InspectAPedia.com InspectAPedia®
 

Free Encyclopedia of Building & Environmental Inspection, Testing, Diagnosis, Repair

Ask a Question or Search InspectAPedia

  • HOME
  • AIR CONDITIONING
  • ELECTRICAL
  • EXTERIORS
  • HEATING
  • HOME INSPECTION
  • INTERIORS
  • PLUMBING
  • ROOFING
  • SEPTIC SYSTEMS
  • STRUCTURE
  • WATER SUPPLY
  • ENERGY SAVINGS
  • ENVIRONMENT
  • INDOOR AIR IAQ
  • INSULATION
  • MOLD INSPECT TEST REMOVE
  • NOISE
  • ODORS
  • SOLAR ENERGY
  • VENTILATION
  • EXPERTS DIRECTORY
  • CONTACT US


Mobile Phone/PDA website viewMobile View
INTERIORS of buildings

ACOUSTICAL SEALANT CHOICES
AIR BYPASS LEAKS
AIR LEAK DETECTION TOOLS
AIR LEAK MINIMIZATION
AIR LEAK SEALING PROCEDURE
AIR SEALING STRATEGIES

ANIMAL ALLERGENS
APPLIANCE EFFICIENCY RATINGS
ASBESTOS FLOORING HAZARD REDUCTION
ASBESTOS-FREE INSULATION MATERIALS
ASBESTOS IDENTIFICATION IN buildings
ATTIC LEAKS, CONDENSATION & ATTIC MOLD
ATTIC VENTILATION

BASEMENT CEILING VAPOR BARRIER
BASEMENT HEAT LOSS
BASEMENT LEAKS, INSPECT FOR
BASEMENT WATERPROOFING

BATH & KITCHEN DESIGN GUIDE
BATHROOM VENTILATION
BIOGAS PRODUCTION & USE
BLOWER DOORS & AIR INFILTRATION
BLOWER FAN CONTINUOUS OPERATION
BLOWER FAN OPERATION & TESTING
BLOWN-IN INSULATION

BRICK LINED WALLS
BRICK VENEER WALL INSULATION
BRICK VENEER WALL Loose, Bulged
BRICK WALL DRAINAGE WEEP HOLES
BUCKLED FOUNDATIONS due to INSULATION?
BUILDING NOISE DIAGNOSIS & CURE

CATHEDRAL CEILING INSULATION
CATHEDRAL CEILING VENTILATION
CEILING FINISHES INTERIOR
CEILINGS, DROP or SUSPENDED PANEL
CEILINGS, PLASTER TYPES

CHIMNEY INSPECTION DIAGNOSIS & REPAIR
COOLING LOAD REDUCTION by ROOF VENTS
COMBUSTION AIR for TIGHT buildings
CONDENSING BOILERS/FURNACES DAMAGE

CATHEDRAL CEILING INSULATION
CATHEDRAL CEILING VENTILATION
CEILING FINISHES INTERIOR
CEILINGS, DROP or SUSPENDED PANEL
CEILINGS, PLASTER TYPES

CHIMNEY INSPECTION DIAGNOSIS & REPAIR
COOLING LOAD REDUCTION by ROOF VENTS
COMBUSTION AIR for TIGHT BUILDINGS
CONDENSING BOILERS/FURNACES DAMAGE
CONDENSATION or SWEATING PIPES, TANKS
COOLING LOAD REDUCTION by ROOF VENTS
CRAWL SPACES

DEFINITION of Heating & Cooling Terms
DEHUMIDIFICATION PROBLEMS
DEW POINT CALCULATION for WALLS
DEW POINT TABLE - CONDENSATION POINT GUIDE
DUCT SYSTEM & DUCT DEFECTS

