIFS & STUCCO EXTERIORS ENGINEERED WOOD Flooring ENGINEERED WOOD Products FIRE DAMAGE vs MOLD DAMAGE FLOOD DAMAGE ASSESSMENT, SAFETY & CLEANUP FLOOD DAMAGE TO FOUNDATIONS FLOODED HEATING EQUIPMENT REPAIR FLOODED SEPTIC SYSTEMS, REPAIR FLOODED WATER HEATER REPAIR FLOODS IN BUILDINGS, MOLD PREVENTION FLOOR, ENGINEERED WOOD & LAMINATES FLOOR FRAMING & SUBFLOOR for TILE FLOOR TYPES & DEFECTS FLOOR TILE ASBESTOS IDENTIFICATION FLOOR TILE HISTORY & INGREDIENTS FOOTING & FOUNDATION DRAINS FOOTINGS EXPOSED, Repair Methods FOUNDATION BULGE or LEAN MEASUREMENTS FOUNDATION CONSTRUCTION TYPES FOUNDATION CONTRACTORS, ENGINEERS FOUNDATION CRACKS & DAMAGE GUIDE FOUNDATION DEFECTS OF OMISSION - MISSING FOUNDATION FAILURES by TYPE & MATERIAL FOUNDATION FAILURES by MOVEMENT TYPE FOUNDATION INSPECTION METHODS FOUNDATION INSULATION OPTIONS FOUNDATION MATERIALS, Age, Types FOUNDATION REPAIR METHODS FOUNDATION SETTLEMENT FOUNDATION WATERPROOFING FRAMING DAMAGE, INSPECTION, REPAIR FRAMING DETAILS for BETTER INSULATION FRAMING DETAILS for DOUBLE WALL HOUSES FRAMING CONNECTORS & JOIST HANGERS FRAMING FASTENERS, NAILS, SCREWS, & HIDDEN FRAMING & SUBFLOOR for TILE FRAMING MATERIALS, Age, Types FRAMING SIZE & Spacing, Age, Types FRAMING TABLES, SPANS for DECKS FRENCH DRAINS FROST HEAVES, FOUNDATION, SLAB FRT PLYWOOD GALVANIC SCALE & METAL CORROSION GLUES ADHESIVES, EXTERIOR CONSTRUCTION GRADING, DRAINAGE & SITE WORK GUTTERS & DOWNSPOUTS HOUSE PARTS, DEFINITIONS HOUSEWRAP INSTALLATION DETAILS I-JOISTS, Wood Roof Floor ICE DAM PREVENTION INDOOR AIR QUALITY & HOUSE TIGHTNESS INSECT INFESTATION / DAMAGE KIT HOMES, Aladdin, Sears, Wards, Others LEAD POISONING HAZARDS GUIDE LEED GREEN BUILDING CERTIFICATION LOG HOME GUIDE LVL Laminated Veneer Lumber, Beams MOBILE HOMES, DOUBLEWIDES, TRAILERS MODULAR HOME CONSTRUCTION MOISTURE CONTROL in BUILDINGS NOISE / SOUND DIAGNOSIS & CURE OSB - Oriented Strand Board PANELIZED CONSTRUCTION PLASTER BULGES & PILLOWS PLASTER, LOOSE FALL HAZARDS PLYWOOD Roof, Wall, Floor Decks & Sheathing PORCH CONSTRUCTION & SCREENING PRE-CUT & KIT HOMES Preservative-Treated Framing Lumber RAILINGS, DECK & PORCH RAILINGS, STAIRWAY RETAINING WALL DESIGNS, TYPES, DAMAGE RETAINING WALL GUARD RAILINGS ROT, FUNGUS, INSECT DAMAGE ROT RESISTANT LUMBER ROT, TIMBER FRAME ROT, TIMBER ASSESSMENT SEARS KIT HOUSES SEPTIC & CESSPOOL SAFETY SHEATHING, FIBERBOARD SHEATHING, Gypsum board SHEATHING, OSB SHEATHING, Plywood SHEATHING, FOIL FACED - VENTS SIDING TYPES, INSTALLATION, DEFECTS SINKHOLES, WARNING SIGNS SINKING BUILDINGS SLAB CRACK EVALUATION SLAB CRACK REPAIR Splits in Structural Wood Beams STAIN & BIODETERIORATION AGENT CATALOG STAINS on & in BUILDINGS, CAUSES & CURES STAIN DIAGNOSIS on BUILDING EXTERIORS STAIRS, RAILINGS, LANDINGS, RAMPS STONE CLEANING METHODS STONE FOUNDATIONS STONE VENEER WALLS STRAW BALE CONSTRUCTION STRESS SKIN INSULATED PANELS STUCCO WAll FAILURES DUE TO WEATHER STUCCO WALL METHODS & INSTALLATION STUCCO OVER FOAM INSULATION STUCCO PAINT FAILURES STRUCTURAL DAMAGE PROBING STRUCTURAL WOOD ASSESSMENT SUMP PUMPS GUIDE SWEATING (CONDENSATION) on PIPES, TANKS TERMITES TEST KITS for DUST, MOLD, PARTICLE TESTS Thermal Expansion Cracking of Brick THERMAL EXPANSION of HOT WATER THERMAL EXPANSION of MATERIALS THERMAL IMAGING, THERMOGRAPHY THERMAL IMAGING MOLD SCANS THERMAL MASS in BUILDINGS TIMBER FRAMING, ROT TIMBER ASSESSMENT TRUSS UPLIFT, ROOF TRUSSES, Floor & Roof VAPOR BARRIERS & CONDENSATION in BUILDINGS VENTILATION in BUILDINGS VINYL CHLORIDE HEALTH INFO VINYL SIDING VINYL Siding or PLASTIC Window ODORS Volatile Organic Compounds VOCs WALL CONSTRUCTION BARRIER vs CAVITY WATER BARRIERS, EXTERIOR BUILDING WATER ENTRY in BUILDINGS WIND ENERGY SYSTEMS WIND TURBINES & LIGHTNING WIND WASHING INSULATION At EAVES WINDOWS & DOORS, Age, Types WINTERIZE A BUILDING WOOD FOUNDATIONS More Information |
Structural connectors, fasteners, bolts, nails, joist hangers, rafter ties etc.: this article explains the proper selection and installation of structural connectors, brackets & tie plates used to connect deck or porch framing and support members. USP connectors such as joist hangers, joist angles, joist supports, stud shoes, skew hangers, and face mount hangers used for connecting these hangers and connectors are described, their uses explained, and their applications and specifications linked. Both galvanized steel and stainless steel joist hangers, connectors, & brackets may be applied. Green links show where you are. © Copyright 2013 InspectAPedia.com, All Rights Reserved. Author Daniel Friedman. How