Stairway chair lifts:
This article describes electric chair lifts used to move between building floors by riding on a chair operated by controls on the chair arm or on the building wall.
Here we also define and describe platform lifts used for wheelchairs and similar roll-on aids, and we explain the differences between a stairway chair lift and a platform lift that might move along an incline or might move vertically between building floors.
We include inclined stairway lift standard and building code citations and also a listing of sources for stairway chair lifts in Australia, North America, The U.K., and New Zealand.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
Shown at page top is a chair lift installed along an inclined stairway in a St. Weonards farmhouse in Herefordshire, England. The first stair lift has been attributed to King Henry VIII who used a block and tackle (and servants) to move between floors.
Modern electric stair lifts or chairlifts were designed in the U.S. in the 1920's by C.C. Crispen who wanted to build a chair to assist a friend to travel between floors. [1]
At left is a remote-controlled electric stair climbing chair illustrated by Wikipedia. Typically the chair's arms are hinged to ease entry and exit.
[Click to enlarge any image]
On modern stair carriages or chair lifts, the chair or carriage provides a seat for the user who can operate the chair lift by carriage-arm mounted controls.
The chair carriage ascends or descends the stairway along a rail that is wall or stair surface mounted. Additional controls can summons the chair between building floors.
The chair lift we illustrate at page top above rides on a single railing attached to the building stairway wall and supported further on stair treads affixed along one side of the stairway.
That chair lift makes a turn around an intermediate stairway platform in its ascent to the top floor of the Herefordshire farmhouse where it is installed.
Other stairway chair lifts may ride on a rail or rails set across the nosing of stair treads - an option that can permit installation of a chair lift when walls or guardrails are not of sufficient strength to carry the electric chair mechanism.
Reader Question: 10 Feb 2015 Do exterior concrete stairs leading to two terraces apartments have to be a certain width? One owner wishes to put in chairlift up side of staircase railing. Stairs are 84cm wide. said:
Do exterior concrete stairs leading to two terraces apartments have to be a certain width? One owner wishes to put in chairlift up side of staircase railing. Stairs are 84cm wide.
Reply:
Stairway width (in the U.S. - you don't say where you are located) should be equal to or greater than 36" of clear unobstructed distance measured at all points above the [permitted] hand-railing height.
Your "84 cm stair width", assuming that's the unobstructed width, is 33" or already 3" less than the 36" recommended.
For an example building code pertaining to chair lifts and wheelchair lifts I look at ASME A18.1- 2003, Safety Standard for Platform and Stairway Chairlifts.
This is a very extensive document (cited in detail below) that goes into detail concerning recommended safety features and controls for chair lifts or stairway chairlifts along stairs such as our example illustrated above.
Also see California's Subchapter 6. Elevator Safety Orders Group 2. Existing Elevator Installations, Article 15. (a) Inclined stairway chairlifts shall comply with ASME A17.1-1993, Section 2002, Inclined Stairway Chairlifts, which is hereby incorporated by reference, except Rule 2002.10a and Rule 2002.10c(2).
NOTE: The installation of all inclined stairway chairlifts are subject to local building codes, fire regulations, and contractors licensure.
(Title 24, Part 7, Section 7-3094.4)
NOTE: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code; and Section 18943(b), Health and Safety Code.
In my OPINION the standards and model codes give some leeway to the LOCAL building code official (who's final word is law) to accept a narrowing of the stairway to provide for the inclined stairway lift installation, provided that means of egress for walking residents is not unduly hampered. From the ASME standard I excerpt: "Lifts shall be installed so that means of egress is maintained as required by the authority having jurisdiction. "
Different rules may pertain for private residences than public buildings.
Watch out: depending on where you live, a building permit may be required to install a stairway lift; The U.S. states listed below require that residential stair lift installers be licensed.
