InspectAPedia.com InspectAPedia®
Google
InspectAPedia
 

Free Encyclopedia of Building & Environmental Inspection, Testing, Diagnosis, Repair

Ask a Question or Search InspectAPedia

  • HOME
  • AIR CONDITIONING
  • ELECTRICAL
  • EXTERIORS
  • HEATING
  • HOME INSPECTION
  • INTERIORS
  • PLUMBING
  • ROOFING
  • SEPTIC SYSTEMS
  • STRUCTURE
  • WATER SUPPLY
  • ENERGY SAVINGS
  • ENVIRONMENT
  • INDOOR AIR IAQ
  • INSULATION
  • MOLD INSPECT TEST REMOVE
  • NOISE
  • ODORS
  • SOLAR ENERGY
  • VENTILATION
  • EXPERTS DIRECTORY
  • CONTACT US



Mobile Phone/PDA website viewMobile View
INSULATION IDENTIFICATION GUIDE
INSULATION INSPECTION & IMPROVEMENT

ACOUSTICAL SEALANT CHOICES
AIR BYPASS LEAKS
AIR LEAK MINIMIZATION
AIR LEAK SEALING PROCEDURE

ASBESTOS FLOORING HAZARD REDUCTION
ASBESTOS FLOORING REMOVAL GUIDE
ASBESTOS IDENTIFICATION IN BUILDINGS
ASBESTOS LIST of PRODUCTS
ASBESTOS MATERIAL REGULATIONS
ASBESTOS PHOTO GUIDE to Materials
ASBESTOS RISK ASSESSMENT
ASBESTOS REMOVAL, Wetting Guidelines
ASBESTOS ROOFING / SIDING DUST
Asbestos Under the Microscope

ATTIC LEAKS, CONDENSATION & MOLD

BASEMENT CEILING VAPOR BARRIER
BASEMENT HEAT LOSS
BASEMENT LEAKS, INSPECT FOR
BASEMENT WATERPROOFING
BATH & KITCHEN DESIGN GUIDE
BATHROOM VENTILATION

BLOWER DOORS & AIR INFILTRATION
BLOWER FAN CONTINUOUS OPERATION
BLOWER FAN OPERATION & TESTING
BLOWN-IN INSULATION

BOOKSTORE - INTERIORS
BRICK LINED WALLS
BRICK VENEER WALL INSULATION
BRICK VENEER WALL Loose, Bulged
BRICK WALL DRAINAGE WEEP HOLES
BUCKLED FOUNDATIONS due to INSULATION?
BUILDING NOISE DIAGNOSIS & CURE

CABINETS & COUNTERTOPS
Carbon Nanotube Materials
CACTUS FUNGI / MOLD
CAR MOLD CONTAMINATION
CARPET DUST IDENTIFICATION
CARPET MOLD CONTAMINATION
CARPET TEST PROCEDURE
CARPETING & INDOOR AIR QUALITY
CARPETING, SELECTION & INSTALLATION

CATHEDRAL CEILING INSULATION
CATHEDRAL CEILING VENTILATION
CEILING FINISHES INTERIOR
CEILINGS, DROP or SUSPENDED PANEL
CEILINGS, PLASTER TYPES
CEILINGS, PLASTER, LOOSE HAZARDS
CEILING TILES - Asbestos-Containing

CONDENSATION or SWEATING PIPES, TANKS

CRAWL SPACES

DEFINITION of Heating & Cooling Terms
DECK & PORCH CONSTRUCTION
DEW POINT CALCULATION for WALLS
DEW POINT TABLE - CONDENSATION POINT GUIDE

ENERGY SAVINGS in BUILDINGS

ENVIRONMENTAL HAZARDS - INSPECT, TEST, REMEDY

Fiberboard Insulation Sheathing Mold
FIBERGLASS HAZARDS
FIBERGLASS INSULATION
FIBERGLASS PARTICLE CONTAMINATION TEST
Fiberglass Enviro-Scare
FIBERGLASS INSULATION MOLD
Fireproofing containing Asbestos

