InspectAPedia.com InspectAPedia®
 

Free Encyclopedia of Building & Environmental Inspection, Testing, Diagnosis, Repair

Ask a Question or Search InspectAPedia

  • HOME
  • AIR CONDITIONING
  • ELECTRICAL
  • EXTERIORS
  • HEATING
  • HOME INSPECTION
  • INTERIORS
  • PLUMBING
  • ROOFING
  • SEPTIC SYSTEMS
  • STRUCTURE
  • WATER SUPPLY
  • ENERGY SAVINGS
  • ENVIRONMENT
  • INDOOR AIR IAQ
  • INSULATION
  • MOLD INSPECT TEST REMOVE
  • NOISE
  • ODORS
  • SOLAR ENERGY
  • VENTILATION
  • EXPERTS DIRECTORY
  • CONTACT US


Mobile Phone/PDA website viewMobile View
INTERIORS of buildings

ACOUSTICAL SEALANT CHOICES
AIR BYPASS LEAKS
AIR LEAK DETECTION TOOLS
AIR LEAK MINIMIZATION
AIR POLLUTANTS, COMMON INDOOR
AIR LEAK SEALING PROCEDURE
AIR SEALING STRATEGIES
AIR TEST FOR MOLD: ACCURACY
AIR TEST SAMPLING CASSETTE STUDY
ALLERGEN TESTS for buildings
ALLERGY TESTS for PEOPLE
ALLERGY TEST ACCURACY
ANIMAL ALLERGENS
APPLIANCE EFFICIENCY RATINGS
ASBESTOS FLOORING HAZARD REDUCTION
ASBESTOS-FREE INSULATION MATERIALS
ASBESTOS IDENTIFICATION IN buildings
ATTIC LEAKS, CONDENSATION & ATTIC MOLD
ATTIC VENTILATION

BASEMENT CEILING VAPOR BARRIER
BASEMENT HEAT LOSS
BASEMENT LEAKS, INSPECT FOR
BASEMENT WATERPROOFING

BATH & KITCHEN DESIGN GUIDE
BATHROOM VENTILATION
BIOGAS PRODUCTION & USE
BLOWER DOORS & AIR INFILTRATION
BLOWER FAN CONTINUOUS OPERATION
BLOWER FAN OPERATION & TESTING
BLOWN-IN INSULATION

BRICK LINED WALLS
BRICK VENEER WALL INSULATION
BRICK VENEER WALL Loose, Bulged
BRICK WALL DRAINAGE WEEP HOLES
BUCKLED FOUNDATIONS due to INSULATION?
BUILDING NOISE DIAGNOSIS & CURE

CATHEDRAL CEILING INSULATION
CATHEDRAL CEILING VENTILATION
CEILING FINISHES INTERIOR
CEILINGS, DROP or SUSPENDED PANEL
CEILINGS, PLASTER TYPES

CHIMNEY INSPECTION DIAGNOSIS & REPAIR
COOLING LOAD REDUCTION by ROOF VENTS
COMBUSTION AIR for TIGHT buildings
CONDENSING BOILERS/FURNACES DAMAGE

CATHEDRAL CEILING INSULATION
CATHEDRAL CEILING VENTILATION
CEILING FINISHES INTERIOR
CEILINGS, DROP or SUSPENDED PANEL
CEILINGS, PLASTER TYPES

CHIMNEY INSPECTION DIAGNOSIS & REPAIR
COOLING LOAD REDUCTION by ROOF VENTS
COMBUSTION AIR for TIGHT BUILDINGS
CONDENSING BOILERS/FURNACES DAMAGE
CONDENSATION or SWEATING PIPES, TANKS
COOLING LOAD REDUCTION by ROOF VENTS
CRAWL SPACES

DEFINITION of Heating & Cooling Terms
DEHUMIDIFICATION PROBLEMS
DEW POINT CALCULATION for WALLS
DEW POINT TABLE - CONDENSATION POINT GUIDE
DUCT SYSTEM & DUCT DEFECTS

