InspectAPedia ®

Building & Environmental Inspection, Testing, Diagnosis, Repair, & Problem Prevention Advice
Home | Air
Conditioning
| Electrical
-
Energy Saving
| Environment
Indoor
| Exteriors | Heating | Home
Inspection
| Insulate
-
Ventilate
| Interiors | Mold
Inspect/Test
| Plumbing
Water
Septic
| Roofing | Solar
Energy
| Structure | Contact Us
Directory of Professionals to Inspect or Test a Building


EXTERIORS of BUILDINGS
AGE of a BUILDING - how to determine
ALGAE, FUNGUS, LICHENS, MOSS
ATTIC CONDENSATION
BASEMENT WATERPROOFING
BOOKSTORE - EXTERIORS
CHIMNEY INSPECTION DIAGNOSIS REPAIR
DECK & PORCH CONSTRUCTION
DECK COLLAPSE Case Study
DECK FLASHING LEAKS, ROT Case Study
EARTHQUAKE DAMAGED FOUNDATIONS
ENERGY SAVINGS in BUILDINGS
ENVIRONMENTAL HAZARDS
FLOOD DAMAGE ASSESSMENT, SAFETY & CLEANUP
HEAT TAPES & CABLES on Roofs for Ice Dams
HOUSEWRAP AIR & VAPOR BARRIERS
LEAD TEST KIT for HOME USE
LOG HOME GUIDE
LIGHTNING PROTECTION
MOLD DETECTION & INSPECTION GUIDE
ODORS & SMELLS DIAGNOSIS & CURE
PAINT ANALYSIS USES
PAINT & STAIN GUIDE, EXTERIOR
PAINT FALURE, DIAGNOSIS, CURE, PREVENTION
PORCHES & Sunrooms
ROOFING DIAGNOSIS INSPECTION & REPAIR
SEPTIC SYSTEMS
SHEATHING, Gypsum board
SHEATHING Homasote & Other Board
SHEATHING, OSB
SHEATHING, Plywood
SHEATHING, FOIL FACED - VENTS
SIDING, ASBESTOS CEMENT SHINGLES
SIDING EIFS STUCCO
SIDING HARDBOARD
  Abatibi Siding Claims
  Boise Cascade Siding Claims
  JamesHardie HardiPlank Siding
  Masonite Siding Claims
SIDING VINYL
SIDING WOOD
STAIN DIAGNOSIS on Building Exteriors
STAIN DIAGNOSIS on Indoor Surfaces
STAIRS, RAILINGS, LANDINGS, RAMPS
STUCCO OVER FOAM INSULATION
STUCCO PAINT FAILURES
TERMITES, ROT
THERMAL EXPANSION of MATERIALS
THERMAL MASS in BUILDINGS
  THERMAL MASS FLOOR SLABS
  THERMAL MASS in UPSTAIRS
  THERMAL MASS WALL DESIGN
VAPOR BARRIERS & AIR SEALING at BAND JOISTS
VAPOR BARRIERS & CONDENSATION in BUILDINGS
VAPOR BARRIERS & HOUSEWRAP
VAPOR CONDENSATION & BUILDING SHEATHING
VENTILATION in BUILDINGS
WATER ENTRY in BUILDINGS
  ATTIC LEAKS Moisture or Mold
  BASEMENT HEAT LOSS
  BASEMENT LEAKS Moisture or Mold
  BASEMENT WATERPROOFING
  Chimney Leaks
  CRAWL SPACE Dryout Procedures
  DEW POINT CALCULATION for WALLS
  DEW POINT TABLE - CONDENSATION POINT GUIDE
  EFFLORESCENCE, Salts & White / Brown Deposits
  FLOOD Damage Assessment & Repairs
  FLOOD DAMAGED FOUNDATIONS
  FLOOD VENTS & FLOOD PORTS
  FLOODS IN BUILDINGS-priorities
  FOUNDATION WATERPROOFING
  HUMIDITY CONTROL & TARGETS INDOORS
  HOUSEWRAP AIR & VAPOR BARRIERS
  LOG HOME Leak Diagnosis & Cure
  LOG HOME Condensation &Moisture
  MOISTURE CALCULATIONS
  MOISTURE PROBLEMS: CAUSE & CURE
  MOLD in BUILDINGS
  SEWAGE CONTAMINATION
  SUMP PUMPS GUIDE
  WATER ENTRY in BUILDINGS
WIND TURBINES
WINDOWS & DOORS
  SKYLIGHT LEAK DIAGNOSIS & REPAIR
  SITE BUILT DOUBLE GLAZED WINDOWS
  SLOPED GLAZING DETAILS
  SUNGAIN, FILMS, LOW-E GLASS
  VERTICAL GLAZING DETAILS
  WINDOW / DOOR ENERGY EFFICIENT, DOE
  WINDOW LEAKS INTO BASEMENT
WINTERIZE A BUILDING
MOLD DETECTION & INSPECTION GUIDE
MVOCs & MOLDY MUSTY ODORS
MYCOTOXIN EFFECTS of MOLD EXPOSURE
NOISE / SOUND DIAGNOSIS & CURE
ODOR DIAGNOSIS CHECKLIST
ODORS & SMELLS DIAGNOSIS & CURE
ROOFING INSPECTION & REPAIR

