InspectAPedia.com InspectAPedia®
 

Free Encyclopedia of Building & Environmental Inspection, Testing, Diagnosis, Repair

Ask a Question or Search InspectAPedia

  • HOME
  • AIR CONDITIONING
  • ELECTRICAL
  • EXTERIORS
  • HEATING
  • HOME INSPECTION
  • INTERIORS
  • PLUMBING
  • ROOFING
  • SEPTIC SYSTEMS
  • STRUCTURE
  • WATER SUPPLY
  • ENERGY SAVINGS
  • ENVIRONMENT
  • INDOOR AIR IAQ
  • INSULATION
  • MOLD INSPECT TEST REMOVE
  • NOISE
  • ODORS
  • SOLAR ENERGY
  • VENTILATION
  • EXPERTS DIRECTORY
  • CONTACT US


Mobile Phone/PDA website viewMobile View
CHIMNEY INSPECTION DIAGNOSIS REPAIR

Abandoned Chimneys - Indoor Inspection
  Abandoned Flue Openings
  List of Abandoned Chimney Hazards
Abandoned Chimneys: Outdoors
Angled Chimney Flues

ARCHITECTURE & BUILDING COMPONENT ID

Attic Chimney Inspection
  Holes in Masonry Chimneys
  Dark Stains on Chimney Surface
  White/Light Stains on Chimneys

Backdrafting Appliances

BAROMETRIC DAMPERS
Blocked Chimney Flues
Bracket Chimney Collapse & Fire Risks
B-Vent Chimneys
B-Vent Clearances Table

CARBON DIOXIDE - CO2
CARBON MONOXIDE - CO

CHIMNEY INSPECTION & REPAIR GUIDE

Chimney Cap & Crown Inspection
  Missing Chimney Rain Cap
  Damaged Masonry Chimney Cap or Crown
  Masonry Chimney Top Damage
  Separation of Chimney Flues - Chimney Top
  Soot at the Chimney Top
  UNLINED FLUE INSPECTIONS

Chimney Cleaning Advice, Procedures
Chimney Cleaning Fraud Warning
Chimney Cleanout Doors
  Chimney Cleanout Combustible Clearance
  Chimney Cleanouts Required
  ChimScan: Inspecting Flues by Cameras
  Masonry Fragments & Debris at the Cleanout
  Missing Chimney Cleanout Door

Chimney Components Definitions

Chimney Crack & Collapse Risks, Repairs
  Articles on Collapsing Chimneys
  Bracing for Masonry Chimneys
  Bracing for Masonry Chimneys, Lateral
  Bracing for Metal Chimneys
  Bracket Chimney Collapse & Fire Risks
  Earthquake Chimney Collapse Dangers

Chimney Crack Detection & Diagnosis
  Chimney Leaning, Separation, Movement-Outdoors
  Cracked Brick Chimney Sides
  Cracked Concrete Block Chimneys
  Curved Brick Chimneys
  Split Openings in Brick & Chimney Collapse

Chimney Draft & Performance
  Draft: Thermal Performance of Chimneys

Chimney Flashing Mistakes & Leaks

CHIMNEY HEIGHT & CLEARANCE CODE
  Adjacent Metal Chimney Separation
  B-Vent Clearances Table
  Chimney Too Short
  Chimney Height Extensions
  Chimney Height for Types L & Type B Vents
  Fire Clearances for Masonry Chimneys
  Fire Clearances for Metal Chimneys
  Fire Clearances, Single-Wall Metal Flues
  Masonry Chimney Roof Clearance
  Wood burning Fireplace Roof Clearance
Chimney Height Extensions

Chimney Inspection Checklist
Most Frequent Chimney Defects
Chimney Inspection Checklist - Outdoors
Chimney Inspection Checklist - Indoors
Responsibility of an ASHI Home Inspectors

Chimney Inspection: Flue Interiors
  Chimney Interior Inspection Methods
  Barometric Damper view of Flue
  Chimney Thimble Requirements
  Chimney Thimble Damage
  Cleanout Door view of Flue
  Masonry Fragments & Debris at the Cleanout
ChimScan: Inspecting Flues by Cameras