FRAMING DETAILS for BETTER INSULATION
FRAMING DETAILS for DOUBLE WALL HOUSES
FRAMING METAL STUD PERFORMANCE
FREEZE-PROOF A BUILDING
FROST HEAVES, FOUNDATION, SLAB

HEAT LOSS RATE CALCULATIONS
HEAT LOSS in BUILDINGS
HEAT LOSS DETECTION TOOLS
HEAT LOSS INDICATORS
HEAT LOSS PREVENTION PRIORITIES
HEAT LOSS R U & K VALUE CALCULATION

HOUSEWRAP AIR & VAPOR BARRIERS
HOUSEWRAP INSTALLATION DETAILS
HOUSEWRAP at SILLS, SOLES, TOP PLATES
HUMIDITY LEVEL TARGET

ICE DAM PREVENTION
INDOOR AIR QUALITY & HOUSE TIGHTNESS
INSULATION INSPECTION & IMPROVEMENT

INSULATION CHOICES
INSULATION FACT SHEET- DOE

INSULATION IDENTIFICATION GUIDE

INSULATION INSPECTION & IMPROVEMENT
  Air Bypass Leaks, Thermal Tracking
  AIR LEAK DETECTION TOOLS
  AIR LEAK MINIMIZATION
  AIR SEAL STRATEGIES
  ASBESTOS IDENTIFICATION IN BUILDINGS
  ATTIC CONDENSATION CAUSE & CURE
  BASEMENT CEILING VAPOR BARRIER
  BASEMENT De-Watering Systems
  BASEMENT HEAT LOSS
  Blocked Soffit Intake Vents
  BLOWER DOORS & AIR INFILTRATION
  BLOWN-IN INSULATION
  BRICK or BLOCK WALL CAVITY INSULATION
  BRICK VENEER WALL INSULATION
  BUCKLED FOUNDATIONS due to INSULATION?
  CASEWORK, CABINETS, SHELVING INSTALLATION
  CATHEDRAL CEILING INSULATION
  CATHEDRAL CEILING VENTILATION
  HOT ROOF DESIGNS: Un-Vented Roof Solutions
  ENERGY SAVINGS in BUILDINGS
  ENERGY AUDIT - How to Use a Free One
  ENERGY SAVINGS MAXIMIZE RETURNS ON
  ENERGY SAVINGS PRIORITIES
  ENERGY SAVINGS RETROFIT CASE STUDY
  ENERGY SAVINGS RETROFIT LEAK SEALING GUIDE
  ENERGY SAVINGS RETROFIT OPTIONS
  ENERGY STAR PROGRAM
  ENERGY USE MONITORING
  FIBERGLASS DUCT, RIGID CONSTRUCTION
  Fiberglass Insulation
  FIRE PROTECTION FOR FOAM BOARD INSULATION
  FOUNDATION INSULATION OPTIONS
  FRAMING DETAILS for BETTER INSULATION
  FRAMING DETAILS for DOUBLE WALL HOUSES
  FRAMING METAL STUD PERFORMANCE
  HEATING COST SAVINGS METHODS
  HIGH MASS TRADEOFFS, HEATING vs COOLING
  HOUSE DOCTOR, how-to be
  Inspect Attics for Moisture or Mold
  Inspect Attics for Blocked Soffit Intake Vents
  Inspect Basements for Moisture or Mold
  Inspect Building Exterior - Roof Venting
  Inspect the Ridge Vent System from the Attic
  Inspect the Soffit Vent System from the Attic
  Insects & Foam Insulation
  Insulation Air & Heat Leaks
  INSULATION for GREENHOUSE or SOLARIUM
  INSULATION CHOICES
  INSULATION FACT SHEET- DOE
  INSULATION PLACEMENT in BUILDINGS
  INSULATION R-Values & Properties
  LOG HOME WALL INSULATION VALUES
  MOISTURE in BUILDING WALLS, EFFECTS
  MOISTURE in CELLULOSE INSULATION
  Mold in Fiberglass Insulation
  Mold on Books, Book Conservation
  Mold on Fiberboard Insulating Sheathing
  MOLD in Foam Insulation
  MOLD in INSULATION
  Mold Resistance of Foam Insulation
  MOLD PREVENTION AFTER FLOODING
  MOLD RESISTANT CONSTRUCTION
  PASCAL CALCULATIONS
  PASSIVE SOLAR DESIGN METHOD
  PHENOLIC FOAM INSULATION
  POLYISOCYANURATE FOAM INSULATION
  POLYISOCYANURATE FOAM BELOW SLABS
  POLYSTYRENE FOAM INSULATION
  RADIANT BARRIERS
  REFLECTIVE INSULATION
  RIGID FOAM USE INDOORS
  ROOF VENTING ENERGY SAVING DETAILS
  ROOF VENTING NEEDED?
  ROOF VENTILATION SPECIFICATIONS
  SLAB INSULATION LOCATION
  SLAB INSULATION LOCATION & EXTENT
  SLAB INSULATION, PASSIVE SOLAR
  SLATE THERMAL MASS for SOLAR HEAT STORAGE
  SOUND CONTROL in BUILDINGS
  STRESS SKIN INSULATED PANELS
  STUCCO OVER FOAM INSULATION
  SUPER HI-R INSULATION
  SUPERINSULATION RETROFIT
  Urea Formaldehyde Foam Insulation UFFI
  URETHANE FOAM Deterioration, Outgassing
  VAPOR BARRIERS & AIR SEALING at BAND JOISTS
  VAPOR BARRIERS & CONDENSATION in BUILDINGS
  VAPOR BARRIERS & HOUSEWRAP
  VAPOR CONDENSATION & BUILDING SHEATHING
  VERMICULITE INSULATION