ELECTRIC HEAT
ELECTRIC POWER, PHOTOVOLTAIC, REMOTE SITE
ENERGY SAVINGS in buildings
ENERGY STAR PROGRAM
EVAPORATIVE COOLING SYSTEMS

ENVIRONMENTAL HAZARDS - INSPECT, TEST, REMEDY

FIBERGLASS INSULATION
FIBERGLASS HAZARDS
FIBERGLASS INSULATION MOLD

FLASHING MEMBRANES PEEL & STICK
FLAT ROOF MOISTURE & CONDENSATION

FLOOD DAMAGE ASSESSMENT, SAFETY & CLEANUP
FLOODS IN buildings-mold

FLOOR, CONCRETE SLAB CHOICES
FLOOR, CONCRETE SLAB POURED FINISH
FLOOR DAMAGE DIAGNOSIS
FLOOR RADIANT HEAT Mistakes to Avoid
FLOOR TYPES & DEFECTS

FOUNDATION WATERPROOFING
FRENCH DRAINS
FRAMING DETAILS for BETTER INSULATION
FRAMING DETAILS for DOUBLE WALL HOUSES
FRAMING METAL STUD PERFORMANCE
FREEZE-PROOF A BUILDING
FROST HEAVES, FOUNDATION, SLAB

GREEN BUILDING CONSTRUCTION CODES GUIDES
GREENHOUSE DESIGN for SOLAR HEATING

HEAT LOSS in buildings
HEAT LOSS RATE CALCULATIONS
HEAT LOSS DETECTION TOOLS
HEAT LOSS INDICATORS
HEAT LOSS PREVENTION PRIORITIES
HEAT LOSS R U & K VALUE CALCULATION
HEAT TAPES & CABLES on Roofs for Ice Dams
HEATING COST FUEL & BTU Cost Table
HEATING COST SAVINGS METHODS
HEATING LOSS DIAGNOSIS-BOILERS
HEATING LOSS DIAGNOSIS-FURNACES

HOT ROOF DESIGNS: Un-Vented Roof Solutions
HOUSEWRAP AIR & VAPOR BARRIERS
HOUSE DOCTOR, how-to be

HUMIDITY LEVEL TARGET

ICE DAM PREVENTION
INDOOR AIR HAZARDS TABLE
INDOOR AIR QUALITY & HOUSE TIGHTNESS
INDOOR AIR QUALITY IMPROVEMENT GUIDE
  Air Pollutants, Health Effects
  Air Pollutants, Common Indoor
  INDOOR AIR QUALITY IMPROVEMENT, KEY STEPS
  VENTILATION, WHOLE HOUSE STRATEGIES
  VENTILATION, EXHAUST ONLY
  VENTILATION, SUPPLY-ONLY
  VENTILATION, BALANCED
    Heat Recovery Ventilation
    Energy Recovery Ventilators
  VENTILATION, BALANCED HEAT COST SAVINGS
  Air Filtering Strategies
  Particles in Indoor Air - Chart
  GAS EXPOSURE EFFECTS
  Gas Toxicity Levels
  Gases, Quick Guide to Indoor
  AIR CLEANER PURIFIER TYPES
    Particulate Air Cleaner Table
  Air Filter Effectiveness
  Real-World Effectiveness of Air Cleaners
  Air Pollutants, Finding & Reducing
  Radon Hazards
  Formaldehyde Hazards
  BIOLOGICAL POLLUTANTS
  BUY PRODUCTS for MOLD & ALLERGY CONTROL
  Volatile Organic Compounds VOCs
  Pesticide Exposure Hazards
  Lead Exposure Hazards
  Asbestos Exposure Hazards
  Combustion Appliance Contaminants
  Backdrafting Appliances
  Fireplace & Woodstove Contaminants
  INDOOR AIR HAZARDS TABLE
  INDOOR COMBUSTION PRODUCTS & IAQ
INSULATION CHOICES
Insulation Air & Heat Leaks
INSULATION FACT SHEET- DOE
INSULATION for GREENHOUSE or SOLARIUM
INSULATION IDENTIFICATION GUIDE
INSULATION INSPECTION & IMPROVEMENT
INSULATION LOCATION - WHERE TO PUT IT
INSULATION MOLD
INSULATION R-Values & Properties