Chimney Inspection Indoor Procedures

Chimney Inspection Outdoors From Ground
  Abandoned Chimneys: Outdoors
  Chimney Crack Detection & Diagnosis
  Chimney Footing Defective / Missing
  Chimney Leaning, Separation, Movement
  Foundation Support for Masonry Chimneys
  Three-Sided Chimneys: Outdoors

Chimney Inspection Outdoors at Rooftop
  Angled Chimney Flues
  Blocked Chimney Flues
  Chimney Cap & Crown Inspection
    Missing Chimney Rain Cap
    Damaged Masonry Chimney Cap or Crown
    Separation of Chimney Flues - Chimney Top
  Chimney Crack Detection & Diagnosis
  Chimney Exterior Spalling
  Chimney Flashing Mistakes & Leaks
  Chimney Height Extensions
  Chimney Shoulder Leaks
  Flue Tile Damage in Chimneys
  Masonry Chimney Top Damage
  Soot at the Chimney Top
  UNLINED FLUE INSPECTIONS

Chimney Leaning, Separation, Movement
  Chimney Movement - Causes
  Chimney Movement - Ongoing vs Static
  Chimney Footing Defective / Missing
  Foundation Support for Masonry Chimneys
  Leaning Chimney Repair Methods

Chimney Repair Fraud Warning
Chimney Repair Methods
  Bracing for Masonry Chimneys
  Bracing for Metal Chimneys
  Bracing for Masonry Chimneys, Lateral
  Chimney Height Extensions
  Chimney Top & Clay Flue Tile Repairs
  Connecting Metal Chimney Sections
  Damaged Chimney flues: cracks, holes, spalling
  Draft Inducer Fans
  Leaning Chimney Repair Methods
  Re-Lining Choices for Masonry Chimneys
  Replacement Components for Metal Chimneys

Chimney Safety - CPSC Alert
Chimney Shoulder Leaks
Chimney Spalling, Exterior
Chimney Sweeps

Chimney Types & Materials
  Device Categories vs. Chimney Requirements
  Double-Wall Metal, Type B & Type L Chimneys
  Draft Hood Appliances
  Factory Built Chimneys
  High Efficiency Heating Appliances
  High Temperature Plastic Chimneys & Vents
  Masonry & Clay Tile Chimneys
  Mid-Efficiency Heating Appliances
  New Vent Requirements
  Single-Wall Metal Pipe Chimneys Vents
  Three-Sided Chimneys: Problems
  Transite Pipe Chimneys & Flues

CO2 TOXICITY
COALSTOVE SAFETY
COMBUSTION GASES & PARTICLE HAZARDS
COMBUSTION PRODUCTS & IAQ
COMPLETE COMBUSTION, Stoichiometric

Dead End Chimney Flue Hazards
Definitions of Chimney Types & Parts
DRAFT HOODS - gas fired
DRAFT MEASUREMENT, CHIMNEYS & FLUES
DRAFT REGULATORS, DAMPERS, BOOSTERS

EFFLORESCENCE, Salts & White / Brown Deposits

Fire Clearances for Masonry Chimneys
Fire Clearances for Metal Chimneys
Fire Clearances, Single-Wall Metal Flues
  CHIMNEY HEIGHT & CLEARANCE CODE
  Reduction in Fire Clearance - Heat Shields
  Single Wall Metal Flues - Oil fired heaters
  Single Wall Metal Pipe Flues - Gas heaters
  Wood & Coal Stove Flues
  Fire Clearance Safety Hazards, other

FIREPLACES & HEARTHS
  Chimney Cleanout Combustible Clearance
  Chimney Cleanouts Required
  Chimney / Fireplace Settlement
  Chimney / Fireplace Support Repair
  Creosote Deposits - Fire Hazard
  Dead End Flues / Dead Base Chimney Hazards
  Fireplace Damper Trouble
  Fireplace Fire Hazards: Carpeting
  Fireplace Hearth Size
  Fireplace Inserts
  Fireplace Inspections
  Fireplace & Woodstove Air Contaminants
  Inaccessible Connections Fireplace or Woodstove
  Wood Burning Fireplace Roof Clearance

Fire stopping at Chimney Passage Through Floors

FLAME COLOR, BLUE vs YELLOW COMBUSTION
FLUE SIZE SPECIFICATIONS
Flue Separation Requirements
Flue Tile Damage in Chimneys

