Stains & discoloration on brick surfaces:
This article describes the causes & cures for various types of stains found on brick surfaces both outdoors and indoors. We list the common sources of stains on brick chimneys, walls, walks, and ceilings.
The article distinguishes among common brick stain sources such as algae, bacteria, lichens, moss, soot, sulphur, fungal growth, and other causes of markings on brick.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
[Click to enlarge any image]
Photo above, brick (and stone) staining in the dungeon at Goodrich Castle, Ross on Wye, Herefordshire, England, UK.
Below our photograph at left shows white gunk on the exterior surface of a chimney.
This is almost certainly efflorescence, a mineral salt left behind as water leaks into and evaporates out of the brick chimney.
The next photo (below) shows black soot staining at the top and sides of a brick chimney. If this soot is from an oil fired heating appliance, a service call is needed.
[Click to enlarge any image]
See EFFLORESCENCE SALTS & WHITE DEPOSITS for steps to cure efflorescence and to remove it from brick or other masonry surfaces.
Below we see black or brown tarry stains on the surface of a chimney visible in an attic.
These are most likely creosote, or creosote mixed with soot that has leaked through openings in this antique brick chimney and its flue. We discuss this chimney and what to do about it
See CHIMNEY STAINS & LEAKS for a catalog of stains appearing on, in or around all types of chimneys.
Watch out: water damage or soot, creosote, or other blockages of chimneys may make the chimney or flue unsafe.
See CHIMNEY INSPECTION DIAGNOSIS REPAIR
A reader asked us for an opinion of the cause of the green and black stains on this exterior brick building wall.
While a closer on-site inspection or in some cases a forensic lab analysis of a tape lift of the brick wall surface would be needed for certain identification, this looks much like black and green algae growing on the wall surface.
The reader noted that the dark staining on this brick was occurring only below an area where roof drainage was spilling down the building wall, and s/he asked for advice about how to clean this surface, and whether power-washing would be ok.
To minimize the chances of damage, we like to start cleaning with the most gentle approach first to see if that's sufficient.
Power washing may be OK on this modern hard-fired clay brick wall as long as the washer does not spray water into the wall cavity through weep holes or other openings.
More black stains on an exterior brick wall are shown just below. These are due to rain-splash-up from the lower roof onto the brick sidewall. The increased moisture level has encouraged algal growth on the brick surface.
Above the green stains on this structural brick wall (Vassar College, Poughkeepsie, New York, USA) are almost certainly an algae growth.
The wall is shaded and roof drainage system leaks have made this wall side particularly wet. Later, after the roof drainage system had been repaired, this wall was renovated and portions of it that had been frost-damaged were re-built.
Can you please advise what I should do about my new garden wall? The mortar is starting to turn green. - Anonymous by private email 2021/03/31
The green in your photos is almost certainly algae, though there could be some mold growing there too.
The algae growth occurs "naturally" outdoors on wet masonry (and other surfaces), particularly in a damp or wet climate and more-so where shaded from sun exposure.
You can clean the algae using any of several cleaners that are discussed
and also
at STONE, STUCCO & BRICK CLEANING METHODS - where there are also some prevention suggestions.
Also see ALGAE & MOLD STAINS on EXTERIORS
A competent onsite inspection by an expert usually finds additional clues that would permit a more accurate, complete, and authoritative answer than we can give by email alone. You will find additional depth and detail in articles at this website.
Mahmood
Regarding the dark red stains on the center of the brick window sill in your photo:
My best guess is that previously someone had a window air conditioner in the window in your photo and the A/C condensate rusted the air conditioner base and stained the brick as it drooled down the building wall.
If the red stains on the brick sill are from rust, try an iron or rust stain remover product.
The article STAINS on BRICK SURFACES discusses approaches to cleaning stains on brick as well as preventing their recurrence.
If the red stains on the brick sill in your photo are algae (which seems less likely given the circumstances portrayed in your photo, but still, not impossible), just about any household cleaner may remove it; use plenty of rinse water to avoid any bleach staining of the bricks below.
