InspectAPedia.com InspectAPedia®
Google
InspectAPedia
 

Free Encyclopedia of Building & Environmental Inspection, Testing, Diagnosis, Repair

Ask a Question or Search InspectAPedia

  • HOME
  • AIR CONDITIONING
  • DAMAGE ASSESSMENT
  • ELECTRICAL
  • EXTERIORS
  • HEATING
  • HOME INSPECTION
  • INTERIORS
  • PLUMBING
  • ROOFING
  • SEPTIC SYSTEMS
  • STRUCTURE
  • WATER SUPPLY
  • ENERGY SAVINGS
  • ENVIRONMENT
  • INDOOR AIR IAQ
  • INSULATION
  • MOLD INSPECT TEST REMOVE
  • NOISE
  • ODORS
  • SOLAR ENERGY
  • VENTILATION
  • EXPERTS DIRECTORY
  • CONTACT US



InspectAPedia ® Home

ELECTRICAL INSPECTION, DIAGNOSIS, REPAIR

AFCIs ARC FAULT CIRCUIT INTERRUPTERS
ALUMINUM WIRING HAZARDS & REPAIRS
AMPS VOLTS DETERMINATION
APPLIANCE EFFICIENCY RATINGS

BOOKSTORE - ELECTRICAL

Cadet & Encore Heater Recall
CIRCUIT BREAKER SIZE for A/C or HEAT PUMP
Classified CIRCUIT BREAKER WARNING
CUTLER HAMMER PANEL FIRE
CONDUIT, ELECTRICAL
CORROSION in ELECTRICAL PANELS

DEFINITIONS of ELECTRICAL TERMS
DIRECTORY OF ELECTRICIANS
DMM Digital Multimeter, How to Use

ELECTRIC HEAT
ELECTRIC METERS & METER BASES
ELECTRIC MOTOR DIAGNOSTIC GUIDE
ELECTRIC MOTOR OVERLOAD RESET SWITCH
ELECTRIC PANEL AMPACITY
ELECTRIC PANEL INSPECTION
ELECTRIC PANEL MOISTURE
Electric Power Frequency Table
ELECTRICAL BASICS
EMF RF FIELD & FREQUENCY DEFINITIONS
ELECTRICAL GROUND SYSTEM INSPECTION
ELECTRICAL SERVICE DROP
ELECTRICAL SERVICE ENTRY WIRING
ELECTRICAL TERMS
EMF RF FIELD & FREQUENCY DEFINITIONS

FIRE SAFETY Checklist, CPSC

GENERATORS, ELECTRICAL
GFCI PROTECTION,Testing GFCIs AFCIs

HEATING COST FUEL & BTU Cost Table
HEAT, ELECTRIC
HEAT TAPE USAGE GUIDE
Hertz - Definitions of KHz MHz GHz THz

KNOB & TUBE WIRING

LIGHTING, EXTERIOR GUIDE
LIGHTING, INTERIOR GUIDE
LIGHTNING PROTECTION SYSTEMS
LOW VOLTAGE BUILDING WIRING
LOW VOLTAGE TRANSFORMER TEST

MAIN DISCONNECT
MAIN DISCONNECT AMPACITY
MOISTURE SOURCES in PANELS
MULTI-WIRE CIRCUITS
MURRAY SIEMENS Recall

PHOTOVOLTAIC POWER SYSTEMS
PUSHMATIC - BULLDOG PANELS

REMOTE ELECTRIC POWER, PHOTOVOLTAIC
RUST in ELECTRICAL PANELS

SAFETY for ELECTRICAL INSPECTORS
SE CABLE SIZES vs AMPS
SIEMENS MURRAY Recall
SQUARE-D RECALLS

THERMAL EXPANSION of HOT WATER
THERMAL EXPANSION of MATERIALS

UNDERGROUND SERVICE LATERALS
VOLTS / AMPS MEASUREMENT EQUIP

WIND TURBINES & LIGHTNING

ZINSCO SYLVANIA ELECTRICAL PANELS

More Information

Neutral joined with ground in sub panel (C) Daniel Friedman How Loss of the Neutral Connection in a Sub Panel Led to a Dangerous Electrical Shock
     

