InspectAPedia®   -   Search InspectApedia

Thin wall metal conduit (C) Daniel FriedmanElectrical Conduit Tools & Bending Guide
Bends, connectors, cuts, install electrical conduit

Electrical conduit installation tools, conduit bend types, & how to make conduit bends in EMT.

Here we describe tools used to bend, connect, cut, or install electrical conduit made of metal or non-metallic materials, and we describe each of the EMT or electrical conduit bend types: the 90° Stub-Up bend, the back to back or "U" bend in conduit, the saddle bend to run conduit around any obstacle, the offset conduit bend to zig zag around an obstacle, and the three point saddle bend to run conduit over a small obstacle.

To make a conduit bend successfully you'll need to add length, often referred to as the "shrinkage amount" to allow for the loss in a given length of conduit's effective length when you bend it.

This article series describes both metallic electrical conduit and plastic or non-metallic electrical conduit products, and answers basic questions about installing electrical conduit. Electrical conduit is metal or plastic rigid or flexible tubing used to route electrical wires in a building.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

What tools you need and the procedures for using conduit?

Electrical conduit mistakes (C) D Friedman T Hemm

These electrical conduit tools, methods, tables, bending guides are used for EMT (Electrical Metallic Tubing), IMC (Intermediate Conduit), and also for Rigid Conduit, of steel or aluminum, but note that bending instructions may vary depnding on just what material is being formed.

Cutting, Bending and Threading Electrical Conduit

Electrical conduit is often used to hold and protect house wiring. In some localities electrical conduit is required by the local code.

Conduit protects building wiring from damage better than flexible steel (BX) cabling or plastic sheathing (Non metallic sheathed or NMC wire).

However, it electrical conduit is more difficult to install and it requires both some special tools and some special knowledge about permitted bending radii and similar details.

Instead of damaging rigid electrical conduit tubing (as in the photo above) make your bends using the proper tool, use elbows and fittings, buy pre-formed bends (shown at left in plastic conduit), or use flexible metal or plastic conduit (illustrated above ).

[Click to enlarge any image]

Tools for Cutting Electrical Conduit

Thin-wall metal conduit can be cut with a special electrical conduit cutter. To use the cutter, clamp it around the conduit. To cut the conduit, tighten the knurled nut in the handle.

As you tighten, force the cutter around the conduit. The sharp cutting blade cuts a groove that deepens with each revolution, making a smooth, quick cut. After cutting through the conduit, file off any burrs around the edge of the cut.

EMT scoring tool used for cutting electrical conduit - cited & discussed at InspectApedia.com

Watch out: after metal conduit is cut its cut ends must be reamed or chamfered so that the wire pulled through the conduit won't be damaged.

Tools for Bending Electrical Conduit

Thin-wall electrical conduit can be readily bent by using a special tool designed to make a smooth, even bend with little effort.

Below: a manual or hand-operated electrical conduit bender, this one from Ideal, widely sold at electrical suppliers. Our sketch shows the two most critical measurements when obtaining the leg length or stub-up height when bending conduit.

Electrical conduit bender from Ideal - cited & discussed at InspectApedia.com ,,, Measurement points on metal conduit at bends to get height or length  discussed at InspectApedia.com

Details of the bend markings for this conduit bender are given below.

The more bends in a run of conduit, the more it is to “fish” the wires through. 

Plan the conduit run carefully to avoid sharp bends and to make as few bends as possible. 

Conduit bending tool from Ideal Corp. cited & discussed at InspectApedia.com

Illustration above: Ideal Corporation's tubing bender marks used to make proper bends in EMT.

Never have more than four right angle bends between openings. 

Follow the manufacturer’s instructions for the type of conduit bender you use.

How an electrical conduit bender works

Electrical conduit bender, electrical powered from Klein Tools - cited at InspectApedia.com

Above: an electric-operated electrical conduit bender from Klein Tools.

Standard Bend Radius and Calculations for Electrical Conduit Bends

You'll find these and more details in the electric conduit bending guides cited in this article.

Standard Electrical Conduit Bend Data

Conduit Size Required Bend Radius Deduction for 90 Degree Bend
1/2" 4" 5"
3/4" 4 1/2" 6"
1" 5 3/4" 8"
1 1/4"    

Notes to the table above:

The Deduct numbers tell you how many straight-line linear inches will be occupied by the finished electrical conduit bend.

