InspectAPedia.com InspectAPedia®
 

Free Encyclopedia of Building & Environmental Inspection, Testing, Diagnosis, Repair

Ask a Question or Search InspectAPedia

  • HOME
  • AIR CONDITIONING
  • ELECTRICAL
  • EXTERIORS
  • HEATING
  • HOME INSPECTION
  • INTERIORS
  • PLUMBING
  • ROOFING
  • SEPTIC SYSTEMS
  • STRUCTURE
  • WATER SUPPLY
  • ENERGY SAVINGS
  • ENVIRONMENT
  • INDOOR AIR IAQ
  • INSULATION
  • MOLD INSPECT TEST REMOVE
  • NOISE
  • ODORS
  • SOLAR ENERGY
  • VENTILATION
  • EXPERTS DIRECTORY
  • CONTACT US


Mobile Phone/PDA website viewMobile View
ENERGY SAVINGS in buildings
ENGINEERED WOOD Flooring
ENGINEERED WOOD Products

ENVIRONMENTAL HAZARDS - INSPECT, TEST, REMEDY

AIR CLEANER PURIFIER TYPES
AIR FILTERS for HVAC SYSTEMS
AIR POLLUTANTS, COMMON INDOOR
ALLERGEN TESTS for buildings
ALLERGENS in buildings, RECOGNIZING
ALLERGY TESTS for PEOPLE
ALLERGY TEST ACCURACY
ANIMAL ALLERGENS / PET DANDER
ANIMAL ENTRY POINTS in buildings
ANIMAL ODORS IN buildings
ASBESTOS IDENTIFICATION IN buildings

BASEMENT MOLD
BATHROOM MOLD
BIBLIOGAPHY for ENVIRONMENTAL HEALTH, MOLD, IAQ
BIOLOGICAL POLLUTANTS
BLUE vs YELLOW COMBUSTION FLAMES
BLUERAY Recall
BUILDING SAFETY HAZARDS GUIDE
BUILDING SETTLEMENT

CARBON MONOXIDE - CO
CARBON MONOXIDE WARNING
CABINETS & COUNTERTOPS
CARPETING & INDOOR AIR QUALITY
CARPETING, SELECTION & INSTALLATION
CAT DANDER in buildings
Cell phone Radiation Hazards
CHAIN OF CUSTODY - TEST SAMPLE
CHIMNEY INSPECTION DIAGNOSIS REPAIR
CHIMNEYS & Flues - Asbestos Transite Pipe
CHINESE DRYWALL HAZARDS

DRYER VENTING
DRYWALL INSTALLATION Best Practices
DRYWALL MOLD
DRYWALL MOLD RESISTANT
EMF ELECTROMAGNETIC FIELDS & HUMAN EXPOSURE

ENERGY SAVINGS in buildings
  AFUE DEFINITION, RATINGS
  AIR BYPASS LEAKS
  AIR CHANGE RATE ACH HEAT SAVINGS
  AIR CONDITIONING HEAT PUMP SAVINGS
  AIR LEAK SEALING PROCEDURE
  APPLIANCE EFFICIENCY RATINGS
  ATTIC LEAKS, CONDENSATION & ATTIC MOLD
  COOLING LOAD REDUCTION by ROOF VENTS
  ENERGY AUDIT - How to Use a Free One
  ENERGY SAVINGS MAXIMIZE RETURNS ON
  ENERGY SAVINGS PRIORITIES
  ENERGY SAVINGS RETROFIT CASE STUDY
  ENERGY SAVINGS RETROFIT LEAK SEALING GUIDE
  ENERGY SAVINGS RETROFIT OPTIONS
  ENERGY STAR PROGRAM
  ENERGY USE MONITORING
  GLASS vs HEAT MIRROR SOLAR GAIN/Loss
  HEAT LOSS in buildings
  HEATING COST SAVINGS METHODS
  HIGH MASS TRADEOFFS, HEATING vs COOLING
  HOUSE DOCTOR, how-to be
  INSULATION INSPECTION & IMPROVEMENT
  INSULATION LOCATION - WHERE TO PUT IT
  RADIANT BARRIERS
  REFLECTIVE INSULATION
  ROOF COLOR RECOMMENDATIONS
  Skylight Energy Efficiency
  SOLAR ENERGY SYSTEMS
  THERMAL MASS in buildings
  TIMERS for ELECTRIC WATER HEATERS
  VENTILATION, BALANCED HEAT COST SAVINGS
  WIND ENERGY SYSTEMS
  WINDOW EFFICIENCY Features & Ratings
  WOOD, COAL STOVES & FIREPLACES