AL, AR, CA, CO, CT, DC, GA, HI, KY, MA, MI, MN, MT, NV, OK, OR, VA, WA, WV, WI
The U.S. states below require licensing for commercial stair lift installations:
AL, AK, AR, CA, CO, CT, DE, DC, FL, GA, HI, ID, IL, IN, IA, KY, ME, MD, MA, MI, MN, MS, MO, MT, NE, NV, NH, NC, OK, OR, RI, TN, UT, VT, VA, WA, WV, WI, WY
Thanks to Spinlife-Harmar (cited below) for these state licensing lists.
2017/05/15 Susan Z. said:
What is the minimum stair width allowable for a chair lift to meet fire rescue needs for emergencies.
It's easy to get confused about this topic since there are fire code specifications for wheelchair lifts, also referred to as platform lifts - those may NOT be the same as the stair lifts described in our article above, but rather are an elevator type lift for wheelchair users.
A short answer that's pretty safe is modeled on the U.S. Wisconsin Code:
SPS 362.1009 Stairway width. This is a department rule in addition to the requirements in IBC section 1009.1: Where installing an inclined platform lift or stairway chairlift, the clear− passage width shall be provided with the lift in the unfolded, usable position
But we provide quite a bit more detail below.
Also, see MEANS of EGRESS and also STAIRWAY CHAIRLIFTS codes and guidelines among the stairway chair lift references cited above and excerpted below.
Some confusion can arise where a wheelchair lift moves not vertically (an elevator design) but along an inclined railway along stairs.
The two forms of platform lift shown above are excerpted from the United States Access Board "Chapter 4: Elevators and Platform Lifts" cited in the references earlier in this article.
You can see that both of these devices are designed to accommodate a roll-on wheeled aid - different from the stairway lift devices illustrated earlier on this page.
For an example of stairway lift regulations we can refer to the Wisconsin code in the U.S. f:
A stairway chairlift is a powered hoisting or lowering mechanism that is guided and equipped with a seat to transport a passenger along a stairway. SPS 318.1004(10)(o).
A stairway chair lift has a seat for a rider, two armrests and a footrest. A stairway chair lift has controls at each landing to call the chair to that landing and up and down controls on the chair for the rider.
A stairway chairlift is not an inclined platform lift. An inclined platform lift is similar to a stairway chairlift in that an inclined platform lift may also be located in a stairway, and is also subject to the stairway width requirements described herein.
Unlike a stairway chairlift. an inclined platform lift has a horizontal platform (folding or stationary) for a rider who may be standing or in a wheelchair. An inclined platform lift may have a fold-down seat in addition to the horizontal platform.
In Wisconsin (as our example) residential stairway lifts are excluded from regulation regarding widths of stairway for fire exit safety.
A stairway chairlift may be installed to serve an individual dwelling unit in a one- or two-family building without regulation by the DSPS elevator safety program, however local permits and inspections may be required.
Note: This also applies to bed and breakfast (B&B) establishments, adult family homes (AFH), community based residential facilities (CBRF) and residential care apartment complexes (RCAC) that are regulated as single family dwellings. A stairway chairlift may be installed entirely within an individual dwelling unit in a larger multifamily and inspections may be required.
A typical apartment or condominium building containing more than two dwellings is considered an R-2 commercial occupancy. Common areas in such a building that may be accessed by two or more dwellings (therefore not limited to one individual dwelling unit) are considered commercial spaces, not part of a single dwelling.
Commercial building code requirements apply to such common areas. Stairway chairlifts installed in common stairways are regulated by the DSPS elevator safety program.
Note: The Petition for Variance process may allow reduction in the width of a shared stairway in such a building where the stairway serves not more than two dwellings above the ground floor.
A petition for variance form must be completed. The residents of the two upper dwellings and the owner of the common area (landlord or condominium association) must provide written statements agreeing to the installation of the lift.
The local fire department must provide a signed position statement on the petition for variance application form. Additional requirements may apply as part of granting a petition for variance.
In the U.S. the ADA Standard (§207.2) requires that platform lifts, where permitted on an accessible means of egress, must have standby power.