Other brick surface cleaners that might work:
Also see research on red stains on buildings and red stain and iron stain removal suggestions found in these InspectApedia articles
FOUNDATION DAMAGE by MATERIAL or INCLUSIONS - red stains caused by inclusions of iron sulfide mineral (pyrrhotite) can appear in concrete and in some brick and stone materials.
RUST STAINS on ROOFS - examples of red rust stains from oxidizing corroding metal
STAINS on STONE, STUCCO DIAGNOSE & CURE - additional cleaning methods that can work on brick
WATER SOFTENER IRON & SEDIMENT REMOVAL - more rust stain remover products
On 2018-09-15 by Mahmood - what caused and what will remove these red stains on brick?
Our outer Brick walls few bricks stained along with window glass from outside due continuously dripping of A/C water. Kindly advice and help how to clean stains from bricks and glass.
The photo is shown above.
Earlier we illustrated white efflorescence staining on a brick chimney, a common spot where efflorescence appears outdoors on masonry buildings.
Our photo above, showing thick white deposits on a structural brick wall in New York (Vassar College) shows that efflorescence can show up anywhere that there are water leaks in or down brick walls.
See EFFLORESCENCE SALTS & WHITE DEPOSITS
But not all white stains on brick surfaces are due to efflorescence
Above the white stains on this brick veneer wall were caused by leaks into the white coated aluminum soffit. White pigment from the soffit has run down the wall leaving a white deposit. There was a bit of green algae in the top area of this stain too.
Really? Brick veneer? Yes.
Before you write to gripe that the small brick-ends indicate a bond course making this a structural brick wall let me explain that no, this is a brick veneer wall constructed by a retired mason who took delight in making it look like a structural wall.
The wall is actually a single wythe brick veneer fastened to a concrete block structural wall.
Below we illustrate another white area on a brick wall that is not due to water or leakage nor to paint pigment wash-down. .
The white "stains" on the brick exterior wall shown above are not stains at all but rather mismatched mortar used by a mason or an amateur who had little concern for preserving this pre-1900 home in Dutchess County, New York.
The bricks in this wall were already spalling but the use of a harder mortar for the repair work is likely to accelerate the spalling damage to this home located in a freezing climate.
Is this efflorescence?
Is this the result of run off water from the exterior shutters?
I noted that similar staining on brick surfaces on inspectapedia and it was recommended to use a TSP (equivalent) cleaning solution would you recommend that here too?
Thinking of recommending professional cleaning.
Notice the pattern of white staining is most notable immediately below the edges of those white-painted shutter?
Most-likely it's white paint pigment runoff from the shutters.
There are some whitish bricks that may each be producing their own personal patch of efflorescence - take a closer look at
Watch out: Experts like Grimm (1990) widely warn against sand-blasting to clean brick surfaces of buildings. That aggressive approach damages the brick and mortar and can lead to rapid deterioration of the wall.
Furthermore, on antique, soft brick, even power washing can remove the brick's harder-fired surface, leaving the softer brick interior vulnerable to water and frost damage and causing costly building damage.
Power washing can also remove older soft mortars. And even on the modern hard clay brick wall, the washer needs to be used with care, starting from a more distant position in order to avoid leaving too-light power-sprayer marks on the wall.
Extra care must be taken if cleaning a brick-veneer wall as there may be more weep openings or leaks around window or door penetrations through which water may be inadvertently sprayed into the wall cavity.
Other brick wall cleaning methods such as using lasers, photocatalytics, or special cleaners are discussed both at
theReferences or Citations for this article
and
at STONE, STUCCO & BRICK CLEANING METHODS
At below left the black stains on this exterior brick patio located in New York state are probably algae but might also be a fungus. We'd need to examine a sample in the lab. At below right we see moss growth on the same brick patio in a nearby area.
This is a shaded brick patio constructed in the late 1990's. As plantings grew and a shade tree's canopy began to keep more of the patio area in shade in summer months the area covered by algae, moss, and possibly fungi has grown.
