InspectAPedia.com InspectAPedia®
Google
InspectAPedia
 

Free Encyclopedia of Building & Environmental Inspection, Testing, Diagnosis, Repair

Ask a Question or Search InspectAPedia

  • HOME
  • AIR CONDITIONING
  • ELECTRICAL
  • EXTERIORS
  • HEATING
  • HOME INSPECTION
  • INTERIORS
  • PLUMBING
  • ROOFING
  • SEPTIC SYSTEMS
  • STRUCTURE
  • WATER SUPPLY
  • ENERGY SAVINGS
  • ENVIRONMENT
  • INDOOR AIR IAQ
  • INSULATION
  • MOLD INSPECT TEST REMOVE
  • NOISE
  • ODORS
  • SOLAR ENERGY
  • VENTILATION
  • EXPERTS DIRECTORY
  • CONTACT US



Mobile Phone/PDA website viewMobile View
INSULATION IDENTIFICATION GUIDE
INSULATION INSPECTION & IMPROVEMENT

ACOUSTICAL SEALANT CHOICES
AIR BYPASS LEAKS
AIR LEAK DETECTION TOOLS
AIR LEAK MINIMIZATION
AIR LEAK SEALING PROCEDURE
AIR SEALING STRATEGIES
ANIMAL ALLERGENS
APPLIANCE EFFICIENCY RATINGS
ARCHITECTURE & BUILDING COMPONENT ID
ASBESTOS FLOORING HAZARD REDUCTION
ASBESTOS-FREE INSULATION MATERIALS
ASBESTOS IDENTIFICATION IN BUILDINGS
ATTIC LEAKS, CONDENSATION & MOLD
ATTIC VENTILATION

BACKDRAFTING HEATING EQUIPMENT
BASEMENT CEILING VAPOR BARRIER
BASEMENT HEAT LOSS
BASEMENT LEAKS, INSPECT FOR
BASEMENT WATERPROOFING
BATH & KITCHEN DESIGN GUIDE
BATHROOM VENTILATION
BLOWER DOORS & AIR INFILTRATION
BLOWER FAN CONTINUOUS OPERATION
BLOWER FAN OPERATION & TESTING
BLOWN-IN INSULATION
BRICK LINED WALLS
BRICK VENEER WALL INSULATION
BRICK VENEER WALL Loose, Bulged
BRICK WALL DRAINAGE WEEP HOLES
BUCKLED FOUNDATIONS due to INSULATION?
BUILDING NOISE DIAGNOSIS & CURE

CATHEDRAL CEILING INSULATION
CATHEDRAL CEILING VENTILATION
CEILING FINISHES INTERIOR
CEILINGS, DROP or SUSPENDED PANEL
CEILINGS, PLASTER TYPES
CHIMNEY INSPECTION DIAGNOSIS & REPAIR
COOLING LOAD REDUCTION by ROOF VENTS
COMBUSTION AIR for TIGHT BUILDINGS
CONDENSING BOILERS/FURNACES DAMAGE

CATHEDRAL CEILING INSULATION
CATHEDRAL CEILING VENTILATION
CEILING FINISHES INTERIOR
CEILINGS, DROP or SUSPENDED PANEL
CEILINGS, PLASTER TYPES
CHIMNEY INSPECTION DIAGNOSIS & REPAIR
COOLING LOAD REDUCTION by ROOF VENTS
COMBUSTION AIR for TIGHT BUILDINGS
CONDENSING BOILERS/FURNACES DAMAGE
CONDENSATION or SWEATING PIPES, TANKS
COOLING LOAD REDUCTION by ROOF VENTS
CRAWL SPACES

DEFINITION of Heating & Cooling Terms
DEHUMIDIFICATION PROBLEMS
DEW POINT CALCULATION for WALLS
DEW POINT TABLE - CONDENSATION POINT GUIDE
DUCT SYSTEM & DUCT DEFECTS
REMOTE ELECTRIC POWER, PHOTOVOLTAIC

ELECTRIC HEAT
ELECTRIC POWER, PHOTOVOLTAIC, REMOTE SITE
ENERGY SAVINGS in buildings
ENERGY STAR PROGRAM
EVAPORATIVE COOLING SYSTEMS

