InspectAPedia.com InspectAPedia®
 

Free Encyclopedia of Building & Environmental Inspection, Testing, Diagnosis, Repair

Ask a Question or Search InspectAPedia

  • HOME
  • AIR CONDITIONING
  • ELECTRICAL
  • EXTERIORS
  • HEATING
  • HOME INSPECTION
  • INTERIORS
  • PLUMBING
  • ROOFING
  • SEPTIC SYSTEMS
  • STRUCTURE
  • WATER SUPPLY
  • ENERGY SAVINGS
  • ENVIRONMENT
  • INDOOR AIR IAQ
  • INSULATION
  • MOLD INSPECT TEST REMOVE
  • NOISE
  • ODORS
  • SOLAR ENERGY
  • VENTILATION
  • EXPERTS DIRECTORY
  • CONTACT US


Mobile Phone/PDA website viewMobile View
ENERGY SAVINGS in buildings

ACOUSTICAL SEALANT CHOICES

AIR BYPASS LEAKS
AIR CHANGE RATE ACH HEAT SAVINGS
AIR CLEANER PURIFIER TYPES
AIR FILTERS for HVAC SYSTEMS
AIR FILTERS, OPTIMUM INDOOR
AIR HANDLER / BLOWER UNITS

AIR LEAK DETECTION TOOLS
AIR LEAK MINIMIZATION
AIR LEAK SEALING PROCEDURE
AIR POLLUTANTS, COMMON INDOOR
AIR SEALING STRATEGIES

APPLIANCE EFFICIENCY RATINGS
ASBESTOS IDENTIFICATION IN buildings

ATTIC LEAKS, CONDENSATION & ATTIC MOLD
ATTIC VENTILATION

BASEMENT CEILING VAPOR BARRIER
BASEMENT HEAT LOSS
BASEMENT LEAKS, INSPECT FOR
BASEMENT WATERPROOFING
BATHROOM VENTILATION
BIOGAS PRODUCTION & USE

BLOWER DOORS & AIR INFILTRATION
BLOWER FAN CONTINUOUS OPERATION
BLOWER FAN OPERATION & TESTING
BLOWN-IN INSULATION

BRICK LINED WALLS
BUCKLED FOUNDATIONS due to INSULATION?

CATHEDRAL CEILING INSULATION
CATHEDRAL CEILING VENTILATION
Ceramic Insulation

COOLING LOAD REDUCTION by ROOF VENTS
COMBUSTION AIR for TIGHT buildings
CONDENSING BOILERS/FURNACES DAMAGE
CRAWL SPACES

DEW POINT CALCULATION for WALLS
DEW POINT TABLE - CONDENSATION POINT GUIDE
DEFINITION of Heating & Cooling Terms
DUCT SYSTEM & DUCT DEFECTS

ELECTRIC HEAT
ELECTRIC POWER, PHOTOVOLTAIC, REMOTE SITE
ENERGY SAVINGS in buildings
ENERGY STAR PROGRAM
EVAPORATIVE COOLING SYSTEMS

FIBERGLASS INSULATION
FINANCIAL AID
FIREPLACES & HEARTHS
FLAT ROOF MOISTURE & CONDENSATION
FLOOR TYPES & DEFECTS
FOUNDATION WATERPROOFING
FRAMING DETAILS for BETTER INSULATION
FRAMING DETAILS for DOUBLE WALL HOUSES
FRAMING METAL STUD PERFORMANCE
FREEZE-PROOF A BUILDING
FROST HEAVES, FOUNDATION, SLAB

GEOTHERMAL HEATING SYSTEMS
GREEN BUILDING CONSTRUCTION CODES GUIDES
GREENHOUSE DESIGN for SOLAR HEATING
GREENHOUSE / SUNSPACE GLARE

HEAT LOSS in buildings
HEAT LOSS RATE CALCULATIONS
HEAT LOSS DETECTION TOOLS
HEAT LOSS INDICATORS
HEAT LOSS PREVENTION PRIORITIES
HEAT LOSS R U & K VALUE CALCULATION
HEAT PUMPS
HEAT TAPES & CABLES on Roofs for Ice Dams

HEATING COST SAVINGS METHODS
HEATING OIL USAGE RATE
HEATING SYSTEMS
HEATING COST FUEL & BTU Cost Table
HEATING LOSS DIAGNOSIS-BOILERS
HEATING LOSS DIAGNOSIS-FURNACES
HEATING SYSTEM INSPECTION PROCEDURE
HOUSEWRAP AIR & VAPOR BARRIERS
HOUSEWRAP INSTALLATION DETAILS
HOUSEWRAP at SILLS, SOLES, TOP PLATES
HOUSE DOCTOR, how-to be
HOT ROOF DESIGNS: Un-Vented Roof Solutions
HUMIDITY LEVEL TARGET