KIT HOMES, Aladdin, Sears, Wards, Others
KITCHEN & BATH DESIGN GUIDE

LEED GREEN BUILDING CERTIFICATION
LOG HOME ENERGY EFFICIENCY
LOG HOME GUIDE

MOBILE HOME INSPECTIONS
MOISTURE CONTROL in buildings
MOLD in FOAM INSULATION, RESISTANCE
MOLD INFORMATION CENTER

Nanomaterials Hazards
NOISE / SOUND DIAGNOSIS & CURE
NOISE CONTROL for HEATING SYSTEMS
NOISE CONTROL for FLOORS
NOISE CONTROL for PLUMBING
NOISE CONTROL for ROOFS

ODORS & SMELLS DIAGNOSIS & CURE

PAINT FALURE, DIAGNOSIS, CURE, PREVENTION
PASSIVE SOLAR DESIGN METHOD
PASSIVE SOLAR HEAT PERFORMANCE
PASSIVE SOLAR HOME, LOW COST
PHOTOVOLTAIC POWER SYSTEMS
PLASTER & BEAVERBOARD & DRYWALL
PASCAL CALCULATIONS

RADIANT BARRIERS
RADIANT HEAT
RADIANT HEAT Floor Mistakes to Avoid
RADIANT HEAT TEMPERATURES
RADIANT SLAB FLOORING CHOICES
RADIANT SLAB TUBING & FLUID CHOICES
REFLECTIVE INSULATION
RIGID FOAM USE INDOORS
ROOF VENTING ENERGY SAVING DETAILS
ROOF VENTING NEEDED?
ROOF VENTILATION SPECIFICATIONS
ROT, FUNGUS, TERMITES
ROT, TIMBER FRAME

ROOF ARCHITECTURAL STYLES - PHOTO GUIDE
ROOF CLEANING RECOMMENDATIONS
ROOF DORMER TYPES - PHOTO GUIDE
ROOF VENTILATION SPECIFICATIONS
ROOF VENTING ENERGY SAVING DETAILS
ROOF VENTING NEEDED?
ROT, FUNGUS, TERMITES
ROT, TIMBER FRAME

SEARS KIT HOUSES
Soffit Ventilation
SOUND CONTROL in buildings
STAIN & BIODETERIORATION AGENT CATALOG
STAINS on buildings - QUICK GUIDE
STAIN DIAGNOSIS on BUILDING EXTERIORS
STAIN DIAGNOSIS on BUILDING INTERIORS
STAINS on INDOOR SURFACES: PHOTO GUIDE