INSULATION LOCATION - WHERE TO PUT IT
  BLOWN-IN INSULATION
  INSULATION CHOICES
  INSULATION FACT SHEET- DOE
  INSULATION LOCATION & QUANTITY for ATTICS
  INSULATION LOCATION for BASEMENT FLOORS
  INSULATION LOCATION for BASEMENT WALLS
  INSULATION LOCATION for BRICK or BLOCK WALL CAVITY
  INSULATION LOCATION for BRICK VENEER WALLS
  INSULATION LOCATION for CAPES, CRAWLSPACES
  INSULATION LOCATION for CATHEDRAL CEILINGS
  INSULATION LOCATION for GREENHOUSE or SOLARIUM
  INSULATION LOCATION for PASSIVE SOLAR FLOOR SLAB
  INSULATION LOCATION & EXTENT for SLABS
  INSULATION LOCATION for SOUND CONTROL
  INSULATION LOCATION for SUSPENDED PANELS
  INSULATION LOCATION for SWIMMING, INDOOR

INSULATION MOLD
INSULATION R-Values & Properties

KIT HOMES, Aladdin, Sears, Wards, Others
KITCHEN & BATH DESIGN GUIDE
KITCHEN VENTILATION

LEED GREEN BUILDING CERTIFICATION
LOG HOME ENERGY EFFICIENCY
LOG HOME GUIDE

MOLD in FOAM INSULATION, RESISTANCE
MOISTURE CONTROL in BUILDINGS
MSDS Material Safety Data Sheets
MVOCs & MOLDY MUSTY ODORS
MYCOPHOBIA, STAINS MISTAKEN for MOLD
MYCOTOXIN EFFECTS of MOLD EXPOSURE

Nanomaterials Hazards
NOISE / SOUND DIAGNOSIS & CURE
NOISE CONTROL for HEATING SYSTEMS
NOISE CONTROL for FLOORS
NOISE CONTROL for PLUMBING
NOISE CONTROL for ROOFS

ODORS & SMELLS DIAGNOSIS & CURE
ODOR DIAGNOSIS CHECKLIST

PAINT FALURE, DIAGNOSIS, CURE, PREVENTION
Paper Duct Insulation Containing Asbestos
PASCAL CALCULATIONS

PASSIVE SOLAR DESIGN METHOD
PASSIVE SOLAR HEAT PERFORMANCE
PASSIVE SOLAR HOME, LOW COST
PHOTOVOLTAIC POWER SYSTEMS

RADIANT BARRIERS
RADIANT HEAT
RADIANT HEAT Floor Mistakes to Avoid
RADIANT HEAT TEMPERATURES
RADIANT SLAB FLOORING CHOICES
RADIANT SLAB TUBING & FLUID CHOICES
REFLECTIVE INSULATION
RIGID FOAM USE INDOORS