FIBERGLASS INSULATION
FIBERGLASS INSULATION MOLD
FLASHING MEMBRANES PEEL & STICK
FLAT ROOF MOISTURE & CONDENSATION
FLOOD DAMAGE ASSESSMENT, SAFETY & CLEANUP
FLOODS IN buildings-mold
FLOOR, CONCRETE SLAB CHOICES
FLOOR, CONCRETE SLAB POURED FINISH
FLOOR DAMAGE DIAGNOSIS
FLOOR RADIANT HEAT Mistakes to Avoid
FLOOR TYPES & DEFECTS
FOUNDATION WATERPROOFING
FRENCH DRAINS
FRAMING DETAILS for BETTER INSULATION
FRAMING DETAILS for DOUBLE WALL HOUSES
FRAMING METAL STUD PERFORMANCE
FREEZE-PROOF A BUILDING
FROST HEAVES, FOUNDATION, SLAB

GREEN BUILDING CONSTRUCTION CODES GUIDES
GREENHOUSE DESIGN for SOLAR HEATING

HEAT LOSS in BUILDINGS
HEAT LOSS RATE CALCULATIONS
HEAT LOSS DETECTION TOOLS
HEAT LOSS INDICATORS
HEAT LOSS PREVENTION PRIORITIES
HEAT LOSS R U & K VALUE CALCULATION
HEAT TAPES & CABLES on Roofs for Ice Dams
HEATING SYSTEMS
HEATING COST FUEL & BTU Cost Table
HEATING COST SAVINGS METHODS
HEATING LOSS DIAGNOSIS-BOILERS
HEATING LOSS DIAGNOSIS-FURNACES
HEATING SYSTEM INSPECTION PROCEDURE

HOT ROOF DESIGNS: Un-Vented Roof Solutions
HOUSEWRAP AIR & VAPOR BARRIERS
HOUSE DOCTOR, how-to be
HUMIDITY LEVEL TARGET

ICE DAM PREVENTION
INDOOR AIR QUALITY & HOUSE TIGHTNESS
INDOOR AIR QUALITY IMPROVEMENT GUIDE
INSULATION CHOICES
INSULATION FACT SHEET- DOE
INSULATION for GREENHOUSE or SOLARIUM

INSULATION IDENTIFICATION GUIDE
  ASBESTOS-FREE INSULATION MATERIALS
  ASBESTOS IDENTIFICATION IN BUILDINGS
  Asbestos Pipe Insulation
  Balsam Wool Batt Insulation
  BLOWN-IN INSULATION
  BRICK LINED WALLS
  BRICK VENEER WALL INSULATION
  Cellulose loose fill insulation
  Ceramic Insulation
  Concrete insulation, light-weight
  Cotton Insulating Batts
  FIBERGLASS DUCT, RIGID CONSTRUCTION
  Fiberglass Insulation
  Foam Board Insulation
  Foam Insulation Types - Visual Id
  Homasote & Other Insulating Board
  Icynene Foam Spray Insulation
  Insects & Foam Insulation
  Mineral Wool - Rock Wool Insulation
  Paper Duct Insulation
  Perlite Insulation
  PHENOLIC FOAM INSULATION
  POLYISOCYANURATE FOAM INSULATION
  POLYISOCYANURATE FOAM BELOW SLABS
  POLYSTYRENE FOAM INSULATION
  RADIANT BARRIERS
  REFLECTIVE INSULATION
  RIGID FOAM USE INDOORS
  STRESS SKIN INSULATED PANELS
  STUCCO OVER FOAM INSULATION
  SUPER HI-R INSULATION
  SUPERINSULATION RETROFIT
  Urea Formaldehyde Foam Insulation UFFI
  URETHANE FOAM Deterioration, Outgassing
  VERMICULITE INSULATION