to Choose the Correct Bolts or Fasteners for Structural Framing Connections in Wood Frame Construction, Decks & Porches Details about choosing the right structural connectors for decks and how they should be installed are at Fasteners/Connectors, Ties, Structural. At Fasteners, Nails, Screws, Hidden, for Decks we discuss choosing the proper nail, screw, or hidden fastener for fastening deck boards, railings, or joist hangers. Spans, sizes and spacings for deck joists and deck beams are discussed in detail at FRAMING TABLES, SPANS for DECKS and are shown in Table 4-7 and Table 4-8. Basic building framing information is found at FRAMING SIZE & Spacing, Age, Types. Also see Deck Framing Tables, Spans and Deck & Porch Connections: Ledger Boards. And see Preservative-Treated Framing Lumber. see Rot-Resistant Deck Lumber & Flooring for a discussion of lumber and flooring alternatives to preservative-treated wood. At minimum, all structural hardware for decks should be hot-dipped galvanized steel. For the best protection, use stainless steel (see “Joist Hangers and Connectors,” below). At connections carrying structural loads, such as deck ledgers or railing posts, use through-bolts or lag screws. Through-bolts are stronger and should be used where possible. For the heaviest connections on a deck, such as where ledgers attach to the house or to posts, use 1/2-inch bolts or lags. Place large washers under the heads of lags and at both ends of through-bolts. Re tighten bolts and lags after the first year and check periodically for tightness. Machine-Threaded Bolts Used for Deck Construction
After drilling, saturate the hole with preservative. Use large washers under both the head and nut. Re tighten after the first year, since the wood may have shrunk. Lag Bolts Used for Deck ConstructionFor lag bolted deck connections, drill a full-diameter pilot hole for the unthreaded portion and a smaller hole (65 to 75% of the lag’s diameter) for the threaded portion. So, for example, a 1/2-inch lag would get a 5/16-inch pilot hole for the threaded portion; a 3/8-inch diameter lag would get a 1/4-inch diameter pilot hole. After drilling, saturate the pilot hole with wood preservative. It is also important that at least half the length of the lag is threaded into solid wood. For example, driving a 5-inch lag through a 4x4 post into a 2x joist will produce a weak connection with only 1 1/2 inches of anchoring. Instead, the lag screw should go through the 2x and be threaded into the thicker 4x4. Use a large washer under the head, and re tighten after the first year in case materials have shrunk. Joist Hangers and Steel Connectors Used for Deck ConstructionAt a minimum, use hot-dipped galvanized hardware. With pressuretreated wood, hot-dipped galvanized steel should conform to ASTM A153 (for fasteners) or ASTM A653, G185 (for connectors). Stainless steel offers the best protection. Type 304 or higher stainless steel is recommended for very wet environments such as poolside decks; or Type 326 for exposure to salt or saltwater. Watch out: Also, do not mix metals: Use stainless-steel fasteners with stainless-steel connectors and galvanized fasteners with galvanized connectors. And at Fasteners, Nails, Screws, Hidden, for Decks we include examples of fasteners that should not be used in joist hangers, such as drywall screws and other non-structural screws. or roofing nails. Also see Deck Nails, Screws, Hidden Fasteners and see New Preservatives and Corrosion where we describe structural fasteners designed for use in pressure-treated lumber. Suppliers of Joist, Post & Beam Hangers & Connectors & the Nails or Fasteners used With Them
-- Adapted with permission from Best Practices Guide to Residential Construction. Also see DECK COLLAPSE Case Study (collapse of a new code-approved deck) and DECK FLASHING LEAKS, ROT Case Study for an example of an older deck with rot and collapse due to improper construction and missing building flashing. Frequently Asked Questions (FAQs) about framing connectiors, fasteners, joist hangers, rafter ties... Ask a Question or Search InspectApediaQuestions & answers or comments about what types of joist & beam hangers & connectors are required for deck construction: joist hangers, connectors, steel tie plates, etc. . Ask a Question or Enter Search Terms in the InspectApedia search box just below. Technical Reviewers & ReferencesRelated Topics, found near the top of this page suggest articles closely related to this one.
Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair
| |||||||