Mold contamination occurrences in fiberglass insulation:
This article, one of a series of texts about mould contamination in building insulation, explains the cause, detection, and hazards of mold growth in fiberglass insulation in residential and light-commercial buildings.
We illustrate how to find or test for moldy insulation in buildings, the probable cause of mold contamination in building insulation, and how to recognize conditions that make that problem likely in a particular case.
This website discusses health hazards associated with moldy fiberglass in buildings, with focus on fiberglass insulation, fiberglass fragments, fiberglass in heating and air conditioning duct work, and invisible but toxic mold growth in fiberglass which has been wet, exposed to high humidity, or exposed to other moldy conditions.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Editor/Publisher - See WHO ARE WE?
Mold and mold-odors in building wall and ceiling and even floor cavities can be traced to leaks into the cavity or in humid climates such as areas in the U.K. and North America if homes in those climates are not properly constructed to keep both leaks and humid air out of the wall, ceiling or floor cavity.
The literature indicates that fiberglass can serve as a support matrix for the collection of debris which, when moist, have the capability of supporting the growth of mold. Further, binding and paper-based moisture barriers from fiberglass resins are also capable of supporting the growth of mold when moist. (Van Loo 2004)
Our own study has shown that significant mold contamination can be found in some building insulation materials even when to the naked eye the insulation looks "clean". Originally that finding was a surprise, but one that was confirmed by repeated field and laboratory tests.
[Click to enlarge any image]
This is an important finding because it means that in cleaning a mold-contaminated building or one whose insulation has been water-damaged, it could be a serious error to ignore the building insulation. Mold can show up in fiberglass insulation in several ways as we list here:
Note: Given a few boots of temperature, humidity, or food it likes, mold of one genera/species or another can grow on just about anything. Here we focus on mold growth in and on fiberglass insulation; paper and other organics such as flax insulation, more affected by moisture, may be even better hosts for mold growth. (Klamer 2004).
The 720x photographs above and just below show active fungal growth along the surface of a fiberglass insulation fiber collected the suspended ceiling of a building suffering wet conditions and moldy in-slab HVAC ducts.
Fiberglass in building insulation is a topic I have been testing and studying for nearly forty years, after having first traced a building mold contamination reservoir to a hidden source in this material. I frequently find high levels of mold-contaminated fiberglass insulation in buildings which contain other large mold reservoirs.
I [DF] have also detected high levels of problematic mold in fiberglass building insulation where other mold reservoirs were either not present or had been previously removed.
Our moldy building insulation photo at page top (contributed by a reader) shows an obvious case: very wet fiberglass insulation under a roof and extensive black mold growth on at least the insulation surface, probably inside the insulation as well.
But in a more subtle, and not easily visible form, problematic building contamination by mold is often found in otherwise clean-looking basement fiberglass insulation, crawl space fiberglass insulation, fiberglass wall insulation, heating or cooling duct fiberglass insulation, and attic or roof insulation in buildings which have either been wet or have been exposed to high levels of mold from other sources.
That "hidden" insulation mold is the focus of our discussion in this article.
Except for some superficial "dust staining" that is often simply thermal tracking by house dust, the pink fiberglass insulation shown below (left) looked clean.
Unlike our black insulation mold photo above, there was no visible mold on the pink fiberglass insulation shown at below left.
But vacuuming the center (most clean-looking area) of that mold and lab examination of the vacuum dust sample contents showed the long Penicillium/Aspergillus spore chains (below right) consistent with local problematic mold growth.
High levels of mold may be present in fiberglass insulation:
We have measured very high levels of airborne problematic mold spores which were traced to a building reservoir of moldy fiberglass insulation.
Recapping, the pair of photographs (above) shows fairly clean-looking fiberglass insulation over a crawl space which in fact had been subjected to flooding.
While the insulation itself did not appear to have been flooded, and while there was no mold visible on or in this fiberglass insulation, a simple vacuum test demonstrated that the insulation was severely contaminated with Aspergillus sp. mold.
The presence of both mold spore chains and conidiophores of Aspergillus sp. in the insulation test samples whose photos are shown above confirmed that not only was the crawl space ceiling fiberglass insulation moldy, but it was supporting active fungal growth.
Our screening samples confirmed that this mold was present in other building areas, most-likely emanating from this mold reservoir of mold-contaminated fiberglass insulation.
In some of cases, non-visible mold contamination in fiberglass insulation has been enough to cause IAQ, health, or other mold-related complaints by building occupants, and in some cases
In the partially-opened basement wall shown here, the water track stains on the cavity side of the exposed drywall (shown after a test cut was made) indicate that water passed in this wall from above.