ELECTRICAL INSPECTION, DIAGNOSIS, REPAIR

ENERGY SAVINGS in buildings
  AFUE DEFINITION, RATINGS
  AIR BYPASS LEAKS
  AIR CHANGE RATE ACH HEAT SAVINGS
  AIR CONDITIONING HEAT PUMP SAVINGS
  AIR LEAK SEALING PROCEDURE
  APPLIANCE EFFICIENCY RATINGS
  ATTIC LEAKS, CONDENSATION & ATTIC MOLD
  COOLING LOAD REDUCTION by ROOF VENTS
  ENERGY AUDIT - How to Use a Free One
  ENERGY SAVINGS MAXIMIZE RETURNS ON
  ENERGY SAVINGS PRIORITIES
  ENERGY SAVINGS RETROFIT CASE STUDY
  ENERGY SAVINGS RETROFIT LEAK SEALING GUIDE
  ENERGY SAVINGS RETROFIT OPTIONS
  ENERGY STAR PROGRAM
  ENERGY USE MONITORING
  GLASS vs HEAT MIRROR SOLAR GAIN/Loss
  HEAT LOSS in buildings
  HEATING COST SAVINGS METHODS
  HIGH MASS TRADEOFFS, HEATING vs COOLING
  HOUSE DOCTOR, how-to be
  INSULATION INSPECTION & IMPROVEMENT
  INSULATION LOCATION - WHERE TO PUT IT
  RADIANT BARRIERS
  REFLECTIVE INSULATION
  ROOF COLOR RECOMMENDATIONS
  Skylight Energy Efficiency
  SOLAR ENERGY SYSTEMS
  THERMAL MASS in buildings
  TIMERS for ELECTRIC WATER HEATERS
  VENTILATION, BALANCED HEAT COST SAVINGS
  WIND ENERGY SYSTEMS
  WINDOW EFFICIENCY Features & Ratings
  WOOD, COAL STOVES & FIREPLACES

ENVIRONMENTAL HAZARDS - INSPECT, TEST, REMEDY

EXTERIOR WALL SIDING TRIM & FINISHES

FIBERGLASS INSULATION
FIBERGLASS HAZARDS
FIBERGLASS INSULATION MOLD

FLASHING MEMBRANES PEEL & STICK
FLAT ROOF MOISTURE & CONDENSATION

FLOOD DAMAGE ASSESSMENT, SAFETY & CLEANUP
FLOODS IN buildings-mold

FLOOR, CONCRETE SLAB CHOICES
FLOOR, CONCRETE SLAB POURED FINISH
FLOOR DAMAGE DIAGNOSIS
FLOOR RADIANT HEAT Mistakes to Avoid
FLOOR TYPES & DEFECTS

FOUNDATION WATERPROOFING
FRENCH DRAINS
FRAMING DETAILS for BETTER INSULATION
FRAMING DETAILS for DOUBLE WALL HOUSES
FRAMING METAL STUD PERFORMANCE
FREEZE-PROOF A BUILDING
FROST HEAVES, FOUNDATION, SLAB

GREEN BUILDING CONSTRUCTION CODES GUIDES
GREENHOUSE DESIGN for SOLAR HEATING

HEAT LOSS in buildings
HEAT LOSS RATE CALCULATIONS
HEAT LOSS DETECTION TOOLS
HEAT LOSS INDICATORS
HEAT LOSS PREVENTION PRIORITIES
HEAT LOSS R U & K VALUE CALCULATION
HEAT TAPES & CABLES on Roofs for Ice Dams
HEATING COST FUEL & BTU Cost Table
HEATING COST SAVINGS METHODS
HEATING LOSS DIAGNOSIS-BOILERS
HEATING LOSS DIAGNOSIS-FURNACES

HOT ROOF DESIGNS: Un-Vented Roof Solutions
HOUSEWRAP AIR & VAPOR BARRIERS
HOUSE DOCTOR, how-to be

HUMIDITY LEVEL TARGET

ICE DAM PREVENTION
INSULATION CHOICES
Insulation Air & Heat Leaks
INSULATION FACT SHEET- DOE
INSULATION for GREENHOUSE or SOLARIUM
INSULATION IDENTIFICATION GUIDE
INSULATION INSPECTION & IMPROVEMENT
INSULATION LOCATION - WHERE TO PUT IT
  INSULATION LOCATION & QUANTITY for ATTICS
  INSULATION LOCATION for BASEMENT FLOORS
  INSULATION LOCATION for BASEMENT WALLS
  INSULATION LOCATION for BRICK or BLOCK WALL CAVITY
  INSULATION LOCATION for BRICK VENEER WALLS
  INSULATION LOCATION for CAPES, CRAWLSPACES
  INSULATION LOCATION for CATHEDRAL CEILINGS
  INSULATION LOCATION for GREENHOUSE or SOLARIUM
  INSULATION LOCATION for PASSIVE SOLAR FLOOR SLAB
  INSULATION LOCATION & EXTENT for SLABS
  INSULATION LOCATION for SOUND CONTROL
  INSULATION LOCATION for SUSPENDED PANELS
  INSULATION LOCATION for SWIMMING, INDOOR

