InspectAPedia.com InspectAPedia®
 

Free Encyclopedia of Building & Environmental Inspection, Testing, Diagnosis, Repair

Ask a Question or Search InspectAPedia

  • HOME
  • AIR CONDITIONING
  • ELECTRICAL
  • EXTERIORS
  • HEATING
  • HOME INSPECTION
  • INTERIORS
  • PLUMBING
  • ROOFING
  • SEPTIC SYSTEMS
  • STRUCTURE
  • WATER SUPPLY
  • ENERGY SAVINGS
  • ENVIRONMENT
  • INDOOR AIR IAQ
  • INSULATION
  • MOLD INSPECT TEST REMOVE
  • NOISE
  • ODORS
  • SOLAR ENERGY
  • VENTILATION
  • EXPERTS DIRECTORY
  • CONTACT US


Mobile Phone/PDA website viewMobile View
AIR CONDITIONING & HEAT PUMP SYSTEMS
ENERGY SAVINGS in buildings

INSULATION IDENTIFICATION GUIDE

INSULATION INSPECTION & IMPROVEMENT
INTERIORS of buildings

ACOUSTICAL SEALANT CHOICES
AIR BYPASS LEAKS
AIR CHANGE RATE ACH HEAT SAVINGS
AIR CLEANER PURIFIER TYPES

AIR FILTER EFFECTIVENESS
AIR FILTERS for HVAC SYSTEMS
AIR FILTERS, OPTIMUM INDOOR
AIR FILTERS, SOURCES FOR
AIR FILTERING STRATEGIES
AIR FILTERING CONTINUOUS FAN OPERATION
AIR HANDLER / BLOWER UNITS
AIR POLLUTANTS, COMMON INDOOR

AIR LEAK DETECTION TOOLS
  Find Heat Loss & Air Leaks
  Heat Loss Investigation Sequence
  Blower Door Test Data Results
  Smoke Gun for Air Leaks
  Smoke Pencil / Smoke Gun Suppliers
  Attic Energy Losses - InfraRed
  Basement Energy Losses- IR & Visual
  Duct System Air Movement
  Living Space Heat Loss
  Targets & Hidden Leak Points
  Thermography IR Infra Red & Thermal Scanners
  Convective Loops & Thermal Bypass Leaks
  HOUSE DOCTOR, how-to be
  Insulation Air & Heat Leaks
  The Bottom Line on Energy Retrofits
AIR LEAK MINIMIZATION
AIR LEAK SEALING PROCEDURE
AIR SEALING STRATEGIES

ANIMAL ALLERGENS
APPLIANCE EFFICIENCY RATINGS
ASBESTOS FLOORING HAZARD REDUCTION
ASBESTOS-FREE INSULATION MATERIALS
ASBESTOS IDENTIFICATION IN buildings
ATTIC LEAKS, CONDENSATION & ATTIC MOLD
ATTIC VENTILATION

BASEMENT CEILING VAPOR BARRIER
BASEMENT HEAT LOSS
BASEMENT LEAKS, INSPECT FOR
BASEMENT WATERPROOFING

BATH & KITCHEN DESIGN GUIDE
BATHROOM VENTILATION
BIOGAS PRODUCTION & USE
BLOWER DOORS & AIR INFILTRATION
BLOWER FAN CONTINUOUS OPERATION
BLOWER FAN OPERATION & TESTING
BLOWN-IN INSULATION

BRICK LINED WALLS
BRICK VENEER WALL INSULATION
BRICK VENEER WALL Loose, Bulged
BRICK WALL DRAINAGE WEEP HOLES
BUCKLED FOUNDATIONS due to INSULATION?
BUILDING NOISE DIAGNOSIS & CURE

CATHEDRAL CEILING INSULATION
CATHEDRAL CEILING VENTILATION
CEILING FINISHES INTERIOR
CEILINGS, DROP or SUSPENDED PANEL
CEILINGS, PLASTER TYPES

CHIMNEY INSPECTION DIAGNOSIS & REPAIR
COOLING LOAD REDUCTION by ROOF VENTS
COMBUSTION AIR for TIGHT buildings
CONDENSING BOILERS/FURNACES DAMAGE

CATHEDRAL CEILING INSULATION
CATHEDRAL CEILING VENTILATION
CEILING FINISHES INTERIOR
CEILINGS, DROP or SUSPENDED PANEL
CEILINGS, PLASTER TYPES

CHIMNEY INSPECTION DIAGNOSIS & REPAIR
COOLING LOAD REDUCTION by ROOF VENTS
COMBUSTION AIR for TIGHT BUILDINGS
CONDENSING BOILERS/FURNACES DAMAGE
CONDENSATION or SWEATING PIPES, TANKS
COOLING LOAD REDUCTION by ROOF VENTS
CRAWL SPACES

DEFINITION of Heating & Cooling Terms
DEHUMIDIFICATION PROBLEMS
DEW POINT CALCULATION for WALLS
DEW POINT TABLE - CONDENSATION POINT GUIDE
DUCT SYSTEM & DUCT DEFECTS

