Insulation & Energy Saving Retrofit Problem Solvers
Ultra lightweight concrete insulation retrofit
Weather-seal double-hung sash-weighted windows, using simple window sash control
Foam foundation forms save on concrete and labor
Strip vents to add soffit or roof eaves intake venting
Solar Age Magazine Articles on Renewable Energy, Energy Savings, Construction Practices
Our site offers impartial, unbiased advice without conflicts of interest.
We will block advertisements which we discover or readers inform us are associated with bad business practices,
false-advertising, or junk science. Our contact info is at
InspectAPedia.com/Contact.htm.
This article discusses a selection of energy saving building retrofit steps including using Air Krete ultralightweight concrete building insulation, sealing leaky sash-weight-operated double hung windows, foam foundation forms, and adding soffit intake ventilation for the roof cavity. Sketch at page top and accompanying text are reprinted/adapted/excerpted with permission from Solar Age Magazine - editor Steven Bliss.
"Eight Retrofit Problem Solvers - new products, time tested techniques, and shortcuts make the hard work of insulation or energy retrofitting a little easier" - provided in original PDF form in the links below, and expanded/updated in text just below.
Insulating Existing Wall Cavities with Ultra Lightweight Concrete
The perfect building insulation for retrofitting cavity walls would be non-toxic, non-shrinking, fire-resistant, high in R-value, non-corrosive, and moisture and mold-resistant. It would also have the ability to flow into irregular spaces behind the walls, and be dense enough to stop air leaks. And it's got to be cheap. A product whose use dates to 1983, Air Krete, appears to fit this tall order well.
Air Krete (page top photo) is a cement-based product that weighs about the same as extruded polystyrene - 2 pounds per square foot - and has an R-value of 3.9 per inch. Produced on-site from three components plus water, Air Krete installs much the same way as pump-in foam insulating products. When it dries it is lightweight and crumbly.
According to the company, wet Air Krete will flow in and seal the smallest crevices in a wall, but sets up quickly - within 20 seconds. Because Air Krete hydrates like concrete, when drying it gives off less water than some foam products such as the no-longer used urea-formaldehyde foam insulation (UFFI). Independent testing showed that this concrete wall insulating product shrinks less than 0.25 percent and it is virtually fireproof. [At the time of the original article - see links above - product testing for water-vapor permeance and water absorption were incomplete.]
Because this ultra lightweight concrete has over 80 percent closed cells, the company described it (back in 1985) as similar to expanded polystyrene foam insulation in its reaction to water - that is, it should be a moderate water vapor retarder and a slow absorber of actual water.
Air-Krete is available through licensed installers. Doing a good job is not difficult, but requires a close watch of the equipment. On a good day, a three person crew can put in 14,000 board feet of this insulating material. Cleanup is easy since the raw materials are water soluble.
Prime applications of lightweight concrete insulation include brick cavity wall construction and masonry block cores. For wood-framed building walls, lightweight concrete will get tough competition from blown-in chopped fiberglass or cellulose insulation. Those products can be blown into building walls for about half the cost of lightweight concrete. In 1985 Air Krete installed for $1.25 to $1.50 per square foot in a 2x4 wood framed wall. (1985 prices - check for current costs).
But if high R-values are needed or if you are concerned about settling, fire resistance [seems less a concern with masonry walls], or moisture absorption, Air Krete or similar ultra lightweight concrete wall insulating products are worth looking into. Also these products maybe code-approved for fire stops and fire-walls.
Retrofits for Stopping Drafts at Double-Hung Windows & Window Sashes
Weathersealing an old double-hung window is no one's idea of a good time. Retrofit contractors have found a cheap and simple device that makes that task easier: the Quiki window control. Other window sash controls include an aluminum track that tacks into the existing window sash opening after you remove the parting strips that will be found between the existing sashes. The Quiki window control, or spring-loaded sides of the window track insert will hold the sashes firmly in any position.
An alternative to the window track, if you're just using the window clip, is the installation of plastic V-strips along the bottom sash at the meeting rail and against the parting strips found between the house-interior faces of the stops and the lower sash. Some retrofitters caulk the top sash in place, but if you use the track insert we have cited, that won't be needed.
These products mean you can remove the window sash cords, pulleys, and sash weights from the wall cavities found on either side of older double-hung window sashes, adding foam or fiberglass insulation in those spaces to eliminate what amounts to an un-insulated building wall area on either side of every window. Adding insulation using foam squirted into the cavity will be most effective in stopping drafts. To avoid springing the sides of some less-rigid window frames it may be necessary to wedge a stick between the window opening sides while the foam cures.
Foam Foundation Forms
There are presently a wide variety of foam foundation form manufacturers whose products combine fast concrete forms that also insulate the foundation perimeter. Back in 1985 a leader in this approach was Branch River Plastics who used expanded polystyrene to produce Fast Forms.
