InspectAPedia.com InspectAPedia®
 

Free Encyclopedia of Building & Environmental Inspection, Testing, Diagnosis, Repair

Ask a Question or Search InspectAPedia

  • HOME
  • AIR CONDITIONING
  • ELECTRICAL
  • EXTERIORS
  • HEATING
  • HOME INSPECTION
  • INTERIORS
  • PLUMBING
  • ROOFING
  • SEPTIC SYSTEMS
  • STRUCTURE
  • WATER SUPPLY
  • ENERGY SAVINGS
  • ENVIRONMENT
  • INDOOR AIR IAQ
  • INSULATION
  • MOLD INSPECT TEST REMOVE
  • NOISE
  • ODORS
  • SOLAR ENERGY
  • VENTILATION
  • EXPERTS DIRECTORY
  • CONTACT US


Mobile Phone/PDA website viewMobile View
AIR CONDITIONING & HEAT PUMP SYSTEMS
ENERGY SAVINGS in buildings

INSULATION IDENTIFICATION GUIDE

INSULATION INSPECTION & IMPROVEMENT
INTERIORS of buildings

ACOUSTICAL SEALANT CHOICES
AIR BYPASS LEAKS
AIR CHANGE RATE ACH HEAT SAVINGS
AIR CLEANER PURIFIER TYPES

AIR FILTER EFFECTIVENESS
AIR FILTERS for HVAC SYSTEMS
AIR FILTERS, OPTIMUM INDOOR
AIR FILTERS, SOURCES FOR
AIR FILTERING STRATEGIES
AIR FILTERING CONTINUOUS FAN OPERATION
AIR HANDLER / BLOWER UNITS
AIR POLLUTANTS, COMMON INDOOR

AIR LEAK DETECTION TOOLS
  Find Heat Loss & Air Leaks
  Heat Loss Investigation Sequence
  Blower Door Test Data Results
  Smoke Gun for Air Leaks
  Smoke Pencil / Smoke Gun Suppliers
  Attic Energy Losses - InfraRed
  Basement Energy Losses- IR & Visual
  Duct System Air Movement
  Living Space Heat Loss
  Targets & Hidden Leak Points
  Thermography IR Infra Red & Thermal Scanners
  Convective Loops & Thermal Bypass Leaks
  HOUSE DOCTOR, how-to be
  Insulation Air & Heat Leaks
  The Bottom Line on Energy Retrofits
AIR LEAK MINIMIZATION
AIR LEAK SEALING PROCEDURE
AIR SEALING STRATEGIES

ANIMAL ALLERGENS
APPLIANCE EFFICIENCY RATINGS
ASBESTOS FLOORING HAZARD REDUCTION
ASBESTOS-FREE INSULATION MATERIALS
ASBESTOS IDENTIFICATION IN buildings
ATTIC LEAKS, CONDENSATION & ATTIC MOLD
ATTIC VENTILATION

BASEMENT CEILING VAPOR BARRIER
BASEMENT HEAT LOSS
BASEMENT LEAKS, INSPECT FOR
BASEMENT WATERPROOFING

BATH & KITCHEN DESIGN GUIDE
BATHROOM VENTILATION
BIOGAS PRODUCTION & USE
BLOWER DOORS & AIR INFILTRATION
BLOWER FAN CONTINUOUS OPERATION
BLOWER FAN OPERATION & TESTING
BLOWN-IN INSULATION

BRICK LINED WALLS
BRICK VENEER WALL INSULATION
BRICK VENEER WALL Loose, Bulged
BRICK WALL DRAINAGE WEEP HOLES
BUCKLED FOUNDATIONS due to INSULATION?
BUILDING NOISE DIAGNOSIS & CURE

CATHEDRAL CEILING INSULATION
CATHEDRAL CEILING VENTILATION
CEILING FINISHES INTERIOR
CEILINGS, DROP or SUSPENDED PANEL
CEILINGS, PLASTER TYPES

CHIMNEY INSPECTION DIAGNOSIS & REPAIR
COOLING LOAD REDUCTION by ROOF VENTS
COMBUSTION AIR for TIGHT buildings
CONDENSING BOILERS/FURNACES DAMAGE

CATHEDRAL CEILING INSULATION
CATHEDRAL CEILING VENTILATION
CEILING FINISHES INTERIOR
CEILINGS, DROP or SUSPENDED PANEL
CEILINGS, PLASTER TYPES

CHIMNEY INSPECTION DIAGNOSIS & REPAIR
COOLING LOAD REDUCTION by ROOF VENTS
COMBUSTION AIR for TIGHT BUILDINGS
CONDENSING BOILERS/FURNACES DAMAGE
CONDENSATION or SWEATING PIPES, TANKS
COOLING LOAD REDUCTION by ROOF VENTS
CRAWL SPACES

DEFINITION of Heating & Cooling Terms
DEHUMIDIFICATION PROBLEMS
DEW POINT CALCULATION for WALLS
DEW POINT TABLE - CONDENSATION POINT GUIDE
DUCT SYSTEM & DUCT DEFECTS

