InspectAPedia.com InspectAPedia®
 

Free Encyclopedia of Building & Environmental Inspection, Testing, Diagnosis, Repair

Ask a Question or Search InspectAPedia

  • HOME
  • AIR CONDITIONING
  • ELECTRICAL
  • EXTERIORS
  • HEATING
  • HOME INSPECTION
  • INTERIORS
  • PLUMBING
  • ROOFING
  • SEPTIC SYSTEMS
  • STRUCTURE
  • WATER SUPPLY
  • ENERGY SAVINGS
  • ENVIRONMENT
  • INDOOR AIR IAQ
  • INSULATION
  • MOLD INSPECT TEST REMOVE
  • NOISE
  • ODORS
  • SOLAR ENERGY
  • VENTILATION
  • EXPERTS DIRECTORY
  • CONTACT US


Mobile Phone/PDA website viewMobile View
ELECTRICAL INSPECTION, DIAGNOSIS, REPAIR

AFCIs ARC FAULT CIRCUIT INTERRUPTERS
ALUMINUM SECs & WIRING
ALUMINUM WIRING HAZARDS & REPAIRS
AMPS & VOLTS DETERMINATION
AMPACITY - the LIMITING FACTOR
APPLIANCE EFFICIENCY RATINGS

BACKUP ELECTRICAL GENERATORS
BOOKSTORE - ELECTRICAL
BUILDING SAFETY HAZARDS GUIDE

Cadet & Encore Heater Recall
CIRCUIT BREAKER FAILURE
Classified CIRCUIT BREAKER WARNING
CIRCUIT BREAKER SIZE for A/C or HEAT PUMP
Classified CIRCUIT BREAKER WARNING
CUTLER HAMMER PANEL FIRE
CONDUIT, ELECTRICAL
CORROSION in ELECTRICAL PANELS
CORROSION & MOISTURE SOURCES in PANELS

DEFINITIONS of ELECTRICAL TERMS

DIRECTORY OF ELECTRICIANS

ELECTRIC HEAT
ELECTRIC METERS & METER BASES
ELECTRIC MOTOR DIAGNOSTIC GUIDE
ELECTRIC MOTOR OVERLOAD RESET SWITCH
ELECTRIC PANEL AMPACITY
ELECTRIC PANEL INSPECTION
ELECTRIC PANEL MOISTURE
Electric Power Frequency Table
ELECTRICAL BASICS
  Electricity Basics - how it works
  Electrical Circuit ID, Map & Label
  Electrical Circuits, shorts
  Electrical Code Basics
  ELECTRICAL CONDUIT
  Electrical Grounding Basics
    Grounding
    Knob-and-tube wiring
    Electrical Shorts
    Polarized Plugs, Receptacles, Lights
  Electrical Outlet-how to add
  Electrical Splices, how to make
  Electrical Tools & Tests
  Electrical Wire Stripping Tips
  Electrical Wiring Books & Guides
  Electrical Wiring in Old Houses
EMF RF FIELD & FREQUENCY DEFINITIONS

ELECTRICAL GENERATORS
ELECTRICAL GROUND SYSTEM INSPECTION

ENERGY SAVINGS in buildings

FEDERAL PACIFIC FPE HAZARDS
  Gas Piping Ground Bond
  TABLE OF GROUND WIRE SIZES
  Old House Electrical Grounding
  False Ground at Receptacles
  False Neutral Connections
  Case History: Double Fault Leads to Loss of Power
  Case History:Loss of Neutral Shocks Homeowner
  Electrical Service Grounding Checklist
  Why Grounding is Needed
FEDERAL PACIFIC FPE HAZARDS
ELECTRICAL GROUND SYSTEM INSPECTION
FIRE SAFETY Checklist, CPSC

GENERATORS, ELECTRICAL
GFCI PROTECTION,Testing GFCIs AFCIs

HEATING COST FUEL & BTU Cost Table
HEAT, ELECTRIC
HEAT TAPE USAGE GUIDE
Hertz - Definitions of KHz MHz GHz THz