Polystyrene insulating concrete foundation form products lend themselves to sunspace construction or other small slab-on-grade jobs where you want to get the backhoe and mixer in and out in a hurry. Fast Forms and similar foam foundation insulating forms come in 4 x 8 foot sections that lock together with dovetail keys and special corners.
The foam foundation forms are engineered to work without rebar in normal soils with typical loads. Concentrated point loads go on special pier forms that fit to the standard sections. After pouring the forms are left in place to insulate the perimeter of the concrete slab.
Because the foam foundation forms are left in the ground, the trenches need to be only 18 to 24 inches wide and can be backfilled as soon as the forms are set. Footing, slab, and wall are poured monolithically, so only one concrete delivery is required. The foam foundation forms help the concrete cure well by retarding the heat and water of concrete hydration. The insulation also helps in cold-weather concrete slab pours.
At their introduction in the 1980's these foam foundation forms cost about $10.40 per lineal foot, but they save on concrete and labor.
Adding Soffit Intake Vents
In several InspectAPedia articles we have emphasized the importance of effective under-roof ventilation to prevent moisture and mold in roof cavities as well as to avoid inadvertently sucking heat out of the building (by providing traditional exit vents or gable end vents without intake venting.
ROOF VENTILATION SPECIFICATIONS describes how to correct inadequate attic ventilation, stop attic condensation, and stop ice dam formation, thus avoiding building leaks, mold, and structural damage.
Roof Venting: Soffit Intake Vent-Continuous emphasizes that continuous soffit intake venting is essential for roof ventilation to work properly. In the sketch at left you'll see little round holes drilled through the soffit, covered by a soffit vent strip that can be purchased inexpensively at any building supply house.
DON'T RELY ON LITTLE HOLES in the soffit. Having inspected thousands of homes and seen many attic moisture and ice dam problems on homes where a variety of roof venting systems were installed, we are convinced that what is needed is a continuous opening along the full length of the soffit. Typically the opening is cut about 2" wide - to match the soffit vent strip minus its support flanges. Using a circular saw overhead risks sawdust in the eye, so wear protective goggles. But don't take any shortcuts - it won't work.
ROOF VENTING NEEDED? explains why under-roof ventilation is needed, and includes warnings about un-vented and "hot roof" designs.
The text below paraphrases, quotes-from, updates, and comments an original article, (see links just above) from Solar Age Magazine and written by Steven Bliss - with permission.
Here we include solar energy, solar heating, solar hot water, and related building energy efficiency improvement articles reprinted/adapted/excerpted with permission from Solar Age Magazine - editor Steven Bliss.
Critique, contributions wanted: Contact Us to suggest corrections or additions to articles at this website, and if you wish, to receive online listing and credit as a contributor. Particular thanks are due to the many experts and also consumers who read and critique technical articles at InspectAPedia.com.
Additional technical contributors & reference sources for this article are listed below.
Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.
Solar Age Magazine was the official publication of the American Solar Energy Society. The contemporary solar energy magazine associated with the Society is Solar Today. "Established in 1954, the nonprofit American Solar Energy Society (ASES) is the nation's leading association of solar professionals & advocates. Our mission is to inspire an era of energy innovation and speed the transition to a sustainable energy economy. We advance education, research and policy. Leading for more than 50 years.
ASES leads national efforts to increase the use of solar energy, energy efficiency and other sustainable technologies in the U.S. We publish the award-winning SOLAR TODAY magazine, organize and present the ASES National Solar Conference and lead the ASES National Solar Tour – the largest grassroots solar event in the world."
Steven Bliss served as editorial director and co-publisher of The Journal of Light Construction for 16 years and previously as building technology editor for Progressive Builder and Solar Age magazines. He worked in the building trades as a carpenter and design/build contractor for more than ten years and holds a masters degree from the Harvard Graduate School of Education.
Excerpts from his recent book, Best Practices Guide to Residential Construction, Wiley (November 18, 2005) ISBN-10: 0471648361, ISBN-13: 978-0471648369, appear throughout this website, with permission and courtesy of Wiley & Sons. Best Practices Guide is available from the publisher, J. Wiley & Sons, and also at Amazon.com.
Excerpts with updates and annotations expanding the original Best Practices Guide text can be found in the online review and book summary at BEST CONSTRUCTION PRACTICES GUIDE and also at DECK & PORCH CONSTRUCTION, at INDOOR AIR QUALITY IMPROVEMENT GUIDE, and in other articles found at InspectAPedia.com such as HOUSEWRAP AIR & VAPOR BARRIERS, SOUND CONTROL in BUILDINGS, and other topics.
Quiki Window Control, Holmes & Hemphill, 6186 Olson Hwy, Golden Valley MN 55422 800-328-2281
Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair
Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.