Flue Vent Connectors - Boilers, Furnaces
  Blocked Chimney at the Flue Vent Connector
  Dead End Chimney Flue Hazards
  Extended Too Far into Chimney
  Joint Connections - Single Wall Metal Flues
  Length Limits for a Flue Vent Connector
  Loose, Leaky, Not Sealed, Flue Vent Connector
  Plastic Heater Vents
  Plastic Vents Goodman HTPV Recall
  Rusted Metal Flue Vent Connectors
  Slope, Proper Flue Vent Connector

Fuel Changes for Heating Appliances

HEATING COST FUEL & BTU Cost Table
HEATING INSPECTIONS
HOME HEATING SAFETY
HEATING SYSTEMS

Lennox SAFETY WARNING

Metal Chimneys & Flues
  Bracing for Metal Chimneys
  Class A Chimneys, MetalBestos™
  Connecting Metal Chimney Sections
  Continuous metal chimneys
  Definitions of Chimney Types & Parts
  Fire Clearances for Metal Chimneys
  Height required for L Vents & B Vents
  Indoor Hazards, Metal Chimney & Vent
  Manufactured Chimneys
  Offset from Vertical in Chimneys, excessive
  Replacement Components for Metal Chimneys
  Single-Wall Metal Vents & Chimneys
  Super Chimneys, 629 Chimneys
  Triple-Wall Metal Fireplace Chimneys
  Type B-Vents
  Type L Vents
  Wet time & Corrosion in Chimneys, Vents
  Wood Framed Chimney Chases

Moisture Problems Damage Chimneys

Nanomaterials Hazards
NOISE / SOUND DIAGNOSIS & CURE

ODORS & SMELLS DIAGNOSIS & CURE
ODORS FROM HEATING SYSTEMS
OIL HEAT SAFETY INSPECTIONS

PLASTIC HEATER VENTS

Safety Recalls, Chimneys, Vents, Heaters
  BLUE vs YELLOW COMBUSTION FLAMES
  BLUERAY Recall
  CHIMNEYS & Flues - Asbestos Transite
  Goodman HTPV RECALL
  Lennox Furnace Manuals
  Lennox SAFETY WARNING
  PLASTIC Plexvent / Ultravent RECALL
  Weil McLain RECALL

Shared Chimney & Shared Flue Hazards
  Shared Chimney Flue Examples
  Exceptions: Shared Flues Permitted?
  Wood & Oil Fired Heaters
  Two Gas Fired Appliances Vent in One Flue
  Multiple Fireplaces Sharing One Flue

STAIN DIAGNOSIS on BUILDING EXTERIORS
Stains on chimneys

Three-Sided Chimneys: Problems
Transite Pipe Chimneys & Flues

UNLINED FLUE INSPECTIONS

WOOD, COAL STOVES & FIREPLACES
  Chimney Clearance & Condition Safety
  Coalstove Safety
  Creosote Deposits - Fire Hazard
  Dead End Flues - Dead Base Chimney Hazards
  Fire Clearance Safety Hazards
  Fire Clearance Wood & Coal Stove Flues
  Fire stopping at Chimney Passage Through Floors
  FIREPLACES & HEARTHS
  Fireplace Inserts
  Fireplace Inspections
  Fireplace & Woodstove Air Contaminants
  HEATING COST FUEL & BTU Cost Table
  Inaccessible Connections Fireplace or Woodstove
WOOD STOVE SAFETY

More Information

Fireplace insert into chimney (C) Carson Dunlop Fireplace Inserts & Zero-Clearance Fireplaces
InspectAPedia®  -    

  • Antique coal grates inserted into fireplace openings (photos)
  • Modern wood & coal stove fireplace inserts
  • Zero-clearance fireplace safety inspection warnings
  • How does a fireplace insert such as a woodstove block inspection and cleaning of the chimney?
  • Chimney inspection limitations, further inspection & cleaning advice
InspectAPedia offers impartial, unbiased advice without conflicts of interest. We will block advertisements which we discover or readers inform us are associated with bad business practices, false-advertising, or junk science. Our contact info is at InspectAPedia.com/Contact.htm.