ELECTRICAL INSPECTION, DIAGNOSIS, REPAIR

ENERGY SAVINGS in buildings
  AFUE DEFINITION, RATINGS
  AIR BYPASS LEAKS
  AIR CHANGE RATE ACH HEAT SAVINGS
  AIR CONDITIONING HEAT PUMP SAVINGS
  AIR LEAK SEALING PROCEDURE
  APPLIANCE EFFICIENCY RATINGS
  ATTIC LEAKS, CONDENSATION & ATTIC MOLD
  COOLING LOAD REDUCTION by ROOF VENTS
  ENERGY AUDIT - How to Use a Free One
  ENERGY SAVINGS MAXIMIZE RETURNS ON
  ENERGY SAVINGS PRIORITIES
  ENERGY SAVINGS RETROFIT CASE STUDY
  ENERGY SAVINGS RETROFIT LEAK SEALING GUIDE
  ENERGY SAVINGS RETROFIT OPTIONS
  ENERGY STAR PROGRAM
  ENERGY USE MONITORING
  GLASS vs HEAT MIRROR SOLAR GAIN/Loss
  HEAT LOSS in buildings
  HEATING COST SAVINGS METHODS
  HIGH MASS TRADEOFFS, HEATING vs COOLING
  HOUSE DOCTOR, how-to be
  INSULATION INSPECTION & IMPROVEMENT
  INSULATION LOCATION - WHERE TO PUT IT
  RADIANT BARRIERS
  REFLECTIVE INSULATION
  ROOF COLOR RECOMMENDATIONS
  Skylight Energy Efficiency
  SOLAR ENERGY SYSTEMS
  THERMAL MASS in buildings
  TIMERS for ELECTRIC WATER HEATERS
  VENTILATION, BALANCED HEAT COST SAVINGS
  WIND ENERGY SYSTEMS
  WINDOW EFFICIENCY Features & Ratings
  WOOD, COAL STOVES & FIREPLACES

ENVIRONMENTAL HAZARDS - INSPECT, TEST, REMEDY

EXTERIOR WALL SIDING TRIM & FINISHES

FIBERGLASS INSULATION
FIBERGLASS HAZARDS
FIBERGLASS INSULATION MOLD

FLASHING MEMBRANES PEEL & STICK
FLAT ROOF MOISTURE & CONDENSATION

FLOOD DAMAGE ASSESSMENT, SAFETY & CLEANUP
FLOODS IN buildings-mold

FLOOR, CONCRETE SLAB CHOICES
FLOOR, CONCRETE SLAB POURED FINISH
FLOOR DAMAGE DIAGNOSIS
FLOOR RADIANT HEAT Mistakes to Avoid
FLOOR TYPES & DEFECTS

FOUNDATION WATERPROOFING
FRENCH DRAINS
FRAMING DETAILS for BETTER INSULATION
FRAMING DETAILS for DOUBLE WALL HOUSES
FRAMING METAL STUD PERFORMANCE
FREEZE-PROOF A BUILDING
FROST HEAVES, FOUNDATION, SLAB

GREEN BUILDING CONSTRUCTION CODES GUIDES
GREENHOUSE DESIGN for SOLAR HEATING

HEAT LOSS in buildings
HEAT LOSS DETECTION TOOLS
  Find Heat Loss & Air Leaks
  Heat Loss Investigation Sequence
  Blower Door Test Data Results
  Smoke Gun for Air Leaks
  Smoke Pencil / Smoke Gun Suppliers
  Attic Energy Losses - InfraRed
  Basement Energy Losses- IR & Visual
  Duct System Air Movement
  Living Space Heat Loss
  Targets & Hidden Leak Points
  Thermography IR Infra Red & Thermal Scanners
  Convective Loops & Thermal Bypass Leaks
  HOUSE DOCTOR, how-to be
  Insulation Air & Heat Leaks
  The Bottom Line on Energy Retrofits
HEAT LOSS INDICATORS
HEAT LOSS PREVENTION PRIORITIES
HEAT LOSS R U & K VALUE CALCULATION
HEAT TAPES & CABLES on Roofs for Ice Dams
HEATING COST SAVINGS METHODS

HOT ROOF DESIGNS: Un-Vented Roof Solutions
HOUSEWRAP AIR & VAPOR BARRIERS
HOUSE DOCTOR, how-to be

HUMIDITY LEVEL TARGET

ICE DAM PREVENTION
INSULATION CHOICES
Insulation Air & Heat Leaks
INSULATION FACT SHEET- DOE
INSULATION for GREENHOUSE or SOLARIUM
INSULATION IDENTIFICATION GUIDE
INSULATION INSPECTION & IMPROVEMENT
INSULATION LOCATION - WHERE TO PUT IT
  INSULATION LOCATION & QUANTITY for ATTICS
  INSULATION LOCATION for BASEMENT FLOORS
  INSULATION LOCATION for BASEMENT WALLS
  INSULATION LOCATION for BRICK or BLOCK WALL CAVITY
  INSULATION LOCATION for BRICK VENEER WALLS
  INSULATION LOCATION for CAPES, CRAWLSPACES
  INSULATION LOCATION for CATHEDRAL CEILINGS
  INSULATION LOCATION for GREENHOUSE or SOLARIUM
  INSULATION LOCATION for PASSIVE SOLAR FLOOR SLAB
  INSULATION LOCATION & EXTENT for SLABS
  INSULATION LOCATION for SOUND CONTROL
  INSULATION LOCATION for SUSPENDED PANELS
  INSULATION LOCATION for SWIMMING, INDOOR

INSULATION MOLD
INSULATION R-Values & Properties

INSULATION IDENTIFICATION GUIDE
INSULATION INSPECTION & IMPROVEMENT
  ATTIC CONDENSATION CAUSE & CURE
  Air Bypass Leaks, Thermal Tracking
  Blocked Soffit Intake Vents
  BRICK or BLOCK WALL CAVITY INSULATION
  BRICK VENEER WALL INSULATION
  CATHEDRAL CEILING INSULATION
  CATHEDRAL CEILING VENTILATION
  ENERGY SAVINGS in buildings
  FIBERGLASS DUCT, RIGID CONSTRUCTION
  FIRE PROTECTION FOR FOAM BOARD INSULATION
  FOUNDATION INSULATION OPTIONS
  FRAMING DETAILS for BETTER INSULATION
  FRAMING DETAILS for DOUBLE WALL HOUSES
  FRAMING METAL STUD PERFORMANCE
  HOT ROOF DESIGNS: Un-Vented Roof Solutions
  Inspect Attics for Moisture or Mold
  Inspect Attics for Blocked Soffit Intake Vents
  Inspect Basements for Moisture or Mold
  Inspect Building Exterior - Roof Venting
  Inspect the Ridge Vent System from the Attic
  Inspect the Soffit Vent System from the Attic
  Insects & Foam Insulation
  HOUSE DOCTOR, how-to be
  Insulation Air & Heat Leaks
  INSULATION R-Values & Properties
  LOG HOME WALL INSULATION VALUES
  MOISTURE in BUILDING WALLS, EFFECTS
  MOISTURE in CELLULOSE INSULATION
  Mold in Fiberglass Insulation
  Mold on Books, Book Conservation
  Mold on Fiberboard Insulating Sheathing
  MOLD in Foam Insulation
  MOLD in INSULATION
  Mold Resistance of Foam Insulation
  MOLD PREVENTION AFTER FLOODING
  MOLD RESISTANT CONSTRUCTION
  PASCAL CALCULATIONS
  PHENOLIC FOAM INSULATION
  POLYISOCYANURATE FOAM INSULATION
  POLYISOCYANURATE FOAM BELOW SLABS
  POLYSTYRENE FOAM INSULATION
  RADIANT BARRIERS
  REFLECTIVE INSULATION
  RIGID FOAM USE INDOORS
  STRESS SKIN INSULATED PANELS
  STUCCO OVER FOAM INSULATION
  SUPER HI-R INSULATION
  SUPERINSULATION RETROFIT
  Urea Formaldehyde Foam Insulation UFFI
  URETHANE FOAM Deterioration, Outgassing
  VERMICULITE INSULATION