More Information

InspectAPedia.comInspectAPedia ® Home & Site Map
InspectAPedia Blog - News Updates
Air Conditioning & Heat Pumps
Bookstore
Electrical
Environment
Exteriors
Heating
Home Inspection
Insulate Ventilate
Interiors
Mold Inspect/Test
Plumbing Water Septic
Roofing
Structure
Accuracy & Privacy Policies
Contact Us



Photograph of deteriorated James Hardiplank hardboard siding.

James HardiPlank® Cementboard Siding Information
InspectAPedia®  -    

  • James HardiPlank® cement board siding information & company contact data.
  • James HardiPlank® stain coating failure case study
  • James HardiPlank® lap siding installation instruction guide
  • Typical diagnostic steps and lab assessment fees for assessing coating failures on cementious building siding materials
Our site offers impartial, unbiased advice without conflicts of interest. We will block advertisements which we discover or readers inform us are associated with bad business practices, false-advertising, or junk science. Our contact info is at InspectAPedia.com/appointment.htm.

James Hardiplank™ cementboard siding product information. On the James Hardiplank cement board siding shown at the top of this page stain was found flaking off of the siding - a subject of consumer complaint about this home located in central Nebraska. Building paper was installed below the siding, there was no evidence of delamination or water damage, and the siding was delivered to the builder (Wardcraft) already stained.

James Hardiplank™cement board siding is a cementious product (also see SIDING, ASBESTOS CEMENT SHINGLES). This material is NOT the same composition as hardboard siding products sold by Abatibi Corp, Masonite Corp., Boise Cascade, and Georgia Pacific Corp, all of which experience failures of delamination, swelling, softening, and general deterioration when exposed to water and weather, depending on the quality of installation, exterior coatings, and maintenance.

James Hardiplank Surface Coating Failure Investigation & Case History

Reader Marie Carr provided the page top photograph along with the following case history as part of a an investigation into the most-likely cause of a stain flaking problem observed on this building's siding: (See PAINT FALURE, DIAGNOSIS, CURE, PREVENTION for a detailed paint and stain failure analysis guide.)

We have James Hardiplank siding that was stained. When we tried to make a claim against the company, they indicated that they recommended their siding not be stained. So then we are trying to make a claim against the company that stained the product, and they indicate that it was moisture in the board that is causing the siding to flake. So as you can see, we are going in circles at this time. The stain company suggests we paint over the siding as a correction and we would like your opinion on that corrective measure. We would like an independent company determine, if possible, what is actually causing the siding to flake off.

We are looking for independent lab to test siding to see why stain is lifting from the cement board siding.
It is also spider web cracking. Here is the picture of the area we removed the siding from. We are not sure how the stain was applied. From what we know, the siding was delivered to Wardcraft stained. We purchased additional siding from them when we completed our garage and it was wrapped with packing material between the pieces. The home was assembled in doors at their factory in Minden, NE, siding was placed on the home there, for the most part in Feb 2005, with the remaining siding placed on the home once it was set at our site, March 2005. The only siding that was put on the home at the site was the top peak on the north side. Weather, from what I can remember, was sunny. As I indicated, the siding was stained when they placed it on the home.

When we picked up the siding we bought for the garage from Wardcraft, we asked for some stain at that time, and they told us that we could use stain that we purchased from a local supplier, they didn't have any stain there.

Typical Steps in Diagnosing & Curing Hardiplank™ or Other Cementious-Siding Flaking and Cracking Problems

We also want to inspect or otherwise see photos of all sides of the home, showing distant and closeup images of the failures. We want to know how the peeling varies by location.

We will also want to know the age and leak history of the home – any leaks of any kind that have ever occurred, and where water passed.

HardiPlank® siding instructions require that the surface be painted; they recommend a combination of factory primer and an acrylic topcoat. They are within their rights to object to coating with a stain.

Once a siding coating failure has been observed, we would not paint over the stain before we have some confidence that we know the cause of the failure, and further, that we have some assurance that the paint-over coating will bond with the surface adequately (special prep may be needed) and that it is chemically compatible with the existing stain. Else you may have a new failure.

A very careful collection of surface samples of peeling material as well as some tape samples of the surface right under where a fresh peeled stain has just come off might be diagnostic.