INSULATION INSPECTION & IMPROVEMENT
  Air Bypass Leaks, Thermal Tracking
  AIR LEAK DETECTION TOOLS
  AIR LEAK MINIMIZATION
  AIR SEAL STRATEGIES
  ASBESTOS IDENTIFICATION IN BUILDINGS
  ATTIC CONDENSATION CAUSE & CURE
  BASEMENT CEILING VAPOR BARRIER
  BASEMENT De-Watering Systems
  BASEMENT HEAT LOSS
  Blocked Soffit Intake Vents
  BLOWER DOORS & AIR INFILTRATION
  BLOWN-IN INSULATION
  BRICK or BLOCK WALL CAVITY INSULATION
  BRICK VENEER WALL INSULATION
  BUCKLED FOUNDATIONS due to INSULATION?
  CASEWORK, CABINETS, SHELVING INSTALLATION
  CATHEDRAL CEILING INSULATION
  CATHEDRAL CEILING VENTILATION
  HOT ROOF DESIGNS: Un-Vented Roof Solutions
  ENERGY SAVINGS in BUILDINGS
  ENERGY AUDIT - How to Use a Free One
  ENERGY SAVINGS MAXIMIZE RETURNS ON
  ENERGY SAVINGS PRIORITIES
  ENERGY SAVINGS RETROFIT CASE STUDY
  ENERGY SAVINGS RETROFIT LEAK SEALING GUIDE
  ENERGY SAVINGS RETROFIT OPTIONS
  ENERGY STAR PROGRAM
  ENERGY USE MONITORING
  FIBERGLASS DUCT, RIGID CONSTRUCTION
  Fiberglass Insulation
  FIRE PROTECTION FOR FOAM BOARD INSULATION
  FOUNDATION INSULATION OPTIONS
  FRAMING DETAILS for BETTER INSULATION
  FRAMING DETAILS for DOUBLE WALL HOUSES
  FRAMING METAL STUD PERFORMANCE
  HEATING COST SAVINGS METHODS
  HIGH MASS TRADEOFFS, HEATING vs COOLING
  HOUSE DOCTOR, how-to be
  Inspect Attics for Moisture or Mold
  Inspect Attics for Blocked Soffit Intake Vents
  Inspect Basements for Moisture or Mold
  Inspect Building Exterior - Roof Venting
  Inspect the Ridge Vent System from the Attic
  Inspect the Soffit Vent System from the Attic
  Insects & Foam Insulation
  Insulation Air & Heat Leaks
  INSULATION for GREENHOUSE or SOLARIUM
  INSULATION CHOICES
  INSULATION FACT SHEET- DOE
  INSULATION PLACEMENT in BUILDINGS
  INSULATION R-Values & Properties
  LOG HOME WALL INSULATION VALUES
  MOISTURE in BUILDING WALLS, EFFECTS
  MOISTURE in CELLULOSE INSULATION
  Mold in Fiberglass Insulation
  Mold on Books, Book Conservation
  Mold on Fiberboard Insulating Sheathing
  MOLD in Foam Insulation
  MOLD in INSULATION
  Mold Resistance of Foam Insulation
  MOLD PREVENTION AFTER FLOODING
  MOLD RESISTANT CONSTRUCTION
  PASCAL CALCULATIONS
  PASSIVE SOLAR DESIGN METHOD
  PHENOLIC FOAM INSULATION
  POLYISOCYANURATE FOAM INSULATION
  POLYISOCYANURATE FOAM BELOW SLABS
  POLYSTYRENE FOAM INSULATION
  RADIANT BARRIERS
  REFLECTIVE INSULATION
  RIGID FOAM USE INDOORS
  ROOF VENTING ENERGY SAVING DETAILS
  ROOF VENTING NEEDED?
  ROOF VENTILATION SPECIFICATIONS
  SLAB INSULATION LOCATION
  SLAB INSULATION LOCATION & EXTENT
  SLAB INSULATION, PASSIVE SOLAR
  SLATE THERMAL MASS for SOLAR HEAT STORAGE
  SOUND CONTROL in BUILDINGS
  STRESS SKIN INSULATED PANELS
  STUCCO OVER FOAM INSULATION
  SUPER HI-R INSULATION
  SUPERINSULATION RETROFIT
  Urea Formaldehyde Foam Insulation UFFI
  URETHANE FOAM Deterioration, Outgassing
  VAPOR BARRIERS & AIR SEALING at BAND JOISTS
  VAPOR BARRIERS & CONDENSATION in BUILDINGS
  VAPOR BARRIERS & HOUSEWRAP
  VAPOR CONDENSATION & BUILDING SHEATHING
  VERMICULITE INSULATION


INSULATION LOCATION - WHERE TO PUT IT
  BLOWN-IN INSULATION
  INSULATION CHOICES
  INSULATION FACT SHEET- DOE
  INSULATION LOCATION & QUANTITY for ATTICS
  INSULATION LOCATION for BASEMENT FLOORS
  INSULATION LOCATION for BASEMENT WALLS
  INSULATION LOCATION for BRICK or BLOCK WALL CAVITY
  INSULATION LOCATION for BRICK VENEER WALLS
  INSULATION LOCATION for CAPES, CRAWLSPACES
  INSULATION LOCATION for CATHEDRAL CEILINGS
  INSULATION LOCATION for GREENHOUSE or SOLARIUM
  INSULATION LOCATION for PASSIVE SOLAR FLOOR SLAB
  INSULATION LOCATION & EXTENT for SLABS
  INSULATION LOCATION for SOUND CONTROL
  INSULATION LOCATION for SUSPENDED PANELS
  INSULATION LOCATION for SWIMMING, INDOOR

