InspectAPedia.com InspectAPedia®
 

Free Encyclopedia of Building & Environmental Inspection, Testing, Diagnosis, Repair

Ask a Question or Search InspectAPedia

  • HOME
  • AIR CONDITIONING
  • ELECTRICAL
  • EXTERIORS
  • HEATING
  • HOME INSPECTION
  • INTERIORS
  • PLUMBING
  • ROOFING
  • SEPTIC SYSTEMS
  • STRUCTURE
  • WATER SUPPLY
  • ENERGY SAVINGS
  • ENVIRONMENT
  • INDOOR AIR IAQ
  • INSULATION
  • MOLD INSPECT TEST REMOVE
  • NOISE
  • ODORS
  • SOLAR ENERGY
  • VENTILATION
  • EXPERTS DIRECTORY
  • CONTACT US


Mobile Phone/PDA website viewMobile View
FOOTING & FOUNDATION DRAINS
FOUNDATION CRACKS & DAMAGE GUIDE
ADVANCED INSPECTION METHODS
BASEMENT CEILING VAPOR BARRIER
BASEMENT HEAT LOSS
BASEMENT LEAKS, INSPECT FOR
BASEMENT WATERPROOFING
BEST CONSTRUCTION PRACTICES GUIDE
BUILDING NOISE DIAGNOSIS & CURE
CHIMNEY INSPECTION DIAGNOSIS REPAIR
CONDENSATION or SWEATING PIPES, TANKS
COOLING LOAD REDUCTION by ROOF VENTS
Cracks, Checking or Splitting Beams & Log Homes

CRAWL SPACES

DECK & PORCH CONSTRUCTION
DECK COLLAPSE Case Study
DECK FINISHES COATINGS PRESERVATIVES
DECK FLASHING LEAKS, ROT Case Study
DECKS, ROOFTOP CONSTRUCTION
DEFINITIONS of Mobile Home, Doublewide, Modular, Panelized
DEFINITIONS of ENGINEERED WOOD OSB LVL etc
CONDENSATION or SWEATING PIPES, TANKS
COOLING LOAD REDUCTION by ROOF VENTS

DEHUMIDIFICATION PROBLEMS
DEW POINT CALCULATION for WALLS
DEW POINT TABLE - CONDENSATION POINT GUIDE
DISASTER BUILDING INSPECTION & REPAIR SAFEY

EARTHQUAKE DAMAGED FOUNDATIONS
ENERGY SAVINGS in buildings

FLOOD DAMAGE ASSESSMENT, SAFETY & CLEANUP
FLOODS IN buildings-mold
FLOOR, ENGINEERED WOOD & LAMINATES
FLOOR FRAMING & SUBFLOOR for TILE
FLOOR TYPES & DEFECTS
FLOOR TILE ASBESTOS IDENTIFICATION
FLOOR TILE HISTORY & INGREDIENTS
FOOTING & FOUNDATION DRAINS
FOUNDATION BULGE or LEAN MEASUREMENTS
FOOTING & FOUNDATION DRAINS
FOUNDATION CRACKS & DAMAGE GUIDE
EARTHQUAKE DAMAGED FOUNDATIONS
FOUNDATION CONSTRUCTION TYPES
FOUNDATION INSPECTION METHODS
FOUNDATION FAILURES by TYPE & MATERIAL
FOUNDATION FAILURES by MOVEMENT TYPE
  BUCKLED FOUNDATIONS due to INSULATION?
    Insulation's Role in Foundation Damage
    Foundation Damage Generally Involves Water
    Ice Lenses, Frost Heaves vs. Frozen Soil Pressure
    Frost-Lens-Push-Proof Structural Pier
    Wet, Frozen Soil Expansion Data
    Main Cause of Foundation Failures in Clay Soils
    How Avoid Foundation Cave-Ins
  BULGED vs. LEANING FOUNDATIONS
  COMBINATIONS OF FOUNDATION MOVEMENT
  HORIZONTAL MOVEMENT IN FOUNDATIONS
  VERTICAL MOVEMENT IN FOUNDATIONS
FLOOD DAMAGE TO FOUNDATIONS
FOUNDATION DEFECTS OF OMISSION
FOUNDATION CRACK EVALUATION
FOUNDATION BULGE or LEAN MEASUREMENTS
FOUNDATION DAMAGE SEVERITY
FOUNDATION DAMAGE REPORTS
FOUNDATION INSPECTION STANDARDS
FOUNDATION MOVEMENT ACTIVE vs. STATIC
FOUNDATION REPAIR METHODS
  Bulged foundation Repairs
  Crack Repair Methods
  Horizontal Movement Repairs
  Seal Cracks by Polyurethane Foam Injection
  Seal Cracks in Concrete, How To
  Shrinkage Crack Repairs
  Vertical Foundation Movement Repairs
FROST HEAVES, FOUNDATION, SLAB
SITE FACTORS AFFECTING FOUNDATIONS
SINKHOLES, WARNING SIGNS
SINKING BUILDINGS
SLAB CRACK EVALUATION
FOUNDATION WATERPROOFING
FRAMING DAMAGE, INSPECTION, REPAIR
FRAMING DETAILS for BETTER INSULATION
FRAMING DETAILS for DOUBLE WALL HOUSES
FRAMING & SUBFLOOR for TILE
FRAMING MATERIALS, Age, Types
FRAMING METAL STUD PERFORMANCE
FRAMING METHODS, Age, Types
FRAMING SIZE & Spacing, Age, Types
FRAMING TABLES, SPANS for DECKS
FRENCH DRAINS
FROST HEAVES, FOUNDATION, SLAB
FRT PLYWOOD