INSULATION MOLD
INSULATION R-Values & Properties

KIT HOMES, Aladdin, Sears, Wards, Others
KITCHEN & BATH DESIGN GUIDE

LEED GREEN BUILDING CERTIFICATION
LOG HOME ENERGY EFFICIENCY
LOG HOME GUIDE

MOBILE HOME INSPECTIONS
MOISTURE CONTROL in buildings
MOLD in FOAM INSULATION, RESISTANCE
MOLD INFORMATION CENTER

Nanomaterials Hazards
NOISE / SOUND DIAGNOSIS & CURE
NOISE CONTROL for HEATING SYSTEMS
NOISE CONTROL for FLOORS
NOISE CONTROL for PLUMBING
NOISE CONTROL for ROOFS

ODORS & SMELLS DIAGNOSIS & CURE

PAINT FALURE, DIAGNOSIS, CURE, PREVENTION
PASSIVE SOLAR DESIGN METHOD
PASSIVE SOLAR HEAT PERFORMANCE
PASSIVE SOLAR HOME, LOW COST
PHOTOVOLTAIC POWER SYSTEMS
PLASTER & BEAVERBOARD & DRYWALL
PASCAL CALCULATIONS

RADIANT BARRIERS
RADIANT HEAT
RADIANT HEAT Floor Mistakes to Avoid
RADIANT HEAT TEMPERATURES
RADIANT SLAB FLOORING CHOICES
RADIANT SLAB TUBING & FLUID CHOICES
REFLECTIVE INSULATION
RIGID FOAM USE INDOORS
ROOF VENTING ENERGY SAVING DETAILS
ROOF VENTING NEEDED?
ROOF VENTILATION SPECIFICATIONS
ROT, FUNGUS, TERMITES
ROT, TIMBER FRAME

ROOF ARCHITECTURAL STYLES - PHOTO GUIDE
ROOF CLEANING RECOMMENDATIONS
ROOF DORMER TYPES - PHOTO GUIDE
ROOF VENTILATION SPECIFICATIONS
  ATTIC VENTILATION
  CATHEDRAL CEILING INSULATION
  CATHEDRAL CEILING VENTILATION
  HOT ROOF DESIGNS: Un-Vented Roof Solutions
  Inspect Attics for Moisture or Mold
  Inspect Attics for Blocked Soffit Intake Vent
  Inspect Basements for Moisture or Mold
  Inspect Building Exterior - Roof Venting
  Inspect the Ridge Vent System from the Attic
  Inspect the Soffit Vent System from the Attic
  Insects & Foam Insulation
  HOUSE DOCTOR, how-to be
  Insulation Air & Heat Leaks
  Roof Venting: Intake - Outlet Area Ratios
  Roof Venting: Proper Locations
  Roof Venting: Both Ridge & Eaves Venting Needed
  Roof Venting: Eaves Intake if no Overhang
  Roof Venting: Soffit Intake Vent-Continuous
  Roof Venting: Un-Vented Hot Roof Solutions
  ROOF VENTING ENERGY SAVING DETAILS
  ROOF VENTING NEEDED?
  SKYLIGHT VENTILATION DETAILS
  Soffit Ventilation
ROT, FUNGUS, TERMITES
  TERMITE SHIELDS vs TERMITICIDE
ROT, TIMBER FRAME