In this circumstance, even when the fiberglass insulation looks clean, I often find high levels of Penicillium sp. or Aspergillus sp. in this material.
Comparison tests of fiberglass which is new at a building supply store or in homes where the insulation has not been wet nor infested with rodents or other pests, mold is rarely a problem. That signifies that mold is not arriving in new clean building insulation, but it can get there after installation.
The photo at above right shows a very dense presence of Pen/Asp spores and spore chains as well as a portion of a conidiophore (lower left) in this insulation test sample, indicating that mold appeared to be growing in the insulation, not simply accumulated there from another building mold reservoir.
[Click to enlarge any image]
Above: white "growth" found on the interior surface of fiberglass-lined HVAC ducts in a home in Atlanta, GA in 2016.
Look closely to see the presence of clear adhesive tape being used to collect a sample from this surface to permit laboratory analysis.
Samples from this fiberglass duct were examined in our InspectApedia.com forensic laboratory. Below: an example of lab test results included these:
Above first photo, sample 2, Aspergillus sp. conidiophore and hyphae at upper left, Penicillium conidiophore at lower right.
Below, second photo sample 2, Cladosporium sp. in dense fungal growth on the surface.
Details of this air duct mold contamination study are found
at FIBERGLASS AIR DUCT MOLD TEST
Just below is an individual Curvularia-like mold spore to the left of what is probably a fragment of gypsum or drywall material.
More subtle in this photo are individual Penicillium/Aspergillus mold spores.
Small and colorless these are harder to see unless the microscopist takes care and time.
The combination of these particles in a vacuum sample of fiberglass insulation suggests that this insulation became contaminated by airborne debris, perhaps during demolition of moldy drywall.
Below is a large hyphal fragment in fiberglass insulation; from this observation we can be confident that wet conditions and growing mold have been present in the building where this sample was collected.
The image does not mean that this fungus was necessarily growing in or on the fiberglass itself. As we said in our introduction, a few isolated spores in insulation are insignificant. All mold is everywhere, all the time - at low levels.
But when we find large hyphal fragments in any indoor environmental sample we know that most-likely there is or was significant nearby mold growth in or on the building.
Below are multiple Stachybotrys chartarum mold spores in a fiberglass insulation sample nd in the background I see some colorless Pen/Asp spores as well.
This sample strongly suggests that there has been demolition of moldy materials, probably drywall, in the area where this fiberglass was exposed.
There is no evidence that these fungi are growing on or in this particular insulation sample.
Any thick fibrous material can collect airborne particles and can be difficult or impossible to clean completely. This mold-contaminated fiberglass insulation should be discarded.
Below my photo illustrates a short three-spore chain of Penicillium or Aspergillus mold spores.
These fungal contaminants are a particular concern because their small size (often in the 1u range) means they can be inhaled deeply into the lungs.
High exposure levels, or repeated exposure to high levels of this type of airborne mold can cause serious illness such as Aspergillosis.
See ASPERGILLOSIS for details.
Watch out: Because these spore chains are very fragile and break into individual spores quickly when airborne, when we find a spore chain of Penicillium or Aspergillus mold in an environmental sample I am confident that there has been or is currently nearby active growth of one or both of these mold genera/species.
I have on occasion found actual Penicillium or Aspergillus mold conidiophores growing in fiberglass insulation (as well as on or in a very large number of other building materials).
These mold contamination problems occur in buildings that have been wet, flooded, or occasionally subject to very high humidity.
For buildings which do not have other known mold reservoirs, special attention needs to be given to inspecting and testing for problematic mold in
What can be tricky in investigations of mold contamination in building insulation is that severely mold-contaminated fiberglass insulation may look pretty clean to the naked eye.
Special vacuum and agitation methods are needed to sample and test this material and special care is needed in choosing the sample or test location when looking for mold in fiberglass or other building insulation.
The left photo above shows clean fiberglass insulation fragments (taken from a sample of new fiberglass building insulation).
The right photo of a sample collected from fiberglass insulation in an older building exposed to moisture and leaks shows a high level of particulate debris, almost certainly including organic debris such as skin cells, animal hair, and insect fragments which can form a base for mold growth.
See details at FIBER & HAIR IDENTIFICATION
Watch out: not all stained or dirty-looking fiberglass is moldy or even contaminated.
A very common source of black, gray or tan "stains" on building fiberglass is air bypass leaks that deposit ordinary house dust or building dust on or in the insulation as air passes over or through the material.