Where Platform Lifts are Permitted [§206.7]
Platform lifts can be part of an accessible route in existing facilities that are altered. In new construction, platform lifts can be used to provide an accessible route to these areas only:
They also are permitted in new construction where topography or other existing exterior site constraints make a ramp or elevator infeasible.
While the site constraint must reflect exterior conditions, the lift can be installed in the interior of a building. For example, an exterior or interior platform lift could be used to provide an accessible entrance or to coordinate interior floor levels at a new building constructed between and connected to two existing buildings if there is not sufficient space to coordinate floor levels and also to provide ramped entry from the public way.
Also, you can see how a solution to adequate stairway width (for fire egress) can be provided by a folding platform design:
Platform lifts must meet the ASME A18.1 Safety Standard for Platform Lifts and Stairway Chairlifts. The ASME A18.1 covers the design, construction, installation, operation, inspection, testing, maintenance and repair of lifts that are intended for transportation of persons with disabilities.
Inclined platform lifts can have a folding platform and are typically located at stairways. They must be installed so they do not encroach on required means of egress. Passenger retaining arms are permitted as an alternative to a platform enclosure under the ASME A18.1 Standard.
Using as a model building code the ICBO, I excerpt:
1007.5 Platform lifts. Platform (wheelchair) lifts shall not serve as part of an accessible means of egress, except where allowed as part of a required accessible route in Section 1109.7, Items 1 through 9 of the International Building Code. Standby power shall be provided in accordance with Section 604.2.6 for platform lifts permitted to serve as part of a means of egress.
1007.5.1 Openness. Platform lifts on an accessible means of egress shall not be installed in a fully enclosed or fire rated shaft.
Thank you for asking
Above: the Acorn 130 straight stairlift. [Click to enlarge any image]
Above - AmeriGlide stair lift.
Below: the Bruno Elan Stair Lift cited just below, shown here in its "folded" position.
Above: Harmar Access Stairlift model SL350AC specifications excerpted from the documents cited below.
[In Process; we are adding to this data; contributions are welcome. Use the page top or bottom CONTACT link]
Watch out: when shopping for a stair lift, and asking prices from stairlift manufacturers, dealers, installers: there is considerable variation in transparency in quoting prices, and a risk of a sort of bait-and-switch tactic among some of these brands and their installers. The product quality and installation may be fine but the installed price may be a surprise.
The average installed-cost for a stairlift is $8,000, with installed prices ranging between $3,000 and $20,000 with curved and outdoor stairlifts at the higher end of that range.
Stair Lift Specifications: weight capacity, track, footprint |
|||||||||
Brand / Model |
Capacity Lbs 2 |
Track Length | Track Size | Unit Footprint 1 | Rail Angle | ||||
Std | Opt | Width |
Foot- |
In Use |
Parked | Min | Max | ||
Acorn 130 Stair Lift 3 | 280 - 350 lbs 127 kg |
22.5" | 12.25" | ||||||
AmeriGlide / Horizon Standard 4 | 300 lbs | 80.4" | + 63" ? | 24.8" | 13.5" | 25° | 55° | ||
AmeriGlide / Rave 2 5 | 350 lbs | 15.5 ft |
70 ft | 4.875" | 7"1 | 22.5" | 11" | ||
Bruno Elan straight | Vertical 5" frm Wall |
||||||||
Bruno Elite curved | 450 lbs | ||||||||
Harmar SLC350 | 350 lbs 159 kg |
16 ft 4.9 m |
14" 35.6 cm |
||||||
Handicare 950 straight | 310 lbs | ||||||||
Savaria straight | 350 lbs | ||||||||
Spinlife (Harmar) | 350 lbs | ||||||||
Stannah | 300 lbs |
Most of these companies offer multiple stair lift models and within each model there may be multiple features and accessories among which to choose. Models vary by straight vs. curved stair cases and by indoor or outdoor use.
Most tracks are extruded aluminum.