ICE DAM PREVENTION
INDOOR AIR QUALITY & HOUSE TIGHTNESS
INDOOR AIR QUALITY IMPROVEMENT GUIDE

INSULATION CHOICES
Insulation Air & Heat Leaks
INSULATION FACT SHEET- DOE
INSULATION for GREENHOUSE or SOLARIUM
INSULATION IDENTIFICATION GUIDE
INSULATION INSPECTION & IMPROVEMENT
INSULATION LOCATION - WHERE TO PUT IT
INSULATION MOLD
INSULATION R-Values & Properties

LEED GREEN BUILDING CERTIFICATION
LEED Building Designation & IAQ
LIGHTING, INTERIOR GUIDE
LOG HOME ENERGY EFFICIENCY
LOG HOME WALL INSULATION VALUES

METHANE GAS SOURCES
MOBILE HOME INSPECTIONS
MOISTURE CONTROL in buildings

PASCAL CALCULATIONS
PLASTER & BEAVERBOARD & DRYWALL

RADIANT BARRIERS
RADIANT HEAT
RADIANT HEAT Floor Mistakes to Avoid
RADIANT HEAT TEMPERATURES
RADIANT SLAB FLOORING CHOICES
RADIANT SLAB TUBING & FLUID CHOICES
REFLECTIVE INSULATION
RIGID FOAM USE INDOORS
ROOF VENTILATION SPECIFICATIONS

SHEATHING, FOIL FACED - VENTS

SOLAR ENERGY SYSTEMS
  BLOCKBED RADIANT FLOORS - SOLAR DESIGN
  FLOOR, CONCRETE SLAB CHOICES
  FLOOR, CONCRETE SLAB POURED FINISH
  GLASS vs HEAT MIRROR SOLAR GAIN/Loss
  GREENHOUSE DESIGN for SOLAR HEATING
  GREENHOUSE / SUNSPACE GLARE
  PASSIVE SOLAR DESIGN KEY ELEMENTS
  PASSIVE SOLAR DESIGN METHOD
  PASSIVE SOLAR ENERGY MONITORING
  PASSIVE SOLAR FLOOR TILES, PHASE CHANGE
  PASSIVE SOLAR HEAT PERFORMANCE
  PASSIVE SOLAR HOME, LOW COST
  PASSIVE SOLAR PERFORMANCE PROBE
  PASSIVE SOLAR Roof & Window Overhangs
  PHOTOVOLTAIC POWER SYSTEMS
  POLYCARBONATE GLAZING
  REMOTE ELECTRIC POWER, PHOTOVOLTAIC
  ROCK-BED SOLAR HEAT STORAGE DESIGN
  SLAB INSULATION, PASSIVE SOLAR
  SLATE THERMAL MASS for SOLAR HEAT STORAGE
  SOLAR COLLECTOR AIR or GAS COLLECTION
  SOLAR COLLECTOR EFFICIENCY COMPARISONS
  SOLAR COLLECTOR FILMS
  SOLAR COLLECTOR OUTGASSING
  SOLAR COLLECTOR WOOD HOUSINGS
  SOLAR GAIN CALCULATION
  SOLAR HEATING SYSTEM DESIGNS
  SOLAR HOT WATER HEATERS
  SOLAR HOUSE EVALUATION
  SOLAR MODULE MANUFACTURERS
  SOLAR SHADES & SUNSCREENS
  SOLAR SHADES, LOW-E EFFECTIVENESS
  SOLAR WATER DISINFECTION
  SOLAR HOT WATER HEATERS
  SUNSPACE DESIGN for SOLAR HEATING
  SUNSPACE GLAZING for SUNTANNING
  STORM WINDOW INTERIOR
  STORM WINDOW PLASTIC CHOICES
  STORM WINDOW WEEP HOLES
  SUNGAIN, FILMS, LOW-E GLASS
  SUNSPACE GLAZING for SUNTANNING
  SWIMMING POOL SOLAR HEAT, INDOOR
  SWIMMING POOL SOLAR HEAT, OUTDOOR DIAGNOSIS
  THERMAL MASS in buildings

STAINS on INDOOR SURFACES: PHOTO GUIDE
STRESS SKIN INSULATED PANELS
STUCCO WAll FAILURES DUE TO WEATHER
STUCCO WALL METHODS & INSTALLATION
STUCCO OVER FOAM INSULATION
SWEATING (CONDENSATION) on PIPES, TANKS