SEARS KIT HOUSES

SOLAR ENERGY SYSTEMS
  BLOCKBED RADIANT FLOORS - SOLAR DESIGN
  FLOOR, CONCRETE SLAB CHOICES
  FLOOR, CONCRETE SLAB POURED FINISH
  GLASS vs HEAT MIRROR SOLAR GAIN/Loss
  GREENHOUSE DESIGN for SOLAR HEATING
  GREENHOUSE / SUNSPACE GLARE
  PASSIVE SOLAR DESIGN KEY ELEMENTS
  PASSIVE SOLAR DESIGN METHOD
  PASSIVE SOLAR ENERGY MONITORING
  PASSIVE SOLAR FLOOR TILES, PHASE CHANGE
  PASSIVE SOLAR HEAT PERFORMANCE
  PASSIVE SOLAR HOME, LOW COST
  PASSIVE SOLAR PERFORMANCE PROBE
  PASSIVE SOLAR Roof & Window Overhangs
  PHOTOVOLTAIC POWER SYSTEMS
  POLYCARBONATE GLAZING
  REMOTE ELECTRIC POWER, PHOTOVOLTAIC
  ROCK-BED SOLAR HEAT STORAGE DESIGN
  SLAB INSULATION, PASSIVE SOLAR
  SLATE THERMAL MASS for SOLAR HEAT STORAGE
  SOLAR COLLECTOR AIR or GAS COLLECTION
  SOLAR COLLECTOR EFFICIENCY COMPARISONS
  SOLAR COLLECTOR FILMS
  SOLAR COLLECTOR OUTGASSING
  SOLAR COLLECTOR WOOD HOUSINGS
  SOLAR GAIN CALCULATION
  SOLAR HEATING SYSTEM DESIGNS
  SOLAR HOT WATER HEATERS
  SOLAR HOUSE EVALUATION
  SOLAR MODULE MANUFACTURERS
  SOLAR SHADES & SUNSCREENS
  SOLAR SHADES, LOW-E EFFECTIVENESS
  SOLAR WATER DISINFECTION
  SOLAR HOT WATER HEATERS
  SUNSPACE DESIGN for SOLAR HEATING
  SUNSPACE GLAZING for SUNTANNING
  STORM WINDOW INTERIOR
  STORM WINDOW PLASTIC CHOICES
  STORM WINDOW WEEP HOLES
  SUNGAIN, FILMS, LOW-E GLASS
  SUNSPACE GLAZING for SUNTANNING
  SWIMMING POOL SOLAR HEAT, INDOOR
  SWIMMING POOL SOLAR HEAT, OUTDOOR DIAGNOSIS
  THERMAL MASS in buildings

SOUND CONTROL in buildings
STAIN & BIODETERIORATION AGENT CATALOG
STAINS on buildings - QUICK GUIDE
STAIN DIAGNOSIS on BUILDING EXTERIORS
STAIN DIAGNOSIS on BUILDING INTERIORS
STAINS on INDOOR SURFACES: PHOTO GUIDE

STRESS SKIN INSULATED PANELS
STUCCO OVER FOAM INSULATION
SWEATING (CONDENSATION) on PIPES, TANKS

THERMAL EXPANSION of MATERIALS
THERMAL MASS in buildings
  THERMAL MASS FLOOR SLABS
  THERMAL MASS in UPSTAIRS
  THERMAL MASS WALL DESIGN
  THERMAL MASS in HOMES - STUDY
  THERMAL MASS TRADEOFFS, HEATING vs COOLING

THERMAL TRACKING & HEAT LOSS

VAPOR BARRIERS & CONDENSATION in buildings
VENTILATION in buildings
  Air Bypass Leaks, Thermal Tracking
  AIR CHANGE RATE ACH HEAT SAVINGS
  ATTIC CONDENSATION CAUSE & CURE
  BALANCED VENTILATION, HEAT COST SAVINGS
  BATH & KITCHEN DESIGN GUIDE
  BATHROOM VENTILATION
  Blocked Soffit Intake Vents
  BLOWER DOORS & AIR INFILTRATION
  BLOWN-IN INSULATION
  BRICK or BLOCK WALL CAVITY INSULATION
  BRICK VENEER WALL INSULATION
  CATHEDRAL CEILING INSULATION
  CATHEDRAL CEILING VENTILATION
  CLOTHES DRYER VENTING
  COOLING LOAD REDUCTION by ROOF VENTS
  CRAWL SPACE VENTING & Dryout Procedures
  HEAT LOSS: How to Calculate Heat Loss in a Building
  HOT ROOF DESIGNS: Un-Vented Roof Solutions
  HOUSEWRAP AIR & VAPOR BARRIERS
  HUMIDITY LEVEL TARGET
  ICE DAM PREVENTION
  Inspect Attics for Moisture or Mold
  Inspect Attics for Blocked Soffit Intake Vents
  Inspect Basements for Moisture or Mold
  Inspect Building Exterior - Roof Venting
  Inspect the Ridge Vent System from the Attic
  Inspect the Soffit Vent System from the Attic
  Insects & Foam Insulation
  HOUSE DOCTOR, how-to be
  Insulation Air & Heat Leaks
  MOISTURE CONTROL in buildings
  MOISTURE CALCULATIONS
  MOISTURE METER STUDY
  MOISTURE PROBLEMS: CAUSE & CURE
  ROOF VENTILATION SPECIFICATIONS
  Roof Venting: Eaves Intake if no Overhang
  Roof Venting: Soffit Intake Vent-Continuous
  Roof Venting: Un-Vented Hot Roof Solutions
  ROOF VENTING ENERGY SAVING DETAILS
  ROOF VENTING NEEDED?
  SKYLIGHT VENTILATION DETAILS
  Soffit Ventilation
  VENTILATION, BALANCED HEAT COST SAVINGS
  VENTILATION DESIGN PROBLEMS & SOLUTIONS
  VENTILATION, WHOLE HOUSE STRATEGIES