Stair Lift Specifications: speed, seat features, dimensions |
||||||||||
Brand / Model |
Speed | Seat | ||||||||
Width | Depth | Height | Back | Bet. Arms |
Seat Swivel |
Seat Flip-up |
Arm Rests Flip-up |
Lap Belt |
||
Acorn Stair Lift 2 | 4.8"/sec 24 fpm |
23.25 (overall) |
16" | 17.25 | Y | |||||
AmeriGlide Horizon Standard 3 | 22 1/4" | 16" w | ? | Manual | Y | Y | Y | |||
AmeriGlide / Rave 2 4 | 19 1/2" | Y | Y | Y | ||||||
Bruno Elan | 15 3/4" 391mm |
16 3/4" 416mm |
20 1/4" 514 mm |
Power available |
||||||
Bruno Elite curved | Power available |
|||||||||
Harmar SLC350 | 20 fpm | Y | ||||||||
Handicare | ||||||||||
Savaria straight | ||||||||||
Spinlife (Harmar) Summit | ||||||||||
Stannah |
Stair Lift Specifications: height footrest, controls, power |
|||||||||
Brand / Model | Unit |
Footrest | Footrest Safety Sensor |
Constant Pressure Control |
Control | Key Lock |
Call Stations |
Diagnostic Display |
Power 1 |
Acorn Stair Lift | 38.5" | 12 1/4" W | 24VDC Battery |
||||||
AmeriGlide Horizon Standard | 35" | Y | Y | Armrest Switch |
Y | Optional | Y | Battery | |
AmeriGlide / Rave 2 | Y | Y | Armrest Switch |
N | Wireless | N | Battery |
||
Bruno Elan | 10 1/2 L x 11 W 267 x 279 mm |
Armrest |
Wireless | ||||||
Harmar SLC350 | Power folding available |
||||||||
Handicare | |||||||||
Savaria straight | |||||||||
Spinlife | |||||||||
Stannah |
Stair Lift Costs Table |
|||||
Brand | Attach to |
Price New / Used |
Install |
Self Install |
Drive |
Acorn Stair Lift | Stairs | $2,500 to $5,500 straight 1 |
Y | Rack & Pinon |
|
AmeriGlide Horizon Standard 1 | $1,700 to $8,100 $1,300 used |
N | Y | Rack & Pinon |
|
AmeriGlide / Rave 2 | Stairs | $2,000 | N | Y | Polymer Worm |
Bruno Elan straight 3050 | Stairs 5 | $3,000 / $1,500 $4,000 installed |
N | Y | |
Bruno Elite curved | Stairs | $10,500 | |||
Harmar SLC350AC | Stairs | $2,300 - $3,500 | Cable | ||
Handicare 950 / 2000 | $2,500 / $6,200 4 | ||||
Savaria straight / curved | $2,750 / $8,800 | ||||
Spinlife (Harmar) Summit indoor | $2,300 | ||||
Stannah straight / curved | $3,000 / $12,000 & up |
Examples include:
For some people a home elevator may be a useful alternative to a stair / chair lift. Some home lifts such as the Trio Alta from Stiltz can accomodate a wheelchair.
Also of interest
Below you will find questions and answers previously posted on this page at its page bottom reader comment box.
@Barbara Wolford,
The requirement for elevator and chair lift safety inspections vary by jurisdiction (terms vary by country).
Looking at the Virginia codes we could not find an explicit requrement for chair-lift inspections, nor is there such a requirement in the Maryland code that I first found on this topic. You should ask your local building department for clarification.
The choice of using an independent "witness" to elevator inspections appears to be in the hands of the local authorities and of the inspection company itself; the witness, as we explain in more detail below, is there to assure an independent confirmation that the proper tests and inspections have been made: a step asserted to reduce the liability for both those performing these safety inspections and for the elevator or stair lift or escalator users, as well as for the property owner. Yes you might decide to eschew that extra level of certification if your local authorities so permit.
In general, in Virginia, elevators are inspected every six months [this may vary by local municipal authority] and are tested (this is a more thorough step than visual inspection) every one, three, or five years depending on the type of elevator equipment installed.