Types of Electrical or EMT Conduit Bends & How They Are Made

Conduit bending tools are provided for both ductable iron rigid conduit and EMT. You'll use a different conduit bending tool depending on the conduit material.

Here we illustrate the basic bends formed in metal conduit or that can be purchased pre-bent in EMT or plastic conduit. Details of exactly where and how to measure distances to get these bends exactly right for your job are in the conduit bending guides [PDFs as free downloads] provided later on this page.

90° Stub-Up Bend in EMT

A stub bend forms a length of conduit into an L-shape or a 90° angle as shown below.

EMT or metal conduit 90 degree L or Stub Bend adapted from Klein Tools Conduit Bender Giude Cited & Discussed at InspectApedia.com

To make an L-bend that finishes with the desired free-end height that you want when the conduit has been bent to shape, you need to subtract the stub height that will be taken up by the actual 90° angle.

Klein and other conduit bending tool manufacturers provide a guide that shows, for a given conduit diameter, the stub-height that must be subtracted from the total desired free-end height (given below along with the company's contact information).

For example,

Back-to-Back or "U" Bends in Electrical Conduit

90 degree double back bend to bend electric conduit between two obstacles (C) InspectApedia.com adapted from Klein cited in detail in this article

A pair of 90° Stub Bends is used to shape conduit between two obstacles, such as between two opposing walls or columns. This U-shaped conduit bend can be as short as two 90° stub bends joined together or of any greater length or distance as shown in our drawing, adapted from Klein, cited below.

To make a conduit U-bend you need to follow these steps: (see the instructions for your specific brand and model conduit bending tool)

  1. Measure the total distance between the two obstructions (the red line in our sketch).
  2. Make the first 90° stub-up bend at one end of the conduit
  3. Measure the distance from the back-end of the first stub-up bend to find where to place the conduit bender on the other (straight) end of the conduit (green lines in our sketch) and mark this as the second conduit bend index point.
  4. Place the bending tool on the conduit so that its index point (the "Star Point Symbol" if you're using the Klein conduit bending tool) is in line with the second-bend index point marked on the conduit
  5. Complete the second bend

Offset Bends in EMT Conduit

An offset bend allows conduit to shift up or down, or left or right, while continuing in the same original direction, such as to zig-zag around an obstruction.

Conduit offset bend at cabin on Bearskin Lake, Minnesota (C) Daniel Friedman at Inspectapedia.com

Above: we see a typical application of an offset bend in conduit: jogging around a change in wall thickness. This electrical conduit installation is on the exterior of a guest cabin on Bearskin Lake in northern Minnesota.

Our illustration of an offset bend shown below is adapted from Klein Tools, cited in detail further below.

EMT or metal conduit 45 degree offset Bends around an obstacle, adapted from Klein Tools Conduit Bender Giude Cited & Discussed at InspectApedia.com

Various offset bend angles may be used depending on the space needed to clear an obstacle or change elevation and the distance over which the change must be achieved. Bending angles include 10°, 22 1/2°, 30°, 45° and 60 °. You would prefer to avoid a pair of 90° bends as pulling wire may be made too difficult.

To make an offset bend the installer chooses the necessary angle to clear an obstacle over a given distance, measuring

Conduit bending guides will give a constant multiplier for each bend angle. Use the constant multiplier to increase the total conduit length needed to clear the distances involved, thus allowing for the loss in effective length that occurs when you bend (thus shortening) the conduit's travel distance.

Theoretical stair design (C) Daniel Friedman

Above, from our framing article cited below, we illustrate the calculations you'd need to route conduit over a change in height or across a jog in a wall.

Using that same drawing for electrical conduit bends, angle ab is the bend to leave the floor and slope up, and angle ac is the necessary angle to continue again on the flat or horizontal.

The calculations of these angles always require using a "right triangle" with the 90 degree angle shown in the sketch.

Since every triangle will have three angles, and we know they'll add up to 180 degrees (a straight line), if we have any two angles we calculate the third.

Example: if angle ab is 30° and we know that the right angle is 90° (by definition), and since those two add up to 90°+30°=120° we can calculate

Angle ac = (180° - 120°) = 60°

See also FRAMING TRIANGLES & CALCULATIONS for help in using simple triangles to calculate the length and rise (or drop) in conduit as well as the necessary bends shown in the table above.