STAIRS, RAILINGS, LANDINGS, RAMPS
STONE CLEANING METHODS

STUCCO WAll FAILURES DUE TO WEATHER
STUCCO WALL METHODS & INSTALLATION
STUCCO OVER FOAM INSULATION
STUCCO PAINT FAILURES

SUMP PUMPS GUIDE
SWEATING (CONDENSATION) on PIPES, TANKS
VAPOR BARRIERS & AIR SEALING at BAND JOISTS
VAPOR CONDENSATION & BUILDING SHEATHING
THERMAL EXPANSION of MATERIALS
THERMAL MASS in buildings
THERMAL TRACKING & HEAT LOSS
VAPOR BARRIERS & AIR SEALING at BAND JOISTS
VAPOR BARRIERS & HOUSEWRAP
VAPOR CONDENSATION & BUILDING SHEATHING
VENTILATION in buildings
  Air Bypass Leaks, Thermal Tracking
  AIR CHANGE RATE ACH HEAT SAVINGS
  ATTIC CONDENSATION CAUSE & CURE
  BALANCED VENTILATION, HEAT COST SAVINGS
  BATH & KITCHEN DESIGN GUIDE
  BATHROOM VENTILATION
  Blocked Soffit Intake Vents
  BLOWER DOORS & AIR INFILTRATION
  BLOWN-IN INSULATION
  BRICK or BLOCK WALL CAVITY INSULATION
  BRICK VENEER WALL INSULATION
  CATHEDRAL CEILING INSULATION
  CATHEDRAL CEILING VENTILATION
  CLOTHES DRYER VENTING
  COOLING LOAD REDUCTION by ROOF VENTS
  CRAWL SPACE VENTING & Dryout Procedures
  HEAT LOSS: How to Calculate Heat Loss in a Building
  HOT ROOF DESIGNS: Un-Vented Roof Solutions
  HOUSEWRAP AIR & VAPOR BARRIERS
  HUMIDITY LEVEL TARGET
  ICE DAM PREVENTION
  Inspect Attics for Moisture or Mold
  Inspect Attics for Blocked Soffit Intake Vents
  Inspect Basements for Moisture or Mold
  Inspect Building Exterior - Roof Venting
  Inspect the Ridge Vent System from the Attic
  Inspect the Soffit Vent System from the Attic
  Insects & Foam Insulation
  HOUSE DOCTOR, how-to be
  Insulation Air & Heat Leaks
  MOISTURE CONTROL in buildings
  MOISTURE CALCULATIONS
  MOISTURE METER STUDY
  MOISTURE PROBLEMS: CAUSE & CURE
  ROOF VENTING ENERGY SAVING DETAILS
  ROOF VENTING NEEDED?
  SKYLIGHT VENTILATION DETAILS
  Soffit Ventilation
  VENTILATION DESIGN PROBLEMS & SOLUTIONS
  VENTILATION, WHOLE HOUSE STRATEGIES

WALL SIDING TRIM & FINISHES
WALL FINISHES INTERIOR

WATER BARRIERS, EXTERIOR BUILDING
WATER ENTRY in buildings
WIND ENERGY SYSTEMS
WIND TURBINES & LIGHTNING
WIND WASHING INSULATION At EAVES
WINDOWS & DOORS

WINTERIZE A BUILDING
Wood Burning Heaters Fireplaces Stoves
Woodstove Safety

ZONE VALVES

More Information

  (C) Daniel Friedman

Ventilation Design Issues for Tight Homes
InspectAPedia®  -    

  • What are the design issues & design solutions for ventilation systems for tight or energy efficient homes?
  • Building ventilation supply air & return air problems & solutions
  • Building indoor air pressure drop during ventilation
  • Building indoor air ventilation system noise problems & solutions
  • Ventilation airflow controls
  • Solar Age Magazine Articles on Renewable Energy, Energy Savings, Construction Practices
  • Questions & answers about indoor air quality or combustion air hazards, effective ventilation and ventilation problems/solutions for tight houses
InspectAPedia offers impartial, unbiased advice without conflicts of interest. We will block advertisements which we discover or readers inform us are associated with bad business practices, false-advertising, or junk science. Our contact info is at InspectAPedia.com/Contact.htm.

This article describes common design issues in making a successful building ventilation system, providing solutions for various building venting and moisture problems with supply air & return air problems & solutions, building indoor air pressure drop during ventilation, building indoor air ventilation system noise problems & solutions, and building ventilation airflow controls. Sketch at page top and accompanying text are reprinted/adapted/excerpted with permission from Solar Age Magazine - editor Steven Bliss. The sketch shows a very basic building ventilation defect - lack of under-roof venting - and its role in causing ice dams. More subtle is the question of indoor air quality and the building design and mechanical systems that affect that concern.

Readers concerned with good design for indoor air ventilation systems should see INDOOR AIR QUALITY & HOUSE TIGHTNESS and
INDOOR AIR QUALITY IMPROVEMENT GUIDE as well as VENTILATION in buildings. Contact us to suggest text changes and additions and, if you wish, to receive online listing and credit for that contribution.