In Virginia the building owner is required to use an approved elevator inspector who in turn, provides an elevator ( or chair lift, etc) report to the local municipal authority. Below is an excerpt from the pertinent Virginia Building Code, Title 35, Housing, Chapter 6, Article 1, General Provisions,
§ 36-105.01. Elevator inspections by contract.
The inspection of elevators in existing buildings and the enforcement of the Building Code for elevators shall be in compliance with the regulations adopted by the Board.
The building department may also provide for such inspection by an approved agency or through agreement with other local certified elevator inspectors.
An approved agency includes any individual, partnership or corporation who has met the certification requirements established by the Board.
The Board shall establish such qualifications and procedures as it deems necessary to certify an approved agency. Such qualifications and procedures shall be based upon nationally accepted standards.
1994, c. 574; 1999, cc. 333, 341.
The chapters of the acts of assembly referenced in the historical citation at the end of this section may not constitute a comprehensive list of such chapters and may exclude chapters whose provisions have expired.
Virginia's building code effective in 2021 is not currently made available free to the public (as in my OPINION it ought to be if the state wants to make compliance easy), but you can purchase a copy of the Virginia building code at
For additional information for Frederick County VIRGINIA contact:
For other readers: here's another Frederick County in the U.S. -
Special thanks to R. Kaese Dillman, Chief Elevator Inspector for Maryland, for a rapid, clear, and courteous reply to our request for clarification on the Maryland law on this point. Excepting from that correspondence:
Mr. Friedman, the question that Mrs. Wolford posted appears to be for Frederick County Virginia, not Frederick County Maryland.
She also states that she is paying $200 a month for a chairlift inspection. There is no requirement for a monthly inspection on a chairlift per the A18.1 code.
As far as Maryland law and regulations are concerned, you already have the link in your email to our website which has a copy of the law and regulations posted.
In a nutshell the current law requires an annual inspection and an annual test and this has been law for many years
. What the new law requires effective 10/1/21 in privately owned buildings is that the inspection and test be performed at the same time. The inspector is required to witness the test just as he/she would do every 5 years under the current law.
There is no official witness other than the inspector.
The new law does not add any extra tests or inspections and actually can save the owner money. Since the inspector is there with the elevator/lift company, if they find something wrong it can be addressed on the spot.
In the past the unit would fail then the owner would have to hire the elevator/lift company to come back out and fix the problem then hire the inspector to come back out and re-inspect the unit. If there is anything I can assist you with please let me know. - Private email Dillman to Friedman 2021/07/12
According to Maryland's elevator safety law and the state experts,
"Currently, annual testing may be “verified” by an authorized/registered TPQEI through documentation during an onsite inspection. Witnessing of the annual test is currently an option in Maryland for privately owned elevator units, depending on the facility owner’s choice, or the authorized/registered TPQEI’s business practice."
See
and important:
For additional information for readers in Frederick County MARYLAND, contact:
Maryland also provides this
List of approved Third Party Inspector Companies: https://www.dllr.state.md.us/labor/safety/elev/qeiagencies.pdf
Also, if you have not already seen Maryland's Elevator / Lift inspection form take a look at the document at
https://www.dllr.state.md.us/forms/elevtestformlifts.pdf
where on the form bottom we note these signature lines:
Name of Testing Company: ____________________________________________ Date: _________________
Mechanic Signature: __________________________________________________ License #: _______________ Printed Name: ___________________________________
Inspector Signature: ________________________________________ QEI #: _________Date: __________ Printed Name:________________________________________
Continuing:
In searching to understand the need for a witness to elevator and escalator inspections - not finding that in Maryland's documents, we cite this explanatory document from New York State, where an independent witness to the safety inspection is required by law rather than optional (as in your state).
Excerpt: What is the Reason for an Independent Expert Witness to Elevator Safety Inspections?
Quoting:
Per the NYC Department of Buildings, only third-party agencies that are licensed by them are permitted to witness annual safety tests.