When your conduit needs to span a rise or fall across a surface such as a curb or step, use the table below to determine the degrees of bend necessary.

Electrical Conduit Offset Bend Multipliers

 
Bend Angle Degrees Multiplier
10° 6.0
22° 2.6
30° 2.9
45° 1.4
60° 1.2

Notes to the table above:

Watch out: NEC 346.11 sets a limit of four quarter-bends between any two pull points. That's the same as a limit of 360° through four bends.

Three Point Saddle Bend in Electrical Conduit

Illustrated below is the three-point "saddle bend" in EMT, used to clear a small object such as a pipe or cross-under conduit.

EMT Conduit three point saddle bend to clear an obstacle such as a pipe or crossing conduit adapted from Klein cited & discussed at InspectApedia.com

A three point saddle conduit bend is similar to the offset bend we described above. This conduit shape is useful to clear small obstacles such as a crossing pipe.

Like the saddle bend, you will need to add conduit length to accommodate the distance lost from the bend itself, depending on the bending angle you choose.

Detailed three point saddle bend shrinkage amount tables will be given in the instructions for your conduit bending tool, such as the Klein tool from which we adapted the image shown above.

Examples of conduit length shrinkage amounts, or the amount you need to add to the "distance to object" (red in our drawing) for every inch of height in the object offset distance (green in our drawing) include:

Three Point Saddle Bends Using 45 ° Center

Three Point Saddle Bends using 60 ° Center

Watch out: Be sure to double check tables of shrinkage amounts (or length extensions) to allow for various bends and to see exactly where to place the bending tool according to the instructions for your specific electrical conduit or EMT bending tool's manufacturer and model.

Non-Metallic Conduit Bends

A 90 degree sweep or bend using Cantex PVC nonmetallic rigid plastic electrical conduit (C) Daniel Friedman

Sweeps and bends traversing 45 degrees and 90 degrees for non-metallic plastic conduit are sold pre-formed, such as the PVC 90-degree Bell-End elbow conduit example I'm holding in the photo above.

How to thread electrical wires through conduit

A fish tape is a thin, flexible metal tape with a hook on one end. The tape is usually packaged on some type of reel. The tape is used to pull wires through conduit or through openings in walls. For conduit use, the tape is inserted in one conduit opening and worked through to the next opening. The wires to be drawn through the conduit are bent around the hook on the fish tape.

If the run is long and has a few bends it is a good idea to wrap some electrical tape around the wires to hold them on the hook.  The tape is then reeled in to draw the wires through the conduit.  A slow, steady is less likely to kink the tape or jam the wires than is a series of sharp.

Electrical codes allow multiple electrical wires to be pulled through a single conduit, but limit the number of wires allowed in a conduit run depending on the number of wires and the wire diameter or gauge.

The more wires you pull, the more crowded the conduit, so buy larger conduit---perhaps 3/4 inch instead of 1/2 inch.

Conduit Connectors

ENT, LFNC, Plastic PVC Conduit connectors

ENT conduit sections and fittings are joined by conduit solvent cement specifically formulated for use with PVC (polyvinyl chloride) plastic conduit ducts and fittings.

Plastic condolet connector for PVC electrical conduit (C) Daniel Friedman ... Low VOC PVC cement for electrical conduit (C) Daniel Friedman

Below: ENT Coupling fittings and expansion couplings for PVC conduit.

ENT plastic conduit coupling (C) Daniel Friedman ... ENT conduit expansion fitting (C) Daniel Friedman

...

EMT Connectors

[in process] Photos, comments, suggestions are invited. Use the page top or bottom CONTACT link. Contributors are cited & linked-to, or can remain anonymous (default). - Ed.

IMC metal conduit in a New York home (C) Daniel Friedman

FMC Connectors

Armored cable, 12/3  Armorlite BX wire (C) Daniel Friedman

[In process]

IMC Connectors

Calbrite™ stainless steel IMC Coupling - at InspectApedia.com

Non-threaded IMC is joined by compression fit type couplings like the stainless steel Calbrite™ IMC coupling shown here.

RMC connectors

The stainless steel C Condulet shown below and used for snaking or connecting electrical wires inside of RMC is a Calbrite™ product - contact information is given below.