INSULATION MOLD
INSULATION R-Values & Properties

KIT HOMES, Aladdin, Sears, Wards, Others
KITCHEN & BATH DESIGN GUIDE

LEED GREEN BUILDING CERTIFICATION
LOG HOME GUIDE
LOG HOME WALL INSULATION VALUES

METHANE GAS SOURCES
MOBILE HOME INSPECTIONS
MOISTURE CONTROL in BUILDINGS
MOLD in FOAM INSULATION, RESISTANCE
MOLD INFORMATION CENTER

Nanomaterials Hazards
NOISE / SOUND DIAGNOSIS & CURE
NOISE CONTROL for HEATING SYSTEMS
NOISE CONTROL for FLOORS
NOISE CONTROL for PLUMBING
NOISE CONTROL for ROOFS

ODORS & SMELLS DIAGNOSIS & CURE

PAINT FALURE, DIAGNOSIS, CURE, PREVENTION
PASSIVE SOLAR DESIGN METHOD
PASSIVE SOLAR HEAT PERFORMANCE
PASSIVE SOLAR HOME, LOW COST
PHOTOVOLTAIC POWER SYSTEMS
PLASTER & BEAVERBOARD & DRYWALL
PASCAL CALCULATIONS

RADIANT BARRIERS
RADIANT HEAT
RADIANT HEAT Floor Mistakes to Avoid
RADIANT HEAT TEMPERATURES
RADIANT SLAB FLOORING CHOICES
RADIANT SLAB TUBING & FLUID CHOICES
REFLECTIVE INSULATION
RIGID FOAM USE INDOORS
ROOF VENTING ENERGY SAVING DETAILS
ROOF VENTING NEEDED?
ROOF VENTILATION SPECIFICATIONS
ROT, FUNGUS, TERMITES
ROT, TIMBER FRAME

RIGID FOAM USE INDOORS
ROOF VENTING ENERGY SAVING DETAILS
ROOF VENTING NEEDED?
ROOF VENTILATION SPECIFICATIONS
ROT, FUNGUS, TERMITES
ROT, TIMBER FRAME

SEARS KIT HOUSES
SHEATHING, FOIL FACED - VENTS
SLAB INSULATION, PASSIVE SOLAR

SOLAR ENERGY SYSTEMS

SOUND CONTROL in BUILDINGS

STAIN & BIODETERIORATION AGENT CATALOG
STAINS on BUILDINGS - QUICK GUIDE
STAIN DIAGNOSIS on BUILDING EXTERIORS
STAIN DIAGNOSIS on BUILDING INTERIORS
STAINS on INDOOR SURFACES: PHOTO GUIDE

STRESS SKIN INSULATED PANELS
STUCCO OVER FOAM INSULATION
SWEATING (CONDENSATION) on PIPES, TANKS

THERMAL EXPANSION of MATERIALS
THERMAL MASS in buildings
  THERMAL MASS FLOOR SLABS
  THERMAL MASS in UPSTAIRS
  THERMAL MASS WALL DESIGN
  THERMAL MASS in HOMES - STUDY
  THERMAL MASS TRADEOFFS, HEATING vs COOLING
THERMAL TRACKING & HEAT LOSS
THERMOSTATS, HEATING / COOLING

VAPOR BARRIERS & CONDENSATION in BUILDINGS
  ATTIC CONDENSATION CAUSE & CURE
  BASEMENT CEILING VAPOR BARRIER
  CONDENSATION or SWEATING PIPES, TANKS
  CRAWL SPACE VAPOR BARRIER
  DEW POINT CALCULATION for WALLS
  DEW POINT TABLE - CONDENSATION POINT GUIDE
  FELT 15# ROOFING, as HOUSEWRAP/VAPOR BARRIER
  HOUSEWRAP AIR & VAPOR BARRIERS
  HOUSEWRAP INSTALLATION DETAILS
  HOUSEWRAP PRODUCT CHOICES
  HOUSEWRAP at SILLS, SOLES, TOP PLATES
  HUMIDITY LEVEL TARGET
  MOISTURE CONTROL in BUILDINGS
  RAIN SPLASH-UP SIDING DAMAGE
  VAPOR BARRIERS & AIR SEALING at BAND JOISTS
  VAPOR BARRIERS & CONDENSATION in BUILDINGS
  VAPOR BARRIERS & HOUSEWRAP
  VAPOR CONDENSATION & BUILDING SHEATHING
  WATER BARRIERS, EXTERIOR
  WOOD SIDING FLASHING DETAILS