Remedies to reduce the staining on the brick shown above include assuring proper drainage, increasing the sun exposure by judicious pruning, sweeping off organic debris that hold water on the surfaces (leaves), and occasional power-washing.
Watch out: algae and moss on a brick walking surface or on any walking surface for that matter, are very slippery and risk a slip-trip-fall injury.
See SLIPPERY STAIRS, WALKS, ROOFS for the static coefficient of friction of various slippery walking surfaces.
Below we illustrate outdoor brick patio or walk surfaces that are not slippery with algae, moss, fungi.
Below we illustrate that a brick walkway, even one built using antique bricks that have been in place for more than 50 years do not have to be slippery with algae, moss, nor fungi.
The Dutchess County New York brick walkway shown above is in a sunny area and is well drained.
However the property manager does need to keep alert for frost-heaved or broken bricks that might form a trip hazard.
Above at left, notice the dark stains on the rear wall and white efflorescence stains on the ceiling of the dungeon at Goodrich Castle, Ross on Wye, Herefordshire, England, UK.
Both of these stain sets can be ascribed to water entry, but we also observed moss and even some fungi growing on these walls.
Below are very black creosote and soot stains on the hearth-face of a stone fireplace installed in a hand-built log cabin at Elk Lake Michigan.
Also see STAINS on INDOOR SURFACES, PHOTO GUIDE.
Finding and fixing leaks into or onto brick structures is a key step in stopping the formation of algae, moss, efflorescence, or fungal staining on brick surfaces.
Here is a summary of good practices when you need to remove any type of paint from an exterior or interior brick wall, fireplace, or other surface. These methods also work well for stone surfaces.
[Click to enlarge any image]
1 June 2016 dennis said:
how do i clean paint pigment run down from white siding on brick
Dennis,
If you are asking only about the simple deposits of runoff from a chalking painted surface, I recommend gentle cleaning of the brick with a natural bristle brush and a TSP substitute cleaning solution.
You can also try household detergent. Please see our warnings below about the dangers of aggressive cleaning or power washing of brick surfaces.
Don't waste time trying bleach as some of our readers did. Bleach won't remove white paint pigment and bleach itself, running down building surfaces can leave white streaks if not washed-off quickly enough.
So I don't think there is a single "right" answer that's optimum for all conditions.
Watch out: For people who are going to jump to "how to" let's first warn off some mistakes that you'll regret:
Choose a paint removal method that suits the amount of paint, type of paint, and condition of the brick or stone itself. A peel away paint remover may also work on some masonry surfaces.
Try Citri-Strip for a less-toxic cleaner that may work on your paint. Newer peel-away chemical paint remover systems that use a fabric + thick paint-on chemical paste can pull paint off of the brick.
Take a look at some of the brick cleaning references I will cite below, especially work where Grimmer was involved.
Below you will find questions and answers previously posted on this page at its page bottom reader comment box.
@Anonymous,
If that's efflorescence then simple household vinegar will reduce it significantly. Try that followed by a clean water rinse.
On 2022-04-21 by Anonymous
@Inspectapedia Com Moderator,
Hi, thank you so much for the reply. I have not tried a detergent cleaner. Is there a specific method on how to clean these bricks or suggested detergent?
Also do you think behind the brick wall could have water damage causing this? It does look like it's getting lighter(see second image attached - this is what it was at first) ... and we have no water entry on the drywall in the house/insulation on that interior wall.
On 2022-04-19 by Inspectapedia Com Moderator - black algae or mold on brick wall
@James,
I agree that two years ought to be more than enough time for wet brick walls to dry out if the leak is truly fixed.
But water running down a brick wall may leave behind stains formed, for example by algae growing in the wet area.
For the dark brick areas, have you tried a simple detergent cleaner to see if that affects the staining?
Or are you talking about those white areas on the brick - efflorescence?
On 2022-04-19 by James
I had a roof leak about 2 years ago that leaked for a large part of the winter. We fixed the leak and we assumed summer time would dry the brick.