ROT, FUNGUS, TERMITES
ROT, TIMBER FRAME

SEARS KIT HOUSES
SHEATHING, FOIL FACED - VENTS
SLAB INSULATION, PASSIVE SOLAR
SOLAR ENERGY SYSTEMS

SOUND CONTROL in BUILDINGS

STAIN & BIODETERIORATION AGENT CATALOG
STAINS on BUILDINGS - QUICK GUIDE
STAIN DIAGNOSIS on BUILDING EXTERIORS
STAIN DIAGNOSIS on BUILDING INTERIORS
STAINS & FINISHES, INTERIOR
STAINS on INDOOR SURFACES: PHOTO GUIDE

STAIRS, RAILINGS, LANDINGS, RAMPS
STONE CLEANING METHODS
STRAW BALE CONSTRUCTION
STRESS SKIN INSULATED PANELS

STUCCO WAll FAILURES DUE TO WEATHER
STUCCO WALL METHODS & INSTALLATION
STUCCO OVER FOAM INSULATION
STUCCO PAINT FAILURES
SUMP PUMPS GUIDE
SWEATING (CONDENSATION) on PIPES, TANKS

THERMAL EXPANSION of MATERIALS
THERMAL MASS in BUILDINGS
THERMAL TRACKING & HEAT LOSS
THERMOSTATS, HEATING / COOLING

TRIM, INTERIOR INSTALLATION
TRUSS UPLIFT, ROOF
TRUSSES, Floor & Roof

VAPOR BARRIERS & CONDENSATION in BUILDINGS
VENTILATION in buildings
VINYL Siding or PLASTIC Window ODORS in buildings
VINYL CHLORIDE HEALTH INFO

WALL FINISHES INTERIOR
WATER BARRIERS, EXTERIOR BUILDING

WATER ENTRY in BUILDINGS

WIND WASHING INSULATION At EAVES
WINDOWS & DOORS
WINTERIZE A BUILDING
WOOD Burning Heaters Fireplaces Stoves

More Information

  (C) Daniel Friedman

Insulation Retrofit Choices for Brick or Block Masonry Wall Cavities
InspectAPedia®  -      

  • What foam insulation would work for insulation retrofit on a brick and block building wall?
  • Is it proper to insulate the air space between brick wythes or between brick and block structure of a masonry wall?
  • Adding insulation to a brick or block masonry building wall
  • Insulation advice for interior walls
  • Questions & answers about retrofit insulation for brick or concrete block building walls
 

Brick or block masonry wall insulation retrofit: this article describes procedures and materials for the insulation retrofit for a brick or block masonry wall cavity.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers nor with topics or services discussed at this website.

© Copyright 2012 InspectAPedia.com, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use page top links to major topics or use links at the left of each page to navigate within topics and documents at this website. Green links show where you are in a document series or at this website.

How Add Insulation to Brick or Block Masonry Wall Cavities

The accompanying text is reprinted/adapted/excerpted with permission from Solar Age Magazine - editor Steven Bliss. Our page top photo shows the Sheffield Stable in Saugerties, NY when we inspected it in 2005. This structural brick building was uninsulated and under consideration for restoration.

Readers should see BRICK VENEER WALL INSULATION and also see the master list of insulation articles at INSULATION INSPECTION & IMPROVEMENT and also see AIR BYPASS LEAKS as well as AIR LEAK MINIMIZATION and finally, see AIR SEALING STRATEGIES.

The question-and-answer article about insulating a masonry wall using foam, quotes-from, updates, and comments an original article from Solar Age Magazine and written by Steven Bliss.

What Foam Insulation is Best for Retrofitting the Cavity in a Brick-and-Block Wall?

Question:

What foam insulation would be appropriate for retrofitting the cavity in a brick and block masonry wall?

How about a 1980's product called Dacotherm, which I heard about a couple of years ago?