Aside from Elevator Test Witnessing Being Legally Mandated, What Are the Major
Benefits to You [of having an independent, certified expert witness to an elevator, escalator, or chair lift inspection] ?
Test witnessing helps you best comply with federal, state and local jurisdictions
New and more rigorous annual elevator inspections attended by independent witnesses are detecting about 50 percent more violations in New York City.
Test witnessing helps you satisfy requirements of insurance carriers and protects your assets
As a building owner or manager, you bear the responsibility under the law for hiring a competent and approved elevator inspection agency to perform elevator and escalator tests. By hiring an unaffiliated third-party agency to witness the inspection, you provide yourself with the extra assurance that you have met the requirements of the law, resulting in your insurance not becoming nullified by negligence.
Test witnessing can minimize your liability by ensuring the safety of elevator and escalator users
When performing an annual test, we subject Elevators and escalators to extreme conditions not typically encountered under normal operation. We do this to bring out any possible adverse situation that can cause the verticals to fail. Acting proactively in this manner helps us spot small issues before they become large ones, keeping all users safe.
- original source:
On 2021-07-09 by Barbara Wolford - inspection requirements for chair lifts in a Maryland church
We have 2 chairlifts in our church. We have an inspection of these once per month at a charge of $200 per chair. Recently we received an additional charge from another company stating that the charge for for an additional inspection to watch the first inspection take place.
We were charge an additional $200 for a total of $600.
Called Frederick County va inspections and they stated that this was o.k.
I work for a doctor's office and we have an elevator for which inspection occurs monthly at a rate of $200 for one man.
Never had any addition person watching another person?
On 2019-10-15 - by (mod) -
BobOn 2019-10-15 by Bob
I live in an adult comunity on the 2fl. I share the 2fl with another person opposite my condo .recently this person got into an accident. She now wants to put an electric stairway chair on the stairs we share to to to our respective homes. Is this a fire hazard or even legal to install on this shared stairway?
4 July 2015 bonita said:
I am no longer able to walk down stairs with the standard drop.
How can I make my drop from step to step shorter?
This Q&A appeared originally at STAIR RISE & RUN CALCULATIONS.
Readers should also
Bonita:
When I'm no longer able to make it safely up and down stairs to my office I will probably install a chair lift -
see STAIRWAY CHAIR LIFTS - you are on this page -
The problem is this: you can indeed re-build a stairway to reduce the riser height but to do so the depth of each tread has to increase significantly too. That means that the entire run (horizontal length) of the stairway will get much longer than it is now, perhaps double.
In the inteiror of most homes, doubling the run of a stairway between floors would be horribly expensive - if it would fit at all, or making a long stairway that winds or turns - taking more room in other dimensions.
I suspect that the cost of a stair rebuild indoors would be much higher than the cost of adding a stair lift.
On 2019-10-04 by (mod) - special stairway chair lifts for narrow stairs
John
Apologies if this article was misleading: it's not "our" device.
InspectApedia is a research and publishing website; to protect reader trust we do not sell anything.
Chair lifts, when folded up or "parked", project into the stairway about a foot; but the actual projection depends on the specific brand and model.
For example the Horizon chair lift shown below has the following footprints or "projections" into the stairway:
Parked: 13.5"
In Use: 24.8"
Added remark:
For narrow stairways, some stair lift companies such as Bruno's Elite Stair Lift can provide a folding rail that compresses more-tightly against the wall when the lift is not in use.
On 2019-09-18 by john -how far does a stairway chair lift device extend into the width of the stairs when in an upright position
how far does your device extend into the width of the stairs when in an upright position, in other words, how far does a stair lift (rail lift) intrude into the clear width of the stair when in the upright stored position?
On 2019-07-22 by (mod) -
Grace,
You don't give country and city, so my best advice is to have the installer stop by or call your local building department to ask the permit procedure, fee, timing.
On 2019-07-22 by Grace
I am an Invalid .How can I get a permit to have a stairlift installed in the building stairway where I live.