In the forensic laboratory we can examine, and dissect a short piece of siding that is representative of the failure. To examine a failure such as that described above we would need to study a sample in the lab using several methods including by stereo microscope. Then we would need to prepare a sample of the peeled-off surface, collecting several samples of the peeling material. Those paint chip samples are then examined in cross-section forensically using high powered microscopy – that can tell us whether or not the stain was coming off due to moisture or from another cause. The fee for that level of analysis is typically around $500. and of course includes a written report and photographic documentation as well as discussion if you have questions about the report and its findings.

A detailed examination of paint or stain thickness on the siding may tell us if the siding was sprayed, and if it was pre-coated before assembly on the home – that might explain, for example, why the stain is very thin on the upper ridges of the material and thicker between them in the simulated wood grain.

See PAINT FALURE, DIAGNOSIS, CURE, PREVENTION for a detailed series of diagnostic steps in paint or stain failure analysis.

If you have additional siding product failure examples or questions that are not found addressed at InspectAPedia.com you are welcome to contact the author to provide additional field photos or information that may assist others in identifying and repairing siding failures.

Share this Article      

...

Technical Reviewers & References

Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

AIR SEALING STRATEGIES
DEW POINT TABLE - CONDENSATION POINT GUIDE

MOISTURE CONTROL in BUILDINGS
MOISTURE PROBLEMS: CAUSE & CURE
PAINT FALURE, DIAGNOSIS, CURE, PREVENTION

SHEATHING, Gypsum board
SHEATHING Homasote & Other Board
SHEATHING, OSB
SHEATHING, Plywood
SHEATHING, FOIL FACED - VENTS
SIDING, ASBESTOS CEMENT SHINGLES
SIDING EIFS STUCCO
SIDING HARDBOARD
  Abatibi Siding Claims
  Boise Cascade Siding Claims
  JamesHardie HardiPlank Siding
  Masonite Siding Claims
SIDING VINYL
SIDING WOOD
STAIN DIAGNOSIS on Building Exteriors
STAIN DIAGNOSIS on Indoor Surfaces

  • Thanks to reader Marie Carr for James Hardiplank siding photograph and case history information. 06/01/2008
  • JamesHardie Hardiplank® Lap Siding information can be found at the company's web page on this material:
    http://www.jameshardie.com/homeowner/products_siding_hardieplankLapSiding.py
  • JamesHardi Corporation, can be contacted at 26300 La Alameda, Suite 400, Mission Viejo, California 92691 - 1-888 J-HARDIE
    1-888 542-7343 or by email to info@JamesHardie.com
  • Instructions for application of HardiePlank lap siding can be found at http://www.jameshardie.com/homeowner/products_siding_hardieplankLapSiding.py?openTab=jsnavLink4

More Information on Building Diagnostic Inspections and Repairs

    ...
InspectAPedia.comInspectAPedia® Home & Site Map - Building & Environmental Inspection, Testing, Diagnosis, Repair, & Problem Prevention Advice: In-depth research & advice on diagnosing, testing, correcting, & preventing building defects & indoor environmental hazards. Unbiased information, no conflicts of interest.
GO TO the MOLD and INDOOR ENVIRONMENT INFORMATION CENTER for in-depth advice on avoiding testing for or cleaning up mold and other indoor environmental hazards, odors, gases, contaminants
The Mold Information Center:
What to Do About Mold in Buildings, When and How to Inspect for Mold, Clean Up Mold, or Avoid Mold Problems
GO TO MOLD TEST KITS: This expert-recommended mold test kit is cheap and yet top performing *IF* you use a competent analysis laboratory!
Use this simple, economical mold test kit
by following our instructions on how to collect and mail mold samples to our lab
GO TO IAQ/MOLD-TEST LAB SERVICES: Mold, Pollen, indoor air quality, field and laboratory services by an expert.Environmental Inspection, Testing, & Diagnosis On-Site IAQ, Gas, Air Testing, Mold Investigation, Sick Building Diagnosis, Lab Services, & Remediation Plan Preparation - indoor air quality testing, problem source determination, supporting lab work, written remediation plan addressing removal of environmental and other hazards and prevention of their recurrence.
GO TO our PRE PURCHASE BUILDING INSPECTION SERVICES: Authoritative information for home buyers and home owners is included with your inspection.
Building Inspection, Problem Diagnosis
, Forensic Investigation & Testing, Repair Consulting

CONTACT Daniel Friedman - Dan is a senior ASHI home inspector, nationally recognized expert on building inspection, building failures, and sick building investigation
Contact Daniel Friedman for website content suggestions or for fee-paid consulting

08/31/2009 - 06/01/2008 - InspectAPedia.com/exterior/James_Hardiplank_Siding.htm - © 2010 - 1988 Copyright Daniel Friedman All Rights Reserved - InspectAPedia® is a Registered U.S. Trademark