- Blair Pollock, Integrated Energy Systems, Chapel Hill NC

Answer:

Foam air leak testing (C) Daniel FriedmanAccording to Jerry Carrier, an engineer at the Brick Institute of America in McLean VA, the 1-inch cavity between the brick and the blocks should not be filled with any type of insulation. That space is there to let any moisture that gets into the wall drain out.

If you fill the air space between brick wythes or between a brick veneer and a structural block wall, moisture may be trapped within the wall.

In a freezing climate moisture trapped in a masonry wall can lead to serious structural damage from frost.

Mike Ondra, a designer with the Shelter Design Group, Stoney Run PA, said that although he had heard of some retrofits where the 1-inch cavity in the masonry wall was foamed full of urethane insulation (in the 1970's or 1980's), he had never tried it himself.

Ondra preferred (in a 1985 interview) to stud up an interior 2x3 wall and fill that cavity with foam insulation. The stud wall is build one-inch out from the masonry wall to ensure that the foam forms an uninterrupted thermal break with the outdoor-exposed masonry wall.

Another option is to nail the ties directly to the studs between each 24-inch course of rigid insulation board glued to the interior surface of the masonry wall [discussed at BRICK VENEER WALL INSULATION].

Keep in mind however that insulating inside of a masonry building loses the potentially beneficial effect (in some climates) of the thermal mass of the building. See THERMAL MASS in BUILDINGS and see   THERMAL MASS WALL DESIGN as well as THERMAL MASS in HOMES - STUDY.

Solar Age also contacted Diamond Shamrock (Irving TX), the manufacturers of Dacotherm, a loose-fill inert silicate material. They do not recommend the use of Dacotherm in block walls. Dacotherm is biodegradable. If it gets wet it breaks down. It is suitable for dry locations.

Our foam insulation photograph (above) shows testing for air leaks at voids in a spray-applied icynene foam insulation retrofit project.

Here we include solar energy, solar heating, solar hot water, and related building energy efficiency improvement articles reprinted/adapted/excerpted with permission from Solar Age Magazine - editor Steven Bliss.

The link to the original Q&A article in PDF form immediately below is preceded by an expanded/updated online version of this article.

Q & A: How to add Insulation in a Brick or Block Wall: Insulating a Brick Cavity - PDF version, use your browser's back button to return to this page

Questions & Answers regarding this article

Questions & answers about retrofit insulation for brick or concrete block building walls

Ask a Question or Search InspectAPedia

HTML Comment Box is loading comments...

Recommend / Share this Article            

...

Technical Reviewers & References

  • InspectAPedia.com® - Daniel Friedman - Publisher & Editor.
  • InspectAPedia Bookstore lists recommended books, organized by topic & available for purchase. Most of our articles also include a list of recommended books for the specific article topic as well as other references, and information sources.
  • Critique, contributions wanted: Contact Us to suggest corrections or additions to articles at this website, and if you wish, to receive online listing and credit as a contributor. Particular thanks are due to the many experts and also consumers who read and critique technical articles at InspectAPedia.com.
  • Additional technical contributors & reference sources for this article are listed below.

Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.


ENERGY SAVINGS in BUILDINGS
  AFUE DEFINITION, RATINGS
  AIR BYPASS LEAKS
  AIR CHANGE RATE ACH HEAT SAVINGS
  AIR CONDITIONING HEAT PUMP SAVINGS
  AIR LEAK SEALING PROCEDURE
  APPLIANCE EFFICIENCY RATINGS
  ATTIC LEAKS, CONDENSATION & MOLD
  COOLING LOAD REDUCTION by ROOF VENTS
  DRYER VENTING
  ENERGY AUDIT - How to Use a Free One
  ENERGY SAVINGS MAXIMIZE RETURNS ON
  ENERGY SAVINGS PRIORITIES
  ENERGY SAVINGS RETROFIT CASE STUDY
  ENERGY SAVINGS RETROFIT LEAK SEALING GUIDE
  ENERGY SAVINGS RETROFIT OPTIONS
  ENERGY STAR PROGRAM
  ENERGY USE MONITORING
  GLASS vs HEAT MIRROR SOLAR GAIN/Loss
  HEAT LOSS in BUILDINGS
  HEATING COST SAVINGS METHODS
  HIGH MASS TRADEOFFS, HEATING vs COOLING
  HOUSE DOCTOR, how-to be
  INSULATION INSPECTION & IMPROVEMENT
  INSULATION LOCATION - WHERE TO PUT IT
  RADIANT BARRIERS
  REFLECTIVE INSULATION
  ROOF COLOR RECOMMENDATIONS
  Skylight Energy Efficiency
  SOLAR ENERGY SYSTEMS
  THERMAL MASS in buildings
  TIMERS for ELECTRIC WATER HEATERS
  VENTILATION, BALANCED HEAT COST SAVINGS
  WIND ENERGY SYSTEMS
  WINDOW EFFICIENCY Features & Ratings
  WOOD, COAL STOVES & FIREPLACES