  • LOST NEUTRAL Shocks Homeowner - Case history of a neutral wire failure, improper joining of neutral and ground wiring in a sub panel, burning-up electrical ground wires, and a homeowner who received a nasty electrical shock
    • Photographs of electrical sub panel mis-wiring, overheating, and shock hazards
    • How to inspect the electrical ground system: wires, grounding conductors, connectors, ground rods
    • Why Do Electrical Power Surges or Lightning Strike Current Go to Ground While Short Circuits Follow a Path to the Utility Ground?
  • FALSE GROUND at Receptacles - separate article
  • FALSE NEUTRAL Connections - separate article
  • LOST ELECTRICAL GROUND - separate article
  • Questions & Answers about neutral wire troubleshooting: what can happen when the neutral connections are lost or weak at a building?
  • References

Click to Show or Hide Related Topics

  • ELECTRICAL INSPECTION, DIAGNOSIS, REPAIR - home
  • AFCIs ARC FAULT CIRCUIT INTERRUPTERS
  • DEFINITIONS of ELECTRICAL TERMS
  • DIRECTORY OF ELECTRICIANS
  • DMM Digital Multimeter, HOW TO USE
  • DMM & VOM SAFETY
  • ELECTRIC PANEL INSPECTION
  • ELECTRICAL BASICS
  • Electrical Code Basics
  • ELECTRICAL TOOLS BASIC
  • GFCI PROTECTION,Testing GFCIs AFCIs
  • GROUND SYSTEM INSPECTION
    • DOUBLE FAULT, LOSS OF ELECTRICITY
    • ELECTRICAL GROUNDING BASICS
    • ELECTRICAL GROUND INSPECTION SAFETY
    • ELECTRICAL GROUND REQUIREMENTS
    • FALSE GROUND at RECEPTACLES
    • FALSE NEUTRAL CONNECTIONS
    • GAS PIPING GROUND BOND
    • LOST ELECTRICAL GROUND
    • LOST NEUTRAL Shocks Homeowner
    • OLD HOUSE ELECTRICAL GROUNDING
    • SERVICE GROUNDING DEFECTS
  • GROUND SYSTEM REQUIREMENTS
  • KNOB & TUBE WIRING
  • LIGHTNING PROTECTION SYSTEMS
  • LOW VOLTAGE BUILDING WIRING
  • OLD HOUSE ELECTRICAL WIRING
  • SAFETY for ELECTRICAL INSPECTORS
  • TEST EQUIPMENT, ELECTRICAL
  • THERMISTORS
  • VOLTAGE DETECTION & MEASUREMENT
  • VOLTS / AMPS MEASUREMENT EQUIP
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

Lost neutral or weak neutral wire electrical connections at a building: what can happen? This document describes a case history of loss of the neutral connection in an electrical panel combined with failure to isolate the neutral and ground buses leading to an electrical shock.

Green links show where you are. © Copyright 2013 InspectAPedia.com, All Rights Reserved. Author Daniel Friedman.

Case History of an Electrical Ground Failure - Loss of a Neutral Connection in an Electrical Sub Panel Badly Shocks a Homeowner

Burned ground wires in a badly wired sub panel (C) Daniel FriedmanBuilding owner gets a nasty electrical shock: In an electrical failure case which we investigated, a building owner asked us to determine why he had received a severe electrical shock when he touched his metal work bench located in a detached garage.

Here is what we found in the electrical sub panel in the detached garage:

[Click any image in these articles to see an enlarged, detailed version.]

  • Remote sub panel: The detached garage received its electricity through a sub panel mounted in the garage and connected back to the main electrical panel in the home.
  • Local grounding: A ground wire ran from the panel ground bus to a local grounding electrode at the garage.
  • Evidence of overheating ground wires: The panel's copper ground wire was blackened - it was obviously dark from overheating (none of the other copper wires in the panel were discolored).
  • Other circuit ground wires that had been twisted together in the sub panel were also black from overheating.
  • Improper bonding of neutral bus and ground bus in a sub panel led to electric shock: The owner, intending to make his electrical panel "safer", had violated electrical code and good practice by bonding together the neutral bus and the grounding bus in his electrical panel.
  • There was no ground wire connection back to the main electrical panel, just incoming hot wires and incoming neutral wire.