This is not mold contamination and this fiberglass insulation - shown in our photo - does not need to be removed. Rather it makes sense to find and fix those air bypass leaks.
See for details INSULATION STAINS - AIR BYPASS LEAKS
Keep in mind that the air bypass stains as well as mold, insect fragments or other contaminants described in this article can also be found on or in many building materials and in porous materials may be difficult or impossible to clean economically.
Also see MOLD APPEARANCE - STUFF THAT IS NOT MOLD
Details of this topic are now
at WHEN to TEST INSULATION for MOLD
We do not recommend routine mold testing of building fiberglass for mold
in non-suspect cases. "Spot checks" by "mold testing" in buildings, if conducted without an expert diagnostic visual inspection and history gathering, are simply not reliable and thus not cost-justified.
We also do not recommend mold-testing of fiberglass or other building insulation that is visibly moldy
(such as mold growth on kraft paper facings) nor of building insulation that has been wet. Such testing is not necessary and would not change the advice given by experts: Such insulation areas should be treated as follows:
See ATTIC MOISTURE or MOLD SOURCES for a discussion of common sources of moisture in attics that can cause moldy insulation, and similarly,
See BASEMENT LEAKS, INSPECT FOR for the same problem in basements.
Readers ducting cool air through a crawl space or who have damp or wet crawl spaces under their building should
Below you will find questions and answers previously posted on this page at its page bottom reader comment box.
(July 28, 2014) Bill B said:
We are searching for an answer to gray spots that have appeared on the inside surface of our cathedral ceiling. It has fiberglass insulation between the sheetrock and the shingled roof.
The house and ceiling is 40 years old These spots started appearing two years ago and are slowly increasing in size.
They only appear on the western side leaving the eastern side completely clear. There is an outside ridge vent on the roof and vents in the eves.
The summer they were first noticed was a drought year here in Nebraska so not much moisture was present for quite some time. Any guidance on what this could be, who to contact, or advise is greatly appreciated. Thank you.
Bill I suspect you're describing thermal tracking where ceiling drywall nails or screws are placed, not mold contamination.
Take a look at
inspectapedia.com/interiors/Thermal_Tracking.php
(Jan 2, 2015) danebendixen said:
I recently discovered a mold problem in my attic (blown in yellow fiberglass insulation) due to an old roof leak from before I bought the house and remediated a small area (just a few square feet).
While I was in the attic, I noticed other areas with no evidence of leakage, but where the yellow fiberglass was a gray-brown color and in some places, closer to the bottom of the pile, it was very dark, almost black.
I'm not sure if this is mold or simply accumulation of dirt over time (house is 36 years old). There was also evidence of rodents (mice) in at least a couple places, but no evidence that they are currently present. Two questions-
-1) Are the darker areas in the fiberglass likely mold, and if so, do I need to remove all the insulation in the attic?
2) Would a past rodent infestation be a possible cause of mold?
Dan
Often we see gray-to-black deposits on fiberglass insulation where there are air bypass leaks that deposit house dust - that's not mold. But any insulation that was wet should be replaced.
See this article on air bypass leak stains on insulation
inspectapedia.com/interiors/Stains_on_Insulation.php
Rodents in mold leave urine and fecal contamination - another reason to replace any such infested insulating materials.
Other insulation that has not been wet, is not mouse infested, can be left in place. Where insulation is marked by air-bypass leakage alone (no water nor rodents) it can be left in place but I'd give some attention to finding and fixing the air leaks.
Research on Fiberglass Fragments as an Indoor Air Quality & Health Concern and a summary of indoor fiberglass hazards are
On 2017-03-23 by (mod) - making sense of "we got sick after the attic was insulated"
Linda,
I can understand that a qualified professional would be reluctant to take on a complex contentious mess pro-bono.
But there should have been some simple steps that could sort out some of the concerns you describe.
1. You say "tests were performed' - simple particle collection (search InspectApedia.com for DUST SAMPLE METHOD ) can provide representative samples that any forensic lab could use to identify the dominant particles in the building's settled dust and probably the "black specks" you describe. Knowing what particles are can usually point to their source.
2. A visual inspection of the insulation job work area as well as a review of just what was done would also be instructive.
I would not assume a thing about what came contaminated before knowing what the material is. For example someone could have inadvertently damaged an HVAC duct, or roof debris from a re-roof job could have gotten into an HVAC air return, or insulation could have been blown-in improperly - I can't sort that out from your note.
You need an onsite expert who will sort through the visual data, historical data, complaint data, and perhaps help you collect a very few samples for diagnostic testing.