ELECTRICAL INSPECTION, DIAGNOSIS, REPAIR

ENERGY SAVINGS in buildings
  AFUE DEFINITION, RATINGS
  AIR BYPASS LEAKS
  AIR CHANGE RATE ACH HEAT SAVINGS
  AIR CONDITIONING HEAT PUMP SAVINGS
  AIR LEAK SEALING PROCEDURE
  APPLIANCE EFFICIENCY RATINGS
  ATTIC LEAKS, CONDENSATION & ATTIC MOLD
  COOLING LOAD REDUCTION by ROOF VENTS
  ENERGY AUDIT - How to Use a Free One
  ENERGY SAVINGS MAXIMIZE RETURNS ON
  ENERGY SAVINGS PRIORITIES
  ENERGY SAVINGS RETROFIT CASE STUDY
  ENERGY SAVINGS RETROFIT LEAK SEALING GUIDE
  ENERGY SAVINGS RETROFIT OPTIONS
  ENERGY STAR PROGRAM
  ENERGY USE MONITORING
  GLASS vs HEAT MIRROR SOLAR GAIN/Loss
  HEAT LOSS in buildings
  HEATING COST SAVINGS METHODS
  HIGH MASS TRADEOFFS, HEATING vs COOLING
  HOUSE DOCTOR, how-to be
  INSULATION INSPECTION & IMPROVEMENT
  INSULATION LOCATION - WHERE TO PUT IT
  RADIANT BARRIERS
  REFLECTIVE INSULATION
  ROOF COLOR RECOMMENDATIONS
  Skylight Energy Efficiency
  SOLAR ENERGY SYSTEMS
  THERMAL MASS in buildings
  TIMERS for ELECTRIC WATER HEATERS
  VENTILATION, BALANCED HEAT COST SAVINGS
  WIND ENERGY SYSTEMS
  WINDOW EFFICIENCY Features & Ratings
  WOOD, COAL STOVES & FIREPLACES

ENVIRONMENTAL HAZARDS - INSPECT, TEST, REMEDY

EXTERIOR WALL SIDING TRIM & FINISHES

FIBERGLASS INSULATION
FIBERGLASS HAZARDS
FIBERGLASS INSULATION MOLD

FLASHING MEMBRANES PEEL & STICK
FLAT ROOF MOISTURE & CONDENSATION

FLOOD DAMAGE ASSESSMENT, SAFETY & CLEANUP
FLOODS IN buildings-mold

FLOOR, CONCRETE SLAB CHOICES
FLOOR, CONCRETE SLAB POURED FINISH
FLOOR DAMAGE DIAGNOSIS
FLOOR RADIANT HEAT Mistakes to Avoid
FLOOR TYPES & DEFECTS

FOUNDATION WATERPROOFING
FRENCH DRAINS
FRAMING DETAILS for BETTER INSULATION
FRAMING DETAILS for DOUBLE WALL HOUSES
FRAMING METAL STUD PERFORMANCE
FREEZE-PROOF A BUILDING
FROST HEAVES, FOUNDATION, SLAB

GREEN BUILDING CONSTRUCTION CODES GUIDES
GREENHOUSE DESIGN for SOLAR HEATING

HEAT LOSS in buildings
HEAT LOSS DETECTION TOOLS
  Find Heat Loss & Air Leaks
  Heat Loss Investigation Sequence
  Blower Door Test Data Results
  Smoke Gun for Air Leaks
  Smoke Pencil / Smoke Gun Suppliers
  Attic Energy Losses - InfraRed
  Basement Energy Losses- IR & Visual
  Duct System Air Movement
  Living Space Heat Loss
  Targets & Hidden Leak Points
  Thermography IR Infra Red & Thermal Scanners
  Convective Loops & Thermal Bypass Leaks
  HOUSE DOCTOR, how-to be
  Insulation Air & Heat Leaks
  The Bottom Line on Energy Retrofits
HEAT LOSS INDICATORS
HEAT LOSS PREVENTION PRIORITIES
HEAT LOSS R U & K VALUE CALCULATION
HEAT TAPES & CABLES on Roofs for Ice Dams
HEATING COST SAVINGS METHODS

HOT ROOF DESIGNS: Un-Vented Roof Solutions
HOUSEWRAP AIR & VAPOR BARRIERS
HOUSE DOCTOR, how-to be

HUMIDITY LEVEL TARGET

ICE DAM PREVENTION
INSULATION CHOICES
Insulation Air & Heat Leaks
INSULATION FACT SHEET- DOE
INSULATION for GREENHOUSE or SOLARIUM
INSULATION IDENTIFICATION GUIDE
INSULATION INSPECTION & IMPROVEMENT
INSULATION LOCATION - WHERE TO PUT IT
  INSULATION LOCATION & QUANTITY for ATTICS
  INSULATION LOCATION for BASEMENT FLOORS
  INSULATION LOCATION for BASEMENT WALLS
  INSULATION LOCATION for BRICK or BLOCK WALL CAVITY
  INSULATION LOCATION for BRICK VENEER WALLS
  INSULATION LOCATION for CAPES, CRAWLSPACES
  INSULATION LOCATION for CATHEDRAL CEILINGS
  INSULATION LOCATION for GREENHOUSE or SOLARIUM
  INSULATION LOCATION for PASSIVE SOLAR FLOOR SLAB
  INSULATION LOCATION & EXTENT for SLABS
  INSULATION LOCATION for SOUND CONTROL
  INSULATION LOCATION for SUSPENDED PANELS
  INSULATION LOCATION for SWIMMING, INDOOR