THERMAL EXPANSION of MATERIALS
THERMAL MASS in buildings
  THERMAL MASS FLOOR SLABS
  THERMAL MASS in UPSTAIRS
  THERMAL MASS WALL DESIGN
  THERMAL MASS in HOMES - STUDY
  THERMAL MASS TRADEOFFS, HEATING vs COOLING

THERMAL TRACKING & HEAT LOSS
THERMOSTATS, HEATING / COOLING

VAPOR BARRIERS & CONDENSATION in buildings
VENTILATION in buildings

WALL SIDING TRIM & FINISHES
WALL FINISHES INTERIOR

WATER BARRIERS, EXTERIOR BUILDING
WATER ENTRY in buildings
WIND ENERGY SYSTEMS
WIND TURBINES & LIGHTNING
WIND WASHING INSULATION At EAVES

WINDOWS & DOORS

WINTERIZE A BUILDING
WOOD Burning Heaters Fireplaces Stoves

More Information

Insulating a radiant slab (C) Daniel Friedman Flooring Choices for Use Over Concrete Slabs Using Thermal Mass
InspectAPedia®  -    

  • What finish flooring materials are best to use over a concrete floor slab to retain the thermal mass properties of the slab?
  • Flooring materials for passive solar floor slab designs where direct solar gain and passive solar heat storage are desired.
  • Questions & answers about how to choose a finish floor to be installed over a concrete slab where thermal mass is important
  • Solar Age Magazine Articles on Renewable Energy, Energy Savings, Construction Practices

This article discusses the best choices for finish flooring to use over a concrete floor slab intended to provide direct solar heat gain and heat storage.

InspectAPedia offers impartial, unbiased advice without conflicts of interest. We will block advertisements which we discover or readers inform us are associated with bad business practices, false-advertising, or junk science. Our contact info is at InspectAPedia.com/Contact.htm.

Accompanying text are reprinted/adapted/excerpted with permission from Solar Age Magazine - editor Steven Bliss. Our page top photograph shows a well-designed radiant-heat floor slab being constructed in Two Harbors, Minnesota where it gets too cold to fool around.

Also see FLOOR, CONCRETE SLAB POURED FINISH, and see THERMAL MASS in buildings and also PASSIVE SOLAR FLOOR TILES, PHASE CHANGE and THERMAL MASS WALL DESIGN and see these thermal mass articles: THERMAL MASS in buildings and THERMAL MASS in UPSTAIRS as well as the passive solar design articles organized at SOLAR ENERGY SYSTEMS.

© Copyright 2012 InspectAPedia.com, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use page top links to major topics or use links at the left of each page to navigate within topics and documents at this website. Green links show where you are in a document series or at this website.

Q&A on What Finish Flooring to Use to Cover a Concrete Floor Slab

The link to the original Q&A article in PDF form immediately below is followed by an expanded/updated online version of this article.

  • Q&A on Flooring Choices Over a Concrete Slab: Covering the Slab - PDF version, Use your browser's back button to return to this page

The question-and-answer article below paraphrases, quotes-from, updates, and comments an original article, (see links just above) from Solar Age Magazine and written by Steven Bliss.

What Flooring Materials are Best to Use Over a Concrete Floor Slab

Brick interior passive solar floor (C) Daniel Friedman

Question:

I'm in the process of building a home.

Are there any floor-covering products I can install over a pre cast concrete second floor (see THERMAL MASS in UPSTAIRS) and a cast-in-place poured concrete first floor slab (see THERMAL MASS in buildings).

I want a resilient (soft clay, brick?) finish floor that will yet retain the thermal mass properties of the concrete slab below. I understand the necessity for thermal mass [in my passive solar design home] but I would like to find a more pliable floor covering [than ceramic tile].

Our photograph (left) shows a passive solar brick interior floor, constructed over a poured concrete slab. This building is on the Vassar College Campus in Poughkeepsie, NY.


Tile floor over radiant heat and passive solar slab (C) Daniel Friedman

Answer:

Assuming you are interested in using these floors for direct-gain passive solar heat storage, we see two possible approaches:

  1. Try to find a finish flooring material that has a high heat capacity itself
  2. Look for a finish floor material that has negligible heat capacity but has good absorptive and good thermal conductivity.

Either of these approaches will allow the finish floor covering to transfer heat into the concrete floor slab which itself has a high heat storage capacity.

We know of no soft floor covering with high heat capacity, but the second approach shows some promise. A 1980's study by industry researchers concluded that any floor covering whose thermal conductance exceeded about 10 BTU/hr-ft2 would not impair the thermal storage capability of the concrete slab.