WALL SIDING TRIM & FINISHES
WALL FINISHES INTERIOR

WATER BARRIERS, EXTERIOR BUILDING
WATER ENTRY in buildings
WIND ENERGY SYSTEMS
WIND TURBINES & LIGHTNING
WIND WASHING INSULATION At EAVES
WINDOWS & DOORS
  ALUMINUM WINDOWS
  Best Practices Guide for Windows & Doors:
  CLIMATE, WINDOW CHOICES FOR
  CONDENSATION on WINDOWS & SKYLIGHTS
  Doors, Exterior, Energy Efficiency Guide
  Doors, Exterior Flashing Details
  Doors, Exterior, Frames
  DOORS, EXTERIOR, Selecting & Installing
  DOORS, INTERIOR
  FIBERGLASS WINDOWS
  GLASS vs HEAT MIRROR SOLAR GAIN/Loss
  HURRICANE, WIND, & STORM-Resistant WINDOWS
  LOW-E WINDOW GLAZING
  LOW-E VS QUAD-GLAZING
  LOW-E RETROFIT ADD-ON FILMS
  POLYCARBONATE GLAZING
  SITE BUILT DOUBLE GLAZED WINDOWS
  SKYLIGHTS, Guide to Choosing & Installing
  Skylight Condensation Problems
  Skylight Window Design Issues
  Skylight Energy Efficiency
  Skylight Installation Procedures
  SKYLIGHT LEAK DIAGNOSIS & REPAIR
  SKYLIGHT VENTILATION DETAILS
  SLIDING GLIDING WINDOW DEFECTS
  SLOPED GLAZING DETAILS
  STORM WINDOW INTERIOR
  STORM WINDOW PLASTIC CHOICES
  STORM WINDOW WEEP HOLES
  SUNGAIN, FILMS, LOW-E GLASS
  SUNSPACE GLAZING for SUNTANNING
  VERTICAL GLAZING DETAILS
  VINYL WINDOWS
  VINYL / PVC WINDOW WARPING
  WINDOW / DOOR ENERGY EFFICIENT, DOE
  WINDOW / DOOR AIR LEAK SEALING HOW TO
  Window Certification
  WINDOW EFFICIENCY Features & Ratings
  Window Flashing & Sealing Guide
  WINDOW HARDWARE PHOTOS
  Window Installation, Flange-Type
  Window Installation, w/ Integral Brickmold
  WINDOW LEAKS INTO BASEMENT
  Window Materials & Construction
  Window Types, Guide
  WINDOW TYPES - Photo Guide
  Window & Door Sources

WINTERIZE A BUILDING
Wood Burning Heaters Fireplaces Stoves
Woodstove Safety

ZONE VALVES

More Information

  (C) Daniel Friedman

Is Roof Venting Needed?
InspectAPedia®  -    

  • The need for roof ventilation, proposals for "un-vented" roofs, and the risks of omitting roof ventilation
  • What problems occur on un-vented roofs?
  • Critique of the "hot roof" building design principle
  • Solar Age Magazine Articles on Renewable Energy, Energy Savings, Construction Practices
InspectAPedia offers impartial, unbiased advice without conflicts of interest. We will block advertisements which we discover or readers inform us are associated with bad business practices, false-advertising, or junk science. Our contact info is at InspectAPedia.com/Contact.htm.

This article discusses the options for venting versus un-vented roof. Sketch at page top and accompanying text are reprinted/adapted/excerpted with permission from Solar Age Magazine - editor Steven Bliss. Readers should not fail to review the more extensive information about the need for and methods of roof ventilation found at ROOF VENTILATION SPECIFICATIONS.