VENTILATION in BUILDINGS

WALL FINISHES INTERIOR
WATER BARRIERS, EXTERIOR BUILDING

WATER ENTRY in BUILDINGS
WIND ENERGY SYSTEMS
WIND TURBINES & LIGHTNING
WIND WASHING INSULATION At EAVES
WINDOWS & DOORS
WINTERIZE A BUILDING
WOOD Burning Heaters Fireplaces Stoves

More Information

Table of building insulation costs (C) Daniel Friedman

High R-Value Building Insulation Choices Described
InspectAPedia®  -      

  • Properties of various building insulation materials: fiberglass insulation, expanded polystyrene insulation, foil-faced polyisocyanurate insulation, and extruded polystyrene.
  • Solar Age Magazine Articles on Renewable Energy, Energy Savings, Construction Practices
  • Questions & answers about High R-value insulation products & choices

Building insulation choices & properties: This article discusses the properties of various building insulation materials: fiberglass insulation, expanded polystyrene insulation, foil-faced polyisocyanurate insulation, and extruded polystyrene.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers nor with topics or services discussed at this website.

© Copyright 2012 InspectAPedia.com, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use page top links to major topics or use links at the left of each page to navigate within topics and documents at this website. Green links show where you are in a document series or at this website.

Building insulation properties of fiberglass insulation, expanded polystyrene insulation, foil-faced polyisocyanurate insulation, and extruded polystyrene

Foam insulation sprayed in a crawl space - this is not mold - Daniel Friedman 04-11-01Readers should see our complete INSULATION R-Values & Properties article. The table of insulation properties at page top and accompanying text are reprinted/adapted/excerpted with permission from Solar Age Magazine - editor Steven Bliss.

For a complete listing of types of building insulation, their properties, and how to identify or use them, see INSULATION IDENTIFICATION GUIDE. Readers should also see INSULATION INSPECTION & IMPROVEMENT and see INSULATION R-Values & Properties for an extensive table describing the properties of different insulating materials used in buildings. Also see the list of very high R-value insulation products listed at SUPER HI-R INSULATION.

"Insulation Options, a few facts to help you choose among foams and fibers":

This article explains the insulating properties and relative costs of common building insulating materials including fiberglass insulation, expanded polystyrene insulation, foil-faced polyisocyanurate insulation, and extruded polystyrene.

The insulation figure of merit, "cost of insulation per square foot R-value, is explained as a means of comparing insulating materials. While the insulation cost data in the original article dates back to November 1983, the concept of using an R-value normalized cost to evaluate insulation is useful today.

For superinsulated buildings the article concludes that a double-stud wall with fiberglass batts provided the greatest insulating value per dollar. However other insulating products may be a better choice depending on other construction details and space limitations.

Our photograph (left) shows an insulation retrofit in a crawl space where icynene foam spray was applied to the crawl space wall and between the floor joists overhead.

The article also discusses the question of air permeability of fiberglass insulation and its impact on the actual insulating value of the material compared with impermeable (to air) foam insulation products. The impact of moisture on the R-value of fiberglass insulation is also discussed (it's low). Fiberglass both gains and loses moisture more rapidly than some other insulating products.

Foil-faced polyisocyanurate insulation such as the Thermax® and Hi-R® brands are discussed - these products give the highest R-value per inch among insulating materials. Also, as we tested in the 1970's, the use of these products combined with a 3/4" air space permits achieving an additional R 2.7 provided that the foil is clean and the gap or air space is uniform.

See POLYISOCYANURATE FOAM INSULATION for details about polyisocyanurate insulation use.

The polystyrene family of insulations are discussed and are recommended particularly for insulation below grade using expanded polystyrene (EPS or beadboard) and extruded polystyrene (such as Styrofoam® - photo at below left, or Foamular®).

Crawl space insulation with foam board (C) D FriedmanThe article pointed out that in the 1980's there were more than 150 different manufacturers of EPS/beadboard and only three or four of extruded polystyrene.

Claims (perhaps by competitors) that EPS absorbs water are dismissed as nonsense - the material is used to float docks. The article also discusses the use of polystyrene insulation as a non-structural building sheathing (permitting insulating over building band joists and headers) and as an added control of air infiltration.

Problems reported with use of polystyrene as non-structural sheathing where horizontal wood siding is installed included loose clapboards, cupping or cracked clapboards, and nail pulling due to thermal movement of the foam. The article concludes:

The wood problems are attributed to the tendency of these relatively impervious insulations to aggravate thermal and moisture cycling in the siding, since they soak up little heat and moisture themselves. One solution may be to strap out the siding, though this reduces the savings obtained by eliminating the sheathing in the first place.