It did get better but still it looks like the brick is wet almost 2 years later. Any ideas on what can be done? Thanks in advance!
@Kimberley,
That's probably soot or dirt washing down onto the upper wall sides from the wall cap-masonry. Try some simple detergent cleaners first. Other brick cleaning products are described in the page above.
Let me know how that works.
On 2022-04-17 by Kimberley
Perhaps you have some input for this photo of mine, how to get rid of the black on this colour of brick?
On 2022-03-23 by Inspectapedia Com Moderator - mold on bricks?
@George,
I can't see any obvious mold on the bricks in your photo. Mold of various genera/species can be found growing on almost any surface but when it's found on stone, brick, concrete, concrete block, I expect that there is a surface coating of either paint or organic dust and debris - some material that's mold-friendly and organic, providing food for the fungus to eat.
So perhaps there is something else on your brick, such as efflorescence or debris, even tar or paint, from having used old, re-cycled brick in construction of the fireplace.
If there is efflorescence you'll want to look for and fix the moisture source such as a chimney leak or missing chimney cap.
See details starting at EFFLORESCENCE SALTS & WHITE DEPOSITS https://inspectapedia.com/Wet_Basements/Efflorescence-White.php
and at
EFFLORESCENCE & BROWN DEPOSITS https://inspectapedia.com/Wet_Basements/Brown_Red_Effloresence.php
On 2022-03-23 by George
We have several bricks on an interior, lower level brick fireplace. We had them treated for mold with no results. I tried bleach and white vinegar with no results. The room is carpeted and heated.
On 2021-10-24 by Anonymous
@inspectapedia.com.moderator, @inspectapedia.com.moderator,
Then
And you very much for your guidance. Vey much appreciated.
@Mike,
It can take weeks or in some cases even several months of dry and warm weather for watermark bricks to dry out such that you no longer see that dark area in your photo.
As long as it wasn't some chemical or other contaminants look leaks down the wall it's likely that that mark will mostly disappear with time.
I don't see weep holes in what I think is a brick veneer wall. Can I see water stains below the window.
Depending on how much water ran down your wall it's possible that the wall cavity itself as wet and it may be worth exploring the wall cavity from inside the building to be sure that you're not breeding a mold palace.
On 2021-10-23 by Mike
Hi, This is a new wall that got soaked when guttering was disconnected. Doesn’t seem to have dried at all in the last three weeks (October).
Will we be left with a permanent darkened area where the facing brick has absorbed the water? Or is there a likelihood or hope it will dry out eventually in warmer months? Thank you
On 2021-08-29 by inspectapedia.com.moderator
@Rob,
First I'd give the area time to dry, after you've fixed leaks at the sill or window that have let water run behind those bricks. (Remember to look inside for moisture, mold, water damage, insect attack, etc.)
When you're sure the dark area is not simply higher moisture, thus leaving us to guess that we're seeing a fungus or algae, then you can try some of the cleaning methods described at
STONE, STUCCO & BRICK CLEANING METHODS https://inspectapedia.com/exterior/Stone_Cleaning.php
On 2021-08-29 by Rob
Hi I have dark stain below window sill. Cement under sill is cracked and sill is tilted inside. I think stain is caused by water leak. I'm getting sill fixed but wondering how to remove stain from brick. Thanks
@Sam firth,
Please see
STONE, STUCCO & BRICK CLEANING METHODS
On 2021-07-09 by Sam firth
How to remove black carbon pollution of stone
On 2021-05-08 by (mod) - variations in brick mortar, color, stains on 100 year old Utrecht building
It would be expected that over its life some of the brickwork on a century-old building has been re-built, particularly over that door lintel, also in areas prone to water damage;
Moisture seeping into brick will often produce a white efflorescence; so we'll see at least three brick colours and may on closer inspection see differences in the mortar mix or even tooling details at the mortar joints - supporting an understanding of the building's history.