INSULATION MOLD
INSULATION R-Values & Properties

INSULATION IDENTIFICATION GUIDE
INSULATION INSPECTION & IMPROVEMENT
  ATTIC CONDENSATION CAUSE & CURE
  Air Bypass Leaks, Thermal Tracking
  Blocked Soffit Intake Vents
  BRICK or BLOCK WALL CAVITY INSULATION
  BRICK VENEER WALL INSULATION
  CATHEDRAL CEILING INSULATION
  CATHEDRAL CEILING VENTILATION
  ENERGY SAVINGS in buildings
  FIBERGLASS DUCT, RIGID CONSTRUCTION
  FIRE PROTECTION FOR FOAM BOARD INSULATION
  FOUNDATION INSULATION OPTIONS
  FRAMING DETAILS for BETTER INSULATION
  FRAMING DETAILS for DOUBLE WALL HOUSES
  FRAMING METAL STUD PERFORMANCE
  HOT ROOF DESIGNS: Un-Vented Roof Solutions
  Inspect Attics for Moisture or Mold
  Inspect Attics for Blocked Soffit Intake Vents
  Inspect Basements for Moisture or Mold
  Inspect Building Exterior - Roof Venting
  Inspect the Ridge Vent System from the Attic
  Inspect the Soffit Vent System from the Attic
  Insects & Foam Insulation
  HOUSE DOCTOR, how-to be
  Insulation Air & Heat Leaks
  INSULATION R-Values & Properties
  LOG HOME WALL INSULATION VALUES
  MOISTURE in BUILDING WALLS, EFFECTS
  MOISTURE in CELLULOSE INSULATION
  Mold in Fiberglass Insulation
  Mold on Books, Book Conservation
  Mold on Fiberboard Insulating Sheathing
  MOLD in Foam Insulation
  MOLD in INSULATION
  Mold Resistance of Foam Insulation
  MOLD PREVENTION AFTER FLOODING
  MOLD RESISTANT CONSTRUCTION
  PASCAL CALCULATIONS
  PHENOLIC FOAM INSULATION
  POLYISOCYANURATE FOAM INSULATION
  POLYISOCYANURATE FOAM BELOW SLABS
  POLYSTYRENE FOAM INSULATION
  RADIANT BARRIERS
  REFLECTIVE INSULATION
  RIGID FOAM USE INDOORS
  STRESS SKIN INSULATED PANELS
  STUCCO OVER FOAM INSULATION
  SUPER HI-R INSULATION
  SUPERINSULATION RETROFIT
  Urea Formaldehyde Foam Insulation UFFI
  URETHANE FOAM Deterioration, Outgassing
  VERMICULITE INSULATION

INSULATION LOCATION - WHERE TO PUT IT
INSULATION MOLD
INSULATION R-Values & Properties

LEED GREEN BUILDING CERTIFICATION
LEED Building Designation & IAQ
LIGHTING, INTERIOR GUIDE
LOG HOME ENERGY EFFICIENCY
LOG HOME GUIDE

MOBILE HOME INSPECTIONS
MOISTURE CONTROL in buildings
MOLD in FOAM INSULATION, RESISTANCE
MOLD INFORMATION CENTER

Nanomaterials Hazards
NOISE / SOUND DIAGNOSIS & CURE
NOISE CONTROL for HEATING SYSTEMS
NOISE CONTROL for FLOORS
NOISE CONTROL for PLUMBING
NOISE CONTROL for ROOFS

ODORS & SMELLS DIAGNOSIS & CURE

PAINT FALURE, DIAGNOSIS, CURE, PREVENTION
PASSIVE SOLAR DESIGN METHOD
PASSIVE SOLAR HEAT PERFORMANCE
PASSIVE SOLAR HOME, LOW COST
PHOTOVOLTAIC POWER SYSTEMS
PLASTER & BEAVERBOARD & DRYWALL
PASCAL CALCULATIONS

RADIANT BARRIERS
RADIANT HEAT
RADIANT HEAT Floor Mistakes to Avoid
RADIANT HEAT TEMPERATURES
RADIANT SLAB FLOORING CHOICES
RADIANT SLAB TUBING & FLUID CHOICES
REFLECTIVE INSULATION
RIGID FOAM USE INDOORS
ROOF VENTING ENERGY SAVING DETAILS
ROOF VENTING NEEDED?
ROOF VENTILATION SPECIFICATIONS
ROT, FUNGUS, TERMITES
ROT, TIMBER FRAME

SEARS KIT HOUSES

SOLAR ENERGY SYSTEMS
SOUND CONTROL in buildings
STAIN & BIODETERIORATION AGENT CATALOG
STAINS on buildings - QUICK GUIDE
STAIN DIAGNOSIS on BUILDING EXTERIORS
STAIN DIAGNOSIS on BUILDING INTERIORS
STAINS on INDOOR SURFACES: PHOTO GUIDE

STRESS SKIN INSULATED PANELS
STUCCO OVER FOAM INSULATION
SWEATING (CONDENSATION) on PIPES, TANKS

THERMAL EXPANSION of MATERIALS
THERMAL MASS in buildings
  THERMAL MASS FLOOR SLABS
  THERMAL MASS in UPSTAIRS
  THERMAL MASS WALL DESIGN
  THERMAL MASS in HOMES - STUDY
  THERMAL MASS TRADEOFFS, HEATING vs COOLING

THERMAL TRACKING & HEAT LOSS
  Ceiling Thermal Tracking Marks
  Wall Thermal Tracking Stains
  Floor Carpet Thermal Tracking Stains
  Air Bypass Leaks Marks on Insulation
  Thermal Tracking to Diagnose IAQ
  Stains HVAC Supply Registers
  Pet Stains on Floors
  Pet Stains on Walls
  Human Occupant Stains on Walls
  Stains from Candles, Woodstoves, Fireplaces
  Other Stains on Indoor Walls & Ceilings
  What to Do About Thermal Tracking