This article describes the antique and modern fireplace inserts used for wood, coal, or pellet fuel heating. We discuss fireplace inserts and zero-clearance fireplaces, both antique and modern, and their hazards and inspection limitations.

Watch out: Because a fireplace insert blocks direct access to the chimney flue from inside a building, the condition of an inaccessible flue is often unknown, and possibly dangerous fire or carbon monoxide hazards could be present. Expert inspection and cleaning are appropriate as at least an annual safety check. Our page top sketch of a typical fireplace insert is provided courtesy of Carson Dunlop & Associates.

Readers of this article should be sure to review Fireplace Damage & Unsafe Hearths, and also see Fireplace Inspections for a professional chimney sweep's fireplace and chimney hazard checklist. At Fireplace Inserts we discuss fireplace inserts and zero-clearance fireplaces, both antique and modern, and their hazards and inspection limitations. Readers should also see Inaccessible Connections Fireplace or Woodstove. The inspection of chimney interiors is discussed at Chimney Inspection: Flue Interiors.

This website also provides detailed suggestions describing how to perform a thorough visual inspection of chimneys for safety and other defects. Chimney inspection methods and chimney repair methods are also discussed. As with most inspection and safety topics, this material may be incomplete. Readers should also see Chimney Inspection: Flue Interiors and ChimScan: Inspecting Flues by Cameras.

© Copyright 2012 InspectAPedia.com, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use page top links to major topics or use links at the left of each page to navigate within topics and documents at this website. Green links show where you are in a document series or at this website.

Antique Fireplace Inserts - Coal-Burning

Below we provide photographs of the exploration of the condition of a cast-iron "fireplace" or fireplace grate that was originally intended for burning large chunks of coal, probably soft coal. This installation was found in a home built in Poughkeepsie NY ca 1900 and restored by the author.

Antique coal burning fireplace Poughkeepsie (C) Daniel Friedman Antique coal burning fireplace Poughkeepsie (C) Daniel Friedman

Working carefully so as not to damage the ceramic tile fireplace facade and hearth, we removed and disassembled this antique coal burning fireplace insert (burning wood in our photo) to inspect the condition and construction of the chimney flue (above right). The flue was un-damaged, needed cleaning, and was also a bit small for any expanded fuel use in this installation.

Antique coal burning fireplace Poughkeepsie (C) Daniel Friedman Antique coal burning fireplace Poughkeepsie (C) Daniel Friedman

Our fireplace photos above show the back and top of this coal burning insert (above left) and the grate assembly (above right).

At below left we show the solid (8" or more) masonry firebox and the opening into a basement ash pit below this fireplace. Our reproduction of an antique fireplace grate insert (below right) was a Dixon's Low-Down Grate. Low fireplace grates were intended for use over an ash pit opening. For upper floor rooms where no ash pit connection was possible, Dixon sold an Elevated Fire Grate.

The installation of low cast iron fire grates over an ash pit was made as shown in this sketch. Dixon's design intended to draw combustion air for the fire from the basement (cellar) or from outside, not from the room being heated - a design considered proper practice in modern homes and required by code in some areas. Here is another beautiful antique fireplace opening cover/grate observed in Minneapolis and contributed by Roger Hankey.

Watch out: some older homes used a shared flue among fireplaces and heating appliances on different floors - a practice that is considered unsafe and is prohibited today.

Antique coal burning fireplace Poughkeepsie (C) Daniel Friedman Antique coal burning fireplace Poughkeepsie (C) Daniel Friedman

Modern Fireplace Inserts for Burning Wood, Coal, Pellet Fuel

Fireplace insert (C) Daniel Friedman

A modern fireplace insert for burning wood is shown at left. You can see why inspecting the chimney from inside is impossible without removing the appliance. This installation is particularly interesting. If you click to enlarge the photo you can see light colored bricks at the right of the fireplace insert: the installer appears to have bricked the original fireplace opening to better fit the new insert.

Watch out: adding a fireplace insert that moves the fire doors closer to the edge of the hearth reduces fire clearance (for heat or if the doors are open, sparks and coals) between the appliance opening and nearby combustibles or flooring.

The owners have placed a "fireproof rug" in front of this unit - that semi-circular carpet observed on the floor. Is this adequate? Be sure to consult your local fire inspector when installing or converting a fireplace or fuel burning appliance.