HOUSEWRAP INSTALLATION DETAILS

ICE DAM PREVENTION

INDOOR AIR QUALITY & HOUSE TIGHTNESS

INSULATION CHOICES
Insulation Air & Heat Leaks
INSULATION FACT SHEET- DOE
INSULATION for GREENHOUSE or SOLARIUM
INSULATION IDENTIFICATION GUIDE
INSULATION INSPECTION & IMPROVEMENT
  Air Bypass Leaks, Thermal Tracking
  AIR LEAK DETECTION TOOLS
  AIR LEAK MINIMIZATION
  AIR SEAL STRATEGIES
  ASBESTOS IDENTIFICATION IN buildings
  ATTIC CONDENSATION CAUSE & CURE
  BASEMENT CEILING VAPOR BARRIER
  BASEMENT HEAT LOSS
  Blocked Soffit Intake Vents
  BLOWER DOORS & AIR INFILTRATION
  BLOWN-IN INSULATION
  BRICK or BLOCK WALL CAVITY INSULATION
  BRICK VENEER WALL INSULATION
  BUCKLED FOUNDATIONS due to INSULATION?
  CASEWORK, CABINETS, SHELVING INSTALLATION
  CATHEDRAL CEILING INSULATION
  CATHEDRAL CEILING VENTILATION
  HOT ROOF DESIGNS: Un-Vented Roof Solutions
  ENERGY SAVINGS in buildings
  ENERGY AUDIT - How to Use a Free One
  ENERGY SAVINGS MAXIMIZE RETURNS ON
  ENERGY SAVINGS PRIORITIES
  ENERGY SAVINGS RETROFIT CASE STUDY
  ENERGY SAVINGS RETROFIT LEAK SEALING GUIDE
  ENERGY SAVINGS RETROFIT OPTIONS
  ENERGY STAR PROGRAM
  ENERGY USE MONITORING
  FIBERGLASS DUCT, RIGID CONSTRUCTION
  FIRE PROTECTION FOR FOAM BOARD INSULATION
  FOUNDATION INSULATION OPTIONS
  FRAMING DETAILS for BETTER INSULATION
  FRAMING DETAILS for DOUBLE WALL HOUSES
  FRAMING METAL STUD PERFORMANCE
  HEATING COST SAVINGS METHODS
  HIGH MASS TRADEOFFS, HEATING vs COOLING
  HOUSE DOCTOR, how-to be
  Inspect Attics for Moisture or Mold
  Inspect Attics for Blocked Soffit Intake Vents
  Inspect Basements for Moisture or Mold
  Inspect Building Exterior - Roof Venting
  Inspect the Ridge Vent System from the Attic
  Inspect the Soffit Vent System from the Attic
  Insects & Foam Insulation
  Insulation Air & Heat Leaks
  INSULATION for GREENHOUSE or SOLARIUM
  INSULATION CHOICES
  INSULATION FACT SHEET- DOE
  INSULATION PLACEMENT in buildings
  INSULATION R-Values & Properties
  LOG HOME WALL INSULATION VALUES
  MOISTURE in BUILDING WALLS, EFFECTS
  MOISTURE in CELLULOSE INSULATION
  Mold in Fiberglass Insulation
  Mold on Books, Book Conservation