Contact us to suggest text changes and additions and, if you wish, to receive online listing and credit for that contribution.

© Copyright 2012 InspectAPedia.com, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use page top links to major topics or use links at the left of each page to navigate within topics and documents at this website. Green links show where you are in a document series or at this website.

Article on the Need for Roof Ventilation and Options for Un-Vented Roofs

Ridge vent on modern home (C) Daniel Friedman"Is Roof Venting Necessary? The old rules may not apply to new roofs" - links to the original article in PDF form immediately below are followed by an expanded/updated online version of this article. Our photo (left) shows a ridge vent on a modern asphalt shingle roof. Is this outlet vent necessary? Is it enough?

  • Is Roof Venting Needed? - PDF form, se your browser's back button to return to this page
  • Is Roof Venting Needed? - part 2

This article provides a review of roof ventilation theory, explaining the importance of preventing attic moisture (and mold), ice dam leaks, and at the same time, energy loss in buildings. Mr. Bliss explains how moisture and the resulting condensation gets into roof cavities and building walls following moisture laden air that leaks through gaps in building drywall, around exposed beams, intersecting walls and ceilings, at light fixtures, electrical outlets, and other openings by riding air convection currents that move air in and out of building cavities as building interior conditions change.

Arguments for and about Un-Vented Roofs

Two approaches for insulating cathedral ceilings and flat roofs (C) Carson Dunlop Illustrated HomeMr. Bliss points out that often the air/vapor barrier installation is imperfect or has been compromised, permitting leaks into building cavities. He also points out that improperly installed ventilation (such as installing a ridge vent at the top of a roof without installing air intake openings at the soffits or eaves) can make building air movement, moisture, and condensation problems worse.

Bliss cites researchers at Lawrence Berkeley Labs who found that in a mild climate (3000 degree days), most attic moisture comes from the ventilation air itself, not from air inside the house. In general attics are wetter in winter than summer (due to cooler temperatures causing condensation in that space), but in both daily and seasonal cycles, the water entering from outside vent air is stored (and later released) safely from the attic lumber and sheathing.

The "no-vent" or "hot roof" design is discussed, and the author points out that construction, including the vapor barrier, must be just about perfect for this approach to work.

Sketch (above left) is courtesy of Carson Dunlop shows the two basic strategies for insulating cathedral ceilings and flat roofs.

While the article omits later field experience of experts like Henri DeMarne, we caution readers that the hot roof design is extra vulnerable to severe rot and mold damage from hidden, un-discovered leaks that cause more rapid, more extreme damage in enclosed un-vented building cavities than in well-ventilated ones such as a vented roof space.

Ice dams (see the sketch at page top), form when snow sits on a roof for three or four sub-freezing days. Light dry snow makes good insulation on top of the roof, permitting warmth from or inside the attic space below to warm and melt the underside of the snow. This water runs down the roof surface until it meets the cold roof edge or eaves where it freezes to form a dam of ice along the roof edge.

When sufficient water backs up above the ice dam, over the warmer sections of the lower roof edges, water leaks up under the shingles, into the attic, or into the building wall cavities. Mr. Bliss points out that super-insulated modern homes may be at less risk of ice dams than older homes with poorly-insulated attics or roof cavities. In theory, enough insulation can prevent ice dam formation on roofs, except probably on low-slope roofs that hold so much snow as to compete with the R-values provided by the roof insulation.

The article also cites a few complaints of rain or snow blowing in at ridge vents, though in nearly 40 years of building inspections we have almost never found building damage nor mold from this cause.

Conditions Under Which Un-Vented Roofs Might Work

Based on research in Sweden, an un-vented roof can work if:

  • the vapor barrier is perfect
  • the roof covering material is clay tiles or concrete tiles, or other materials that are not absolutely air tight
  • the climate is comparable to southern Sweden (6000 to 8000 degree days)
  • great care is taken that the lumber does not get soaked before or during construction
  • [added by DJF] over the life of the building, no roof leak or roof damage from any other source ever occurs