Woodstove inserted (C) Daniel FriedmanUnsafe Fireplace Inserts

By "fireplace insert" we refer to a wood or coal-burning stove designed to be inserted into an existing masonry fireplace opening.

The wood-stove installed in the fireplace at left may work in such a location, but it was not designed as an "insert" - and does not fit the opening of this odd fireplace. In fact not much would fit in this angled firebox.

Placing the feet of the woodstove past the hearth and onto a rug, as well as less than 3' from combustibles, are further fire hazards - this is an unsafe installation.

Zero-clearance Fireplaces

Zero clearance gas fireplace (C) Daniel Friedman

Do not confuse a fireplace insert woodstove or coalstove with a "zero-clearance" fireplace such as the unit shown here.

Zero-clearance fireplaces are typically steel constructed fireplaces to burn wood or perhaps other fuels such as LP or natural gas in modern homes, usually connected to a metal chimney.

Our photo (left) shows a zero-clearance gas fireplace. Other zero clearance fireplaces burn wood or perhaps other fuels.

The clearance to combustibles is not "zero" but one or more inches, depending on the materials, construction, and manufacturers' instructions.

Zero clearance metal fireplace (C) Daniel Friedman

Watch out: we have found a few zero-clearance fireplaces improperly installed too close to combustibles. The installer did not understand the purpose of steel clearance-assuring projections welded to the zero-clearance fireplace, and s/he had hammered them flat to "shoe-horn" the zero clearance fireplace into a too-small wood-framed rough opening. The result was a serious building fire hazard and a building code violation as well.

Our photo of a zero-clearance fireplace from inside the framed opening (above) shows the clearance guards intact next to our ruler. But inspection showed chimney leaks onto this unit - evidenced by the rust and white stains that can ultimately damage the flue (at upper right) and the fireplace unit, making it unsafe.

Inspecting the Chimney where a Fireplace Insert for Wood or Coal is Installed

In fact it is just about impossible to see the condition of these components and their connections unless the insert is removed or inspected from above using a chimney inspection camera system.

If a woodstove/free-standing fireplace like this were to be used it would probably require at least three feet of clearance from combustibles.

Local codes and fire regulations need to be consulted, and in most jurisdictions, a building permit and safety inspection are required for the installation of a woodstove or similar device.

See WOOD STOVE SAFETY for important details and also see Chimney Safety Alert for Wood Burning Appliances - US CPSC Alert Document 5017, wood stoves, fireplace.

More help with inspecting chimney flue interiors can be found in these articles:

Chimney Inspection: Flue Interiors
  Chimney Interior Inspection Methods
  Barometric Damper view of Flue
  Chimney Thimble Requirements
  Chimney Thimble Damage
  Cleanout Door view of Flue
  Masonry Fragments & Debris at the Cleanout
ChimScan: Inspecting Flues by Cameras

Fireplace Inspections

Abandoning or Removing a Fireplace Insert?

Often when a fireplace insert has been installed, the original fireplace damper has been modified (cut to pass the flue vent connector) or simply removed entirely. If you are discontinuing a fireplace insert, you may need to repair or replace the fireplace damper, or perhaps install a chimney-top damper instead.

Questions & Answers regarding this article

.

Ask a Question or Search InspectAPedia

HTML Comment Box is loading comments...

Share this Article      

...

Technical Reviewers & References

  • InspectAPedia.com® - Daniel Friedman - Publisher & Editor.
  • InspectAPedia Bookstore lists recommended books, organized by topic & available for purchase. Most of our articles also include a list of recommended books for the specific article topic as well as other references, and information sources.
  • Critique, contributions wanted: Contact Us to suggest corrections or additions to articles at this website, and if you wish, to receive online listing and credit as a contributor. Particular thanks are due to the many experts and also consumers who read and critique technical articles at InspectAPedia.com.
  • Additional technical contributors & reference sources for this article are listed below.

Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

CHIMNEY INSPECTION DIAGNOSIS REPAIR

Abandoned Chimneys - Indoor Inspection
Abandoned Chimneys: Outdoors
Angled Chimney Flues

ARCHITECTURE & BUILDING COMPONENT ID

Attic Chimney Inspection

BAROMETRIC DAMPERS
CARBON DIOXIDE - CO2
CARBON MONOXIDE - CO
Chimney Components Definitions
Abandoned Chimneys
Backdrafting Appliances
Chimney Cleaning Advice, Procedures
Chimney Cleaning Fraud Warning
Chimney Cleanout Doors
Chimney Crack & Collapse Risks, Repairs
Chimney Crack Detection & Diagnosis
Chimney Leaning, Separation, Movement
Chimney Draft & Performance
CHIMNEY HEIGHT & CLEARANCE CODE
Chimney Inspection Checklist
Most Frequent Chimney Defects
Chimney Inspection Checklist - Outdoors
Chimney Inspection Checklist - Indoors
Responsibility of an ASHI Home Inspectors
Chimney Inspection: Flue Interiors
  Chimney Interior Inspection Methods
  Barometric Damper view of Flue
  Chimney Thimble Requirements
  Chimney Thimble Damage
  Cleanout Door view of Flue
  Masonry Fragments & Debris at the Cleanout
ChimScan: Inspecting Flues by Cameras
Chimney Inspection Indoor Procedures
Blocked Chimney Flues
Chimney Crack Detection & Diagnosis
Dead End Chimney Flue Hazards

Fire Clearance Safety Hazards
Fire stopping at Chimney Passage Through Floors

Three-Sided Chimneys: Problems
Transite Pipe Chimneys & Flues
Chimney Inspection Outdoors From Ground
Chimney Inspection Outdoors at Rooftop
Angled Chimney Flues
Blocked Chimney Flues
Chimney Cap & Crown Inspection
Chimney Crack Detection & Diagnosis
Chimney Exterior Spalling
Chimney Flashing Mistakes & Leaks
Chimney Height Extensions
Chimney Shoulder Leaks
Flue Tile Damage in Chimneys
Masonry Chimney Top Damage
Soot at the Chimney Top
UNLINED FLUE INSPECTIONS
Chimney Repair Fraud Warning
Chimney Repair Methods
Chimney Types & Materials
CO2 TOXICITY
COALSTOVE SAFETY
COMBUSTION GASES & PARTICLE HAZARDS
COMBUSTION PRODUCTS & IAQ
COMPLETE COMBUSTION, Stoichiometric
Dead End Chimney Flue Hazards
Definitions of Chimney Types & Parts
DRAFT HOODS - gas fired
DRAFT REGULATORS, DAMPERS, BOOSTERS
Fire Clearances for Masonry Chimneys
Fire Clearances for Metal Chimneys
Fire Clearances, Single-Wall Metal Flues
FIREPLACES & HEARTHS
  Creosote Deposits - Fire Hazard
  Dead End Flues - Dead Base Chimney Hazards
  Fireplace Inserts
  Fireplace Inspections
  Fireplace & Woodstove Air Contaminants
  Inaccessible Connections Fireplace or Woodstove

Fire stopping at Chimney Passage Through Floors
FLAME COLOR, BLUE vs YELLOW COMBUSTION
FLUE SIZE SPECIFICATIONS
Flue Vent Connectors - Boilers, Furnaces
Fuel Changes for Heating Appliances

HEATING COST FUEL & BTU Cost Table
HEATING INSPECTIONS
HOME HEATING SAFETY
HEATING SYSTEMS

Lennox SAFETY WARNING

Metal Chimneys & Flues
Moisture Problems Damage Chimneys

ODORS FROM HEATING SYSTEMS
OIL HEAT SAFETY INSPECTIONS

PLASTIC HEATER VENTS
Safety Recalls
Shared Chimney & Shared Flue Hazards
Stains on chimneys

Three-Sided Chimneys: Problems
Transite Pipe Chimneys & Flues

UNLINED FLUE INSPECTIONS

WOOD, COAL STOVES & FIREPLACES
  Chimney Clearance & Condition Safety
  Coalstove Safety
  Creosote Deposits - Fire Hazard
  Dead End Flues - Dead Base Chimney Hazards
  Fire Clearance Safety Hazards
  Fire Clearance Wood & Coal Stove Flues
  Fire stopping at Chimney Passage Through Floors
FIREPLACES & HEARTHS
  Fireplace Inserts
  Fireplace & Woodstove Air Contaminants
  Fireplace Inspections
  HEATING COST FUEL & BTU Cost Table
  Inaccessible Connections Fireplace or Woodstove
  WOOD STOVE SAFETY