© Copyright 2012 InspectAPedia.com, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use page top links to major topics or use links at the left of each page to navigate within topics and documents at this website. Green links show where you are in a document series or at this website.

Ventilation Design Issues - part 2: Supplies & Returns, Pressure Drop, Noise, Airflow, Controls

"The Importance of Ventilation, Part II" - links to the original article in PDF form immediately below are followed by an expanded/updated online version of this article.

  • The Importance of Ventilation: Ventilation Design Issues part 2 - PDF version, use your browser's back button to return to this page
  • The Importance of Ventilation: Ventilation Design Issues part 2 - part 2 continued

This article reviews the design issues that can make or break a residential ventilation system. The text below paraphrases, quotes-from, updates, and comments an original article, "The Importance of Ventilation, Part II", (see links just above) from Solar Age Magazine and written by Steven Bliss.

Building Fresh Air Supplies and Air Returns

According to Gautam Dutt, of Princeton University's Center for Energy and Environmental Studies, natural infiltration probably doesn't ventilate houses very well. The basement may get the freshest air, drawn in by the stack effect (warm air rising in a building and exiting at high points draws outdoor air into the building from openings at lower levels on the structure). Other rooms in the building may not see much fresh air.

A fresh air distribution system can guarantee good air ventilation throughout the building. This article provides basic design principles and installation tips for fresh air ventilation systems. At VENTILATION in buildings we provide a detailed guide to building ventilation, and at INDOOR AIR QUALITY IMPROVEMENT GUIDE we provide in-depth technical detail about the identification and cure of indoor air quality problems, including details about the whole array of house ventilation approaches.

While it makes complete sense to identify and remove significant indoor air quality problem reservoirs such as mold contamination or smelly carpets, furniture, or even animal waste that can explain bad indoor air quality, an efficient fresh air distribution system in a building will also remove lower levels or more subtle air pollutants at their source and will deliver fresh air to the prime living areas.

In practice this means putting exhaust air pickups in rooms that produce moisture and odors, and fresh air supplies in bedrooms and living rooms. Rooms with intermittent use, such as a den used occasionally for entertaining, might have an exhaust pickup that can be opened when needed. (For more information see VENTILATION, EXHAUST ONLY).

Keep fresh air supply registers (see VENTILATION, SUPPLY-ONLY) away from return air registers to avoid short-circuiting of air streams. (This makes sense for heating and air conditioning registers as well.) It's also important to locate air supply diffusers where they won't blow cool air on the occupants. In Europe many window-mounted air inlets are taped over by disgruntled tenants. good air supply locations are near ceilings, in hallways, and in closets (provided the closet has a louvered door).

A closet fresh air supply can help assure that clothing stored there will smell fresh, and properly designed a closet supply can also avoid moldy clothing in these sometimes damp, un-heated storage areas, especially when the closet is located on an exterior all.

Open building space plans that promote good flow of heated or cooled air in a building will also improve the flow of fresh air indoors. When air is supplied from centralized locations such as a hallway, undercut the bedroom doors so that air can enter those spaces.

In central fresh air systems, the kitchen will need an exhaust pickup, plus a recirculating-type range hood. Keep the central kitchen exhaust pickup several feet away from the range so that it doesn't get greased-up (a fire hazard).

Building Indoor Air Pressure Drop Due to Ventilating Systems

During the heating season we don't want positive pressures inside the building as that may push moisture into building walls. Some Montana homeowners, for example, have reported frozen door locks due to unbalanced heat exchangers that pressurized indoor air, sending moist air flowing out through door lock openings.

But we don't want large negative pressures in indoor air either. There is evidence that negative indoor air pressures can be dangerous, not only drawing increased levels of radon gas from soils where that contaminant is present (see Radon Hazards), but also negative indoor air pressure can cause dangerous backdrafting of flue gases from (atmospherically-vented) heating appliances, even causing the production of potentially fatal carbon monoxide (see Backdrafting Appliances and COMBUSTION GASES & PARTICLE HAZARDS).