Loose neutral connection in a sub panel (C) Daniel Friedman

  • The panel's incoming neutral wire from the home was not connected. It looked connected but when we wiggled it (power had been shut off at the main building) the neutral wire lifted right out of the connector.

Our photo at left has a black arrow pointing to the incoming neutral wire in the sub panel. The neutral wire looked connected, but it was not.

  • The owner had a high horsepower 3-phase ("converted magically to 2-phase") electric motor driven air compressor in use in the garage. He had modified the motor's electrical wiring as well.
  • The owner had, for safety, grounded his compressor motor and his metal work bench back to the electrical panel's grounding bus.

Question: What did all of these sub panel neutral and ground wire problems & electrical wiring errors mean?

When the air compressor motor was running it was producing a significant current on the compressor's neutral circuit.

The garage neutral circuit had no connection back to the main building (where it would have been connected to earth in the main panel, but because the owner had (improperly) bonded together the ground and neutral bus in his garage sub panel, the garage neutral circuit was indeed finding a path to earth through a small diameter (and thus overheated and dark) copper ground wire and a local grounding electrode.

Bud, a master electrician from Minnesota points out that in the 2005 NEC there are 2 ways to connect a subpanel in a detached garage. In both methods grounding electrode(s) are required at the garage.

  1. Hot-hot-neutral-ground are run to the garage. The neutral bar is isolated. Separate ground bar. The grounding electrode(s) connect to the ground bar.
  2. Hot-hot-neutral are run to the garage (NO ground). This is connected like a service. A “main bonding jumper” is installed to connect the neutral bar to the enclosure. The grounding electrodes are connected to the neutral (or ground) bar. (This method is no longer allowed in the 2008 NEC.)

The description of the garage event above is a case of example #2 above - there needs to be a MBJ [jumper wire] to connect the neutral and “ground”. The connection was not an error. Without the Neutral-to-Ground bond there is no metal return path for ground fault currents back to the utility transformer. The path would depend on an earth connection, which is not effective and is not allowed. (This is the same error as in my original complaint.)

Normally the neutral-to-ground bond is made in the main electrical panel and not in sub panels, lest grounding conductors end up carrying current during normal operations - a shock hazard. As Bud describes above, in the now obsolete, not allowed case, it was possible to wire a remote outbuilding sub panel as if it were a "main", with no ground returning to the actual remote main panel, and with a neutral-ground bond in the sub panel plus an effective local grounding electrode. We do not recommend this obsolete wiring approach. - Ed.

The problem in this case is the loss of the feeder neutral.

Summarizing some key observations in this lost neutral sub panel case:

  1. Neutral wire between sub panel & main panel was not connected; there was a loose, bad connection in sub panel
  2. The only grounding in this outbuilding was a local ground rod (maybe ineffective?)
  3. A 3-phase compressor was "DIY" wired to run 240V - something fishy there
  4. The compressor circuit included two "hot" wires (black and neutral - the upper right two-pole breaker in the page top photo), and a bare ground wire that was overheated and burned.
  5. A metal workbench was connected to subpanel ground and was "live" when the compressor was running - owner got shocked
  6. Wires to circuit breakers in the panel were overheated (feeding the compressor)
  7. The internal bus in the panel was overheated (behind the CBs)
  8. Ground wires were overheated and burned (and were new at the outset) at the sub panel
  9. No mis-wiring nor overheating related to this case were observed in the property's main electrical panel
  10. In the sub panel, the neutral bus and ground bus were connected, so any neutral circuit current that should have traveled back on the main neutral to the main panel was forced to travel on the local ground wiring and grounding conductors.

Summarizing our conclusions (we will amend if with readers we develop a different analysis of this case):

A combination of missing main neutral in sub panel back to main panel, connecting neutral and ground buses in the sub panel, local ground at the sub panel, connection of metal work bench to panel ground bus, and modified 3-phase compressor in operation produced an electrically live workbench (owner was shocked), and conspired to visibly overheat grounding conductors, hot wires to the panel, panel bus behind the breakers, and grounding wire to the local electrode.

