Repairs to condensate leaks at ductless split-system air conditioners:
Diagnosis & repair of condensate leaks from a split system air conditioning system. This article explains the common causes of water found dripping from the indoor half of a split system air conditioner or heat pump unit and offers repair suggestions matched to the AC unit leak cause.
Condensate leaks from a wall mounted air conditioner can cause costly building damage including mold contamination of wall cavities or other building areas.
This article series describes split system air conditioning & heat pump systems.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
A split system or "ductless" air conditioning (or A/C & heat pump) system dispenses with duct work entirely, using a wall-mounted indoor evaporator/blower unit and a separate outside compressor/condenser (below left and right). In this split system air conditioning design, one compressor/condenser may serve multiple wall-mount indoor units.
Each of these indoor units must have a condensate drain that directs condensate, produced by cooling humid indoor air, to the outdoors.
Before it lost so much refrigerant that the split system air conditioner simply stopped cooling it had exhibited a different failure: condensate sometimes dripped out of the bottom of the unit into the occupied space where it was installed.
The white pipe in our photo at left is the outdoor termination of a condensate drain for the indoor wall-mounted half of a split system air conditioner.
We'd like all of the condensate produced by the air conditioner to empty at this point.
But sometimes instead we find condensate dripping from the indoor unit. At below left, the indoor AC unit periodically dripped water down the wall and into the room below.
At below we show the same unit with its cover on and then in a second photo the cover has been removed to permit inspection of the condensate drip tray, drain line opening, and perhaps to discover other causes of dripping water from the unit.
When a wall-mounted split system air conditioner drips water (actually air conditioner condensate) out onto the walls or floor below, there are the following most-likely causes, in order of probability:
Watch out: condensate leaks that you don't see but that occur inside of a wall cavity can lead to wet insulation, costly mold damage, and over a longer time, structural rot or insect infestation damage.
While the AirServ technician worked outside to add R-22 refrigerant at the compressor/condenser unit we removed the cover of the inside unit and promptly observed that the wall mounted unit was connected to its mounting bracket only at one end.
It was in fact hanging lopsided so that condensate in the drip tray flowed away from rather than towards the condensate drain.
It was no surprise that this unit dripped onto the floors below.
It was possible that the dripping was worse previously due to an iced-over coil as this unit also had now lost its refrigerant charge.
And to be sure that we were not also leaving a clogged refrigerant line unattended, we borrowed the service tech's (kindly-loaned) CO2 gun and adapter to blast-out the condensate drain's discharge tube.
See CONDENSATE DRAIN CLEAN & DE-CLOG for more options for clearing a clogged HVACR condensate drain line.
There we commented that while we have found this CO2 condensate drain blaster a very helpful tool that will sometimes send a condensate drain obstruction out through the condensate drain system, in working on split system air conditioners whose condensate drain opening is difficult to access you may find that you cannot get the rubber condensate drain line plug securely in place.
Watch out: don't go blasting condensate drain lines without warning your partner working outside lest you startle someone and cause an injury.
Below you will find questions and answers previously posted on this page at its page bottom reader comment box.
On 2021-01-19 - by (mod) - If the adjacent wall has water damage how should it be properly repaired?
Ann
The proper repair for an interior wall depends on the wall materials as well as the extent of damage. For example if water leaked into a drywall surfaced cavity there is risk of both rot and mold contamination as well as wet insulation, all of which justify at the very least an invasive inspection of the wall cavity to see if demolition is needed.
Moldy drywall is cut out, the exposed surfaces cleaned, and then the leak cause must be repaired before the wall is restored.
On 2021-01-19 by Ann Griffin
If the adjacent wall has water damage how should it be properly repaired?
On 2019-08-18 - by (mod) -
Sandy
Thanks for sharing your opinion of ductless (split system) A/C systems.
There are millions of split system A/C and heat pump systems installed; properly installed and maintained they are a very effective and successful product.
And if you are seeing condensate leaks from your air conditioner or heat pump, that is certainly not a problem confined to ductless or split systems.
For example see
CONDENSATE LEAKS
But I agree that if split system A/C is not properly installed you could have a condensate spillage problem.
On 2019-08-16 by Sandy
I would not have one of these ductless split air conditioners. I would have a puddle of water or more condensate on the wall, between the walls, and on
the floor in the room where it is installed. It could cause a real mess and do a lot of damage in my house.
On 2018-09-19 - by (mod) -
Scott
If the leak you are seeing is wet or water there are two common causes repair.
When is that the condensate drain from your unit has become clogged
The other is that the unit is not sloped properly on the wall in condensate in the tray is not flowing to the drain
Of course other possible causes but I'm giving you the two most likely
On 2018-09-18 by Scott
My mini split leaks down the wall from the back of the unit the only thing I can figure is where the line that goes through the wall warm air is coming in could this be the problem
On 2017-11-07 - by (mod) -
Ma,
I think you're talking about an air conditioning or heat pump system. An electrically-operated system like that is not burning a fossil fuel and would not be expected to be a soot source.
On 2017-11-06 by Ma
Will using a Mitsubishi air and Heating wall unit cause a sooty resude on items in your home when dirty
...
Continue reading at CONDENSATE DRAIN CLEAN & DE-CLOG or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
SPLIT SYSTEM AC CONDENSATE LEAK REPAIR at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Questions & answers or comments about split system air conditioner operation, installation, maintenance, & repair
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
Our Comment Box is provided by Countable Web Productions countable.ca
In addition to any citations in the article above, a full list is available on request.