INSULATION LOCATION - WHERE TO PUT IT
INSULATION MOLD
INSULATION R-Values & Properties

LEED GREEN BUILDING CERTIFICATION
LEED Building Designation & IAQ
LIGHTING, INTERIOR GUIDE
LOG HOME ENERGY EFFICIENCY
LOG HOME GUIDE

MOBILE HOME INSPECTIONS
MOISTURE CONTROL in buildings
MOLD in FOAM INSULATION, RESISTANCE
MOLD INFORMATION CENTER

Nanomaterials Hazards
NOISE / SOUND DIAGNOSIS & CURE
NOISE CONTROL for HEATING SYSTEMS
NOISE CONTROL for FLOORS
NOISE CONTROL for PLUMBING
NOISE CONTROL for ROOFS

ODORS & SMELLS DIAGNOSIS & CURE

PAINT FALURE, DIAGNOSIS, CURE, PREVENTION
PASSIVE SOLAR DESIGN METHOD
PASSIVE SOLAR HEAT PERFORMANCE
PASSIVE SOLAR HOME, LOW COST
PHOTOVOLTAIC POWER SYSTEMS
PLASTER & BEAVERBOARD & DRYWALL
PASCAL CALCULATIONS

RADIANT BARRIERS
RADIANT HEAT
RADIANT HEAT Floor Mistakes to Avoid
RADIANT HEAT TEMPERATURES
RADIANT SLAB FLOORING CHOICES
RADIANT SLAB TUBING & FLUID CHOICES
REFLECTIVE INSULATION
RIGID FOAM USE INDOORS
ROOF VENTING ENERGY SAVING DETAILS
ROOF VENTING NEEDED?
ROOF VENTILATION SPECIFICATIONS
ROT, FUNGUS, TERMITES
ROT, TIMBER FRAME

ROOF ARCHITECTURAL STYLES - PHOTO GUIDE
ROOF CLEANING RECOMMENDATIONS
ROOF DORMER TYPES - PHOTO GUIDE
ROOF VENTILATION SPECIFICATIONS
ROT, FUNGUS, TERMITES
  TERMITE SHIELDS vs TERMITICIDE
ROT, TIMBER FRAME

SEARS KIT HOUSES

SOLAR ENERGY SYSTEMS
SOUND CONTROL in buildings
STAIN & BIODETERIORATION AGENT CATALOG
STAINS on buildings - QUICK GUIDE
STAIN DIAGNOSIS on BUILDING EXTERIORS
STAIN DIAGNOSIS on BUILDING INTERIORS
STAINS on INDOOR SURFACES: PHOTO GUIDE

STRESS SKIN INSULATED PANELS
STUCCO OVER FOAM INSULATION
SWEATING (CONDENSATION) on PIPES, TANKS

THERMAL EXPANSION of MATERIALS
THERMAL MASS in buildings
  THERMAL MASS FLOOR SLABS
  THERMAL MASS in UPSTAIRS
  THERMAL MASS WALL DESIGN
  THERMAL MASS in HOMES - STUDY
  THERMAL MASS TRADEOFFS, HEATING vs COOLING

THERMAL TRACKING & HEAT LOSS
  Ceiling Thermal Tracking Marks
  Wall Thermal Tracking Stains
  Floor Carpet Thermal Tracking Stains
  Air Bypass Leaks Marks on Insulation
  Thermal Tracking to Diagnose IAQ
  Stains HVAC Supply Registers
  Pet Stains on Floors
  Pet Stains on Walls
  Human Occupant Stains on Walls
  Stains from Candles, Woodstoves, Fireplaces
  Other Stains on Indoor Walls & Ceilings
  What to Do About Thermal Tracking

VAPOR BARRIERS & CONDENSATION in buildings
  ATTIC CONDENSATION CAUSE & CURE
  BASEMENT CEILING VAPOR BARRIER
  CONDENSATION or SWEATING PIPES, TANKS
  CRAWL SPACE VAPOR BARRIER
  DEW POINT CALCULATION for WALLS
  DEW POINT TABLE - CONDENSATION POINT GUIDE
  FELT 15# ROOFING, as HOUSEWRAP/VAPOR BARRIER
  HOUSEWRAP AIR & VAPOR BARRIERS
  HOUSEWRAP INSTALLATION DETAILS
  HOUSEWRAP PRODUCT CHOICES
  HOUSEWRAP at SILLS, SOLES, TOP PLATES
  HUMIDITY LEVEL TARGET
  MOISTURE CONTROL in buildings
  RAIN SPLASH-UP SIDING DAMAGE
  VAPOR BARRIERS & AIR SEALING at BAND JOISTS
  VAPOR BARRIERS & CONDENSATION in buildings
  VAPOR BARRIERS & HOUSEWRAP
  VAPOR CONDENSATION & BUILDING SHEATHING
  WATER BARRIERS, EXTERIOR
  WOOD SIDING FLASHING DETAILS