Additional photographs from this case are shown just below. Thanks to reader Randy Gardner for discussing this lost neutral case and opening an argument for clarification of just what was going on.

Below left: metal workbench that was connected to ground wire bus in the sub panel. Below right: overheated corroded main bus connections in the sub panel.

Lost neutral short and shock (C) Daniel Friedman Lost neutral short and shock (C) Daniel Friedman

Below left: 3-phase compressor "re-wired" to run on 240V (we suspect that a 3rd leg was connected to a neutral or ground wire at this hookup. Below right: overheated wires in the sub panel at circuit breakers (we suspect these were powering the compressor motor).

Lost neutral short and shock (C) Daniel Friedman Lost neutral short and shock (C) Daniel Friedman

Why Do Electrical Power Surges or Lightning Strike Current Go to Ground While Short Circuits Follow a Path to the Utility Ground?

Question: We were a little unclear as to why surges find their way to the local earth connection (higher resistance path) while in an emergency such as a short circuit hot to neutral or hot to ground wire, the current does not.

Answer: Bud continued this helpful explanation:

It is a question of what is path is necessary to complete the circuit.

If you want to trip a circuit breaker the fault is hot to “ground” you must complete a path back from “ground” to the transformer neutral. If you wan t to trip a breaker, the path must be metal. That requires a N-G bond and return on the service neutral.

For lightning, you accumulate a different charge between the cloud and the earth. The path is then to the earth to neutralize the charges. (A service panel surge suppressor would have current hot-to-ground/earth.) (Any surge current on the neutral connects to earth through the N-G bond.)

The next most major cause of surges is probably utility switching (normal and abnormal). Switching power factor correction capacitors can be a major source. There the path is probably hot to neutral. (A service panel suppressor would have current hot-to-neutral.)

If there is a utility short that causes a fuse to open, there is high current through the inductance of the power wires that stores energy in a magnetic field. When the fuse opens, the current falls causing the magnetic field to collapse which produces a high voltage. Surge current is probably hot to neutral.

If a high voltage distribution wire falls on the wires to a house, the path needs to be back to the high voltage transformer. The path is likely through the earth, but could be through the service neutral if there is a path (there is probably a continuous neutral connection between transformers that feed houses).

Question: Isn't it the case that current always prefers the path of least resistance and that the current can actually be calculated to flow on two (for example) different paths as a direct function of the relative resistance of each path?

Answer: Nicely stated, particularly the end. And in the case of the ground fault tripping a breaker there will be some current through the earth, just like there is some normal neutral current through the earth. But the resistance of the service neutral is far lower than the earth.

The root causes of this electrical shock were:

Neutral should not be  joined with ground in sub panel (C) Carson Dunlop
  • Improper electrical wiring - bonding the ground and neutral wires together in the sub panel
  • A binding steel screw in an aluminum wiring lug in the sub panel's incoming neutral wire connector - tightening the screw made the installer think he was securing the neutral wire when he was not.

Because the garage electrical system was carrying current that should have been flowing only on the insulated neutral wires in the building, when the owner touched his grounded metal work bench and was also touching a damp floor, current flowed through the ground wire, through the metal work bench, through the owner, to earth.

Sketch courtesy of Carson Dunlop Associates.

Our case study of a double fault involving loss of both the utility company ground and the local building ground shows how power can simply be lost in a building due to grounding system defects.

...


Frequently Asked Questions (FAQs) about electrical neutral wiring inspection, troubleshooting, repairs

...

Ask a Question or Search InspectApedia

Questions & answers or comments about neutral wire troubleshooting: what can happen when the neutral connections are lost or weak at a building? .

Ask a Question or Enter Search Terms in the InspectApedia search box just below.

Technical Reviewers & References

Related Topics, found near the top of this page suggest articles closely related to this one.