Roof Vent Debate Conclusions

  • Mr. Bliss concluded (back in 1985, and we agree today) that a non-vented roof is a bit risky, but with a good [read "perfect"] vapor barrier [and, if no roof leaks ever occur over the life of the building] you can probably get away with it.
  • Shallow low-slope roofs such as over shed-dormers should be vented if at all possible.
  • Where roof ventilation is not possible, as in some retrofits or in complex roof designs, pay close attention to sealing air leaks into the roof cavity through the ceiling.
  • Consider using waterproof membranes such as ice and water shield over hard to vent roof sections where ice dams are likely or where they have occurred in the past. [added-DJF]
  • In unvented roofs we would prefer (DJF and Mr. Bliss) if the roofing were air- and moisture-permeable. Wood shingles and shakes (and slate roofs installed on spaced nailers) meet these tests.
  • In un-vented "hot roof" designs, you should expect shorter roof covering life unless the materials are clay tiles, concrete tiles, metal, slate, or something else that is not very affected by the hotter roof temperatures that will be encountered during summer weather [added DJF)

Readers should not fail to review the more extensive information about the need for and methods of roof ventilation found at ROOF VENTILATION SPECIFICATIONS. Also see ICE DAM PREVENTION and Ice Dams: Comparing Two Houses.

Here we include solar energy, solar heating, solar hot water, and related building energy efficiency improvement articles reprinted/adapted/excerpted with permission from Solar Age Magazine - editor Steven Bliss.

Questions & Answers regarding this article

.

Ask a Question or Search InspectAPedia

HTML Comment Box is loading comments...

Share this Article      

...

Technical Reviewers & References

  • InspectAPedia.com® - Daniel Friedman - Publisher & Editor.
  • InspectAPedia Bookstore lists recommended books, organized by topic & available for purchase. Most of our articles also include a list of recommended books for the specific article topic as well as other references, and information sources.
  • Critique, contributions wanted: Contact Us to suggest corrections or additions to articles at this website, and if you wish, to receive online listing and credit as a contributor. Particular thanks are due to the many experts and also consumers who read and critique technical articles at InspectAPedia.com.
  • Additional technical contributors & reference sources for this article are listed below.

Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

ICE DAM PREVENTION

ROOF VENTILATION SPECIFICATIONS
  ATTIC VENTILATION
  CATHEDRAL CEILING INSULATION
  CATHEDRAL CEILING VENTILATION
  HOT ROOF DESIGNS: Un-Vented Roof Solutions
  Inspect Attics for Moisture or Mold
  Inspect Attics for Blocked Soffit Intake Vent
  Inspect Basements for Moisture or Mold
  Inspect Building Exterior - Roof Venting
  Inspect the Ridge Vent System from the Attic
  Inspect the Soffit Vent System from the Attic
  Insects & Foam Insulation
  HOUSE DOCTOR, how-to be
  Insulation Air & Heat Leaks
  Roof Venting: Intake - Outlet Area Ratios
  Roof Venting: Proper Locations
  Roof Venting: Both Ridge & Eaves Venting Needed
  Roof Venting: Eaves Intake if no Overhang
  Roof Venting: Soffit Intake Vent-Continuous
  Roof Venting: Un-Vented Hot Roof Solutions
  ROOF VENTING ENERGY SAVING DETAILS
  ROOF VENTING NEEDED?
  Soffit Ventilation