VENTILATION in buildings

WATER ENTRY in buildings
WIND ENERGY SYSTEMS
WIND TURBINES & LIGHTNING
WIND WASHING INSULATION At EAVES
WINDOWS & DOORS

WINTERIZE A BUILDING
Wood Burning Heaters Fireplaces Stoves
Woodstove Safety

ZONE VALVES

More Information

Open partition wall (C) Daniel Friedman

Convective Loops, Air Leaks & Heat Loss Analysis for buildings
InspectAPedia®  -    

  • How to find & diagnose convection loop heat losses in buildings
  • Heat loss due to convection loops in fire walls, party walls, & interior partition walls
  • Heat loss due to convective loops in bathrooms & plumbing chaseways
  • Heat loss due to cold air leaks into return ducts routed through building framing chaseways
  • How convection loops pump heat out of a building even with no air leaks
  • Where convection loops most often occur in buildings
  • Solar Age Magazine Articles on Renewable Energy, Energy Savings, Construction Practices
InspectAPedia offers impartial, unbiased advice without conflicts of interest. We will block advertisements which we discover or readers inform us are associated with bad business practices, false-advertising, or junk science. Our contact info is at InspectAPedia.com/Contact.htm.

This article series discusses how to find and correct convective loop heat losses in buildings, a step in how to find points of heat loss and air leaks in buildings using a variety of tools and inspection methods including infra red, smoke tests, visual inspection, and tests. This detailed article accompanies a building weatherization and energy-savings company through a detailed building inspection for heat loss points and air leaks. The author accompanied Princeton Energy Partners as they used the blower door, thermal imaging, smoke guns, and visual inspection to pinpoint building air leaks, convective loops, heat loss points, air infiltration and air exfiltration on a building. Readers should also see AIR BYPASS LEAKS as well as HEAT LOSS in buildings and HEAT LOSS INDICATORS.

Our page top photo shows an uninsulated interior partition wall forming a convective heat loop as well as a thermal bypass loop in a building. Contact us to suggest text changes and additions and, if you wish, to receive online listing and credit for that contribution.

© Copyright 2012 InspectAPedia.com, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use page top links to major topics or use links at the left of each page to navigate within topics and documents at this website. Green links show where you are in a document series or at this website.

How to Find Points of Convective Heat Loop - Heat Loss in buildings

This article series explains how to survey a building for air and heat loss or gain points and how to correct them.

As we introduced above, in this article the author, Steven Bliss, accompanies a building weatherization and energy-savings company through a detailed building inspection for heat loss points, convective loops, and air leaks. The author accompanies Princeton Energy Partners as they use thermal imaging, smoke guns, and visual inspection to pinpoint building air leaks, heat loss points, air infiltration and air exfiltration on a building. The importance of setting priorities for sealing these points of energy wasted is emphasized and discussed, and sketches as well as photographs of common points of building heat loss, or unwanted heat gain, and air leaks are provided.

  • Building Heat Loss & Air Leaks - use your browser's back button to return to this page
  • Building Heat Loss & Air Leaks - part 2
  • Building Heat Loss & Air Leaks - part 3 - Convective loops and heat loss
  • Building Heat Loss & Air Leaks - part 4 - Convective loops and heat loss (continued)

The text below paraphrases, quotes-from, updates, and comments an original article, "House Doctors with Better Medicine, Princeton Energy Partners use the latest diagnostic tools to comb a house for the major causes of heat loss. Their findings are often astonishing. Their strong prescriptions bring results', Steven Bliss, (see links just above) from Solar Age Magazine and written by Steven Bliss.

Convective Heat Loops & Leaks - Thermal Bypass Leaks in buildings

Thermal Bypasses, Air Leaks, & Convective Heat Loops in Building Partitions

Convective loop heat loss (C) Daniel Friedman

The energy contractors assert that their work consistently saves the homeowner considerably more money than is predicted by the reductions in air infiltration alone. This seeming magic is attributed to the elimination of "thermal bypasses", that is, the myriad ways heat gets out of the building other than through wall and ceiling components following the rules and regulations of ASHRAE.

Prominent among these heat leaks are convective loops - wall and ceiling cavities that act as room-sized heat exchangers, relentlessly pumping heat out of a building even if there is no direct air leakage from indoors to outdoors.

The convective loop shown in the sketch at left depicts heat movement in an interior hollow core masonry block partition wall in a building. In many cases PEP (the energy consulting and weatherizing firm in the original article) finds interior partitions colder than outside walls.

Since the cooling effect of a convective loop is only partly due to air leakage, even a completely closed wall cavity such as a (hollow core block) masonry party wall can cause problems.

In multi-unit dwellings energy retrofitters often encounter concrete-block party walls between adjoining living spaces and extending into the building attic. Warm air rises through the masonry block hollow cores, is cooled in the un-heated attic, and falls again.

Regardless of whether or not the block wall is capped with solid blocks in the attic (or outside above the rooftop), this convective heat loop chills the party wall and robs heat from the building. A related problem might be a reduction in building wall R-values if air flows through fiberglass insulation. While this phenomenon has been reported many times in the research literature, it is generally overlooked since it defies accurate prediction.

One cure in the case of a masonry party wall is a solid course of block at the ceiling level at each floor level, isolating the airflow within the heated space. Of course this is most easily accomplished during new construction. Sealing a block party wall against convection loops as a retrofit is a challenge and may be costly. An example might include drilling every block at ceiling level to inject fire-block-rated foam.

Convective loop heat losses occur in buildings within uninsulated, wood-framed or metal stud interior partition walls, not just in hollow core masonry walls, as we discuss below at Convection Loops at Interior Partition Walls.