  • Mark Cramer Inspection Services Mark Cramer, Tampa Florida, Mr. Cramer is a past president of ASHI, the American Society of Home Inspectors and is a Florida home inspector and home inspection educator. Mr. Cramer serves on the ASHI Home Inspection Standards. Contact Mark Cramer at: 727-595-4211 mark@BestTampaInspector.com
  • John Cranor is an ASHI member and a home inspector (The House Whisperer) is located in Glen Allen, VA 23060. He is also a contributor to InspectApedia.com in several technical areas such as plumbing and appliances (dryer vents). Contact Mr. Cranor at 804-747-7747 or by Email: johncranor@verizon.net
  • Carson, Dunlop &
Associates Ltd., TorontoCarson, Dunlop & Associates Ltd., 120 Carlton Street Suite 407, Toronto ON M5A 4K2. (416) 964-9415 1-800-268-7070 info@carsondunlop.com. The firm provides professional home inspection services & home inspection education & publications. Alan Carson is a past president of ASHI, the American Society of Home Inspectors. Thanks to Alan Carson and Bob Dunlop, for permission for InspectAPedia to use text excerpts from The Home Reference Book & illustrations from The Illustrated Home. Carson Dunlop Associates' provides:
    • Commercial Building Inspection Courses - protocol ASTM Standard E 2018-08 for Property Condition Assessments
    • Home Inspection Education Courses including home study & live classes at eleven colleges & universities.
    • Home Inspection Education Home Study Courses - ASHI@Home Training 10-course program.
      Special Offer: Carson Dunlop Associates offers InspectAPedia readers in the U.S.A. a 5% discount on these courses: Enter INSPECTAHITP in the order payment page "Promo/Redemption" space. InspectAPedia.com editor Daniel Friedman is a contributing author.
    • The Home Reference Book, a reference & inspection report product for building owners & inspectors.
      Special Offer: For a 10% discount on any number of copies of the Home Reference Book purchased as a single order. Enter INSPECTAHRB in the order payment page "Promo/Redemption" space. InspectAPedia.com editor Daniel Friedman is a contributing author.
    • The Home Reference eBook, an electronic version for PCs, the iPad, iPhone, & Android smart phones.
      Special Offer: For a 5% discount on any number of copies of the Home Reference eBook purchased as a single order. Enter inspectaehrb in the order payment page "Promo/Redemption" space.
    • The Illustrated Home illustrates construction details and building components, a reference for owners & inspectors.
      Special Offer: For a 5% discount on any number of copies of the Illustrated Home purchased as a single order Enter INSPECTAILL in the order payment page "Promo/Redemption" space.
    • The Horizon Software System manages business operations,scheduling, & inspection report writing using Carson Dunlop's knowledge base & color images. The Horizon system runs on always-available cloud-based software for office computers, laptops, tablets, iPad, Android, & other smartphones.
  • Special thanks to Bud - a master electrician in Minnesota who contributed text and suggestions for explaining why we need electrical grounding, electrical neutrals, and for discussing the shortcomings of neon testers and plug-in receptacle testers - 1/22/2009
  • Thanks to Randy Gardner for discussing this lost neutral case and opening an argument for clarification of just what was going on - 12/27/2010
  • See ELECTRICAL GROUND SYSTEM INSPECTION and Definition of Electrical Ground Terms. Also, see details about electrical grounding at Electrical Circuits, shorts, and at Electrical Wiring in Old Houses and at Electricity Basics - how it works.

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.
  • Home Reference Book - Carson DunlopThe Home Reference Book - the Encyclopedia of Homes, Carson Dunlop & Associates, Toronto, Ontario, 25th Ed., 2012, is a bound volume of more than 450 illustrated pages that assist home inspectors and home owners in the inspection and detection of problems on buildings. The text is intended as a reference guide to help building owners operate and maintain their home effectively. Field inspection worksheets are included at the back of the volume. Special Offer: For a 10% discount on any number of copies of the Home Reference Book purchased as a single order. Enter INSPECTAHRB in the order payment page "Promo/Redemption" space. InspectAPedia.com editor Daniel Friedman is a contributing author.