VAPOR BARRIERS & CONDENSATION in buildings
  ATTIC CONDENSATION CAUSE & CURE
  BASEMENT CEILING VAPOR BARRIER
  CONDENSATION or SWEATING PIPES, TANKS
  CRAWL SPACE VAPOR BARRIER
  DEW POINT CALCULATION for WALLS
  DEW POINT TABLE - CONDENSATION POINT GUIDE
  FELT 15# ROOFING, as HOUSEWRAP/VAPOR BARRIER
  HOUSEWRAP AIR & VAPOR BARRIERS
  HOUSEWRAP INSTALLATION DETAILS
  HOUSEWRAP PRODUCT CHOICES
  HOUSEWRAP at SILLS, SOLES, TOP PLATES
  HUMIDITY LEVEL TARGET
  MOISTURE CONTROL in buildings
  RAIN SPLASH-UP SIDING DAMAGE
  VAPOR BARRIERS & AIR SEALING at BAND JOISTS
  VAPOR BARRIERS & CONDENSATION in buildings
  VAPOR BARRIERS & HOUSEWRAP
  VAPOR CONDENSATION & BUILDING SHEATHING
  WATER BARRIERS, EXTERIOR
  WOOD SIDING FLASHING DETAILS

VENTILATION in buildings

WATER ENTRY in buildings
WIND ENERGY SYSTEMS
WIND TURBINES & LIGHTNING
WIND WASHING INSULATION At EAVES
WINDOWS & DOORS

WINTERIZE A BUILDING
Wood Burning Heaters Fireplaces Stoves
Woodstove Safety

ZONE VALVES

More Information

Cellulose insulation retrofit (C) Daniel Friedman

Value of Energy Retrofits for Air Leaks & Heat Loss
InspectAPedia®  -    

  • The bottom line value of energy retrofits for air leaks and heat loss in buildings
  • How to find, diagnose, & correct air leaks & heat losses in buildings
  • "House Doctors" survey buildings to find and fix energy losing air & heat leaks
  • Solar Age Magazine Articles on Renewable Energy, Energy Savings, Construction Practices
InspectAPedia offers impartial, unbiased advice without conflicts of interest. We will block advertisements which we discover or readers inform us are associated with bad business practices, false-advertising, or junk science. Our contact info is at InspectAPedia.com/Contact.htm.

This article series discusses finding and curing air leaks and heat losses in buildings, here focusing on the bottom line value of energy savings retrofits - where to spend your weatherization and insulation money. This detailed article accompanies a building weatherization and energy-savings company through a detailed building inspection for heat loss points and air leaks. Readers should also see HEAT LOSS in buildings, see HEAT LOSS R U & K VALUE CALCULATION, and see HEAT LOSS INDICATORS. And see ENERGY SAVINGS RETROFIT OPTIONS for energy savings products and tops like lightweight concrete insulation, fixing window leaks, and more.

Our page top photo shows the risk of an insulation blow-in retrofit by an amateur. The heating cost reduction from adding cellulose to the attic floor may be offset by the installer's mistake of knocking down and failing to replace improperly-installed horizontal fiberglass batts on the attic side of a wall between the attic and heated space. The net gain of this incomplete insulation retrofit may have been small.

But properly performed, an energy retrofit that determines the main heat loss points in a building (or un-wanted heat gain during the cooling season) can pay for itself very quickly.

Contact us to suggest text changes and additions and, if you wish, to receive online listing and credit for that contribution.

© Copyright 2012 InspectAPedia.com, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use page top links to major topics or use links at the left of each page to navigate within topics and documents at this website. Green links show where you are in a document series or at this website.

Bottom Line Value on Energy Retrofits for Air Leaks & Heat Loss in buildings

This article series explains how to survey a building for air and heat loss or gain points and how to correct them.

As we introduced above, in this article the author, Steven Bliss, accompanies a building weatherization and energy-savings company through a detailed building inspection for heat loss points, convective loops, and air leaks. The author accompanies Princeton Energy Partners as they use thermal imaging, smoke guns, and visual inspection to pinpoint building air leaks, heat loss points, air infiltration and air exfiltration on a building. The importance of setting priorities for sealing these points of energy wasted is emphasized and discussed, and sketches as well as photographs of common points of building heat loss, or unwanted heat gain, and air leaks are provided.

  • Building Heat Loss & Air Leaks - PDF form, use your browser's back button to return to this page
  • Building Heat Loss & Air Leaks - part 2
  • Building Heat Loss & Air Leaks - part 3
  • Building Heat Loss & Air Leaks - part 4 - what is the bottom line value of energy retrofits to stop air leaks & heat loss?

The text below paraphrases, quotes-from, updates, and comments an original article, "House Doctors with Better Medicine, Princeton Energy Partners use the latest diagnostic tools to comb a house for the major causes of heat loss. Their findings are often astonishing. Their strong prescriptions bring results', Steven Bliss, (see links just above) from Solar Age Magazine and written by Steven Bliss.

The Bottom Line on Energy Retrofits Using Caulks and Sealants

Energy retrofitting reduces drafts and cold spots and, according to PEP, produces some unanticipated benefits such as fewer rodent problems and fewer frozen pipes. Still, to sell the service to big buyers - the developers, housing authorities, and government agencies - it has to show an attractive return on investment. Says Gadsby referring to conventional weathersealing treatments, "To do a job for $1200. that's going to save $50. a year is just not the way to do business."