Stacked Bathrooms & Plumbing Chases & Return Ducts Run Through Framing Form Convective Loops

Convective heat loss loops at stacked bathrooms (C) Daniel Friedman

 

In multifamily and even single family buildings it is common for bathrooms to be "stacked" one on top of the other, forming a giant convective loop.

The sketch at left shows warm air and heat leaking into the ceiling around a bathroom light and exhaust fan (the red arrows).

The blue arrows in the sketch depict cold air falling from an un-heated attic into the heating cool-air return duct, leaking through wire holes and gaps in framing, allowing un-wanted cold air to be drawn into the heating system duct work.

Also, since this is a bathroom wall, moist air is likely to be drawn into the framing as well. The solution is to seal off the duct space (run through framing members in this building) so that it functions properly.

 

Convective Loop Heat Losses at Kitchen Cabinets & Soffits

Kitchen soffit thermal bypass and convective leaks (C) Daniel Friedman

 

As we cited earlier at Living Space Heat Loss, air leaks through kitchen cabinets and interior soffits can be very significant heat loss points in buildings. Soffited ceilings are popular in kitchens and baths, and make a handy home for recessed lights. But improper insulation installation or openings cut for recessed lights, wiring, or plumbing can permit air leaks into the ceiling cavity or directly into the attic. Such leaks can be extensive.

An infrared scan or invasive inspection can identify this energy loss location.

Sealing the connection between the cabinet soffit and the building's exterior wall reduced building air leakage by 20 percent at a townhouse investigated by the experts in the original article given here.

The sketch at left demonstrates how a kitchen soffit can become a heat pump, moving warm air (red arrows) and heat into a cold attic space while bringing cold air down into the living area.

A small soffit over a kitchen cabinet may not look like much until you discover that it is drawing air from all kinds of wall and ceiling spaces.

Convection Loops at Interior Partition Walls & Party Walls or Fire Walls

Open partition wall (C) Daniel Friedman

As our photo at the top of this page shows an open, uninsulated interior partition wall top, viewed from a building attic. In an older wood frame building an interior partition wall such as this one may extend from the attic down through two floors in the building, finding a stop only at a sill plate or "shoe" where the partition wall begins on the first floor.

Our photo of a fire-rated drywall party wall (left) shown extending into the attic of a multi-unit dwelling, describes a tall, often uninsulated interior partition wall that can form a convective heating loop. Party walls between building units are required to slow the spread of fire from one building section to another.

(A catastrophic fire occurred in an older section of the Fox Hill condominiums in Poughkeepsie NY (ca 1980) as fire spread rapidly through an attic where these fire barriers had been omitted.) The party wall either extends through and above the roof, or the roof sheathing may be protected (typically for four feet) on either side of the party wall using fire retardant treated plywood or fire-rated drywall covering.

The hollow chimney created by an interior partition wall, regardless of whether or not it extends up through the attic, forms a heat pump, moving building warmth into the cold attic during the heating season.

Simply sealing the wall top in the attic will help alot, as would fire-blocking (now required in many jurisdictions) at each floor and ceiling level in such a wall. Fire-blocking retrofit that can also interrupt this thermal convection loop may be permitted in your jurisdiction using a fire-rated foam - check with your local building department.

When we observe thermal tracking stains on the upper section of an interior partition wall, one possible explanation is that convective loops within the wall, even if it is not leaking badly into the attic, are cooling the upper part of the wall. See THERMAL TRACKING & HEAT LOSS for details.

Estimating convective loop heat losses

In addition to their effect on energy bills, the impact of convective loops in buildings can be gauged by measuring attic temperatures before and after sealing off thermal bypasses such as chases and wall partitions, or it can be roughly modeled from the temperature difference and the height of the convective loop.

Questions & Answers regarding this article

.

Ask a Question or Search InspectAPedia

HTML Comment Box is loading comments...

Share this Article      

...

Technical Reviewers & References

  • InspectAPedia.com® - Daniel Friedman - Publisher & Editor.
  • InspectAPedia Bookstore lists recommended books, organized by topic & available for purchase. Most of our articles also include a list of recommended books for the specific article topic as well as other references, and information sources.
  • Critique, contributions wanted: Contact Us to suggest corrections or additions to articles at this website, and if you wish, to receive online listing and credit as a contributor. Particular thanks are due to the many experts and also consumers who read and critique technical articles at InspectAPedia.com.
  • Additional technical contributors & reference sources for this article are listed below.

Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

AIR CONDITIONING & HEAT PUMP SYSTEMS
ENERGY SAVINGS in buildings

INSULATION IDENTIFICATION GUIDE

INSULATION INSPECTION & IMPROVEMENT
INTERIORS of buildings

ACOUSTICAL SEALANT CHOICES
AIR BYPASS LEAKS
AIR CHANGE RATE ACH HEAT SAVINGS
AIR CLEANER PURIFIER TYPES

AIR FILTER EFFECTIVENESS
AIR FILTERS for HVAC SYSTEMS
AIR FILTERS, OPTIMUM INDOOR
AIR FILTERS, SOURCES FOR
AIR FILTERING STRATEGIES
AIR FILTERING CONTINUOUS FAN OPERATION
AIR HANDLER / BLOWER UNITS
AIR POLLUTANTS, COMMON INDOOR

AIR LEAK DETECTION TOOLS
  Find Heat Loss & Air Leaks
  Heat Loss Investigation Sequence
  Blower Door Test Data Results
  Smoke Gun for Air Leaks
  Smoke Pencil / Smoke Gun Suppliers
  Attic Energy Losses - InfraRed
  Basement Energy Losses- IR & Visual
  Duct System Air Movement
  Living Space Heat Loss
  Targets & Hidden Leak Points
  Thermography IR Infra Red & Thermal Scanners
  Convective Loops & Thermal Bypass Leaks
  HOUSE DOCTOR, how-to be
  Insulation Air & Heat Leaks
  The Bottom Line on Energy Retrofits
AIR LEAK MINIMIZATION
AIR LEAK SEALING PROCEDURE
AIR SEALING STRATEGIES