    Or choose the The Home Reference eBook for PCs, Macs, Kindle, iPad, iPhone, or Android Smart Phones. Special Offer: For a 5% discount on any number of copies of the Home Reference eBook purchased as a single order. Enter INSPECTAEHRB in the order payment page "Promo/Redemption" space.

  • GO TO Carson Dunlop's Home Study Course Information - How to Become a Home Inspector: Carson Dunlop's nationally recognized Home Study Course, selected by ASHI the American Society of Home Inspectors and other professionals and associations. This website author is a contributor to this course.
  • GO TO Carson Dunlop's Home Study Course Information - How to Become a Home Inspector: Carson Dunlop's nationally recognized Home Study Course, selected by ASHI the American Society of Home Inspectors and other professionals and associations. This website author is a contributor to this course.
  • GO TO Carson Dunlop's Home Study Course Information - How to Become a Home Inspector: Carson Dunlop's nationally recognized Home Study Course, selected by ASHI the American Society of Home Inspectors and other professionals and associations. This website author is a contributor to this course.
    Building inspection education & report writing systems from Carson, Dunlop & Associates Ltd
  • Recommended books on electrical inspection, electrical wiring, electrical problem diagnosis, and electrical repair can be found in the Electrical Books section of the InspectAPedia Bookstore. (courtesy of Amazon.com)
  • * Safety Hazards and Safe Inspection Procedures for Electrical and Home Inspectors at Residential Electric Panels
  • Aluminum Wiring Information Website Aluminum Electrical Wiring Hazards and Repairs: in-depth authoritative info, photos, documents including selection of proper vs. ineffective repair methods. E.g.: Ideal 65 "Twister" purple connector fails in field and lab testing with aluminum wire.
  • Ampacity of an Electrical Service: How to determine the electrical service size or ampacity entering a building
  • Circuit Breaker, a bad one fails to trip failure at aluminum bus-to-circuit breaker connection - field report and photographs
  • Electrical Panels, How to Inspect in buildings, safety for electrical inspectors, electrical panel, fusing, wiring defects, defective products. Inspection Class Presentation
  • Federal Pacific Electric (FPE) Stab-Lok Circuit Breaker Panel Hazards Website - Latent fire hazards, in-depth authoritative research, documents, advice on Stab-Lok electric panel and circuit breaker failures and what to do when this equipment is found in buildings.
  • Zinsco Electrical Circuit Breaker Failures: overheating, failure to trip, burn-ups involving Zinsco and certain Sylvania electrical panel components - page under development March 2006.
  • "Electrical System Inspection Basics," Richard C. Wolcott, ASHI 8th Annual Education Conference, Boston 1985.
  • "Simplified Electrical Wiring," Sears, Roebuck and Co., 15705 (F5428) Rev. 4-77 1977 [Lots of sketches of older-type service panels.]
  • "How to plan and install electric wiring for homes, farms, garages, shops," Montgomery Ward Co., 83-850.
  • "Simplified Electrical Wiring," Sears, Roebuck and Co., 15705 (F5428) Rev. 4-77 1977 [Lots of sketches of older-type service panels.]
  • "Home Wiring Inspection," Roswell W. Ard, Rodale's New Shelter, July/August, 1985 p. 35-40.
  • "Evaluating Wiring in Older Minnesota Homes," Agricultural Extension Service, University of Minnesota, St. Paul, Minnesota 55108.
  • "Electrical Systems," A Training Manual for Home Inspectors, Alfred L. Alk, American Society of Home Inspectors (ASHI), 1987, available from ASHI. [DF NOTE: I do NOT recommend this obsolete publication, though it was cited in the original Journal article as it contains unsafe inaccuracies]
  • "Basic Housing Inspection," US DHEW, S352.75 U48, p.144, out of print, but is available in most state libraries.
  • Rust and Corrosion in Electrical Panels, A Study and Report on Frequency and Cause for Electrical and Home Inspectors at Residential Electric Panels
  • Directory of Home Inspectors accessible via internet
  • ...

HOME ABOUT CONTACT COPYING DESCRIPTION POLICIES PRINTING PRIVACY © 2013 Copyright InspectAPedia.com