Yet it is difficult to maintain a neutral indoor air pressure with balanced airflow. In the original Ventilation II article, Mr. Bliss argues that a slight negative pressure is preferable except where Radon is a problem. This will avoid forcing indoor moisture into problem areas and may actually help dry out building cavities. This also means that small exhaust-only air ventilation systems are probably fine. To keep negative pressures minimal, exhaust-only house venting systems should have intentional openings (a central duct or through-wall diffusers) to supply makeup air (return air). (See VENTILATION, EXHAUST ONLY).

But with a tight, negatively pressured house, you simply can't have combustion appliances without outside combustion air. (See COMBUSTION AIR for TIGHT buildings).

Whatever ventilation approach you take, make sure that you look at the whole house as a system, and that the path of least resistance for makeup air is not down a heating flue. See VENTILATION, WHOLE HOUSE STRATEGIES for a detailed review of alternative house ventilation strategies, including these sub-topics:

INDOOR AIR QUALITY IMPROVEMENT, KEY STEPS
  VENTILATION, WHOLE HOUSE STRATEGIES
  VENTILATION, EXHAUST ONLY
  VENTILATION, SUPPLY-ONLY
  VENTILATION, BALANCED
    Heat Recovery Ventilation
    Energy Recovery Ventilators
  VENTILATION, BALANCED HEAT COST SAVINGS
  Air Filtering Strategies
  Particles in Indoor Air - Chart
  GAS EXPOSURE EFFECTS
  Gas Toxicity Levels
  Gases, Quick Guide to Indoor
  AIR CLEANER PURIFIER TYPES
    Particulate Air Cleaner Table
  Air Filter Effectiveness
  Real-World Effectiveness of Air Cleaners
  Air Pollutants, Finding & Reducing

Solving Noise Problems with Building Ventilation Systems & Fans

Low-energy buildings tend to shield out street noise better than standard houses. But in an otherwise quiet house, noisy fans sound still noisier. Many an exhaust ventilation system has had its plug pulled to silence the hum.

Look for quiet fans. Manufacturers rate their fans' noise levels in sones. One sone is roughly equal to the sound of a quiet refrigerator in a quiet kitchen. Unlike the decibel noise scale, sones are additive, so 2 sones is twice as loud as one, and so on. The average (noisy) 100 cfm bathroom fan rates at 3 to 5 sones. Look for a fan in the 1.5 to 3 sone range.

In central fresh air ventilation systems, do not locate the fan directly above or below bedrooms. If possible, create a sound-transmission break between the main fan unit and any metal duct runs (which we recommend because metal ducts can be cleaned), using a short length of flexible duct.

Also, special "muffler" sections can be added to dampen the sound from a ventilation system.

Suspend the fan unit or air handler in such a way that it will not transmit its vibrations to the frame of the building. This is usually done by setting the fan unit on foam-covered slats that are hung from overhead joists or rafters.

Advice on Providing Fresh Air at Heating Furnace or Air Conditioner Duct & Air Handlers

Is it a good idea to provide fresh makeup air to a house ventilation system by connecting outdoor air through the return air side of a furnace or central air conditioner air handler for a building that is also ventilated by an exhaust-only air system?

This seems fine, if the exhaust fan is running constantly, or if the fresh-air damper is power-actuated and wired to open only when the exhaust fan is running. But running a furnace fan with the vent open and the exhaust fan off will over-pressurize the building. (See CONTINUOUS BLOWER FAN OPERATION )

How about plugging your air-to-air heat exchanger into the furnace? This, too, is difficult for similar reasons. Besides, in a building that is tight enough to need an air-to-air heat exchanger, the furnace will be off much of the time. Take a look at Heat Recovery Ventilation if you are considering this approach.

Solving Problems with Fresh Air Flow & Building Fans - How Much Air Can the Fan Move

Not all fans are created equal, but all fans move less air as more ductwork is added. Each fan has a unique performance curve that describes how much air it moves at a given static pressure - the resistance to air flow caused by the ductwork.