  • Carson, Dunlop & Associates Ltd., 120 Carlton Street Suite 407, Toronto ON M5A 4K2. (416) 964-9415 1-800-268-7070 info@carsondunlop.com. Thanks to Alan Carson and Bob Dunlop, for permission to use illustrations from their publication, The Illustrated Home which illustrates construction details and building components. Carson Dunlop provides home inspection education including the ASHI-adopted Home Inspection Training Program (home study course), publications such as the Home Reference Book, report writing materials including the Horizon report writer, and home inspection services. Alan Carson is a past president of ASHI, the American Society of Home Inspectors.
  • Thanks to Luke Barnes for suggesting that we add text regarding the hazards of shared chimney flues. USMA - Sept. 2008.
  • Arlene Puentes, an ASHI member and a licensed home inspector in Kingston, NY, and has served on ASHI national committees as well as HVASHI Chapter President. Ms. Puentes can be contacted at ap@octoberhome.com
  • Roger Hankey is principal of Hankey and Brown home inspectors, Eden Prairie, MN, technical review by Roger Hankey, prior chairman, Standards Committee, American Society of Home Inspectors - ASHI. 952 829-0044 - hankeyandbrown.com
  • NFPA 211 - Standards for Chimneys & Fireplaces, NFPA 211: Standard for Chimneys, Fireplaces, Vents, and Solid Fuel-Burning Appliances, 2006 Edition (older editions and standards are found at the same bookstore)
  • NFPA #211-3.1 1988 - Specific to chimneys, fireplaces, vents and solid fuel burning appliances.
  • NFPA # 54-7.1 1992 - Specific to venting of equipment with fan-assisted combustion systems.
  • GAMA - Gas Appliance Manufacturers' Association has prepared venting tables for Category I draft hood equipped central furnaces as well as fan-assisted combustion system central furnaces.
  • National Fuel Gas Code, an American National Standard, 4th ed. 1988 (newer edition is available) Secretariats, American Gas Association (AGA), 1515 Wilson Blvd., Arlington VA22209, and National Fire Protection Association (NFPA), Batterymarch Park, Quincy MA 02269. ANSI Z223.1-1988 - NFPA 54-1988. WARNING: be sure to check clearances and other safety guidelines in the latest edition of these standards.
  • Fire Inspector Guidebook, A Correlation of Fire Safety Requirements Contained in the 1987 BOCA National Codes, (newer edition available), Building Officials and Code Administrators International, Inc. (BOCA), Country Club HIlls, IL 60478 312-799-2300 4th ed. Note: this document is reissued every four years. Be sure to obtain the latest edition.
  • Uniform Mechanical Code - UMC 1991, Sec 913 (a.) Masonry Chimneys, refers to Chapters 23, 29, and 37 of the Building Code.
  • New York 1984 Uniform Fire Prevention and Building Code, Article 10, Heating, Ventilating, and Air Conditioning Requirements
  • New York 1979 Uniform Fire Prevention & Building Code, The "requirement" for 8" of solid masonry OR for use of a flue liner was listed in the One and Two Family Dwelling Code for New York, in 1979, in Chapter 9, Chimneys and Fireplaces, New York 1979 Building and Fire Prevention Code:
  • "Top Ten Chimney (and related) Problems Encountered by One Chimney Sweep," Hudson Valley ASHI education seminar, 3 January 2000, contributed by Bob Hansen, ASHI
  • Chimney Inspection Checklist, Carson Dunlop, Associates, Toronto, Ontario
  • "Rooftop View Turns to Darkness," Martine Costello, Josh Kovner, New Haven Register, 12 May 1992 p. 11: Catherine Murphy was sunning on a building roof when a chimney collapsed; she fell into and was trapped inside the chimney until rescued by emergency workers.
  • "Chimneys and Vents," Mark J. Reinmiller, P.E., ASHI Technical Journal, Vol. 1 No. 2 July 1991 p. 34-38.
  • "Chimney Inspection Procedures & Codes," Donald V. Cohen was to be published in the first volume of the 1994 ASHI Technical Journal by D. Friedman, then editor/publisher of that publication. The production of the ASHI Technical Journal and future editions was cancelled by ASHI President Patrick Porzio. Some of the content of Mr. Cohen's original submission has been included in this more complete chimney inspection article: InspectAPedia.com/chimneys/Chimney_Inspection.htm. Copies of earlier editions of the ASHI Technical Journal are available from ASHI, the American Society of Home Inspectors.
  • Natural Gas Weekly Update: http://tonto.eia.doe.gov/oog/info/ngw/ngupdate.asp Official Energy Statistics from the U.S. Government
  • US Energy Administration: Electrical Energy Costs http://www.eia.doe.gov/fuelelectric.html
  • NFPA 211 - 3-1.10 - Relining guide for chimneys
  • NFPA 211 - 3-2 - Construction of Masonry Chimneys
  • NFPA 211 - 3-3 - Termination Height for chimneys
  • NFPA 211 - 3-4 - Clearance from Combustible Material
  • NFPA 54 - 7-1 - Venting of Equipment into chimneys
  • Brick Institute of America - Flashing Chimneys
    Brick Institute of America - Proper Chimney Crowns
    Brick Institute of America - Moisture Resistance of Brick
  • American Gas Association - New Vent Sizing Tables
  • Chimney Safety Institute of America - Chimney Fires: Causes, Effects, Evaluation
  • National Chimney Sweep Guild - Yellow Pages of Suppliers