In some cases the savings have been spectacular. For example in a 1982 retrofit, PEP spent three months retrofitting the 450-unit Glenhardie Condominium Comlex near Valley Forge, PA, for $62,000.

The 20-building development already had its insulation and heating system upgraded when it went condo four years earlier. After three months of house-doctoring, consisting solely of attic work, the annual heating bill was reduced from2093 to 1329 therms of natural gas, resulting in a first-year savings of $40,600, not including the $9,300. tax credit.

More typical was a proposal to the Baltimore Housing Authority, in which PEP agreed to treat apartments for $550. each while they were undergoing rehab. PEP's work was to be staged over two to three visits.

With annual heating bills in that housing stock running $1200 to $1300 (1984 costs), the simple payback would be under three years. In terms of air infiltration alone, said Gadsby, recently-built townhouses generally measure in at about 10 to 15 ach (1984 data) at 50 Pascals before house-doctoring and are sealed down to about 6 ach after.

Costs for weatherizing are held down by providing the service in a one-day blitz, or in new construction in a series of quick hits. In general, a weatherization company can do more effective work for less money during construction or rehab than with retrofitting, since the problems are more visible and accessible. The cost to the homeowner was estimated to be one half to two-thirds what it would cost to retrofit after construction, and you're probably going to save an extra 5 to 10 percent on energy costs as well.

See HEAT LOSS R U & K VALUE CALCULATION for additional details about calculating building heat losses.

Here we include solar energy, solar heating, solar hot water, and related building energy efficiency improvement articles reprinted/adapted/excerpted with permission from Solar Age Magazine - editor Steven Bliss.

Questions & Answers regarding this article

.

Ask a Question or Search InspectAPedia

HTML Comment Box is loading comments...

Share this Article      

...

Technical Reviewers & References

  • InspectAPedia.com® - Daniel Friedman - Publisher & Editor.
  • InspectAPedia Bookstore lists recommended books, organized by topic & available for purchase. Most of our articles also include a list of recommended books for the specific article topic as well as other references, and information sources.
  • Critique, contributions wanted: Contact Us to suggest corrections or additions to articles at this website, and if you wish, to receive online listing and credit as a contributor. Particular thanks are due to the many experts and also consumers who read and critique technical articles at InspectAPedia.com.
  • Additional technical contributors & reference sources for this article are listed below.

Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

AIR CONDITIONING & HEAT PUMP SYSTEMS
ENERGY SAVINGS in buildings

INSULATION IDENTIFICATION GUIDE

INSULATION INSPECTION & IMPROVEMENT
INTERIORS of buildings

ACOUSTICAL SEALANT CHOICES
AIR BYPASS LEAKS
AIR CHANGE RATE ACH HEAT SAVINGS
AIR CLEANER PURIFIER TYPES

AIR FILTER EFFECTIVENESS
AIR FILTERS for HVAC SYSTEMS
AIR FILTERS, OPTIMUM INDOOR
AIR FILTERS, SOURCES FOR
AIR FILTERING STRATEGIES
AIR FILTERING CONTINUOUS FAN OPERATION
AIR HANDLER / BLOWER UNITS
AIR POLLUTANTS, COMMON INDOOR

AIR LEAK DETECTION TOOLS
  Find Heat Loss & Air Leaks
  Heat Loss Investigation Sequence
  Blower Door Test Data Results
  Smoke Gun for Air Leaks
  Smoke Pencil / Smoke Gun Suppliers
  Attic Energy Losses - InfraRed
  Basement Energy Losses- IR & Visual
  Duct System Air Movement
  Living Space Heat Loss
  Targets & Hidden Leak Points
  Thermography IR Infra Red & Thermal Scanners
  Convective Loops & Thermal Bypass Leaks
  HOUSE DOCTOR, how-to be
  Insulation Air & Heat Leaks
  The Bottom Line on Energy Retrofits
AIR LEAK MINIMIZATION
AIR LEAK SEALING PROCEDURE
AIR SEALING STRATEGIES

ANIMAL ALLERGENS
APPLIANCE EFFICIENCY RATINGS
ASBESTOS FLOORING HAZARD REDUCTION
ASBESTOS-FREE INSULATION MATERIALS
ASBESTOS IDENTIFICATION IN buildings
ATTIC LEAKS, CONDENSATION & ATTIC MOLD
ATTIC VENTILATION

BASEMENT CEILING VAPOR BARRIER
BASEMENT HEAT LOSS
BASEMENT LEAKS, INSPECT FOR
BASEMENT WATERPROOFING

BATH & KITCHEN DESIGN GUIDE
BATHROOM VENTILATION
BIOGAS PRODUCTION & USE
BLOWER DOORS & AIR INFILTRATION
BLOWER FAN CONTINUOUS OPERATION
BLOWER FAN OPERATION & TESTING
BLOWN-IN INSULATION

BRICK LINED WALLS
BRICK VENEER WALL INSULATION
BRICK VENEER WALL Loose, Bulged
BRICK WALL DRAINAGE WEEP HOLES
BUCKLED FOUNDATIONS due to INSULATION?
BUILDING NOISE DIAGNOSIS & CURE

CATHEDRAL CEILING INSULATION
CATHEDRAL CEILING VENTILATION
CEILING FINISHES INTERIOR
CEILINGS, DROP or SUSPENDED PANEL
CEILINGS, PLASTER TYPES

CHIMNEY INSPECTION DIAGNOSIS & REPAIR
COOLING LOAD REDUCTION by ROOF VENTS
COMBUSTION AIR for TIGHT buildings
CONDENSING BOILERS/FURNACES DAMAGE