  • Solar Age Magazine was the official publication of the American Solar Energy Society. The contemporary solar energy magazine associated with the Society is Solar Today. "Established in 1954, the nonprofit American Solar Energy Society (ASES) is the nation's leading association of solar professionals & advocates. Our mission is to inspire an era of energy innovation and speed the transition to a sustainable energy economy. We advance education, research and policy. Leading for more than 50 years. ASES leads national efforts to increase the use of solar energy, energy efficiency and other sustainable technologies in the U.S. We publish the award-winning SOLAR TODAY magazine, organize and present the ASES National Solar Conference and lead the ASES National Solar Tour – the largest grassroots solar event in the world."
  • Steven Bliss served as editorial director and co-publisher of The Journal of Light Construction for 16 years and previously as building technology editor for Progressive Builder and Solar Age magazines. He worked in the building trades as a carpenter and design/build contractor for more than ten years and holds a masters degree from the Harvard Graduate School of Education. Excerpts from his recent book, Best Practices Guide to Residential Construction, Wiley (November 18, 2005) ISBN-10: 0471648361, ISBN-13: 978-0471648369, appear throughout this website, with permission and courtesy of Wiley & Sons. Best Practices Guide is available from the publisher, J. Wiley & Sons, and also at Amazon.com.
    Excerpts with updates and annotations expanding the original Best Practices Guide text can be found in the online review and book summary at BEST CONSTRUCTION PRACTICES GUIDE and also at DECK & PORCH CONSTRUCTION, at INDOOR AIR QUALITY IMPROVEMENT GUIDE, and in other articles found at InspectAPedia.com such as HOUSEWRAP AIR & VAPOR BARRIERS, SOUND CONTROL in buildings, and other topics.
  • Carson, Dunlop & Associates Ltd., 120 Carlton Street Suite 407, Toronto ON M5A 4K2. (416) 964-9415 1-800-268-7070 info@carsondunlop.com. Thanks to Alan Carson and Bob Dunlop, for permission to use illustrations from their publication, The Illustrated Home which illustrates construction details and building components. Carson Dunlop provides home inspection education including the ASHI-adopted Home Inspection Training Program (home study course), publications such as the Home Reference Book, report writing materials including the Horizon report writer, and home inspection services. Alan Carson is a past president of ASHI, the American Society of Home Inspectors.
  • Passive Solar Design Handbook Volume I, the Passive Solar Handbook Introduction to Passive Solar Concepts, in a version used by the U.S. Air Force - online version available at this link and from the USAF also at wbdg.org/ccb/AF/AFH/pshbk_v1.pdf
  • Passive Solar Design Handbook Volume II, the Passive Solar Handbook Comprehensive Planning Guide, in a version used by the U.S. Air Force - online version available at this link and from the USAF also at wbdg.org/ccb/AF/AFH/pshbk_v2.pdf [This is a large PDF file that can take a while to load]
  • Passive Solar Handbook Volume III, the Passive Solar Handbook Programming Guide, in a version used by the U.S. Air Force - online version available at this link and from the USAF also at wbdg.org/ccb/AF/AFH/pshbk_v3.pdf
  • The Passive Solar Design and Construction Handbook, Steven Winter Associates (Author), Michael J. Crosbie (Editor), Wiley & Sons, ISBN 978-047118382 or 0471183083 is available at Amazon.com and via the The Passive Solar Design and Construction Handbook, Steven Winter Associates (Author), Michael J. Crosbie (Editor), Wiley & Sons, ISBN 978-047118382 or 0471183083 is available at Amazon.com and via the InspectAPedia Bookstore
  • "Passive Solar Home Design", U.S. Department of Energy, describes using a home's windows, walls, and floors to collect and store solar energy for winter heating and also rejecting solar heat in warm weather.
  • "Solar Water Heaters", U.S. Department of Energy article on solar domestic water heaters to generate domestic hot water in buildings, explains how solar water heaters work. Solar heat for swimming pools is also discussed.
  • "Heat Exchangers for Solar Water Heating Systems", U.S. DOE describes the types of solar water heater heat exchange methods between the sun and the building's hot water supply
  • "Heat-Transfer Fluids for Solar Water Heating Systems", U.S. DOE, describes the types of fluids selected to transfer heat between the solar collector and the hot water in storage tanks in a building. These include air, water, water with glycol antifreeze mixtures (needed when using solar hot water systems in freezing climates), hydrocarbon oils, and refrigerants or silicones for heat transfer.
  • "Solar Water Heating System Maintenance and Repair", U.S. DOE
  • "Solar Water Heating System Freeze Protection", U.S. DOE,using antifreeze mixture in solar water heaters (or other freeze-resistant heat transfer fluids), as well as piping to permit draining the solar collector and piping system.
  • "Scaling and Corrosion in Solar Water Heating Systems", U.S. DOE
  • www.energysavers.gov/your_home/water_heating/index.cfm/mytopic=12850 is the base U.S. DOE website for these articles
  • "Active Solar Heating Systems", U.S. Department of Energy, including
  • "Radiant Heating Systems" U.S. DOE
  • "Absorption Heat Pumps & Coolers", U.S. DOE
  • "Solar Air Heating" U.S. DOE also referred to as "Ventilation Preheating" in which solar systems use air for absorbing and transferring solar energy or heat to a building
  • "Solar Liquid Heating" U.S. DOE, systems using liquid (typically water) in flat plate solar collectors to collect solar energy in the form of heat for transfer into a building for space heating or hot water heating. The term "solar liquid" is used for accuracy, rather than "solar water" because the water may contain an antifreeze or other chemicals.

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.
  • ...
Home About Us Accuracy Contact Us Content Use Policy Privacy Website Description © 2012 Copyright InspectAPedia.com