"Air tests" if that's what was done, are unreliable as we discuss in an article series here at Inspectapedia.
The wise lady from Philadelphia says let's find out what's in the home that's suspected of bothering you, and let's get your doctor to comment on the possible relationship between your illness complaints and anything that could be in the environments where you spend a lot of time.
On 2017-03-23 by Linda Benson - sick after insulating the attic
We just had the attic insulated after they left we started having serious problems with stuff falling from the vents and health issues we are still having. The entire home has been infected by these black specks.The bathroom where we shower has been affected with it all over the walls.
While I was getting a cup from the kitchen cabinet the vent over head blew in the black dots. I then put a cup that had not completely dry away on top of it not knowing .
Within just a week I began to notice that the wood was decaying. I didn't know at the time what it was so I began to clean it off. My head was inside the area where i was exposed to the airborne particles.
I became very sick during this time trying to clean up whatever was happening at this time. I didn't know until almost 3 months when I happen to see it coming from the vents in all the rooms. It is impossible for us to clean the house from this exposure. Our Insurance company refuses to cover damages. The company who installed it has refused to fix it. I have test results on the insulation and the entire home.
We also have photos plus test results from the infections we have had over the past year since it was installed. I am at a total loss on what to do about this. I have called the EPA, Center for Disease , Board of Health, Environmental toxins, From local state and federal government all have given me the run around. I am in bed most of the time now it is very difficult to make these phone calls.
Unless someone is being paid for their service they don't want to be involved. We have had quotes up to $20-30 thousand dollars. We don't have that kind of money . We have been told to move it's not that easy we only have each other and no other place to go.
We just purchased this home in 2014 the infection happened in 2016. Could this insulation have come from the factory contaminated? Or could this be insulation from some other place where they thought it was safe. I am not sure of much these days. I know for a fact it was not happening before they installed the insulation.
On 2017-02-04 by Gail
Can new insulation be contaminated! We put in our new house we are building and some of it has started to turn black and melt. Is this normal
On 2016-07-23 by (mod) - Johns Manville green insulation with some black mold
Pat
Remove insulation that has been wet as well as visibly-moldy materials;
Physically clean the exposed building cavity;
Then if you want to add a fungicidal spray (search InspectApedia for FUNGICIDAL SPRAY for details) that's fine.
I don't recommend using spraying as a substitute for cleaning as you risk leaving toxic or harmful particles in place even if the spray rendered them non-viable.
On 2016-07-23 by Pat
I have Johns Manville green insulation with some black mold at bottom in bathroom walls for at least 60 years. Is replacing the black insulation and spraying sufficient to resolve this?
On 2015-11-18 by (mod) - man came and said mold and fiberglass insulation is causing this
What man? What is his expertise? Where and what did he see?
Causing what illness? What does your doctor say?
If your building has a large mold reservoir professional action is required.
On 2015-11-18 by dawn
My family has gone to the doctors for the past 3 months.we are coughing, stuffy, joint pain. The man came and said mold and fiberglass insulation is causing this?
On 2013-03-21 by Anonymous - If pink fiberglass is soaking wet
Anon,
If pink fiberglass is soaking wet, I do observe that its color appears darker - but the color change is the least of one's concerns at that point.
Dan L:
Missing insulation means higher energy cost, colder floors, less comfort, and possibly condensation that aggravates mold problems. However putting fiberglass insulation under a floor over a wet crawl space or basement is not a good idea - it risks forming a new mold reservoir.
The solution is to dry out the areas below the floor first, inspect and clean moldy surfaces there, install moisture-resistant insulation such as solid foam, and if it's a crawl space, convert it to a dry, conditioned space.
On 2013-03-21 by Anonymous
I have pink bat insulation in basement In some places the insulation has become a bright pink is this due to water damage?
On 2013-02-09 y Dan .L
Second part to my last comment. Is my mold caused by lack of insulation in my basement?
I live in NW Oregon, and its cold and wet most of the time. My problem is, the last person that lived in my house removed the insulation in the basement ceiling (house floor) which are hardwood. Im getting allot of mold and puddles of water along the walls and floor. It's so bad that in one week we have to clean at least 3 times
On 2012-11-13 by TA
Black stuff on insulation in attic where we had major snow & water damage, it was raining through the light & alarm fixtures. They said they clean it out but they only shoveled out the snow nothing else.
also dust covering the inside of condo, almost pulled out rock quarry in dust & rust. looking inside there appears to be cement corrosive rust & large white looking weird mold looking organisms.