It is a small building with 6 apts. Two on each floor. I am on the second floor. My landlord has agreed to have one installed for me in order to adhere to the accessibility laws in NYC.
How can I get a permit and hoe long will it take to get a permit for a stairlift in a commercial space?
On 2019-05-16 by (mod) -
Ted
This sounds worrisome - it's a question to take to your attorney who will ask much more specific questions and for more information than are in your note. Else one cannot guess. In general a buyer is normally expected to do their own pre-purchase inspections and due diligence, but NOTHING stops someone from suing you.
On 2019-05-11 by Ted Williams
Can a home owner be liable for selling a used stair chair lift if some installs it them self and they get hurt or worse or ii it caused a fire Because of faulty installation and not by a certified elevator company.
On 2017-12-05 by (mod) - Can a condo landlord deny a chairlift in her apartment?
Good question, Rosanne. I suspect the legal answer depends on
- where you live and thus what laws apply
- the question of what accessibility the landlord is obligated to provide may, depending on where you live, depend on the size of the home the number of dwelling units.
In general, excerpting from an explanation from one of the stair lift manufacturers: for homes in the U.S. where the ADA applies:
While stair lifts will not help your building become ADA compliant, platform lifts, also known as wheelchair lifts, will.
Section 4.11 of the ADA details the requirements for compliance when installing platform lifts in a commercial building.
If platform lifts are used at an entrance, they must facilitate unassisted entry, operation, and exit from the lift in compliance with 4.11.2. If you are planning to use platform lifts in your building, they must also meet several other requirements within the ADA, including the ASME A17.1 Safety Code for Elevators and Escalators.
Commercial buildings legally must follow ADA compliance requirements.
To avoid any legal issues, make sure that your building meets all the codes laid out by the legislation.
While stair lifts are not a good way to be compliant with the ADA, platform lifts are. Be sure your building, either being designed or altered, meets all of the ADA requirements. - retrieved 2017/12/04 original source: http://www.indystairlifts.com/
- the physical limitations of the dimensions of the stairwell: can a chairlift be fitted in
On 2017-12-05 by Rosanne
Can a condo landlord deny a chairlift in her apartment. I am handicapped by law.
On 2017-05-15 by (mod) - What is the minimum stair width allowable for a chair lift to meet fire rescue needs for emergencies.
Susan,
The answer is ... as Mark Cramer says ... It depends...
Generally the width of your residential stairway is set by your local, state, provincial building code. We give typical required stairway widths separately
at STAIR DIMENSIONS, WIDTH, HEIGHT https://inspectapedia.com/Stairs/Stair_Dimension_Specifications.php from which I excerpt:
Stairway width should be equal to or greater than 36" of clear unobstructed distance measured at all points above the [permitted] hand-railing height. This is the blue arrow in our photograph below.
Stairway width should also be equal to or greater than 36" of clear unobstructed space between the top of the handraill (the permitted handrailing height) and the required headroom clearance upper height.
For the effect on stairway width of adding a stairway chair lift, the impact on stair width requirement depends further on where you live and also how clearly we distinguish between a stairway chair lift and a vertical or inclined wheelchair lift or platform lift.
It also may depend on whether your stairway chair lift has a foldable seat.
This short answer is from Wisconsin's state code:
SPS 362.1009 Stairway width. This is a department rule in addition to the requirements in IBC section 1009.1: Where installing an inclined platform lift or stairway chairlift, the clear− passage width shall be provided with the lift in the unfolded, usable position
In the article above I have added a much more detailed reply to your question. Please give 24 hours (and purge your browser cache) to see the new information.
Daniel
On 2017-05-15 by Susan Z.
What is the minimum stair width allowable for a chair lift to meet fire rescue needs for emergencies.
...
Continue reading at STAIR DIMENSIONS, WIDTH, HEIGHT or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
STAIRWAY CHAIR LIFTS at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
Our Comment Box is provided by Countable Web Productions countable.ca
In addition to any citations in the article above, a full list is available on request.