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.
  • Fireplace & Chimney Design, Repair Books - Fireplaces, Chimneys: design, repair
  • Fireplace & Chimney Inspection Books - Inspecting and diagnosing chimney problems, fireplace problems, chimney & fireplace standards
  • Ceramic Roofware, Hans Van Lemmen, Shire Library, 2008, ISBN-13: 978-0747805694 - Brick chimneys, chimney-pots and roof and ridge tiles have been a feature of the roofs of a wide range of buildings since the late Middle Ages. In the first instance this ceramic roofware was functional - to make the roof weatherproof and to provide an outlet for smoke - but it could also be very decorative.
    The practical and ornamental aspects of ceramic roofware can still be seen throughout Britain, particularly on buildings of the Victorian and Edwardian periods. Not only do these often have ornate chimneys and roof tiles but they may also feature ornamental sculptures or highly decorative gable ends. This book charts the history of ceramic roofware from the Middle Ages to the present day, highlighting both practical and decorative applications, and giving information about manufacturers and on the styles and techniques of production and decoration.
    Hans van Lemmen is an established author on the history of tiles and has lectured on the subject in Britain and elsewhere. He is founder member and presently publications editor of the British Tiles and Architectural Ceramics Society. Available at the InspectAPedia Bookstore.
  • Chimney Inspection Checklist, Carson Dunlop, Associates, Toronto, Ontario
  • Chimney & Stack Inspection Guidelines, American Society of Civil Engineers, 2003 - These guidelines address the inspection of chimneys and stacks. Each guideline assists owners in determining what level of inspection is appropriate to a particular chimney and provides common criteria so that all parties involved have a clear understanding of the scope of the inspection and the end product required. Each chimney or stack is a unique structure, subject to both aggressive operating and natural environments, and degradation over time. Such degradation may be managed via a prudent inspection program followed by maintenance work on any equipment or structure determined to be in need of attention. Sample inspection report specifications, sample field inspection data forms, and an example of a developed plan of a concrete chimney are included in the guidelines. This book provides a valuable guidance tool for chimney and stack inspections and also offers a set of references for these particular inspections.
  • Fireplaces, a Practical Design Guide, Jane Gitlin
  • Fireplaces, Friend or Foe, Robert D. Mayo
  • NFPA 211 - Standards for Chimneys & Fireplaces, NFPA 211: Standard for Chimneys, Fireplaces, Vents, and Solid Fuel-Burning Appliances, 2006 Edition (older editions and standards are found at the same bookstore)
  • Principles of Home Inspection: Chimneys & Wood Heating (Principles of Home Inspection), Carson Dunlop
Home About Us Accuracy Contact Us Content Use Policy Privacy Website Description © 2012 Copyright InspectAPedia.com