FLOOD DAMAGE ASSESSMENT, SAFETY & CLEANUP

FUNGICIDAL SPRAY & SEALANT USE GUIDE
HIDDEN MOLD, HOW TO FIND
HUMIDITY CONTROL TO PREVENT MOLD

INDOOR AIR QUALITY & HOUSE TIGHTNESS
INDOOR AIR QUALITY IMPROVEMENT GUIDE
  Air Pollutants, Health Effects
  Air Pollutants, Common Indoor
  CABINETS & COUNTERTOPS
CARPETING & INDOOR AIR QUALITY
  CHINESE DRYWALL HAZARDS
  INDOOR AIR QUALITY IMPROVEMENT, KEY STEPS
  VENTILATION, WHOLE HOUSE STRATEGIES
  Whole House Ventilation Table
  VENTILATION, EXHAUST ONLY
  Single-Port Exhaust Venting
  Multiport Exhaust Venting
    Ventilating Heat-Pump Systems
  VENTILATION, SUPPLY-ONLY
    Forced-Air Supply Ventilation
    Multiport Supply Ventilation
  VENTILATION, BALANCED
    Heat Recovery Ventilation
    Energy Recovery Ventilators
  VENTILATION, BALANCED HEAT COST SAVINGS
  Air Filtering Strategies
  Particles in Indoor Air - Chart
  GAS EXPOSURE EFFECTS
  Gas Toxicity Levels
  Gases, Quick Guide to Indoor
  AIR CLEANER PURIFIER TYPES
    Particulate Air Cleaner Table
  Air Filter Effectiveness
  Real-World Effectiveness of Air Cleaners
  Air Pollutants, Finding & Reducing
  Radon Hazards
  Formaldehyde Hazards
  BIOLOGICAL POLLUTANTS
  BUY PRODUCTS for MOLD & ALLERGY CONTROL
  Volatile Organic Compounds VOCs
  Pesticide Exposure Hazards
  Lead Exposure Hazards
  Asbestos Exposure Hazards
  Combustion Appliance Contaminants
  Backdrafting Appliances
  Fireplace & Woodstove Contaminants
  INDOOR AIR HAZARDS TABLE
  INDOOR COMBUSTION PRODUCTS & IAQ
  ODORS, Smells, Gases in buildings
INDOOR AIR QUALITY METHODS COMPARED

LEAD POISONING HAZARDS GUIDE
LEED GREEN BUILDING CERTIFICATION
LEED Building Designation & IAQ

MILDEW in buildings ?
MILDEW ERRORS - MOLD PHOTOS
MILDEW REMOVAL & PREVENTION
MOISTURE CONTROL in buildings

MOLD: A COMPLETE GUIDE to TEST CLEAN PREVENT
MOLD ACTION GUIDE - WHAT TO DO ABOUT MOLD
MOLD ACTIVITY in buildings
MOLD AGE - Old is the Mold?
MOLD APPEARANCE - WHAT MOLD LOOKS LIKE
MOLD APPEARANCE - STUFF THAT IS NOT MOLD
MOLD ATLAS & PARTICLES INDEX
MOLD BY MICROSCOPE
MOLD in the PETRI DISH, PHOTOS
Mold on Books, Book Conservation
MOLD CLASSES, HAZARD LEVELS
MOLD CLEANERS - WHAT TO USE
MOLD CLEANUP COMPANIES
MOLD CLEANUP GUIDE- HOW TO GET RID OF MOLD
MOLD CLEARANCE INSPECTIONS
MOLD CLINICAL REFERENCE TEXTS
MOLD DETECTION & INSPECTION GUIDE
MOLD DOCTORS - ENVIRONMENTAL MEDICINE
MOLD EXPERT, WHEN TO HIRE
MOLD EXPOSURE, FOOD HAZARDS
MOLD EXPOSURE RISK LEVELS
MOLD EXPOSURE STANDARDS
MOLD FAQ's
MOLD FREQUENCY in buildings
MOLD GROWTH on SURFACES
MOLD INSPECTORS & MOLD TESTERS
MOLD LEVEL REPORTS
MOLD LEVELS IN buildings
MOLD BY MICROSCOPE
MOLD in the PETRI DISH, PHOTOS
MOLD ODORS, MUSTY SMELLS
MOLD PREVENTION GUIDE
MOLD RELATED ILLNESS GUIDE
MOLD RELATED ILLNESS SYMPTOMS
MOLD RESISTANT CONSTRUCTION
MOLD SPRAYS, SEALANTS, PAINTS
MOLD STANDARDS