KNOB & TUBE WIRING

LIGHTING, INTERIOR GUIDE

LIGHTNING PROTECTION SYSTEMS

LOW VOLTAGE BUILDING WIRING

MAIN DISCONNECT
MAIN DISCONNECT AMPACITY
MOISTURE SOURCES in PANELS
MULTI-WIRE CIRCUITS
MURRAY SIEMENS Recall

PHOTOVOLTAIC POWER SYSTEMS
PUSHMATIC - BULLDOG PANELS

REMOTE ELECTRIC POWER, PHOTOVOLTAIC
RUST in ELECTRICAL PANELS

SAFETY FOR ELECTRICAL INSPECTORS

SE CABLE SIZES vs AMPS
SIEMENS MURRAY Recall

SOLAR ENERGY SYSTEMS
SQUARE-D RECALLS

UNDERGROUND SERVICE LATERALS
VOLTAGE MEASUREMENT EQUIPMENT

WIND ENERGY SYSTEMS
WIND TURBINES & LIGHTNING

ZINSCO SYLVANIA ELECTRICAL PANELS

More Information

Jumper wires needed at non-conductive pipe fittings (C) Carson Dunlop

Why We Need Electrical System Grounds, Ground Wiring, Grounding Conductors, Grounding Electrodes
InspectAPedia®  -    

  • Why we need electrical grounding - what grounds, grounding, bonding, earthing do for electrical safety
  • Definition of ground, grounding, grounded, grounding conductor, grounded conductor, bonding, earth, earthing
  • Case histories of ground system failures, loss of electrical power, electrical shocks
  • Class on how to inspect electrical panels
  • Home inspection procedures and safety
InspectAPedia offers impartial, unbiased advice without conflicts of interest. We will block advertisements which we discover or readers inform us are associated with bad business practices, false-advertising, or junk science. our contact info is at InspectAPedia.com/Contact.htm.

This document discusses the details of why we need grounding, and definitions of electrical grounding and electrical bonding (what's the difference between these two terms. While we have frequently updated and added to the material, in its original form this information was presented by Daniel Friedman - InspectAPedia.com, at the Hudson Valley chapter of the American Society of Home Inspectors - HVASHI Seminar 12 Sept 2002, Updated April 2006. Sketch at page top courtesy of Carson Dunlop.

“Grounding”, article 250 in the NEC, is probably one of the most difficult of the often used articles. In 2005 article 250 became “Grounding and bonding”. In the 2008 NEC there has been a major revision in language, and phrases like “shall be grounded” have changed to “shall be connected to an equipment grounding conductor.” Here we define electrical ground, grounding, bonding, and earthing terms and explain why there are important differences among these words.

Readers of this article should also be sure to review False Ground at Receptacles where we describe false grounds and un-grounded or un-polarized electrical receptacles and circuits, and see Safety Hazards and Safe Electrical Inspection Procedures for Inspectors examining Residential Electrical Systems and Local Electrical Grounding for safety procedures during inspection of the grounding system. Sketch courtesy of Carson Dunlop.

See Definitions of Electrical Ground, Grounding Electrode, Grounding Conductor, Grounded Conductor, Ground Wire, Neutral Wire, Ground Rod, for definitions of these confusing electrical terms.

© Copyright 2012 InspectAPedia.com, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use page top links to major topics or use links at the left of each page to navigate within topics and documents at this website. Green links show where you are in a document series or at this website.

Why Do We Need Electrical Grounding, Ground Rods, Earthing, Bonding in Electrical Wiring Systems?

Why we need electrical grounding (C) Carson Dunlop

Why we need electrical grounding

Speaking first a bit loosely (we'll get careful and detailed in a minute) the grounding system at a building provides an easy path for electricity to flow to earth should certain problems occur (a power surge, lightning strike).

Bonding or connection in the electrical panel between the neutral wires, ground wires, and the utility company's incoming neutral wire allowing current to flow to the utility company's wiring, assuring that a circuit breaker will trip or fuse will blow should a problem occur such as a short circuit or overloaded circuit.

Properly operating these overcurrent devices help prevent fire and shock.

Should an electrical fault occur where no neutral connection to the utility company or no local ground path is present, the electrical potential is just sitting there waiting for a person to come along, touch some component of the system, and by accidentally providing a path to earth through their body, receive a burn or potentially fatal shock.

Sketch courtesy of Carson Dunlop.