  Mold on Fiberboard Insulating Sheathing
  MOLD in Foam Insulation
  MOLD in INSULATION
  Mold Resistance of Foam Insulation
  MOLD PREVENTION AFTER FLOODING
  MOLD RESISTANT CONSTRUCTION
  PASCAL CALCULATIONS
  PASSIVE SOLAR DESIGN METHOD
  PHENOLIC FOAM INSULATION
  POLYISOCYANURATE FOAM INSULATION
  POLYISOCYANURATE FOAM BELOW SLABS
  POLYSTYRENE FOAM INSULATION
  RADIANT BARRIERS
  REFLECTIVE INSULATION
  RIGID FOAM USE INDOORS
  ROOF VENTING ENERGY SAVING DETAILS
  ROOF VENTING NEEDED?
  ROOF VENTILATION SPECIFICATIONS
  SLAB INSULATION LOCATION
  SLAB INSULATION LOCATION & EXTENT
  SLAB INSULATION, PASSIVE SOLAR
  SLATE THERMAL MASS for SOLAR HEAT STORAGE
  SOUND CONTROL in buildings
  STRESS SKIN INSULATED PANELS
  STUCCO OVER FOAM INSULATION
  SUPER HI-R INSULATION
  SUPERINSULATION RETROFIT
  Urea Formaldehyde Foam Insulation UFFI
  URETHANE FOAM Deterioration, Outgassing
  VAPOR BARRIERS & AIR SEALING at BAND JOISTS
  VAPOR BARRIERS & CONDENSATION in buildings
  VAPOR BARRIERS & HOUSEWRAP
  VAPOR CONDENSATION & BUILDING SHEATHING
  VERMICULITE INSULATION

INSULATION LOCATION - WHERE TO PUT IT
  BLOWN-IN INSULATION
  INSULATION CHOICES
  INSULATION FACT SHEET- DOE
  INSULATION LOCATION & QUANTITY for ATTICS
  INSULATION LOCATION for BASEMENT FLOORS
  INSULATION LOCATION for BASEMENT WALLS
  INSULATION LOCATION for BRICK or BLOCK WALL CAVITY
  INSULATION LOCATION for BRICK VENEER WALLS
  INSULATION LOCATION for CAPES, CRAWLSPACES
  INSULATION LOCATION for CATHEDRAL CEILINGS
  INSULATION LOCATION for GREENHOUSE or SOLARIUM
  INSULATION LOCATION for PASSIVE SOLAR FLOOR SLAB
  INSULATION LOCATION & EXTENT for SLABS
  INSULATION LOCATION for SOUND CONTROL
  INSULATION LOCATION for SUSPENDED PANELS
  INSULATION LOCATION for SWIMMING, INDOOR
INSULATION R-Values & Properties

KIT HOMES, Aladdin, Sears, Wards, Others
KITCHEN & BATH DESIGN GUIDE

LEED GREEN BUILDING CERTIFICATION
LOG HOME ENERGY EFFICIENCY
LOG HOME GUIDE

PORCH CONSTRUCTION & SCREENING
PRE-CUT & KIT HOMES
Preservative-Treated Framing Lumber
MODULAR HOME CONSTRUCTION
MOBILE HOMES, DOUBLEWIDES, TRAILERS
MOISTURE CONTROL in buildings