This eliminates using even the thinnest floor carpeting (whose conductance C is about 0.8 BTU/hr-ft2), and some vinyl floor coverings.

But this criteria permitted use of vinyl-asbestos floor tiles (C = 43 BTU/hr-ft2) until that product was discontinued in buildings, and it probably permits use of the modern replacements of those products. It also permits use of sheet vinyl flooring on felt backing (C = 21.2 BTU/hr-ft2).

Beyond C=10 flooring products, increasing the absorptive does more than increasing the conductivity.

Light flooring materials absorb less solar radiation (heat) and are thus less efficient (as much as 40 percent less for pastel colors).

Also, it is important to install the finish floor covering so that it makes a very good thermal contact through a continuous bond over the floor slab.

Low-density brick and other "soft" masonry materials are not ordinarily considered resilient. If they are well-bonded to the slab, however, they will not reduce its thermal performance much.

Our photograph (above) shows ceramic tile installed over a concrete floor slab intended to provide both passive solar gain and heat storage as well as delivering heat from a backup in-floor radiant heating system. Readers constructing an insulated slab with radiant floor heating, whether by passive solar or any other means, should not fail to read RADIANT HEAT Floor Mistakes to Avoid.

Also see FLOOR, CONCRETE SLAB POURED FINISH where we describe pour-on finish flooring for use over thermal mass concrete slabs.

Readers should also see POLYISOCYANURATE FOAM INSULATION, POLYISOCYANURATE FOAM BELOW SLABS,  INSULATION LOCATION for PASSIVE SOLAR FLOOR SLAB and also RIGID FOAM USE INDOORS. Readers should also see FLOOR, CONCRETE SLAB CHOICES for a discussion of choice of finish floor materials to preserve use of thermal mass of a concrete floor slab. Readers interested in basement insulation improvements should also see INSULATION LOCATION for BASEMENT WALLS and BASEMENT HEAT LOSS.

For more general energy savings advice see ENERGY SAVINGS PRIORITIES, and our insulation home page at INSULATION INSPECTION & IMPROVEMENT. If you are going to insulate under a basement or grade-level concrete slab floor, be sure to read SLAB INSULATION, PASSIVE SOLAR. Finally, readers considering adding insulation inside or outside a basement foundation wall should see POLYSTYRENE FOAM INSULATION as well as BUCKLED FOUNDATIONS due to INSULATION? Contact us to suggest text changes and additions and, if you wish, to receive online listing and credit for that contribution.

Here we include solar energy, solar heating, solar hot water, and related building energy efficiency improvement articles reprinted/adapted/excerpted with permission from Solar Age Magazine - editor Steven Bliss.

Questions & Answers regarding this article

.

Ask a Question or Search InspectAPedia

HTML Comment Box is loading comments...

Share this Article      

...

Technical Reviewers & References

  • InspectAPedia.com® - Daniel Friedman - Publisher & Editor.
  • InspectAPedia Bookstore lists recommended books, organized by topic & available for purchase. Most of our articles also include a list of recommended books for the specific article topic as well as other references, and information sources.
  • Critique, contributions wanted: Contact Us to suggest corrections or additions to articles at this website, and if you wish, to receive online listing and credit as a contributor. Particular thanks are due to the many experts and also consumers who read and critique technical articles at InspectAPedia.com.
  • Additional technical contributors & reference sources for this article are listed below.

Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

  FLOOR, CONCRETE SLAB CHOICES
  FLOOR, CONCRETE SLAB POURED FINISH

  • Solar Age Magazine was the official publication of the American Solar Energy Society. The contemporary solar energy magazine associated with the Society is Solar Today. "Established in 1954, the nonprofit American Solar Energy Society (ASES) is the nation's leading association of solar professionals & advocates. Our mission is to inspire an era of energy innovation and speed the transition to a sustainable energy economy. We advance education, research and policy. Leading for more than 50 years. ASES leads national efforts to increase the use of solar energy, energy efficiency and other sustainable technologies in the U.S. We publish the award-winning SOLAR TODAY magazine, organize and present the ASES National Solar Conference and lead the ASES National Solar Tour – the largest grassroots solar event in the world."
  • Steven Bliss served as editorial director and co-publisher of The Journal of Light Construction for 16 years and previously as building technology editor for Progressive Builder and Solar Age magazines. He worked in the building trades as a carpenter and design/build contractor for more than ten years and holds a masters degree from the Harvard Graduate School of Education. Excerpts from his recent book, Best Practices Guide to Residential Construction, Wiley (November 18, 2005) ISBN-10: 0471648361, ISBN-13: 978-0471648369, appear throughout this website, with permission and courtesy of Wiley & Sons. Best Practices Guide is available from the publisher, J. Wiley & Sons, and also at Amazon.com.
    Excerpts with updates and annotations expanding the original Best Practices Guide text can be found in the online review and book summary at BEST CONSTRUCTION PRACTICES GUIDE and also at DECK & PORCH CONSTRUCTION, at INDOOR AIR QUALITY IMPROVEMENT GUIDE, and in other articles found at InspectAPedia.com such as HOUSEWRAP AIR & VAPOR BARRIERS, SOUND CONTROL in buildings, and other topics.
  • Carson, Dunlop & Associates Ltd., 120 Carlton Street Suite 407, Toronto ON M5A 4K2. (416) 964-9415 1-800-268-7070 info@carsondunlop.com. Thanks to Alan Carson and Bob Dunlop, for permission to use illustrations from their publication, The Illustrated Home which illustrates construction details and building components. Carson Dunlop provides home inspection education including the ASHI-adopted Home Inspection Training Program (home study course), publications such as the Home Reference Book, report writing materials including the Horizon report writer, and home inspection services. Alan Carson is a past president of ASHI, the American Society of Home Inspectors.
  • Passive Solar Design Handbook Volume I, the Passive Solar Handbook Introduction to Passive Solar Concepts, in a version used by the U.S. Air Force - online version available at this link and from the USAF also at wbdg.org/ccb/AF/AFH/pshbk_v1.pdf
  • Passive Solar Design Handbook Volume II, the Passive Solar Handbook Comprehensive Planning Guide, in a version used by the U.S. Air Force - online version available at this link and from the USAF also at wbdg.org/ccb/AF/AFH/pshbk_v2.pdf [This is a large PDF file that can take a while to load]
  • Passive Solar Handbook Volume III, the Passive Solar Handbook Programming Guide, in a version used by the U.S. Air Force - online version available at this link and from the USAF also at wbdg.org/ccb/AF/AFH/pshbk_v3.pdf
  • The Passive Solar Design and Construction Handbook, Steven Winter Associates (Author), Michael J. Crosbie (Editor), Wiley & Sons, ISBN 978-047118382 or 0471183083 is available at Amazon.com and via the The Passive Solar Design and Construction Handbook, Steven Winter Associates (Author), Michael J. Crosbie (Editor), Wiley & Sons, ISBN 978-047118382 or 0471183083 is available at Amazon.com and via the InspectAPedia Bookstore
  • "Passive Solar Home Design", U.S. Department of Energy, describes using a home's windows, walls, and floors to collect and store solar energy for winter heating and also rejecting solar heat in warm weather.
  • "Solar Water Heaters", U.S. Department of Energy article on solar domestic water heaters to generate domestic hot water in buildings, explains how solar water heaters work. Solar heat for swimming pools is also discussed.
  • "Heat Exchangers for Solar Water Heating Systems", U.S. DOE describes the types of solar water heater heat exchange methods between the sun and the building's hot water supply
  • "Heat-Transfer Fluids for Solar Water Heating Systems", U.S. DOE, describes the types of fluids selected to transfer heat between the solar collector and the hot water in storage tanks in a building. These include air, water, water with glycol antifreeze mixtures (needed when using solar hot water systems in freezing climates), hydrocarbon oils, and refrigerants or silicones for heat transfer.
  • "Solar Water Heating System Maintenance and Repair", U.S. DOE
  • "Solar Water Heating System Freeze Protection", U.S. DOE,using antifreeze mixture in solar water heaters (or other freeze-resistant heat transfer fluids), as well as piping to permit draining the solar collector and piping system.
  • "Scaling and Corrosion in Solar Water Heating Systems", U.S. DOE
  • www.energysavers.gov/your_home/water_heating/index.cfm/mytopic=12850 is the base U.S. DOE website for these articles
  • "Active Solar Heating Systems", U.S. Department of Energy, including
  • "Radiant Heating Systems" U.S. DOE
  • "Absorption Heat Pumps & Coolers", U.S. DOE
  • "Solar Air Heating" U.S. DOE also referred to as "Ventilation Preheating" in which solar systems use air for absorbing and transferring solar energy or heat to a building
  • "Solar Liquid Heating" U.S. DOE, systems using liquid (typically water) in flat plate solar collectors to collect solar energy in the form of heat for transfer into a building for space heating or hot water heating. The term "solar liquid" is used for accuracy, rather than "solar water" because the water may contain an antifreeze or other chemicals.

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.
  • ...
Home About Us Accuracy Contact Us Content Use Policy Privacy Website Description © 2012 Copyright InspectAPedia.com