See POLYSTYRENE FOAM INSULATION for details about polystyrene foam board insulation use.

Here we include solar energy, solar heating, solar hot water, and related building energy efficiency improvement articles reprinted/adapted/excerpted with permission from Solar Age Magazine - editor Steven Bliss.

Current High-R Building Insulation Products for Super Insulated Buildings

Spray foam roof (C) D FriedmanThe high-R insulating panel building products currently in most common use are POLYSTYRENE FOAM INSULATION and POLYISOCYANURATE FOAM INSULATION panels and also polyurethane spray foam (URETHANE FOAM Deterioration, Outgassing). These materials have a typical R-value of about R-5 to R-6 per inch, though when installed with a radiant surface (that might help) and a 3/4" air gap, the R-value is increased substantially - as we detail below. Fiberglass batts, which are still most-widely used in residential construction, are about R-3 per inch.

Here are some currently-available high-R building insulation products as well as some specialty very high-R insulation materials:

  • Aerogel has an R-value of about R-10 per inch, is 99% air and insulates up to 37 times higher R-value than fiberglass. The material is costly, and fragile, factors that have limited its use in residential construction. Work is in process to produce a less costly version.
  • Barrier Ultra-R super high-R building panels, produced by Glacier Bay, use Aerogel and are rated up to R-30 per inch, or in Barrier Ultra-r™ panels, R-50 per inch. The Ultra-R™ R-50 insulating panel is a rigid polypropylene-encased vacuum insulation panel that is custom made to the client's specified dimensions. The panels are also available with a fiberglass coating on one or both sides. (Used in refrigeration applications.)

    The company also produces acoustic panels that are Ultra-db resistant and lightweight. Unlike the appliance insulation panels discussed in the original Q&A above on miracle insulation, these Aerogel based panels will continue to retain some, though reduced insulating value if punctured, performing at perhaps R-9 per inch. The product is used in marine refrigerators, but in the future may be available as a residential construction product. The company is researching specialized products in medical, transportation, and aerospace applications.
  • Ceramic Insulation - version of high temperature treated Perlite Insulation
  • Eco-Panel polyurethane foam core structural insulated panels (SIPs) are produced by Eco-Panels Corporation. The 3-inch thick panels include structural elements and panel locking devices. The company offers a super-insulated 8.5-inch thick structural insulated panel and also produces roof panels. The 2.5 pound polyurethane foam used in these panels provides about R-7 per inch; 4-inch panels are rated at R-26, 6 1/2inch panels at R-40.
  • Hightherm R-24, Supertherm R30, and Superthermal R60 wall panels are produced by Supertherm. Wallpanel® uses 18 gauge steel studs spaced 16" on center, staggered to support 24" o.c. roof trusses, combined with high-density (two pound) polystyrene foam insulation. The higher density polystyrene foam insulation permits achieving an R-30 wall panel that is 6" thick (rather than 7" with lower density foam). The panels are finished with an insulating ceramic coating and are warranted for 25 years.
  • Low-E Housewrap Insulation™, is a patented insulation consisting of a closed micro-cell foam core that is heat laminated to foil or polyethylene facings. This foam board insulating product is thin, provided in rolls, intended as a thermal break wrap that is moisture, rodent, and insect resistant.