Nanomaterials Hazards
NOISE / SOUND DIAGNOSIS & CURE
NOISE CONTROL for HEATING SYSTEMS
NOISE CONTROL for FLOORS
NOISE CONTROL for PLUMBING
NOISE CONTROL for ROOFS

ROOFING INSPECTION & REPAIR
ROT, FUNGUS, TERMITES
ROT, TIMBER FRAME

SEARS KIT HOUSES
SHEATHING, Gypsum board
SHEATHING Homasote & Other Board
SHEATHING, OSB
SHEATHING, Plywood
SHEATHING, FOIL FACED - VENTS
SINKHOLES, WARNING SIGNS
SINKING BUILDINGS
SLAB CRACK EVALUATION
SLAB INSULATION, PASSIVE SOLAR
Splits in Structural Wood Beams
STAIRS, RAILINGS, LANDINGS, RAMPS
STONE CLEANING METHODS
STRAW BALE CONSTRUCTION

THERMAL EXPANSION of MATERIALS
THERMAL MASS in buildings
  THERMAL MASS FLOOR SLABS
  THERMAL MASS in UPSTAIRS
  THERMAL MASS WALL DESIGN
  THERMAL MASS in HOMES - STUDY

VENTILATION in BUILDINGS

WALL FINISHES INTERIOR
WATER BARRIERS, EXTERIOR BUILDING
WIND ENERGY SYSTEMS
WIND TURBINES & LIGHTNING
WIND WASHING INSULATION At EAVES
WINDOWS & DOORS

WINTERIZE A BUILDING
Wood Burning Heaters Fireplaces Stoves

ZONE VALVES

More Information

Bulged foundation due to frost and water (C) Daniel FriedmanCan Foundation Insulation Cause Buckled Foundation Damage?
InspectAPedia®  -    

  • Causes of Buckled Foundations: Is Insulation Guilty?
  • Roles of water, frost, clay soils, and insulation in foundation damage cases
  • Can foundation insulation cause cracked, bulged, or buckled foundation walls?
  • What is the difference between ice lensing and freezing earth pressure?
  • How much pressure is exerted by wet, freezing soil?
  • How do we prevent foundation damage - key steps
  • Solar Age Magazine Articles on Renewable Energy, Energy Savings, Construction Practices

This article discusses the causes of foundation cracks, buckling, or collapse in areas of freezing weather, clay soils, or wet soils. We discuss the role of building insulation in foundation damage, the question of whether or not foundation insulation is the root cause of foundation damage or collapse in very cold climates, and the role that water and frost play in foundation damage. We include suggestions to avoid foundation collapses.

InspectAPedia offers impartial, unbiased advice without conflicts of interest. We will block advertisements which we discover or readers inform us are associated with bad business practices, false-advertising, or junk science. Our contact info is at InspectAPedia.com/Contact.htm.

In this article series we include solar energy, solar heating, solar hot water, and related building energy efficiency improvement articles reprinted/adapted/excerpted with permission from Solar Age Magazine - editor Steven Bliss. Photo (above) shows a badly buckled concrete foundation. Notice the water stains starting at the top of the wall in the right side of the photo?

Readers who need to diagnose the cause and decide on the cure for foundation damage should start at FOUNDATION CRACKS & DAMAGE GUIDE. Readers should also see BASEMENT HEAT LOSS for a discussion of basement and foundation insulation. Contact us to suggest text changes and additions and, if you wish, to receive online listing and credit for that contribution.

© Copyright 2012 InspectAPedia.com, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use page top links to major topics or use links at the left of each page to navigate within topics and documents at this website. Green links show where you are in a document series or at this website.

What is Foundation Insulation's Role in Foundation Buckling

"Buckled Foundations: Is Insulation Guilty?" - links to the original article in PDF form immediately below are followed by an expanded/updated online version of this article. This article by Steven Bliss reviews four case reports addressing foundation damage in which the building insulation may have played a role.