ANIMAL ALLERGENS
APPLIANCE EFFICIENCY RATINGS
ASBESTOS FLOORING HAZARD REDUCTION
ASBESTOS-FREE INSULATION MATERIALS
ASBESTOS IDENTIFICATION IN buildings
ATTIC LEAKS, CONDENSATION & ATTIC MOLD
ATTIC VENTILATION

BASEMENT CEILING VAPOR BARRIER
BASEMENT HEAT LOSS
BASEMENT LEAKS, INSPECT FOR
BASEMENT WATERPROOFING

BATH & KITCHEN DESIGN GUIDE
BATHROOM VENTILATION
BIOGAS PRODUCTION & USE
BLOWER DOORS & AIR INFILTRATION
BLOWER FAN CONTINUOUS OPERATION
BLOWER FAN OPERATION & TESTING
BLOWN-IN INSULATION

BRICK LINED WALLS
BRICK VENEER WALL INSULATION
BRICK VENEER WALL Loose, Bulged
BRICK WALL DRAINAGE WEEP HOLES
BUCKLED FOUNDATIONS due to INSULATION?
BUILDING NOISE DIAGNOSIS & CURE

CATHEDRAL CEILING INSULATION
CATHEDRAL CEILING VENTILATION
CEILING FINISHES INTERIOR
CEILINGS, DROP or SUSPENDED PANEL
CEILINGS, PLASTER TYPES

CHIMNEY INSPECTION DIAGNOSIS & REPAIR
COOLING LOAD REDUCTION by ROOF VENTS
COMBUSTION AIR for TIGHT buildings
CONDENSING BOILERS/FURNACES DAMAGE

CATHEDRAL CEILING INSULATION
CATHEDRAL CEILING VENTILATION
CEILING FINISHES INTERIOR
CEILINGS, DROP or SUSPENDED PANEL
CEILINGS, PLASTER TYPES

CHIMNEY INSPECTION DIAGNOSIS & REPAIR
COOLING LOAD REDUCTION by ROOF VENTS
COMBUSTION AIR for TIGHT BUILDINGS
CONDENSING BOILERS/FURNACES DAMAGE
CONDENSATION or SWEATING PIPES, TANKS
COOLING LOAD REDUCTION by ROOF VENTS
CRAWL SPACES

DEFINITION of Heating & Cooling Terms
DEHUMIDIFICATION PROBLEMS
DEW POINT CALCULATION for WALLS
DEW POINT TABLE - CONDENSATION POINT GUIDE
DUCT SYSTEM & DUCT DEFECTS

ELECTRICAL INSPECTION, DIAGNOSIS, REPAIR

ENERGY SAVINGS in buildings
  AFUE DEFINITION, RATINGS
  AIR BYPASS LEAKS
  AIR CHANGE RATE ACH HEAT SAVINGS
  AIR CONDITIONING HEAT PUMP SAVINGS
  AIR LEAK SEALING PROCEDURE
  APPLIANCE EFFICIENCY RATINGS
  ATTIC LEAKS, CONDENSATION & ATTIC MOLD
  COOLING LOAD REDUCTION by ROOF VENTS
  ENERGY AUDIT - How to Use a Free One
  ENERGY SAVINGS MAXIMIZE RETURNS ON
  ENERGY SAVINGS PRIORITIES
  ENERGY SAVINGS RETROFIT CASE STUDY
  ENERGY SAVINGS RETROFIT LEAK SEALING GUIDE
  ENERGY SAVINGS RETROFIT OPTIONS
  ENERGY STAR PROGRAM
  ENERGY USE MONITORING
  GLASS vs HEAT MIRROR SOLAR GAIN/Loss
  HEAT LOSS in buildings
  HEATING COST SAVINGS METHODS
  HIGH MASS TRADEOFFS, HEATING vs COOLING
  HOUSE DOCTOR, how-to be
  INSULATION INSPECTION & IMPROVEMENT
  INSULATION LOCATION - WHERE TO PUT IT
  RADIANT BARRIERS
  REFLECTIVE INSULATION
  ROOF COLOR RECOMMENDATIONS
  Skylight Energy Efficiency
  SOLAR ENERGY SYSTEMS
  THERMAL MASS in buildings
  TIMERS for ELECTRIC WATER HEATERS
  VENTILATION, BALANCED HEAT COST SAVINGS
  WIND ENERGY SYSTEMS
  WINDOW EFFICIENCY Features & Ratings
  WOOD, COAL STOVES & FIREPLACES

ENVIRONMENTAL HAZARDS - INSPECT, TEST, REMEDY

EXTERIOR WALL SIDING TRIM & FINISHES

FIBERGLASS INSULATION
FIBERGLASS HAZARDS
FIBERGLASS INSULATION MOLD

FLASHING MEMBRANES PEEL & STICK
FLAT ROOF MOISTURE & CONDENSATION

FLOOD DAMAGE ASSESSMENT, SAFETY & CLEANUP
FLOODS IN buildings-mold

FLOOR, CONCRETE SLAB CHOICES
FLOOR, CONCRETE SLAB POURED FINISH
FLOOR DAMAGE DIAGNOSIS
FLOOR RADIANT HEAT Mistakes to Avoid
FLOOR TYPES & DEFECTS

FOUNDATION WATERPROOFING
FRENCH DRAINS
FRAMING DETAILS for BETTER INSULATION
FRAMING DETAILS for DOUBLE WALL HOUSES
FRAMING METAL STUD PERFORMANCE
FREEZE-PROOF A BUILDING
FROST HEAVES, FOUNDATION, SLAB