Details of why we need grounding, and definitions of electrical grounding and electrical bonding (what's the difference between these two terms) can be read at Why Grounding is Needed.

Bud, a master electrician from Minnesota has offered these important clarifications:

"Grounding" has 2 main functions.

One is to provide a path to trip a breaker in the event of a 'short' as in the text above. That function relies on a "ground"-to-neutral connection required at services in the US (the "main bonding jumper"). The path is (branch circuit ground wire) to (N-G bond at the service) to (service neutral) to (utility power transformer).

This path *must* be metallic back to the power transformer to provide low resistance to trip a circuit breaker. This function will work even if the service is not connected to earth. And the NEC *does not allow* earth to be used as part of this path.

Fake electrical ground rod (C) Daniel Friedman

One reason is the resistance of an earth path is too high. Assume the earthing is only through a ground rod and the rod has a quite good 10 ohms resistance to earth. Further assume there is a 'short' connecting hot to "ground". The current to earth will be 12A.

There is a good chance this won't even trip a 15A circuit breaker. If the circuit is loaded the breaker will trip, but after a significant time delay. In the mean time, the "ground" potential with respect to the earth away from the ground rod will be 120V.

Note that if you are using the earth as in the quote above, the path is not just into the earth. It is back to the power source, and also depends on the earth connection at the power transformer.

This would be better termed a *bonding* function.

Showing the elecrical path to earth (C) Carson Dunlop

Carson Dunlop's sketch shows how the electrical current in a building can find its way to earth by way of the electrical grounding system. But as you may want to read in our case study of loss of all ground connections at a building, don't assume that the current will always find its way to earth.

Loss of electrical ground at a building is extremely dangerous and risks electrocution.

Some discussion points about electrical grounding are listed just below.

  • Required for safety, lets fuses blow
  • Example: toaster falls into metal sink
  • Grounding Electrode Conductor wire from service equipment to
  • House plumbing (grounds the plumbing)
  • Entering metal water pipe (grounds the system)
  • Grounding Electrode (two now recommended)
  • Continuous, no splices, meter bypass
  • Copper ground wires and grounding conductor (corrosion resistant)
  • Aluminum - insulated solid conductor (See ALUMINUM WIRING HAZARDS & REPAIRS and also ALUMINUM GROUND WIRES)
  • Aluminum - insulated multi-strand
  • Aluminum - bare vs. insulated (risk of corrosion, break in wire, loss of safe grounding - illustrated below)

Why We Need Electrical Grounding in buildings

Bud - Master Electrician, State of Minnesota

Electrical “Grounding” has two jobs in a building: an “earthing” and a “bonding” function.

What is Electrical Grounding? "Earthing"

A major purpose of “grounding” is to provide a path so a “short” will trip a breaker. That requires a low resistance path back to the power source, which is the utility transformer. The path relies on a neutral-ground connection required at all [not entirely true] services.

The second "grounding" function is actually a collection of three safety functions:

  1. minimize the voltage between exposed metal and the earth
  2. minimize the voltage between the power wires and the earth
  3. provide a sink for lightning, power line crosses, and similar hazards

Fake ground electrode disclosed (C) Daniel FriedmanThe 1st grounding function described above is accomplished by connecting the grounding conductors at the service to an earthing electrode.

The 2nd grounding function described above is accomplished by connecting the power neutral (the neutral wire entering from the utility company's service) at the service to an earthing electrode (ground rod). Provided it's a real earthing electrode not a fake one as we found in our photo (left).

The 3rd grounding function described above is accomplished by both of the above.

Practically, all three grounding functions are accomplished by a required neutral-ground connection at the power service, with the combined neutral-ground connected to an earthing electrode or electrodes. This function might best be called “earthing”.

What is Electrical Bonding?

The path is from a ground conductor [which is not necessarily a wire] to the service panel, through the neutral-ground connection, and back to the transformer via the service neutral. To provide high current to trip a breaker this must be a metal path.

The earth is far too high in electrical resistance and is not allowed to be the path. In fact this function will work if the service is not connected to earth. This function might best be called “bonding”.

Connecting exposed metal together to minimize voltage between surfaces is also a “bonding” function.