  • BUCKLED FOUNDATIONS due to INSULATION? page 1 - PDF document, use your browser's back button to return to this page
  • BUCKLED FOUNDATIONS due to INSULATION? page 2
  • BUCKLED FOUNDATIONS due to INSULATION? page 3

Buckled building foundation (C) InspectAPedia.comThe text below includes and expands upon the original material (the two PDF files above); it paraphrases, quotes-from, updates, and comments an original article, (see links just above) from Solar Age Magazine and written by Steven Bliss.

Readers should see BASEMENT HEAT LOSS for a detailed discussion of insulating building foundations. See POLYSTYRENE FOAM INSULATION for a guide to using this material in below-grade foundation insulation applications. See TERMITE SHIELDS vs TERMITICIDE for a discussion of avoiding insect damage when foam insulating board is used below or at ground level. See WET BASEMENT PREVENTION for other exterior treatments of building foundation walls to combine foundation insulation with basement waterproofing membranes and drainage systems.

Buckled Foundations: Is Insulation Guilty?

Every now and then we hear a story about insulation causing a foundation wall to crack. But until I received a letter from Minnesota engineer Paul Shea, I had never had one of these stories verified. Shea wrote that "Buckling of foundations as a result of adding insulation is well known in Duluth, Minnesota. I personally audited three houses in Duluth that performed OK until insulation was installed."

When I called Shea, he had four cases to report, two of which took place in "vegetable rooms" - small basement alcoves for storing product - that had been insulated in otherwise uninsulated basements. In each case, said Shea, the walls buckled after they had been insulated on the building interior side, either with fiberglass or polystyrene insulation.

The failed foundation walls faced uphill sides of sloped sites, which acted as catch basins for rain and meltwater. As far as he knows, all of the walls were of un reinforced concrete block. The soil in the area, he said, is very heavy clay. The climate is very cold (10,000 degree days) and wet. Frost penetrates to five feet and deeper in Duluth, Minnesota. [DJF Note: we have seen similar foundation collapses in New York State where the combination of freezing with very wet soils pushed in the masonry block foundation wall. In similar structures where there is not a problem of wet soils (from improper surface or roof runoff disposal) these problems are rarely seen.]

I Tracked down another foundation damage case in the area and spoke with the owner, who, incidentally, sells masonry supplies for a living. He had insulated two adjacent foundation walls with extruded polystyrene, planning to finish the other two walls later. That winter, one wall cracked and the other burst, pushing up in six inches at one joint. The wall that cracked had a concrete patio next to it. The wall that gave way abutted the driveway. The house, said the owner, had been built around 1920. It cost him $3600 to repair the two foundation walls. At the time the basement burst, he said, the room was cold - it had no heating boiler or furnace - just a small, rarely-used space heater.

In the Duluth area, said the owner, many builders won't insulate foundations on the building interior. Even when they put insulation on the foundation exterior, he said, some hold it a foot short of the footing - to let household heat bleed into the soil to moderate the freezing. Minnesota Power Co. energy auditor Roger Freeman recommends that the basement insulation stop two feet below grade and then flare out if desired (see the "Scandinavian Flared Foundation Insulation Option" described at BASEMENT HEAT LOSS). Some Minnesota contractors refuse (in the 1980's) to install basement insulation altogether - though this cannot be an energy efficient building design.

Across the state of Minnesota, in Fargo, North Dakota, they don't seem to have this problem. Soils Engineer Duane Heley, of Midwest Testing, in Fargo, said he has seen many basements damaged by expansive clay soils, but none he could attribute to frost problems. On the other hand, he has seen frozen soil drag up and displace exterior foundation insulation (frost lensing is discussed at VERTICAL MOVEMENT IN FOUNDATIONS). For that reason, he recommends placing foundation insulation on the building interior, where Mother Nature will not push it around.

In 11,000-degree-day Saskatchewan, they don't seem to have any problems with basement insulation according to building researcher Bob Dumont. The reason may be that Saskatchewan has only 15 inches of precipitation annually, compared with Duluth's 28 inches of rainfall, most of which drops in the summer and fall - saturating clay soils there. Other cold-climate soils engineers I contacted around the country concurred that they had never seen frost action cause structural damage to residential foundations.