CATHEDRAL CEILING INSULATION
CATHEDRAL CEILING VENTILATION
CEILING FINISHES INTERIOR
CEILINGS, DROP or SUSPENDED PANEL
CEILINGS, PLASTER TYPES

CHIMNEY INSPECTION DIAGNOSIS & REPAIR
COOLING LOAD REDUCTION by ROOF VENTS
COMBUSTION AIR for TIGHT BUILDINGS
CONDENSING BOILERS/FURNACES DAMAGE
CONDENSATION or SWEATING PIPES, TANKS
COOLING LOAD REDUCTION by ROOF VENTS
CRAWL SPACES

DEFINITION of Heating & Cooling Terms
DEHUMIDIFICATION PROBLEMS
DEW POINT CALCULATION for WALLS
DEW POINT TABLE - CONDENSATION POINT GUIDE
DUCT SYSTEM & DUCT DEFECTS

ELECTRICAL INSPECTION, DIAGNOSIS, REPAIR

ENERGY SAVINGS in buildings
  AFUE DEFINITION, RATINGS
  AIR BYPASS LEAKS
  AIR CHANGE RATE ACH HEAT SAVINGS
  AIR CONDITIONING HEAT PUMP SAVINGS
  AIR LEAK SEALING PROCEDURE
  APPLIANCE EFFICIENCY RATINGS
  ATTIC LEAKS, CONDENSATION & ATTIC MOLD
  COOLING LOAD REDUCTION by ROOF VENTS
  ENERGY AUDIT - How to Use a Free One
  ENERGY SAVINGS MAXIMIZE RETURNS ON
  ENERGY SAVINGS PRIORITIES
  ENERGY SAVINGS RETROFIT CASE STUDY
  ENERGY SAVINGS RETROFIT LEAK SEALING GUIDE
  ENERGY SAVINGS RETROFIT OPTIONS
  ENERGY STAR PROGRAM
  ENERGY USE MONITORING
  GLASS vs HEAT MIRROR SOLAR GAIN/Loss
  HEAT LOSS in buildings
  HEATING COST SAVINGS METHODS
  HIGH MASS TRADEOFFS, HEATING vs COOLING
  HOUSE DOCTOR, how-to be
  INSULATION INSPECTION & IMPROVEMENT
  INSULATION LOCATION - WHERE TO PUT IT
  RADIANT BARRIERS
  REFLECTIVE INSULATION
  ROOF COLOR RECOMMENDATIONS
  Skylight Energy Efficiency
  SOLAR ENERGY SYSTEMS
  THERMAL MASS in buildings
  TIMERS for ELECTRIC WATER HEATERS
  VENTILATION, BALANCED HEAT COST SAVINGS
  WIND ENERGY SYSTEMS
  WINDOW EFFICIENCY Features & Ratings
  WOOD, COAL STOVES & FIREPLACES

ENVIRONMENTAL HAZARDS - INSPECT, TEST, REMEDY

EXTERIOR WALL SIDING TRIM & FINISHES

FIBERGLASS INSULATION
FIBERGLASS HAZARDS
FIBERGLASS INSULATION MOLD

FLASHING MEMBRANES PEEL & STICK
FLAT ROOF MOISTURE & CONDENSATION

FLOOD DAMAGE ASSESSMENT, SAFETY & CLEANUP
FLOODS IN buildings-mold

FLOOR, CONCRETE SLAB CHOICES
FLOOR, CONCRETE SLAB POURED FINISH
FLOOR DAMAGE DIAGNOSIS
FLOOR RADIANT HEAT Mistakes to Avoid
FLOOR TYPES & DEFECTS

FOUNDATION WATERPROOFING
FRENCH DRAINS
FRAMING DETAILS for BETTER INSULATION
FRAMING DETAILS for DOUBLE WALL HOUSES
FRAMING METAL STUD PERFORMANCE
FREEZE-PROOF A BUILDING
FROST HEAVES, FOUNDATION, SLAB

GREEN BUILDING CONSTRUCTION CODES GUIDES
GREENHOUSE DESIGN for SOLAR HEATING

HEAT LOSS in buildings
HEAT LOSS DETECTION TOOLS
  Find Heat Loss & Air Leaks
  Heat Loss Investigation Sequence
  Blower Door Test Data Results
  Smoke Gun for Air Leaks
  Smoke Pencil / Smoke Gun Suppliers
  Attic Energy Losses - InfraRed
  Basement Energy Losses- IR & Visual
  Duct System Air Movement
  Living Space Heat Loss
  Targets & Hidden Leak Points
  Thermography IR Infra Red & Thermal Scanners
  Convective Loops & Thermal Bypass Leaks
  HOUSE DOCTOR, how-to be
  Insulation Air & Heat Leaks
  The Bottom Line on Energy Retrofits
HEAT LOSS INDICATORS
HEAT LOSS PREVENTION PRIORITIES
HEAT LOSS R U & K VALUE CALCULATION
HEAT TAPES & CABLES on Roofs for Ice Dams
HEATING COST SAVINGS METHODS

HOT ROOF DESIGNS: Un-Vented Roof Solutions
HOUSEWRAP AIR & VAPOR BARRIERS
HOUSE DOCTOR, how-to be