Raw sewage leaks & not proper clean u 2 times in common hallway.
In a nut shell all occupants of our building seem to be very sick including out cat. What can we do to find out if there is mold & toxic dust. Also what is supposed to be proper clean-up efforts for raw sewage leaks involving carpeting? PLEASE or child is very sick as are the rest of us experiencing major issues. THANKS SO MUCH!
On 2012-03-29 by mary sant
We had a huge hail storm over three months ago, large hail stones bigger than golf balls damaged many roof tiles so our roof was flooded and insulation was saturated. After agreeing that the insulation has to be replaced our insurance company now says its dry and they wont replace it.
We have been told that it will eventually get mouldy and dangerous. We are very worried and upset that the insurance company is reneging on what they said they would do.
On 2012-01-14 by PD
I have cut out holes in my drywall with no visible evidence of mold growth. The insulation is also dry. Am I safe to assume that there is no mold growth?
On 2011-12-20 by (mod) - foil-faced fiberglass ductwork is not an innate health hazard
Joseph,
In my OPINION, no, foil-faced fiberglass ductwork is not an innate health hazard as long as it is in good condition. The material typically is more dense than fiberglass insulation batts, and is covered on outside with reinforced aluminum foil and on the inside the material is typically coated with a binder to avoid significant fiberglass fiber release.
However if the ducts are mechanically damaged by aggressive cleaning attempts, the interior binder can become damaged and the result is not only an increased particle and debris release into building air circulating through the ducts, but also possibly an increased rate of accumulation of other airborne debris that cannot be effectively removed or cleaned.
And any HVAC ductwork system, if flooded or wet, can become a problem mold or pathogen reservoir.
On 2011-12-19 by joseph dorsett
is ductwork made from insulation (foil on outside) a hazard to your health, with the exception of a mold condition?
On 2011-10-13 by (mod) - about moldy insulation in the air handler
And about moldy insulation in the air handler, or elsewhere, since it's virtually impossible to clean that material, proper procedure is to remove it, clean the exposed surfaces, and install new proper type of insulation. This is the case whether we're discussing the air handler internals or a wet moldy wall cavity.
On 2011-10-13 by (mod) - can a dirty filter cause a crack in the evaporator pan
Cynthia:
re: "can a dirty filter -- in this case, 6 months old -- cause a crack in the evaporator pan as well as cause the debris found there."
No, not at all likely.
A dirty filter might slow air across the cooling coil, lead to an icing problem, loss of cooling, and even leaks when the ice melted off later. But it would not cause a crack in the condensate tray.
On 2011-10-11 by Cynthia C.
Glad to!!! Well, I just submitted a question/comment for a response in the section re: Dirty Air Conditioner Filters section and this comment is related. Here is my comment from the other section:
"Renting a year-old 'manufactured' home (1 of 8) that was left standing w/the roofs exposed for approximately 2 years to 'the elements', including horrendous rainstorms;
I changed the air filter once within 11 months -- HVAC unit, condenser, evaporator, etc. -- housed indoors within a closet. What developed was a huge problem of mold infestation in and outside the closet area where the HVAC unit is housed, accompanied with lots of water on the floor of the closet housing the unit.
The 'landlord' came out, looked at the damage, in and around the closet housing the unit, removed the filter without me seeing him do so, returned inside the house and told me the damage was caused because I hadn't changed the filter -- which he refused to show me.
Anyway, that same day I called out an HVAC guy who's been in the business for 30 years, who did a thorough inspection and found, among other things, a crack in the evaporator pan as well as insulation debris and some kind of cork debris inside the evaporator!!! He opined that the (substantial) leak was either caused by the crack in the pan or a drain blockage . . .
after all of that, my question is can a dirty filter -- in this case, 6 months old -- cause a crack in the evaporator pan as well as cause the debris found there."
And my comment here, regarding "Mold in Fiberglass" is that the fiberglass insulation that was on the floor of the closet housing the HVAC unit was totally covered with 'black' mold. I called in a mold inspector,
had a mold report done and there were 810,000 Pen/Asp spores per cubic meter, 820,000 Alternaria and 1.3 million Monodictys spores indoors, in the area that houses the HVAC unit . . . Are those high spore amounts? Thanx, Cynthia C.
...
Continue reading at WHEN to TEST INSULATION for MOLD, advice about when where how and why to test building insulation for mold contamination., or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
FIBERGLASS INSULATION MOLD at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
Our Comment Box is provided by Countable Web Productions countable.ca
In addition to any citations in the article above, a full list is available on request.