Foundation Damage from Frost Generally Also Involves Water (Ice)

Frost push damage to a foundation (C) Daniel FriedmanDJF Note: we have seen foundation collapses in New York State where the combination of freezing with very wet soils pushed in the masonry block foundation wall. In similar structures where there is not a problem of wet soils (from improper surface or roof runoff disposal) these problems are rarely seen.

Solving the site's water problems seems critical for builders and owners who want both energy efficient buildings (incorporating at least some foundation insulation) and also to avoid frost damage to the foundation caused by the combination of water and freezing conditions.

In the Hudson Valley of New York State when we see horizontal cracks in the upper third of a concrete block foundation wall that is mostly below grade (photograph at left), we associate that damage with water and frost - the frost line is about three feet down in the Hudson Valley.

When we see cracks and movement low on the foundation wall, near the floor, we associate that damage with earth pressure, possibly exacerbated by the extra weight of water and vehicles, but not with frost. More about diagnosing horizontal foundation cracks and movement is at HORIZONTAL MOVEMENT IN FOUNDATIONS.   BUCKLED FOUNDATIONS due to INSULATION?

Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

  BUCKLED FOUNDATIONS due to INSULATION?
    Insulation's Role in Foundation Damage
    Foundation Damage Generally Involves Water
    Ice Lenses, Frost Heaves vs. Frozen Soil Pressure
    Frost-Lens-Push-Proof Structural Pier
    Wet, Frozen Soil Expansion Data
    Main Cause of Foundation Failures in Clay Soils
    How Avoid Foundation Cave-Ins

Here we include solar energy, solar heating, solar hot water, and related building energy efficiency improvement articles reprinted/adapted/excerpted with permission from Solar Age Magazine - editor Steven Bliss.

Questions & Answers regarding this article

.

Ask a Question or Search InspectAPedia

HTML Comment Box is loading comments...

Share this Article      

...

Technical Reviewers & References

  • InspectAPedia.com® - Daniel Friedman - Publisher & Editor.
  • InspectAPedia Bookstore lists recommended books, organized by topic & available for purchase. Most of our articles also include a list of recommended books for the specific article topic as well as other references, and information sources.
  • Critique, contributions wanted: Contact Us to suggest corrections or additions to articles at this website, and if you wish, to receive online listing and credit as a contributor. Particular thanks are due to the many experts and also consumers who read and critique technical articles at InspectAPedia.com.
  • Additional technical contributors & reference sources for this article are listed below.

Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

 FOOTING & FOUNDATION DRAINS
FOUNDATION CRACKS & DAMAGE GUIDE
ADVANCED INSPECTION METHODS
BASEMENT CEILING VAPOR BARRIER
BASEMENT HEAT LOSS
BASEMENT LEAKS, INSPECT FOR
BASEMENT WATERPROOFING
BEST CONSTRUCTION PRACTICES GUIDE
BUILDING SAFETY HAZARDS GUIDE

CHIMNEY INSPECTION DIAGNOSIS REPAIR
CONDENSATION or SWEATING PIPES, TANKS
COOLING LOAD REDUCTION by ROOF VENTS
Cracks, Checking or Splitting Beams & Log Homes

CRAWL SPACES

DECK & PORCH CONSTRUCTION
DECK COLLAPSE Case Study
DECK FINISHES COATINGS PRESERVATIVES
DECK FLASHING LEAKS, ROT Case Study
DECKS, ROOFTOP CONSTRUCTION
DEFINITIONS of Mobile Home, Doublewide, Modular, Panelized
DEFINITIONS of ENGINEERED WOOD OSB LVL etc
CONDENSATION or SWEATING PIPES, TANKS
COOLING LOAD REDUCTION by ROOF VENTS

DEHUMIDIFICATION PROBLEMS
DEW POINT CALCULATION for WALLS
DEW POINT TABLE - CONDENSATION POINT GUIDE
DISASTER BUILDING INSPECTION & REPAIR SAFEY