HUMIDITY LEVEL TARGET

ICE DAM PREVENTION
INSULATION CHOICES
Insulation Air & Heat Leaks
INSULATION FACT SHEET- DOE
INSULATION for GREENHOUSE or SOLARIUM
INSULATION IDENTIFICATION GUIDE
INSULATION INSPECTION & IMPROVEMENT
INSULATION LOCATION - WHERE TO PUT IT
  INSULATION LOCATION & QUANTITY for ATTICS
  INSULATION LOCATION for BASEMENT FLOORS
  INSULATION LOCATION for BASEMENT WALLS
  INSULATION LOCATION for BRICK or BLOCK WALL CAVITY
  INSULATION LOCATION for BRICK VENEER WALLS
  INSULATION LOCATION for CAPES, CRAWLSPACES
  INSULATION LOCATION for CATHEDRAL CEILINGS
  INSULATION LOCATION for GREENHOUSE or SOLARIUM
  INSULATION LOCATION for PASSIVE SOLAR FLOOR SLAB
  INSULATION LOCATION & EXTENT for SLABS
  INSULATION LOCATION for SOUND CONTROL
  INSULATION LOCATION for SUSPENDED PANELS
  INSULATION LOCATION for SWIMMING, INDOOR

INSULATION MOLD
INSULATION R-Values & Properties

INSULATION IDENTIFICATION GUIDE
INSULATION INSPECTION & IMPROVEMENT
  ATTIC CONDENSATION CAUSE & CURE
  Air Bypass Leaks, Thermal Tracking
  Blocked Soffit Intake Vents
  BRICK or BLOCK WALL CAVITY INSULATION
  BRICK VENEER WALL INSULATION
  CATHEDRAL CEILING INSULATION
  CATHEDRAL CEILING VENTILATION
  ENERGY SAVINGS in buildings
  FIBERGLASS DUCT, RIGID CONSTRUCTION
  FIRE PROTECTION FOR FOAM BOARD INSULATION
  FOUNDATION INSULATION OPTIONS
  FRAMING DETAILS for BETTER INSULATION
  FRAMING DETAILS for DOUBLE WALL HOUSES
  FRAMING METAL STUD PERFORMANCE
  HOT ROOF DESIGNS: Un-Vented Roof Solutions
  Inspect Attics for Moisture or Mold
  Inspect Attics for Blocked Soffit Intake Vents
  Inspect Basements for Moisture or Mold
  Inspect Building Exterior - Roof Venting
  Inspect the Ridge Vent System from the Attic
  Inspect the Soffit Vent System from the Attic
  Insects & Foam Insulation
  HOUSE DOCTOR, how-to be
  Insulation Air & Heat Leaks
  INSULATION R-Values & Properties
  LOG HOME WALL INSULATION VALUES
  MOISTURE in BUILDING WALLS, EFFECTS
  MOISTURE in CELLULOSE INSULATION
  Mold in Fiberglass Insulation
  Mold on Books, Book Conservation
  Mold on Fiberboard Insulating Sheathing
  MOLD in Foam Insulation
  MOLD in INSULATION
  Mold Resistance of Foam Insulation
  MOLD PREVENTION AFTER FLOODING
  MOLD RESISTANT CONSTRUCTION
  PASCAL CALCULATIONS
  PHENOLIC FOAM INSULATION
  POLYISOCYANURATE FOAM INSULATION
  POLYISOCYANURATE FOAM BELOW SLABS
  POLYSTYRENE FOAM INSULATION
  RADIANT BARRIERS
  REFLECTIVE INSULATION
  RIGID FOAM USE INDOORS
  STRESS SKIN INSULATED PANELS
  STUCCO OVER FOAM INSULATION
  SUPER HI-R INSULATION
  SUPERINSULATION RETROFIT
  Urea Formaldehyde Foam Insulation UFFI
  URETHANE FOAM Deterioration, Outgassing
  VERMICULITE INSULATION

INSULATION LOCATION - WHERE TO PUT IT
INSULATION MOLD
INSULATION R-Values & Properties

LEED GREEN BUILDING CERTIFICATION
LEED Building Designation & IAQ
LIGHTING, INTERIOR GUIDE
LOG HOME ENERGY EFFICIENCY
LOG HOME GUIDE

MOBILE HOME INSPECTIONS
MOISTURE CONTROL in buildings
MOLD in FOAM INSULATION, RESISTANCE
MOLD INFORMATION CENTER

Nanomaterials Hazards
NOISE / SOUND DIAGNOSIS & CURE
NOISE CONTROL for HEATING SYSTEMS
NOISE CONTROL for FLOORS
NOISE CONTROL for PLUMBING
NOISE CONTROL for ROOFS

ODORS & SMELLS DIAGNOSIS & CURE

PAINT FALURE, DIAGNOSIS, CURE, PREVENTION
PASSIVE SOLAR DESIGN METHOD
PASSIVE SOLAR HEAT PERFORMANCE
PASSIVE SOLAR HOME, LOW COST
PHOTOVOLTAIC POWER SYSTEMS
PLASTER & BEAVERBOARD & DRYWALL
PASCAL CALCULATIONS

RADIANT BARRIERS
RADIANT HEAT
RADIANT HEAT Floor Mistakes to Avoid
RADIANT HEAT TEMPERATURES
RADIANT SLAB FLOORING CHOICES
RADIANT SLAB TUBING & FLUID CHOICES
REFLECTIVE INSULATION
RIGID FOAM USE INDOORS
ROOF VENTING ENERGY SAVING DETAILS
ROOF VENTING NEEDED?
ROOF VENTILATION SPECIFICATIONS
ROT, FUNGUS, TERMITES
ROT, TIMBER FRAME