There might be some virtues to showing the Neutral-to-Ground bond (called the main bonding jumper). As I wrote previously, it is barely visible in the Carson Dunlap diagram (above) with “Electrical path for ground and neutral wires”.

When a professional examines the interior of a main electrical panel, she looks to see if there has a strap for the bond between neutral and ground buses and to the grounding conductor leading to the earthing rod (ground rod). In some panels such as SquareD the bond is a screw (and very hard to identify if you don’t know what to look for - some home inspectors have trouble finding Neutral-Ground bonds.)

See Definitions of Electrical Ground, Grounding Electrode, Grounding Conductor, Grounded Conductor, Ground Wire, Neutral Wire, Ground Rod, for definitions of these confusing electrical terms.

More details about electrical grounding can be read at ELECTRIC SERVICE GROUNDING SYSTEM INSPECTION and Electrical Circuits, shorts, and at Electrical Wiring in Old Houses.

Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

ELECTRIC PANEL INSPECTION
ELECTRIC PANEL MOISTURE
Electric Power Frequency Table
ELECTRICAL BASICS
  Electricity Basics - how it works
  Electrical Circuit ID, Map & Label
  Electrical Circuits, shorts
  Electrical Code Basics
  ELECTRICAL CONDUIT
  Electrical Definitions
  Electrical Grounding Basics
  Electrical Outlet-how to add
  Electrical Splices, how to make
  Electrical Tools & Tests
  Electrical Wire Stripping Tips
  Electrical Wiring Books & Guides
  Electrical Wiring in Old Houses
EMF RF FIELD & FREQUENCY DEFINITIONS

ELECTRICAL GENERATORS
ELECTRICAL GROUND SYSTEM INSPECTION

ENERGY SAVINGS in buildings

FEDERAL PACIFIC FPE HAZARDS
  Gas Piping Ground Bond
  TABLE OF GROUND WIRE SIZES
  Old House Electrical Grounding
  False Ground at Receptacles
  False Neutral Connections
  Case History: Double Fault Leads to Loss of Power
  Case History:Loss of Neutral Shocks Homeowner
  Electrical Service Grounding Checklist
  Why Grounding is Needed

Also, see details about electrical grounding at Electrical Circuits, shorts, and at Electrical Wiring in Old Houses and at Electricity Basics - how it works.

At ALUMINUM GROUND WIRES we discuss proper repair of aluminum ground wires found in solid conductor branch circuit wiring.

Questions & Answers regarding this article

.

Ask a Question or Search InspectAPedia

HTML Comment Box is loading comments...

Share this Article      

...

Technical Reviewers & References

  • InspectAPedia.com® - Daniel Friedman - Publisher & Editor.
  • InspectAPedia Bookstore lists recommended books, organized by topic & available for purchase. Most of our articles also include a list of recommended books for the specific article topic as well as other references, and information sources.
  • Critique, contributions wanted: Contact Us to suggest corrections or additions to articles at this website, and if you wish, to receive online listing and credit as a contributor. Particular thanks are due to the many experts and also consumers who read and critique technical articles at InspectAPedia.com.
  • Additional technical contributors & reference sources for this article are listed below.

Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

ELECTRICAL GROUND SYSTEM INSPECTION
  Why Grounding is Needed
  Gas Piping Ground Bond
  Table of Ground Wire Sizes
  False Ground at Receptacles
  False Neutral Connections
  Case History: Double Fault Leads to Loss of Power
  Case History:Loss of Neutral Shocks Homeowner
  Electrical Service Grounding Checklist