INSULATION LOCATION - WHERE TO PUT IT
  BLOWN-IN INSULATION
  INSULATION CHOICES
  INSULATION FACT SHEET- DOE
  INSULATION LOCATION & QUANTITY for ATTICS
  INSULATION LOCATION for BASEMENT FLOORS
  INSULATION LOCATION for BASEMENT WALLS
  INSULATION LOCATION for BRICK or BLOCK WALL CAVITY
  INSULATION LOCATION for BRICK VENEER WALLS
  INSULATION LOCATION for CAPES, CRAWLSPACES
  INSULATION LOCATION for CATHEDRAL CEILINGS
  INSULATION LOCATION for GREENHOUSE or SOLARIUM
  INSULATION LOCATION for PASSIVE SOLAR FLOOR SLAB
  INSULATION LOCATION & EXTENT for SLABS
  INSULATION LOCATION for SOUND CONTROL
  INSULATION LOCATION for SUSPENDED PANELS
  INSULATION LOCATION for SWIMMING, INDOOR

  • Solar Age Magazine was the official publication of the American Solar Energy Society. The contemporary solar energy magazine associated with the Society is Solar Today. "Established in 1954, the nonprofit American Solar Energy Society (ASES) is the nation's leading association of solar professionals & advocates. Our mission is to inspire an era of energy innovation and speed the transition to a sustainable energy economy. We advance education, research and policy. Leading for more than 50 years. ASES leads national efforts to increase the use of solar energy, energy efficiency and other sustainable technologies in the U.S. We publish the award-winning SOLAR TODAY magazine, organize and present the ASES National Solar Conference and lead the ASES National Solar Tour – the largest grassroots solar event in the world."
  • Steven Bliss served as editorial director and co-publisher of The Journal of Light Construction for 16 years and previously as building technology editor for Progressive Builder and Solar Age magazines. He worked in the building trades as a carpenter and design/build contractor for more than ten years and holds a masters degree from the Harvard Graduate School of Education. Excerpts from his recent book, Best Practices Guide to Residential Construction, Wiley (November 18, 2005) ISBN-10: 0471648361, ISBN-13: 978-0471648369, appear throughout this website, with permission and courtesy of Wiley & Sons. Best Practices Guide is available from the publisher, J. Wiley & Sons, and also at Amazon.com.
    Excerpts with updates and annotations expanding the original Best Practices Guide text can be found in the online review and book summary at BEST CONSTRUCTION PRACTICES GUIDE and also at DECK & PORCH CONSTRUCTION, at INDOOR AIR QUALITY IMPROVEMENT GUIDE, and in other articles found at InspectAPedia.com such as HOUSEWRAP AIR & VAPOR BARRIERS, SOUND CONTROL in BUILDINGS, and other topics.
  • Arlene Puentes is a licensed home inspector, past chapter president of the Hudson Valley chapter of the American Society of Home Inspectors, an educator, and building failures researcher in Kingston, NY. Contact Arlene Puentes at: ap@octoberhome.htm or at 845-339-7984.

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.
  • ...

Home About Us Accuracy Contact Us Content Use Policy Printing Tips Privacy Website Description © 2012 Copyright InspectAPedia.com