Make sure that the fan you select can deliver the cfm (cubic feet per minute) through the ductwork you plan to install. Not just duct length but cross-section, diameter, interior smoothness, and critically, bends and turns have a big impact on the static pressure the fan will encounter. The static pressure of a duct system can be measured by an HVAC contractor and by some home inspectors, or you can learn how to measure static duct pressure yourself using references from a variety of sources including the HRACI of Canada.

When selecting a ventilating system or exhaust fan, look for a relatively flat fan performance curve. That means that the fan doesn't wimp out as soon as you add a few feet of duct. Choose smooth ducts, short runs, and avoid many turns and sharp turns in the ductwork. Many air ventilation system installers don't get the airflows they expected because they installed cheap fans and poorly designed ductwork.

Manual vs. Automatic Control of Fresh Air Ventilation Systems - Building Owner Controls

Both fully automatic ventilation system controls and fully manual controls are available for vent systems. Mr. Bliss suggests providing both types of controls: install a ventilation system that can work fully automatically, but give the building occupants simple manual overrides.

The most common automatic ventilation system controls include clock timers and dehumidistats. The dehumidistat (or humidistat) responds to changing ventilation needs by sensing the indoor moisture level. They are not foolproof however. In very dry climates they may under-ventilate, and in wet climates or swing seasons they may over-ventilate the building. So the occupants may want to be able to make a little seasonal adjustment to the controls.

Timers and fan/light switches work well in bathrooms. For the kitchen exhaust, the good old manual on-off switch may be best.

Some designers recommend running the ventilation system constantly,at a low speed, speeding the system up when needed, usually for kitchen and bath use. This is fine if the system is quiet and was sized correctly, and it can make for more even, comfortable indoor conditions. (See CONTINUOUS BLOWER FAN OPERATION )

Effective, Quiet House Ventilation Systems Mean Homeowner Will Use Them

Virtually everyone who has worked around ventilation systems, starting with simple bathroom vent fans, can tell you that noisy systems tend to be shut off and simply not used by building occupants. We have seen landlords hard-wire the bath fan so that it will always be on when the bathroom light is on, trying to force tenants to blow high-humidity air outside. We have also seen tenants using a lamp and extension cord to provide bathroom light (possibly dangerous) rather than tolerate a loud bath exhaust fan.

Here we include solar energy, solar heating, solar hot water, and related building energy efficiency improvement articles reprinted/adapted/excerpted with permission from Solar Age Magazine - editor Steven Bliss.

Questions & Answers regarding this article

Questions & answers about indoor air quality or combustion air hazards, effective ventilation and ventilation problems/solutions for tight houses

Ask a Question or Search InspectAPedia

HTML Comment Box is loading comments...

Share this Article      

...

Technical Reviewers & References

  • InspectAPedia.com® - Daniel Friedman - Publisher & Editor.
  • InspectAPedia Bookstore lists recommended books, organized by topic & available for purchase. Most of our articles also include a list of recommended books for the specific article topic as well as other references, and information sources.
  • Critique, contributions wanted: Contact Us to suggest corrections or additions to articles at this website, and if you wish, to receive online listing and credit as a contributor. Particular thanks are due to the many experts and also consumers who read and critique technical articles at InspectAPedia.com.
  • Additional technical contributors & reference sources for this article are listed below.

Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

VENTILATION in buildings
  Air Bypass Leaks, Thermal Tracking
  AIR CHANGE RATE ACH HEAT SAVINGS
  ATTIC CONDENSATION CAUSE & CURE
  BALANCED VENTILATION, HEAT COST SAVINGS
  BATH & KITCHEN DESIGN GUIDE
  BATHROOM VENTILATION
  Blocked Soffit Intake Vents
  BLOWER DOORS & AIR INFILTRATION
  BLOWN-IN INSULATION
  BRICK or BLOCK WALL CAVITY INSULATION
  BRICK VENEER WALL INSULATION
  CATHEDRAL CEILING INSULATION
  CATHEDRAL CEILING VENTILATION
  CLOTHES DRYER VENTING
  COOLING LOAD REDUCTION by ROOF VENTS
  CRAWL SPACE VENTING & Dryout Procedures
  HEAT LOSS: How to Calculate Heat Loss in a Building
  HOT ROOF DESIGNS: Un-Vented Roof Solutions
  HOUSEWRAP AIR & VAPOR BARRIERS
  HUMIDITY LEVEL TARGET
  ICE DAM PREVENTION
  Inspect Attics for Moisture or Mold
  Inspect Attics for Blocked Soffit Intake Vents
  Inspect Basements for Moisture or Mold
  Inspect Building Exterior - Roof Venting
  Inspect the Ridge Vent System from the Attic
  Inspect the Soffit Vent System from the Attic
  Insects & Foam Insulation
  HOUSE DOCTOR, how-to be
  Insulation Air & Heat Leaks
  MOISTURE CONTROL in buildings
  MOISTURE CALCULATIONS
  MOISTURE METER STUDY
  MOISTURE PROBLEMS: CAUSE & CURE
  ROOF VENTING ENERGY SAVING DETAILS
  ROOF VENTING NEEDED?
  SKYLIGHT VENTILATION DETAILS
  Soffit Ventilation
  VENTILATION DESIGN PROBLEMS & SOLUTIONS
  VENTILATION, WHOLE HOUSE STRATEGIES

  • Solar Age Magazine was the official publication of the American Solar Energy Society. The contemporary solar energy magazine associated with the Society is Solar Today. "Established in 1954, the nonprofit American Solar Energy Society (ASES) is the nation's leading association of solar professionals & advocates. Our mission is to inspire an era of energy innovation and speed the transition to a sustainable energy economy. We advance education, research and policy. Leading for more than 50 years. ASES leads national efforts to increase the use of solar energy, energy efficiency and other sustainable technologies in the U.S. We publish the award-winning SOLAR TODAY magazine, organize and present the ASES National Solar Conference and lead the ASES National Solar Tour – the largest grassroots solar event in the world."
  • Steven Bliss served as editorial director and co-publisher of The Journal of Light Construction for 16 years and previously as building technology editor for Progressive Builder and Solar Age magazines. He worked in the building trades as a carpenter and design/build contractor for more than ten years and holds a masters degree from the Harvard Graduate School of Education. Excerpts from his recent book, Best Practices Guide to Residential Construction, Wiley (November 18, 2005) ISBN-10: 0471648361, ISBN-13: 978-0471648369, appear throughout this website, with permission and courtesy of Wiley & Sons. Best Practices Guide is available from the publisher, J. Wiley & Sons, and also at Amazon.com.
    Excerpts with updates and annotations expanding the original Best Practices Guide text can be found in the online review and book summary at BEST CONSTRUCTION PRACTICES GUIDE and also at DECK & PORCH CONSTRUCTION, at INDOOR AIR QUALITY IMPROVEMENT GUIDE, and in other articles found at InspectAPedia.com such as HOUSEWRAP AIR & VAPOR BARRIERS, SOUND CONTROL in buildings, and other topics.
  • Carson, Dunlop & Associates Ltd., 120 Carlton Street Suite 407, Toronto ON M5A 4K2. (416) 964-9415 1-800-268-7070 info@carsondunlop.com. Thanks to Alan Carson and Bob Dunlop, for permission to use illustrations from their publication, The Illustrated Home which illustrates construction details and building components. Carson Dunlop provides home inspection education including the ASHI-adopted Home Inspection Training Program (home study course), publications such as the Home Reference Book, report writing materials including the Horizon report writer, and home inspection services. Alan Carson is a past president of ASHI, the American Society of Home Inspectors.
  • "Residential Heating and Ventilation System Design", Heating, Refrigeration, and Air Conditioning Institute of Canada, 5468 Dundas St. W., Suite 226, Islington, Ontario, M9B 6E3 Canada.

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.
  • ...
Home About Us Accuracy Contact Us Content Use Policy Privacy Website Description © 2012 Copyright InspectAPedia.com