  • See Definitions of Electrical Ground, Grounding Electrode, Grounding Conductor, Grounded Conductor, Ground Wire, Neutral Wire, Ground Rod, for definitions of these confusing electrical terms.
  • More details about electrical grounding can be read at ELECTRIC SERVICE GROUNDING SYSTEM INSPECTION and Electrical Circuits, shorts, and at Electrical Wiring in Old Houses.
  • At ALUMINUM GROUND WIRES we discuss proper repair of aluminum ground wires found in solid conductor branch circuit wiring.
  • Carson, Dunlop & Associates Ltd., 120 Carlton Street Suite 407, Toronto ON M5A 4K2. (416) 964-9415 1-800-268-7070 info@carsondunlop.com. Thanks to Alan Carson and Bob Dunlop, for permission to use illustrations from their publication, The Illustrated Home which illustrates construction details and building components. Carson Dunlop provides home inspection education including the ASHI-adopted Home Inspection Training Program (home study course), publications such as the Home Reference Book, report writing materials including the Horizon report writer, and home inspection services. Alan Carson is a past president of ASHI, the American Society of Home Inspectors.
  • Timothy Hemm, Yucala, CA, contributed the photographs of electrical equipment installed in California buildings. Mr. Hemm can be contacted at TimHemm@yahoo.com
  • Special thanks to Bud - a master electrician in Minnesota who contributed text and suggestions for explaining why we need electrical grounding, and for discussing the shortcomings of neon testers and plug-in receptacle testers - 1/22/2009

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.
  • Recommended books on electrical inspection, electrical wiring, electrical problem diagnosis, and electrical repair can be found in the Electrical Books section of the InspectAPedia Bookstore. (courtesy of Amazon.com)
  • * Safety Hazards and Safe Inspection Procedures for Electrical and Home Inspectors at Residential Electric Panels
  • Aluminum Wiring Information Website Aluminum Electrical Wiring Hazards and Repairs: in-depth authoritative info, photos, documents including selection of proper vs. ineffective repair methods. E.g.: Ideal 65 "Twister" purple connector fails in field and lab testing with aluminum wire.
  • Ampacity of an Electrical Service: How to determine the electrical service size or ampacity entering a building
  • Circuit Breaker, a bad one fails to trip failure at aluminum bus-to-circuit breaker connection - field report and photographs
  • Electrical Panels, How to Inspect in buildings, safety for electrical inspectors, electrical panel, fusing, wiring defects, defective products. Inspection Class Presentation
  • Federal Pacific Electric (FPE) Stab-Lok Circuit Breaker Panel Hazards Website - Latent fire hazards, in-depth authoritative research, documents, advice on Stab-Lok electric panel and circuit breaker failures and what to do when this equipment is found in buildings.
  • Lightning Strike Risk Assessment, Protection Systems & Services
  • Multi-wire branch circuit inspection and defects
  • Rust and Corrosion in Electrical Panels, A Study and Report on Frequency and Cause for Electrical and Home Inspectors at Residential Electric Panels
  • "Electrical System Inspection Basics," Richard C. Wolcott, ASHI 8th Annual Education Conference, Boston 1985.
  • Safety Hazards and Safe Inspection Procedures for Electrical and Home Inspectors at Residential Electric Panels
  • "Simplified Electrical Wiring," Sears, Roebuck and Co., 15705 (F5428) Rev. 4-77 1977 [Lots of sketches of older-type service panels.]
  • "How to plan and install electric wiring for homes, farms, garages, shops," Montgomery Ward Co., 83-850.
  • "Electrical System Inspection Basics," Richard C. Wolcott, ASHI 8th Annual Education Conference, Boston 1985.
  • "Simplified Electrical Wiring," Sears, Roebuck and Co., 15705 (F5428) Rev. 4-77 1977 [Lots of sketches of older-type service panels.]
  • "How to plan and install electric wiring for homes, farms, garages, shops," Montgomery Ward Co., 83-850.
  • "Home Wiring Inspection," Roswell W. Ard, Rodale's New Shelter, July/August, 1985 p. 35-40.
  • "Evaluating Wiring in Older Minnesota Homes," Agricultural Extension Service, University of Minnesota, St. Paul, Minnesota 55108.
  • "Electrical Systems," A Training Manual for Home Inspectors, Alfred L. Alk, American Society of Home Inspectors (ASHI), 1987, available from ASHI. [DF NOTE: I do NOT recommend this obsolete publication, though it was cited in the original Journal article as it contains unsafe inaccuracies]
  • "Basic Housing Inspection," US DHEW, S352.75 U48, p.144, out of print, but is available in most state libraries.
  • Electrical System & Wiring Hazard Inspection, Detection, Cause, Remedy, Prevention - Main Electrical Page
  • ...
Home About Us Accuracy Contact Us Content Use Policy Privacy Website Description © 2012 Copyright InspectAPedia.com