MOLD TEST KITS
MOLD TEST KITS for DIY MOLD TESTS
MOLD TEST PROCEDURES
MOLD TEST REASONS
MOLD TESTING METHOD VALIDITY
MOLD TESTING SERVICES
MSDS Material Safety Data Sheets
MVOCs & MOLDY MUSTY ODORS
MYCOTOXIN EFFECTS of MOLD EXPOSURE

Nanomaterials Hazards
NOISE / SOUND DIAGNOSIS & CURE

ODORS, Smells, Gases in buildings-Diagnosis & Cure

RENTERS & TENANTS GUIDE TO MOLD

SAFETY HAZARDS GUIDE
SEPTIC SYSTEM INSPECT DIAGNOSE REPAIR
SICK HOUSE IAQ QUESTIONNAIRE
SEWAGE BACKUP TEST & CLEANUP
STAIN DIAGNOSIS

TECHNICAL & LAB PROCEDURES
THERMAL TRACKING
TRAPPED MOLD BETWEEN WOOD SURFACES

VENTILATION in buildings
  Air Bypass Leaks, Thermal Tracking
  AIR CHANGE RATE ACH HEAT SAVINGS
  ATTIC CONDENSATION CAUSE & CURE
  BALANCED VENTILATION, HEAT COST SAVINGS
  BATH & KITCHEN DESIGN GUIDE
  BATHROOM VENTILATION
  BLOWER DOORS & AIR INFILTRATION
  BLOWN-IN INSULATION
  BRICK or BLOCK WALL CAVITY INSULATION
  BRICK VENEER WALL INSULATION
  CATHEDRAL CEILING INSULATION
  CATHEDRAL CEILING VENTILATION
  HOT ROOF DESIGNS: Un-Vented Roof Solutions
  CRAWL SPACE VENTING & Dryout Procedures
  HOUSEWRAP AIR & VAPOR BARRIERS
  HUMIDITY LEVEL TARGET
  ICE DAM PREVENTION
  MOISTURE CONTROL in buildings
  MOISTURE CALCULATIONS
  MOISTURE METER STUDY
  MOISTURE PROBLEMS: CAUSE & CURE
  ROOF VENTILATION SPECIFICATIONS
  Roof Venting: Eaves Intake if no Overhang
  Roof Venting: Soffit Intake Vent-Continuous
  Roof Venting: Un-Vented Hot Roof Solutions
  ROOF VENTING ENERGY SAVING DETAILS
  ROOF VENTING NEEDED?
  VENTILATION DESIGN PROBLEMS & SOLUTIONS
  VENTILATION, WHOLE HOUSE STRATEGIES

VINYL Siding or PLASTIC Window ODORS in buildings
VINYL CHLORIDE HEALTH INFO

WALL SIDING TRIM & FINISHES
WALL FINISHES INTERIOR

WATER BARRIERS, EXTERIOR BUILDING
WATER ENTRY in buildings
WATER ODORS, CAUSE CURE

More Information

Ceiling whole house fan system (C) Daniel Friedman Exhaust Fan Ventilation System Guide
InspectAPedia®  -    

  • Guide to using exhaust fans for removing or keeping out indoor contaminants
  • Home exhaust fan ventilation strategies
  • Best methods for cleaning & filtering indoor air
InspectAPedia offers impartial, unbiased advice without conflicts of interest. We will block advertisements which we discover or readers inform us are associated with bad business practices, false-advertising, or junk science. our contact info is at InspectAPedia.com/Contact.htm.