EARTHQUAKE DAMAGED FOUNDATIONS
ENERGY SAVINGS in buildings

FLOOD DAMAGE ASSESSMENT, SAFETY & CLEANUP
FLOODS IN buildings-mold
FLOOR, ENGINEERED WOOD & LAMINATES
FLOOR FRAMING & SUBFLOOR for TILE
FLOOR TYPES & DEFECTS
FLOOR TILE ASBESTOS IDENTIFICATION
FLOOR TILE HISTORY & INGREDIENTS
FOOTING & FOUNDATION DRAINS
FOUNDATION BULGE or LEAN MEASUREMENTS
FOOTING & FOUNDATION DRAINS
FOUNDATION CRACKS & DAMAGE GUIDE
EARTHQUAKE DAMAGED FOUNDATIONS
FOUNDATION CONSTRUCTION TYPES
FOUNDATION INSPECTION METHODS
FOUNDATION FAILURES by TYPE & MATERIAL
FOUNDATION FAILURES by MOVEMENT TYPE
  BUCKLED FOUNDATIONS due to INSULATION?
    Insulation's Role in Foundation Damage
    Foundation Damage Generally Involves Water
    Ice Lenses, Frost Heaves vs. Frozen Soil Pressure
    Frost-Lens-Push-Proof Structural Pier
    Wet, Frozen Soil Expansion Data
    Main Cause of Foundation Failures in Clay Soils
    How Avoid Foundation Cave-Ins
  BULGED vs. LEANING FOUNDATIONS
  COMBINATIONS OF FOUNDATION MOVEMENT
  HORIZONTAL MOVEMENT IN FOUNDATIONS
  VERTICAL MOVEMENT IN FOUNDATIONS
FLOOD DAMAGE TO FOUNDATIONS
FOUNDATION DEFECTS OF OMISSION
FOUNDATION CRACK EVALUATION
FOUNDATION BULGE or LEAN MEASUREMENTS
FOUNDATION DAMAGE SEVERITY
FOUNDATION DAMAGE REPORTS
FOUNDATION INSPECTION STANDARDS
FOUNDATION MOVEMENT ACTIVE vs. STATIC
FOUNDATION REPAIR METHODS
SITE FACTORS AFFECTING FOUNDATIONS
SINKHOLES, WARNING SIGNS
SINKING BUILDINGS
SLAB CRACK EVALUATION
FOUNDATION WATERPROOFING
FRAMING DAMAGE, INSPECTION, REPAIR
FRAMING DETAILS for BETTER INSULATION
FRAMING DETAILS for DOUBLE WALL HOUSES
FRAMING & SUBFLOOR for TILE
FRAMING MATERIALS, Age, Types
FRAMING METAL STUD PERFORMANCE
FRAMING METHODS, Age, Types
FRAMING SIZE & Spacing, Age, Types
FRAMING TABLES, SPANS for DECKS
FRENCH DRAINS
FROST HEAVES, FOUNDATION, SLAB
FRT PLYWOOD

HOUSEWRAP INSTALLATION DETAILS

ICE DAM PREVENTION

INDOOR AIR QUALITY & HOUSE TIGHTNESS

INSULATION CHOICES
Insulation Air & Heat Leaks
INSULATION FACT SHEET- DOE
INSULATION for GREENHOUSE or SOLARIUM
INSULATION IDENTIFICATION GUIDE
INSULATION INSPECTION & IMPROVEMENT
INSULATION LOCATION - WHERE TO PUT IT
  INSULATION LOCATION & QUANTITY for ATTICS
  INSULATION LOCATION for BASEMENT FLOORS
  INSULATION LOCATION for BASEMENT WALLS
  INSULATION LOCATION for BRICK or BLOCK WALL CAVITY
  INSULATION LOCATION for BRICK VENEER WALLS
  INSULATION LOCATION for CAPES, CRAWLSPACES
  INSULATION LOCATION for CATHEDRAL CEILINGS
  INSULATION LOCATION for GREENHOUSE or SOLARIUM
  INSULATION LOCATION for PASSIVE SOLAR FLOOR SLAB
  INSULATION LOCATION & EXTENT for SLABS
  INSULATION LOCATION for SOUND CONTROL
  INSULATION LOCATION for SUSPENDED PANELS
  INSULATION LOCATION for SWIMMING, INDOOR
INSULATION R-Values & Properties