GREEN BUILDING CONSTRUCTION CODES GUIDES
GREENHOUSE DESIGN for SOLAR HEATING

HEAT LOSS in buildings
HEAT LOSS DETECTION TOOLS
  Find Heat Loss & Air Leaks
  Heat Loss Investigation Sequence
  Blower Door Test Data Results
  Smoke Gun for Air Leaks
  Smoke Pencil / Smoke Gun Suppliers
  Attic Energy Losses - InfraRed
  Basement Energy Losses- IR & Visual
  Duct System Air Movement
  Living Space Heat Loss
  Targets & Hidden Leak Points
  Thermography IR Infra Red & Thermal Scanners
  Convective Loops & Thermal Bypass Leaks
  HOUSE DOCTOR, how-to be
  Insulation Air & Heat Leaks
  The Bottom Line on Energy Retrofits
HEAT LOSS INDICATORS
HEAT LOSS PREVENTION PRIORITIES
HEAT LOSS R U & K VALUE CALCULATION
HEAT TAPES & CABLES on Roofs for Ice Dams
HEATING COST SAVINGS METHODS

HOT ROOF DESIGNS: Un-Vented Roof Solutions
HOUSEWRAP AIR & VAPOR BARRIERS
HOUSE DOCTOR, how-to be

HUMIDITY LEVEL TARGET

ICE DAM PREVENTION
INSULATION CHOICES
Insulation Air & Heat Leaks
INSULATION FACT SHEET- DOE
INSULATION for GREENHOUSE or SOLARIUM
INSULATION IDENTIFICATION GUIDE
INSULATION INSPECTION & IMPROVEMENT
INSULATION LOCATION - WHERE TO PUT IT
  INSULATION LOCATION & QUANTITY for ATTICS
  INSULATION LOCATION for BASEMENT FLOORS
  INSULATION LOCATION for BASEMENT WALLS
  INSULATION LOCATION for BRICK or BLOCK WALL CAVITY
  INSULATION LOCATION for BRICK VENEER WALLS
  INSULATION LOCATION for CAPES, CRAWLSPACES
  INSULATION LOCATION for CATHEDRAL CEILINGS
  INSULATION LOCATION for GREENHOUSE or SOLARIUM
  INSULATION LOCATION for PASSIVE SOLAR FLOOR SLAB
  INSULATION LOCATION & EXTENT for SLABS
  INSULATION LOCATION for SOUND CONTROL
  INSULATION LOCATION for SUSPENDED PANELS
  INSULATION LOCATION for SWIMMING, INDOOR

INSULATION MOLD
INSULATION R-Values & Properties

INSULATION IDENTIFICATION GUIDE
INSULATION INSPECTION & IMPROVEMENT
  ATTIC CONDENSATION CAUSE & CURE
  Air Bypass Leaks, Thermal Tracking
  Blocked Soffit Intake Vents
  BRICK or BLOCK WALL CAVITY INSULATION
  BRICK VENEER WALL INSULATION
  CATHEDRAL CEILING INSULATION
  CATHEDRAL CEILING VENTILATION
  ENERGY SAVINGS in buildings
  FIBERGLASS DUCT, RIGID CONSTRUCTION
  FIRE PROTECTION FOR FOAM BOARD INSULATION
  FOUNDATION INSULATION OPTIONS
  FRAMING DETAILS for BETTER INSULATION
  FRAMING DETAILS for DOUBLE WALL HOUSES
  FRAMING METAL STUD PERFORMANCE
  HOT ROOF DESIGNS: Un-Vented Roof Solutions
  Inspect Attics for Moisture or Mold
  Inspect Attics for Blocked Soffit Intake Vents
  Inspect Basements for Moisture or Mold
  Inspect Building Exterior - Roof Venting
  Inspect the Ridge Vent System from the Attic
  Inspect the Soffit Vent System from the Attic
  Insects & Foam Insulation
  HOUSE DOCTOR, how-to be
  Insulation Air & Heat Leaks
  INSULATION R-Values & Properties
  LOG HOME WALL INSULATION VALUES
  MOISTURE in BUILDING WALLS, EFFECTS
  MOISTURE in CELLULOSE INSULATION
  Mold in Fiberglass Insulation
  Mold on Books, Book Conservation
  Mold on Fiberboard Insulating Sheathing
  MOLD in Foam Insulation
  MOLD in INSULATION
  Mold Resistance of Foam Insulation
  MOLD PREVENTION AFTER FLOODING
  MOLD RESISTANT CONSTRUCTION
  PASCAL CALCULATIONS
  PHENOLIC FOAM INSULATION
  POLYISOCYANURATE FOAM INSULATION
  POLYISOCYANURATE FOAM BELOW SLABS
  POLYSTYRENE FOAM INSULATION
  RADIANT BARRIERS
  REFLECTIVE INSULATION
  RIGID FOAM USE INDOORS
  STRESS SKIN INSULATED PANELS
  STUCCO OVER FOAM INSULATION
  SUPER HI-R INSULATION
  SUPERINSULATION RETROFIT
  Urea Formaldehyde Foam Insulation UFFI
  URETHANE FOAM Deterioration, Outgassing
  VERMICULITE INSULATION

INSULATION LOCATION - WHERE TO PUT IT
INSULATION MOLD
INSULATION R-Values & Properties

LEED GREEN BUILDING CERTIFICATION
LEED Building Designation & IAQ
LIGHTING, INTERIOR GUIDE
LOG HOME ENERGY EFFICIENCY
LOG HOME GUIDE

MOBILE HOME INSPECTIONS
MOISTURE CONTROL in buildings
MOLD in FOAM INSULATION, RESISTANCE
MOLD INFORMATION CENTER

Nanomaterials Hazards
NOISE / SOUND DIAGNOSIS & CURE
NOISE CONTROL for HEATING SYSTEMS
NOISE CONTROL for FLOORS
NOISE CONTROL for PLUMBING
NOISE CONTROL for ROOFS

ODORS & SMELLS DIAGNOSIS & CURE

PAINT FALURE, DIAGNOSIS, CURE, PREVENTION
PASSIVE SOLAR DESIGN METHOD
PASSIVE SOLAR HEAT PERFORMANCE
PASSIVE SOLAR HOME, LOW COST
PHOTOVOLTAIC POWER SYSTEMS
PLASTER & BEAVERBOARD & DRYWALL
PASCAL CALCULATIONS