This article explains using exhaust fan ventilation systems to improve indoor air quality in homes. This article includes excerpts or adaptations from Best Practices Guide to Residential Construction, by Steven Bliss, courtesy of Wiley & Sons. See ENVIRONMENTAL HAZARDS - INSPECT, TEST, REMEDY for our full list of environmental hazard identification and remedy related to buildings

© Copyright 2012 InspectAPedia.com, Daniel Friedman, Steve Bliss, Wiley & Sons, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use page top links to major topics or use links at the left of each page to navigate within topics and documents at this website. Green links show where you are in a document series or at this website.

Exhaust-Only Ventilation for Improving Indoor Air Quality

As detailed in Best Practices Guide to Residential Construction:

Exhaust-only ventilation is the most common approach, due to its simplicity and use of familiar components such as bathroom fans. However, unless houses are built very tight, there is little control over where fresh air enters the building. Also, depressurization can be a problem, particularly with high-capacity fans. In addition to the increased potential for backdrafting, a depressurized house tends to draw more soil gases, including radon if it is present. And in hot, humid climates, moist air infiltrating through exterior walls can condense on interior finishes such as the back face of vinyl wallpaper that is chilled by air conditioning.

Below we discuss three exaust-only ventilation approaches, followed by a discussion of Supply Only Ventilation and then VENTILATION, BALANCED.

  1. Single Port Exhaust Ventilation
  2. Multiport Exhaust Ventilation
  3. Ventilating Heat-Pump Water Heater

Single-Port Exhaust House Venting Systems

Single port exhaust ventilation system (C) J Wiley, Steven Bliss

The simplest and least expensive central ventilation system consists of an automatic timer wired to one centrally located bathroom or laundry fan so it cycles on and off for a portion of every hour or for the 8 to 12 hours per day when most people are home, typically mornings and evenings.

See the figure at left (click the image for details) about a single port exhaust house ventilation system.

The simplest ventilation system uses a single, centrally located exhaust fan that runs on a timer or continuously at a low speed. The fan may also serve as a bathroom or laundry fan, but a dedicated fan is optimal.

Passive air inlets are sometimes installed but will only work properly in very tight homes.

Illustration Source: Recommended Ventilation Strategies for Energy-Efficient Production Homes, 1998, by Judy A. Roberson, et al., Lawrence Berkeley National Laboratory, appearing in the text cited above.

Exhaust fan control switch: Since the house ventilation exhaust fan is doing double duty as a bath or laundry fan, it must have a manual override switch for intermittent use. In larger homes, two fans at separate locations can be used. Another upgrade is to use a dedicated fan in a central location, such as a hallway ceiling, which will provide better distribution of both exhaust and supply air.

Exhaust fan noise: For the house ventilation system to work well, it is important to use a quiet exhaust fan of one sone or less and choose a central location. Also, the door to the bathroom with the exhaust fan must be undercut by 3/4 to 1inch, along with doors to all 4 bedrooms and other rooms that require ventilation. An alternative is to connect the rooms with through-the-wall transfer grilles.

The biggest drawback to exhaust-only ventilation is that there is little control over distribution of the incoming air. Makeup air will come via the path of least resistance. In a leaky house, this might be a window or drop ceiling in the bathroom with the exhaust fan, leaving the rest of the house un served by the ventilation system. For this reason, single-port exhaust-only ventilation works well only in relatively small, tight houses.

  • Passive air inlets. Some contractors install passive air inlets in an effort to direct makeup air into bedrooms and main living areas. For these to work properly, however, the house must be extremely tight and doors must be left open or be cut at least an inch above the carpet. If a house is too leaky or rooms are cut off from household airflows, the inlets will function like other random holes in the building shell, leaking air inward or outward, depending on the wind, stack effect, and imbalances in the HVAC system.

    The inlets typically require at least 10 Pascals of negative pressure to operate. They do not eliminate depressurization as sometimes thought. In fact, they require it to work properly.