Stainless steel RMC is used where corrosive environments will exceed the limitations of aluminum, fiberglass, rigid steel, PVC, & PVC Coated conduit. (Calbrite 2017).

Calbrite™ Brand stainless steel C Condulet at InspectApedia.com contact information for Calbrite is in the article where this image appears

 

Electrical Conduit Tool & Equipment Suppliers

Electrical conduit mistakes (C) D Friedman T HemmWatch Out:  Do not attempt to work on your electrical wiring, switches, or outlets unless you are properly trained and equipped to do so. Electrical components in a building can easily cause an electrical shock, burn, or even death.

Even when a hot line switch is off, one terminal on the switch is still connected to the power source.

Before doing any work on the switch, the power source must be turned off by set­ting a circuit breaker to OFF or removing a fuse.

See SAFETY for ELECTRICAL INSPECTORS

and ELECTRICAL WIRING BOOKS & GUIDES

Electrical conduit for wiring has some advantages in protecting wires and also in running multiple wires to a location.

The proper selection of electrical conduit materials, fittings, and installation are important for safe electrical wiring.

Our photo (above left, courtesy of Tim Hemm), shows an electrical conduit snafu along with an unsafe FPE Stab-Lok electrical sub panel. Both flexible electrical conduit and rigid conduit were used. Our arrow points to an improper "bend" made in the rigid metal electrical conduit. [3]

 

 




ADVERTISEMENT





Reader Comments, Questions & Answers About The Article Above

Below you will find questions and answers previously posted on this page at its page bottom reader comment box.

Reader Q&A - also see RECOMMENDED ARTICLES & FAQs

On 2021-04-10 - by (mod) -

Electrical conduit bender, electrical powered from Klein Tools - cited at InspectApedia.com @Fredy floees,

The electrical code does not prohibit specific tools but does require that the conduit bending tool be listed or "identified" as approved for bending conduit.

(2014) U.S. NEC 352.24 Bends — How Made.

Bends shall be so made that the conduit will not be damaged and the internal diameter of the conduit will not be effectively reduced. Field bends shall be made only with identified bending equipment.

Shown above on this page are both an electrical conduit bending tool from Ideal and an electric-operated conduit bender from Klein Tools.

Just comparing prices the hand operated mechanical bender sells for less than $100. U.S. while an electric bending tool may be $1,000 - $12,000.

Below is an electrical conduit bender from Greenlee, the Greenlee 854DX One Shoe Solution EMT, IMC, and Rigid Electric Conduit Bender https://www.greenleestore.com/

In addition to the conduit bending instructions we already included in the article above, Klein Tools offers their own

ELECTRICAL CONDUIT BENDING INSTRUCTIONS [PDF] Klein Tools, Inc - cited above on this page

It seems to me that if you are working a large commercial electrical wiring job where there is a lot of conduit bending it's pefectly justified to buy or rent an electric conduit bender.

On 2021-04-10 by Fredy floees

Requirements for bending conduit by the NEC when to use hand tool benders and when you would use power tools.

On 2020-11-23 - by (mod) -

Anon: the metal conduit tubing bending tools I've seen held the tubing themselves during the bend.

EMT is often cut with a sawzall (foot on pipe on 2x4 scraps or a wood faced vise), with a band saw, with a Milwaukee or equivalent power tool designed for EMT cutting, or using a manual pipe cutter that also holds the tubing.

Conduit is also cut by using a scoring tool that's almost identical to a traditional copper pipe cutting tool - we'll show one below. The tech marks the cut line, adjusts the scoring wheel to the cut mark, and holds the tubing with her free hand.

EMT scoring tool used for cutting electrical conduit - cited & discussed at InspectApedia.com

On 2020-11-23 by Anonymous

use to hold conduit pipes when threading , cutting, and installing fittings


...

Continue reading  at ELECTRICAL CONDUIT DEFECTS & DAMAGE or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see these

Recommended Articles



Suggested citation for this web page

ELECTRICAL CONDUIT BEND CONNECT TOOLS at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.


Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to ELECTRICAL INSPECTION & TESTING

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.

Search the InspectApedia website

Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.

Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification
when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
Our Comment Box is provided by Countable Web Productions countable.ca

Comment Form is loading comments...

Citations & References

In addition to any citations in the article above, a full list is available on request.



ADVERTISEMENT