RADIANT BARRIERS
RADIANT HEAT
RADIANT HEAT Floor Mistakes to Avoid
RADIANT HEAT TEMPERATURES
RADIANT SLAB FLOORING CHOICES
RADIANT SLAB TUBING & FLUID CHOICES
REFLECTIVE INSULATION
RIGID FOAM USE INDOORS
ROOF VENTING ENERGY SAVING DETAILS
ROOF VENTING NEEDED?
ROOF VENTILATION SPECIFICATIONS
ROT, FUNGUS, TERMITES
ROT, TIMBER FRAME

ROOF ARCHITECTURAL STYLES - PHOTO GUIDE
ROOF CLEANING RECOMMENDATIONS
ROOF DORMER TYPES - PHOTO GUIDE
ROOF VENTILATION SPECIFICATIONS
ROT, FUNGUS, TERMITES
  TERMITE SHIELDS vs TERMITICIDE
ROT, TIMBER FRAME

SEARS KIT HOUSES

SOLAR ENERGY SYSTEMS
SOUND CONTROL in buildings
STAIN & BIODETERIORATION AGENT CATALOG
STAINS on buildings - QUICK GUIDE
STAIN DIAGNOSIS on BUILDING EXTERIORS
STAIN DIAGNOSIS on BUILDING INTERIORS
STAINS on INDOOR SURFACES: PHOTO GUIDE

STRESS SKIN INSULATED PANELS
STUCCO OVER FOAM INSULATION
SWEATING (CONDENSATION) on PIPES, TANKS

THERMAL EXPANSION of MATERIALS
THERMAL MASS in buildings
  THERMAL MASS FLOOR SLABS
  THERMAL MASS in UPSTAIRS
  THERMAL MASS WALL DESIGN
  THERMAL MASS in HOMES - STUDY
  THERMAL MASS TRADEOFFS, HEATING vs COOLING

THERMAL TRACKING & HEAT LOSS
  Ceiling Thermal Tracking Marks
  Wall Thermal Tracking Stains
  Floor Carpet Thermal Tracking Stains
  Air Bypass Leaks Marks on Insulation
  Thermal Tracking to Diagnose IAQ
  Stains HVAC Supply Registers
  Pet Stains on Floors
  Pet Stains on Walls
  Human Occupant Stains on Walls
  Stains from Candles, Woodstoves, Fireplaces
  Other Stains on Indoor Walls & Ceilings
  What to Do About Thermal Tracking

VAPOR BARRIERS & CONDENSATION in buildings
  ATTIC CONDENSATION CAUSE & CURE
  BASEMENT CEILING VAPOR BARRIER
  CONDENSATION or SWEATING PIPES, TANKS
  CRAWL SPACE VAPOR BARRIER
  DEW POINT CALCULATION for WALLS
  DEW POINT TABLE - CONDENSATION POINT GUIDE
  FELT 15# ROOFING, as HOUSEWRAP/VAPOR BARRIER
  HOUSEWRAP AIR & VAPOR BARRIERS
  HOUSEWRAP INSTALLATION DETAILS
  HOUSEWRAP PRODUCT CHOICES
  HOUSEWRAP at SILLS, SOLES, TOP PLATES
  HUMIDITY LEVEL TARGET
  MOISTURE CONTROL in buildings
  RAIN SPLASH-UP SIDING DAMAGE
  VAPOR BARRIERS & AIR SEALING at BAND JOISTS
  VAPOR BARRIERS & CONDENSATION in buildings
  VAPOR BARRIERS & HOUSEWRAP
  VAPOR CONDENSATION & BUILDING SHEATHING
  WATER BARRIERS, EXTERIOR
  WOOD SIDING FLASHING DETAILS

VENTILATION in buildings

WATER ENTRY in buildings
WIND ENERGY SYSTEMS
WIND TURBINES & LIGHTNING
WIND WASHING INSULATION At EAVES
WINDOWS & DOORS

WINTERIZE A BUILDING
WOOD Burning Heaters Fireplaces Stoves

  • Solar Age Magazine was the official publication of the American Solar Energy Society. The contemporary solar energy magazine associated with the Society is Solar Today. "Established in 1954, the nonprofit American Solar Energy Society (ASES) is the nation's leading association of solar professionals & advocates. Our mission is to inspire an era of energy innovation and speed the transition to a sustainable energy economy. We advance education, research and policy. Leading for more than 50 years. ASES leads national efforts to increase the use of solar energy, energy efficiency and other sustainable technologies in the U.S. We publish the award-winning SOLAR TODAY magazine, organize and present the ASES National Solar Conference and lead the ASES National Solar Tour – the largest grassroots solar event in the world."
  • Steven Bliss served as editorial director and co-publisher of The Journal of Light Construction for 16 years and previously as building technology editor for Progressive Builder and Solar Age magazines. He worked in the building trades as a carpenter and design/build contractor for more than ten years and holds a masters degree from the Harvard Graduate School of Education. Excerpts from his recent book, Best Practices Guide to Residential Construction, Wiley (November 18, 2005) ISBN-10: 0471648361, ISBN-13: 978-0471648369, appear throughout this website, with permission and courtesy of Wiley & Sons. Best Practices Guide is available from the publisher, J. Wiley & Sons, and also at Amazon.com.
    Excerpts with updates and annotations expanding the original Best Practices Guide text can be found in the online review and book summary at BEST CONSTRUCTION PRACTICES GUIDE and also at DECK & PORCH CONSTRUCTION, at INDOOR AIR QUALITY IMPROVEMENT GUIDE, and in other articles found at InspectAPedia.com such as HOUSEWRAP AIR & VAPOR BARRIERS, SOUND CONTROL in buildings, and other topics.
  • Ice Dam Leaks in building attics and roof cavities, how to inspect for evidence of leaks, identify causes, and correct bad attic ventilation, improper roof venting, and these causes of attic mold or roof structure damage

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.
  • ...
Home About Us Accuracy Contact Us Content Use Policy Privacy Website Description © 2012 Copyright InspectAPedia.com