ROOF ARCHITECTURAL STYLES - PHOTO GUIDE
ROOF CLEANING RECOMMENDATIONS
ROOF DORMER TYPES - PHOTO GUIDE
ROOF VENTILATION SPECIFICATIONS
ROT, FUNGUS, TERMITES
  TERMITE SHIELDS vs TERMITICIDE
ROT, TIMBER FRAME

SEARS KIT HOUSES

SOLAR ENERGY SYSTEMS
SOUND CONTROL in buildings
STAIN & BIODETERIORATION AGENT CATALOG
STAINS on buildings - QUICK GUIDE
STAIN DIAGNOSIS on BUILDING EXTERIORS
STAIN DIAGNOSIS on BUILDING INTERIORS
STAINS on INDOOR SURFACES: PHOTO GUIDE

STRESS SKIN INSULATED PANELS
STUCCO OVER FOAM INSULATION
SWEATING (CONDENSATION) on PIPES, TANKS

THERMAL EXPANSION of MATERIALS
THERMAL MASS in buildings
  THERMAL MASS FLOOR SLABS
  THERMAL MASS in UPSTAIRS
  THERMAL MASS WALL DESIGN
  THERMAL MASS in HOMES - STUDY
  THERMAL MASS TRADEOFFS, HEATING vs COOLING

THERMAL TRACKING & HEAT LOSS
  Ceiling Thermal Tracking Marks
  Wall Thermal Tracking Stains
  Floor Carpet Thermal Tracking Stains
  Air Bypass Leaks Marks on Insulation
  Thermal Tracking to Diagnose IAQ
  Stains HVAC Supply Registers
  Pet Stains on Floors
  Pet Stains on Walls
  Human Occupant Stains on Walls
  Stains from Candles, Woodstoves, Fireplaces
  Other Stains on Indoor Walls & Ceilings
  What to Do About Thermal Tracking

VAPOR BARRIERS & CONDENSATION in buildings
  ATTIC CONDENSATION CAUSE & CURE
  BASEMENT CEILING VAPOR BARRIER
  CONDENSATION or SWEATING PIPES, TANKS
  CRAWL SPACE VAPOR BARRIER
  DEW POINT CALCULATION for WALLS
  DEW POINT TABLE - CONDENSATION POINT GUIDE
  FELT 15# ROOFING, as HOUSEWRAP/VAPOR BARRIER
  HOUSEWRAP AIR & VAPOR BARRIERS
  HOUSEWRAP INSTALLATION DETAILS
  HOUSEWRAP PRODUCT CHOICES
  HOUSEWRAP at SILLS, SOLES, TOP PLATES
  HUMIDITY LEVEL TARGET
  MOISTURE CONTROL in buildings
  RAIN SPLASH-UP SIDING DAMAGE
  VAPOR BARRIERS & AIR SEALING at BAND JOISTS
  VAPOR BARRIERS & CONDENSATION in buildings
  VAPOR BARRIERS & HOUSEWRAP
  VAPOR CONDENSATION & BUILDING SHEATHING
  WATER BARRIERS, EXTERIOR
  WOOD SIDING FLASHING DETAILS

VENTILATION in buildings

WATER ENTRY in buildings
WIND ENERGY SYSTEMS
WIND TURBINES & LIGHTNING
WIND WASHING INSULATION At EAVES
WINDOWS & DOORS

WINTERIZE A BUILDING
WOOD Burning Heaters Fireplaces Stoves

  • Solar Age Magazine was the official publication of the American Solar Energy Society. The contemporary solar energy magazine associated with the Society is Solar Today. "Established in 1954, the nonprofit American Solar Energy Society (ASES) is the nation's leading association of solar professionals & advocates. Our mission is to inspire an era of energy innovation and speed the transition to a sustainable energy economy. We advance education, research and policy. Leading for more than 50 years. ASES leads national efforts to increase the use of solar energy, energy efficiency and other sustainable technologies in the U.S. We publish the award-winning SOLAR TODAY magazine, organize and present the ASES National Solar Conference and lead the ASES National Solar Tour – the largest grassroots solar event in the world."
  • Steven Bliss served as editorial director and co-publisher of The Journal of Light Construction for 16 years and previously as building technology editor for Progressive Builder and Solar Age magazines. He worked in the building trades as a carpenter and design/build contractor for more than ten years and holds a masters degree from the Harvard Graduate School of Education. Excerpts from his recent book, Best Practices Guide to Residential Construction, Wiley (November 18, 2005) ISBN-10: 0471648361, ISBN-13: 978-0471648369, appear throughout this website, with permission and courtesy of Wiley & Sons. Best Practices Guide is available from the publisher, J. Wiley & Sons, and also at Amazon.com.
    Excerpts with updates and annotations expanding the original Best Practices Guide text can be found in the online review and book summary at BEST CONSTRUCTION PRACTICES GUIDE and also at DECK & PORCH CONSTRUCTION, at INDOOR AIR QUALITY IMPROVEMENT GUIDE, and in other articles found at InspectAPedia.com such as HOUSEWRAP AIR & VAPOR BARRIERS, SOUND CONTROL in buildings, and other topics.
  • Ice Dam Leaks in building attics and roof cavities, how to inspect for evidence of leaks, identify causes, and correct bad attic ventilation, improper roof venting, and these causes of attic mold or roof structure damage

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.
  • ...
Home About Us Accuracy Contact Us Content Use Policy Privacy Website Description © 2012 Copyright InspectAPedia.com