    The Low-E Manufacturer states that it outperforms 3-4" of fiberglass insulation. As the product literature points out, "All of these components are referred to as a system R-Value. A 3/4" air space facing the aluminum is ideal because convection currents cannot begin to move in an air space this small. The aluminum actually increases the R-Value of the air space it faces. Low-E is manufactured using a 1/4" polyethylene foam core with scrim reinforced double-sided aluminum facings. It can be used in all facets of the building industry where conventional insulations are used. It can be used alone or in conjunction with mass insulations for high R-systems. " The product is also advertised by some distributors for insulation retrofit products, attics, basements, under-slab insulation, etc.
  • Precision Panel R28 (R-4 to R-7 per inch) Laminated EPS foam core Structural Insulating Panels (SIPs) are produced by Precision Panel Co. located in Idaho, ships insulating panels world wide. The 4-inch thick EPS foam core panels are laminated with exterior sheathing (OSB) and an interior sheathing (OSB or ?). The foam core panels are prepared with window and door rough openings and accept edge splines or top and bottom plates for construction. They include wire chases and are cut to customer specifications.
  • STRAW BALE CONSTRUCTION has been considered a high-R building method for a long time and is discussed at STRAW BALE CONSTRUCTION
  • STYROFOAM™ Brand Spray Polyurethane Foam R 6.1 per inch, (CM Series) produced by DOW Chemical is a "two-component, spray-applied polyurethane foam that creates a seamless, monolithic barrier for protection against water vapor and air on the interior of steel stud walls. This closed-cell, 2-pcf spray foam successfully incorporates the Enovate 3000 blowing agent from Honeywell. This product is designed as a filler for the Thermax Wall System discussed below.
  • Super Therm® insulating ceramic coatings produced by Superior Solar Barrier, are used on buildings as well as freezers and refrigerators, intended as an impenetrable exterior coating. The coating uses a vacuumed microceramic hollow particle (ceramic bubbles) containing a gas,and providing minimal heat conductivity. The particles are distributed in a coating vehicle.
  • Thermax™ Wall System, DOW Chemical, "addresses design considerations for commercial steel stud applications and is not relevant for most residential applications. THERMAX™ Exterior Insulation R6.5 per inch, consists of a glass-fiber-reinforced polyisocyanurate foam core faced with nominal 4 mil embossed BLUE™ acrylic-coated aluminum on one side and 1.25 mil embossed aluminum on the other.
  • Tuff-R™ and Super Tuff-R™, Dow Building Solutions, have an R-value of R 6.5 per inch. Note that the R-value of this insulating board is increased to R-9.3 per inch if construction includes a 3/4" air space. These are closed-cell polyisocyanurate insulating foam core board products.

    The foam core is sandwiched between a choice of exterior faces including aluminum foil, tri-plex aluminum foil, or polyester kraft paper combined with reinforced aluminum foil. One board side is blue, the other is radiant aluminum foil. These products must be covered with a minimum of 1/2" drywall or equivalent thermal barrier in building applications. See POLYISOCYANURATE FOAM INSULATION. Also see Q&A on use of Rigid Foam Insulating Board . Also see the Dow Product Literature for Tuff-R insulating board - PDF file.
  • Vacuum Super-Insulated R-28 Panels from RParts are sold as an alternative to aerogel products. The panels are produced by a third party manufacturer using DOW INstill foam cores sealed at high vacuum in a special multi-layer gas impermeable barrier membrane film.

Original Solar Age Magazine Article on High R Insulation Choices

Links to the original article in PDF form immediately below are preceded by the expanded/updated online version of this article above.

  • Insulation_Options - PDF form, use your browser's back button to return to this page
  • Insulation_Options - PDF form, part 2

Questions & Answers regarding this article

Questions & answers about High R-value insulation products & choices

Ask a Question or Search InspectAPedia

HTML Comment Box is loading comments...

Recommend / Share this Article            

...

Technical Reviewers & References

  • InspectAPedia.com® - Daniel Friedman - Publisher & Editor.
  • InspectAPedia Bookstore lists recommended books, organized by topic & available for purchase. Most of our articles also include a list of recommended books for the specific article topic as well as other references, and information sources.
  • Critique, contributions wanted: Contact Us to suggest corrections or additions to articles at this website, and if you wish, to receive online listing and credit as a contributor. Particular thanks are due to the many experts and also consumers who read and critique technical articles at InspectAPedia.com.
  • Additional technical contributors & reference sources for this article are listed below.

Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

INSULATION CHOICES
INSULATION FACT SHEET- DOE

INSULATION R-Values & Properties

  • Solar Age Magazine was the official publication of the American Solar Energy Society. The contemporary solar energy magazine associated with the Society is Solar Today. "Established in 1954, the nonprofit American Solar Energy Society (ASES) is the nation's leading association of solar professionals & advocates. Our mission is to inspire an era of energy innovation and speed the transition to a sustainable energy economy. We advance education, research and policy. Leading for more than 50 years. ASES leads national efforts to increase the use of solar energy, energy efficiency and other sustainable technologies in the U.S. We publish the award-winning SOLAR TODAY magazine, organize and present the ASES National Solar Conference and lead the ASES National Solar Tour – the largest grassroots solar event in the world."
  • Steven Bliss served as editorial director and co-publisher of The Journal of Light Construction for 16 years and previously as building technology editor for Progressive Builder and Solar Age magazines. He worked in the building trades as a carpenter and design/build contractor for more than ten years and holds a masters degree from the Harvard Graduate School of Education. Excerpts from his recent book, Best Practices Guide to Residential Construction, Wiley (November 18, 2005) ISBN-10: 0471648361, ISBN-13: 978-0471648369, appear throughout this website, with permission and courtesy of Wiley & Sons. Best Practices Guide is available from the publisher, J. Wiley & Sons, and also at Amazon.com.
    Excerpts with updates and annotations expanding the original Best Practices Guide text can be found in the online review and book summary at BEST CONSTRUCTION PRACTICES GUIDE and also at DECK & PORCH CONSTRUCTION, at INDOOR AIR QUALITY IMPROVEMENT GUIDE, and in other articles found at InspectAPedia.com such as HOUSEWRAP AIR & VAPOR BARRIERS, SOUND CONTROL in BUILDINGS, and other topics.
  • Carson, Dunlop & Associates Ltd., 120 Carlton Street Suite 407, Toronto ON M5A 4K2. (416) 964-9415 1-800-268-7070 info@carsondunlop.com. Thanks to Alan Carson and Bob Dunlop, for permission to use illustrations from their publication, The Illustrated Home which illustrates construction details and building components. Carson Dunlop provides home inspection education including the ASHI-adopted Home Inspection Training Program (home study course), publications such as the Home Reference Book, report writing materials including the Horizon report writer, and home inspection services. Alan Carson is a past president of ASHI, the American Society of Home Inspectors.
  • Passive Solar Design Handbook Volume I, the Passive Solar Handbook Introduction to Passive Solar Concepts, in a version used by the U.S. Air Force - online version available at this link and from the USAF also at wbdg.org/ccb/AF/AFH/pshbk_v1.pdf
  • Passive Solar Design Handbook Volume II, the Passive Solar Handbook Comprehensive Planning Guide, in a version used by the U.S. Air Force - online version available at this link and from the USAF also at wbdg.org/ccb/AF/AFH/pshbk_v2.pdf [This is a large PDF file that can take a while to load]
  • Passive Solar Handbook Volume III, the Passive Solar Handbook Programming Guide, in a version used by the U.S. Air Force - online version available at this link and from the USAF also at wbdg.org/ccb/AF/AFH/pshbk_v3.pdf
  • The Passive Solar Design and Construction Handbook, Steven Winter Associates (Author), Michael J. Crosbie (Editor), Wiley & Sons, ISBN 978-047118382 or 0471183083 is available at Amazon.com and via the The Passive Solar Design and Construction Handbook, Steven Winter Associates (Author), Michael J. Crosbie (Editor), Wiley & Sons, ISBN 978-047118382 or 0471183083 is available at Amazon.com and via the InspectAPedia Bookstore
  • "Passive Solar Home Design", U.S. Department of Energy, describes using a home's windows, walls, and floors to collect and store solar energy for winter heating and also rejecting solar heat in warm weather.
  • "Solar Water Heaters", U.S. Department of Energy article on solar domestic water heaters to generate domestic hot water in buildings, explains how solar water heaters work. Solar heat for swimming pools is also discussed.
  • "Heat Exchangers for Solar Water Heating Systems", U.S. DOE describes the types of solar water heater heat exchange methods between the sun and the building's hot water supply
  • "Heat-Transfer Fluids for Solar Water Heating Systems", U.S. DOE, describes the types of fluids selected to transfer heat between the solar collector and the hot water in storage tanks in a building. These include air, water, water with glycol antifreeze mixtures (needed when using solar hot water systems in freezing climates), hydrocarbon oils, and refrigerants or silicones for heat transfer.
  • "Solar Water Heating System Maintenance and Repair", U.S. DOE
  • "Solar Water Heating System Freeze Protection", U.S. DOE,using antifreeze mixture in solar water heaters (or other freeze-resistant heat transfer fluids), as well as piping to permit draining the solar collector and piping system.
  • "Scaling and Corrosion in Solar Water Heating Systems", U.S. DOE
  • www.energysavers.gov/your_home/water_heating/index.cfm/mytopic=12850 is the base U.S. DOE website for these articles
  • "Active Solar Heating Systems", U.S. Department of Energy, including
  • "Radiant Heating Systems" U.S. DOE
  • "Absorption Heat Pumps & Coolers", U.S. DOE
  • "Solar Air Heating" U.S. DOE also referred to as "Ventilation Preheating" in which solar systems use air for absorbing and transferring solar energy or heat to a building
  • "Solar Liquid Heating" U.S. DOE, systems using liquid (typically water) in flat plate solar collectors to collect solar energy in the form of heat for transfer into a building for space heating or hot water heating. The term "solar liquid" is used for accuracy, rather than "solar water" because the water may contain an antifreeze or other chemicals.

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.
  • ...

Home About Us Accuracy Contact Us Content Use Policy Printing Tips Privacy Website Description © 2012 Copyright InspectAPedia.com