Multiport Exhaust House Venting Systems

Single port exhaust system for indoor air quality (C) J Wiley, Steven Bliss

This type of system uses a more powerful exhaust fan that is remotely mounted, typically in the attic or basement. See the figure at left for details of a multi-port whole house exhaust fan vent system).

A multiport exhaust system improves air distribution by picking up air from bathrooms and main living areas. These are often used in conjunction with passive air inlets. Exhaust-only systems are best used in homes with electric heating or sealed-combustion appliances where backdrafting is not a concern.

Illustration Source: Recommended Ventilation Strategies for Energy-Efficient Production Homes, 1998, by Judy A. Roberson, et al., Lawrence Berkeley National Laboratory, appearing in the text cited above.

The multiport house exhaust fan system is ducted to exhaust grilles in bathrooms, laundries, and other wet areas, and sometimes to a centrally located pickup point in the main living space. A room with no outside walls would also benefit from a pickup point.

Systems typically run on a low background speed with timer switches in bathrooms for higher-powered spot ventilation. If installed correctly, these systems are very quiet and provide good distribution of ventilation.

Multiport exhaust systems may incorporate passive air inlets (see description above) that install either in windows or through the wall, providing some control over supply air. The inlets, typically three or four for a small house, go in bedrooms, main living areas, and other occupied rooms, such as dens or home offices. Inlets should be placed high on the wall away from beds, chairs, or other places where drafts might cause discomfort. Placement near a window is preferred.

Because these systems use more powerful fans that depressurize the house, they should not be used in houses with fireplaces or atmospherically vented combustion appliances. They are also not recommended in hot climates, since hot, moist exterior air may be drawn into walls and condense behind interior surfaces chilled from air conditioning.

Packaged multiport house exhaust venting systems are available from American Aldes, Fantech, and a few other few manufacturers (see Resources, page 297 in Best Practices Guide to Residential Construction)

Ventilating Heat-Pump Water Heater

This variation on exhaust-only ventilation passes the exhaust air through a heat-pump water heater, reclaiming heat from the outgoing air stream. Some systems can be reversed in summer, functioning as a supply ventilation system while cooling and dehumidifying the incoming air. A packaged heat-pump ventilating system is available from Therma-Stor.

-- Adapted with permission from Best Practices Guide to Residential Construction.

Questions & Answers regarding this article

.

Ask a Question or Search InspectAPedia

HTML Comment Box is loading comments...

Share this Article      

...

Technical Reviewers & References

Google
  • InspectAPedia.com® - Daniel Friedman - Publisher & Editor.
  • Steven Bliss served as editorial director and co-publisher of The Journal of Light Construction for 16 years and previously as building technology editor for Progressive Builder and Solar Age magazines. He worked in the building trades as a carpenter and design/build contractor for more than ten years and holds a masters degree from the Harvard Graduate School of Education. Excerpts from his recent book, Best Practices Guide to Residential Construction, Wiley (November 18, 2005) ISBN-10: 0471648361, ISBN-13: 978-0471648369, appear throughout this website, with permission and courtesy of Wiley & Sons. Best Practices GuideĀ is available from the publisher, J. Wiley & Sons, and also at Amazon.com.
  • InspectAPedia Bookstore lists recommended books, organized by topic & available for purchase. Most of our articles also include a list of recommended books for the specific article topic as well as other references, and information sources.
  • Critique, contributions wanted: Contact Us to suggest corrections or additions to articles at this website, and if you wish, to receive online listing and credit as a contributor. Particular thanks are due to the many experts and also consumers who read and critique technical articles at InspectAPedia.com.
  • Additional technical contributors & reference sources for this article are listed below.

Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

ENVIRONMENTAL HAZARDS - INSPECT, TEST, REMEDY

AIR CLEANER PURIFIER TYPES
AIR FILTERS for HVAC SYSTEMS
AIR POLLUTANTS, COMMON INDOOR
ALLERGEN TESTS for buildings
ALLERGENS in buildings, RECOGNIZING
ALLERGY TESTS for PEOPLE
ALLERGY TEST ACCURACY
ANIMAL ALLERGENS / PET DANDER
ANIMAL ENTRY POINTS in buildings
ANIMAL ODORS IN buildings
ASBESTOS IDENTIFICATION IN buildings

BASEMENT MOLD
BATHROOM MOLD
BIBLIOGAPHY for ENVIRONMENTAL HEALTH, MOLD, IAQ
BIOLOGICAL POLLUTANTS
BLUE vs YELLOW COMBUSTION FLAMES
BLUERAY Recall
BUILDING SAFETY HAZARDS GUIDE
BUILDING SETTLEMENT

CARBON MONOXIDE - CO
CARBON MONOXIDE WARNING
CABINETS & COUNTERTOPS
CARPETING & INDOOR AIR QUALITY
CARPETING, SELECTION & INSTALLATION
CAT DANDER in buildings
Cell phone Radiation Hazards
CHAIN OF CUSTODY - TEST SAMPLE
CHIMNEY INSPECTION DIAGNOSIS REPAIR
CHIMNEYS & Flues - Asbestos Transite Pipe
CHINESE DRYWALL HAZARDS

DRYER VENTING
DRYWALL INSTALLATION Best Practices
DRYWALL MOLD
DRYWALL MOLD RESISTANT
ENERGY SAVINGS in buildings
ENGINEERED WOOD Flooring
ENGINEERED WOOD Products

FIRE DAMAGE vs MOLD DAMAGE
FLOOD DAMAGE ASSESSMENT, SAFETY & CLEANUP
MOLD: A COMPLETE GUIDE TO MOLD

ACTION GUIDE - WHAT TO DO ABOUT INDOOR MOLD
INDOOR AIR QUALITY & HOUSE TIGHTNESS
INDOOR AIR QUALITY IMPROVEMENT GUIDE
  Air Pollutants, Health Effects
  Air Pollutants, Common Indoor
  CABINETS & COUNTERTOPS
CARPETING & INDOOR AIR QUALITY
  CHINESE DRYWALL HAZARDS
  INDOOR AIR QUALITY IMPROVEMENT, KEY STEPS
  VENTILATION, WHOLE HOUSE STRATEGIES
  Whole House Ventilation Table
  VENTILATION, EXHAUST ONLY
  Single-Port Exhaust Venting
  Multiport Exhaust Venting
    Ventilating Heat-Pump Systems
  VENTILATION, SUPPLY-ONLY
    Forced-Air Supply Ventilation
    Multiport Supply Ventilation
  VENTILATION, BALANCED
    Heat Recovery Ventilation
    Energy Recovery Ventilators
  VENTILATION, BALANCED HEAT COST SAVINGS
  Air Filtering Strategies
  Particles in Indoor Air - Chart
  GAS EXPOSURE EFFECTS
  Gas Toxicity Levels
  Gases, Quick Guide to Indoor
  AIR CLEANER PURIFIER TYPES
    Particulate Air Cleaner Table
  Air Filter Effectiveness
  Real-World Effectiveness of Air Cleaners
  Air Pollutants, Finding & Reducing
  Radon Hazards
  Formaldehyde Hazards
  BIOLOGICAL POLLUTANTS
  BUY PRODUCTS for MOLD & ALLERGY CONTROL
  Volatile Organic Compounds VOCs
  Pesticide Exposure Hazards
  Lead Exposure Hazards
  Asbestos Exposure Hazards
  Combustion Appliance Contaminants
  Backdrafting Appliances
  Fireplace & Woodstove Contaminants
  INDOOR AIR HAZARDS TABLE
  INDOOR COMBUSTION PRODUCTS & IAQ
  ODORS, Smells, Gases in buildings
INDOOR AIR QUALITY METHODS COMPARED

LEAD POISONING HAZARDS GUIDE
LEED GREEN BUILDING CERTIFICATION
LEED Building Designation & IAQ

MILDEW in buildings ?
MILDEW ERRORS - MOLD PHOTOS
MILDEW REMOVAL & PREVENTION
MOISTURE CONTROL in buildings