KIT HOMES, Aladdin, Sears, Wards, Others
KITCHEN & BATH DESIGN GUIDE

LEED GREEN BUILDING CERTIFICATION
LOG HOME ENERGY EFFICIENCY
LOG HOME GUIDE

PORCH CONSTRUCTION & SCREENING
PRE-CUT & KIT HOMES
Preservative-Treated Framing Lumber
MODULAR HOME CONSTRUCTION
MOBILE HOMES, DOUBLEWIDES, TRAILERS
MOISTURE CONTROL in buildings

Nanomaterials Hazards
NOISE / SOUND DIAGNOSIS & CURE
NOISE CONTROL for HEATING SYSTEMS
NOISE CONTROL for FLOORS
NOISE CONTROL for PLUMBING
NOISE CONTROL for ROOFS

ROOFING INSPECTION & REPAIR
ROT, FUNGUS, TERMITES
ROT, TIMBER FRAME

SEARS KIT HOUSES
SHEATHING, Gypsum board
SHEATHING Homasote & Other Board
SHEATHING, OSB
SHEATHING, Plywood
SHEATHING, FOIL FACED - VENTS
SINKHOLES, WARNING SIGNS
SINKING BUILDINGS
SLAB CRACK EVALUATION
SLAB INSULATION, PASSIVE SOLAR
Splits in Structural Wood Beams
STAIRS, RAILINGS, LANDINGS, RAMPS
STONE CLEANING METHODS
STRAW BALE CONSTRUCTION

THERMAL EXPANSION of MATERIALS
THERMAL MASS in buildings
  THERMAL MASS FLOOR SLABS
  THERMAL MASS in UPSTAIRS
  THERMAL MASS WALL DESIGN
  THERMAL MASS in HOMES - STUDY

VENTILATION in BUILDINGS

WALL FINISHES INTERIOR

WATER BARRIERS, EXTERIOR BUILDING
WATER ENTRY in buildings
WIND ENERGY SYSTEMS
WIND TURBINES & LIGHTNING
WIND WASHING INSULATION At EAVES
WINDOWS & DOORS

WINTERIZE A BUILDING

  • Solar Age Magazine was the official publication of the American Solar Energy Society. The contemporary solar energy magazine associated with the Society is Solar Today. "Established in 1954, the nonprofit American Solar Energy Society (ASES) is the nation's leading association of solar professionals & advocates. Our mission is to inspire an era of energy innovation and speed the transition to a sustainable energy economy. We advance education, research and policy. Leading for more than 50 years. ASES leads national efforts to increase the use of solar energy, energy efficiency and other sustainable technologies in the U.S. We publish the award-winning SOLAR TODAY magazine, organize and present the ASES National Solar Conference and lead the ASES National Solar Tour – the largest grassroots solar event in the world."
  • Steven Bliss served as editorial director and co-publisher of The Journal of Light Construction for 16 years and previously as building technology editor for Progressive Builder and Solar Age magazines. He worked in the building trades as a carpenter and design/build contractor for more than ten years and holds a masters degree from the Harvard Graduate School of Education. Excerpts from his recent book, Best Practices Guide to Residential Construction, Wiley (November 18, 2005) ISBN-10: 0471648361, ISBN-13: 978-0471648369, appear throughout this website, with permission and courtesy of Wiley & Sons. Best Practices Guide is available from the publisher, J. Wiley & Sons, and also at Amazon.com.
    Excerpts with updates and annotations expanding the original Best Practices Guide text can be found in the online review and book summary at BEST CONSTRUCTION PRACTICES GUIDE
    and also at DECK & PORCH CONSTRUCTION, at INDOOR AIR QUALITY IMPROVEMENT GUIDE, and in other articles found at InspectAPedia.com such as HOUSEWRAP AIR & VAPOR BARRIERS, SOUND CONTROL in buildings, and other topics.

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.
  • ...
Home About Us Accuracy Contact Us Content Use Policy Privacy Website Description © 2012 Copyright InspectAPedia.com