MOLD: A COMPLETE GUIDE to TEST CLEAN PREVENT
MOLD ACTION GUIDE - WHAT TO DO ABOUT MOLD
MOLD ATLAS & PARTICLES INDEX
MOLD BY MICROSCOPE
MOLD in the PETRI DISH, PHOTOS
Mold on Books, Book Conservation
MOLD CLASSES, HAZARD LEVELS
MOLD CLEANERS - WHAT TO USE
MOLD CLEANUP COMPANIES
MOLD CLEANUP GUIDE- HOW TO GET RID OF MOLD
MOLD DETECTION & INSPECTION GUIDE
ODORS, Smells, Gases in buildings-Diagnosis & Cure
RENTERS & TENANTS GUIDE TO MOLD
SAFETY HAZARDS GUIDE
SEPTIC SYSTEM INSPECT DIAGNOSE REPAIR
SICK HOUSE IAQ QUESTIONNAIRE
SEWAGE BACKUP TEST & CLEANUP
STAIN DIAGNOSIS

TECHNICAL & LAB PROCEDURES
THERMAL TRACKING

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.
  • Best Practices Guide to Residential Construction, by Steven Bliss. John Wiley & Sons, 2006. ISBN-10: 0471648361, ISBN-13: 978-0471648369, Hardcover: 320 pages, available from Amazon.com and also Wiley.com. See our book review of this publication.
  • Decks and Porches, the JLC Guide to, Best Practices for Outdoor Spaces, Steve Bliss (Editor), The Journal of Light Construction, Williston VT, 2010 ISBN 10: 1-928580-42-4, ISBN 13: 978-1-928580-42-3, available from Amazon.com
  • Historic Preservation Technology: A Primer, Robert A. Young, Wiley (March 21, 2008) ISBN-10: 0471788368 ISBN-13: 978-0471788362

Air Leaks, Moisture Problems, Vapor Barriers & Ventilation in buildings - References, Products

  • Basement Moisture Control, U.S. Department of Energy
  • Building Pathology, Deterioration, Diagnostics, and Intervention, Samuel Y. Harris, P.E., AIA, Esq., ISBN 0-471-33172-4, John Wiley & Sons, 2001 [General building science-DF] ISBN-10: 0471331724 ISBN-13: 978-0471331728
  • Building Pathology: Principles and Practice, David Watt, Wiley-Blackwell; 2 edition (March 7, 2008) ISBN-10: 1405161035 ISBN-13: 978-1405161039
  • Crawl Space Moisture Control, U.S. Department of Energy
  • Energy Recover Ventilation Systems for buildings, U.S. Department of Energy
  • Energy Savings Methods: Whole House Systems Approach, U.S. Department of Energy
  • Log Homes: Minimizing Air Leakage in Log Homes, U.S. Department of Energy
  • Log Homes: Controlling Moisture in Log Homes, U.S. Department of Energy
  • Log Homes: Log Home Design, U.S. Department of Energy
  • Moisture Control in buildings, U.S. Department of Energy
  • Moisture Control in Walls, U.S. Department of Energy
  • Quality Standards for the Professional Remodeling Industry, National Association of Home Builders Remodelers Council, NAHB Research Foundation, 1987.
  • Quality Standards for the Professional Remodeler, N.U. Ahmed, # Home Builder Pr (February 1991), ISBN-10: 0867183594, ISBN-13: 978-0867183597
  • Natural Ventilation for buildings, U.S. Department of Energy
  • R-Value of Wood, U.S. Department of Energy
  • Spot Ventilation for houses, U.S. Department of Energy
  • Slab on Grade Foundation Moisture and Air Leakage, U.S. Department of Energy
  • Straw Bale Home Design, U.S. Department of Energy
  • "Vapor Barriers or Vapor Diffusion Retarders", U.S. DOE: how vapor barriers work, types of vapor diffusion barriers, installing vapor barrier
  • Ventilation for energy efficient buildings, Purpose, Strategies, etc.,
  • Weather-Resistive Barriers, how to select and install housewrap and other types of weather resistive barriers, U.S. DOE
  • Whole House Ventilation Systems, U.S. Department of Energy
  • Whole-House Balanced Ventilation Systems, U.S. Department of Energy
  • Whole-House Exhaust Ventilation Systems, U.S. Department of Energy
  • Whole-House Supply Ventilation Systems, U.S. Department of Energy
Home About Us Accuracy Contact Us Content Use Policy Privacy Website Description © 2012 Copyright InspectAPedia.com