Dark brown or black stains I see in an area below the patio wall / flat roof parapet wall are often algae or on occasion, a mold that's invited where there has been extra wetness - perhaps from a leaky parapet capstone covering.
You will want to be sure that there are no leaks into the wall structure particularly from the patio roof above. Very often when we see white stains on brick is efflorescence from moisture. You can read about that in this article series.
[Click to enlarge any image]
On 2021-05-08 by Eva28
The building is in Utrecht, the Netherlands and was built around 1900-1920. Indeed the top left corner seems as if were totally different brick.
The stain I consider the darker patch around 2m high and it seems to be getting a little lighter towards the bottom (color matches the rest of the building there).
Could very well be just some unfortunate choice of placing different colored bricks.
It was built 100 year ago approx.
Please feel free to post it. I believe asking a builder to clean the brick would not hurt even if it would resolve the difference in color.
Perhaps I’ll try to get some brick friendly plants/English ivy.
[Click to enlarge any image]
On 2021-05-08 by (mod)
Ok now, which is the area that you are considering the stain? the darker brick, or the whiter brick?
It looks as if a portion of the wall has been re-built.
Where is this building and what is its age?
What is the history of repairs to the surface of the patio-roof?
On 2021-05-08 by Eva28
It is a roof terrace. I’ll try and get you more pictures. On the indoor on the ground floor is the bathroom but I did not see dampness there. It also was renovated recently.
On 2021-05-08 by (mod)
I see
-
dark stains just below a wall top coping that looks like a roof parapet wall
- areas where mortar is more-white than others
- areas of more-red brick over a door, probably a repair or reconstruction
- area of redder brick below whiter brick that may also be an area of prior repairs.
I would need some more photo showing more of the building, at a distance so I can get some perspective in context, also what's above, is that a flat roof?
On 2021-05-08 by Eva28
Hi! I can’t figure out why there’s a discoloration on the brick of my house I just bought. [Photo above]
Thanks
Eva
I hope you are keeping well in these strange times! I wonder if you have an idea why the below brick wall is discolored (if helpful, on the inside it’s a recently renovated bathroom). Is there any way to fix it ?
On 2021-04-18 by (mod) - dark red-brown soil stains on white brick, near ground lee3l
@MC,
The most likely cause of the discoloration of brick on your veneer wall close to the ground is rain splash-up, caused, in turn by spillage of water from the roof edge.
The proper solution, if that's the case is to make sure that the gutters are cleaned and properly sloped and draining away from the house and not spilling over into that area.
When you've taken care of that it would make sense to clean the brick surface and if the paint has actually come off of the brick then you'll need to repaint the bricks.
On 2021-04-18 by MC
I have a brick face facade on my home. I believe it has a white wash finish.
There are reddish brown stains on it. When it gets wet, you can literally see a what appears the red brick from underneath. I would like to apply sealer but fearful that the red color of brick will stay permanently on the surface.
Is there anything I can do for remedying the staining and waterproofing it somehow so that there is no discoloration when it gets wet ?
On 2020-09-16 - by (mod) -
Try gentle brushing with vinegar or other household cleaners; rinse thoroughly
On 2020-09-15 by meryl
A hibiscus bush with big red flowers greww nest to a newly painted white brick wall, I tried to remove the dried leaves with a sponse and water and it let i light green stain. How can i remove the stain so the brick will return to white color
On 2020-09-10 - by (mod) -
That is weird, David. Try attaching a sharp photo or several (one per comment)
On 2020-09-10 by David
I have a weird issue on the outer brick wall of my house. It is a clear substance--completely transparent--that looks like very thin melted plastic adhering in irregular patterns, almost like it was dripped and pooled in random patterns. .
At first I thought maybe a small clear piece of plastic had melted on the bricks--but then more of the stuff showed up after the previous spots had started to fade.
I'm pretty sure no one is deliberately doing it in the night. So far my best guess is maybe some kind of pollen or sap is being blown and splattered occasionally on that wall.
Haven't found it on any other wall. I am really perplexed as to what it might be. Any thoughts?
On 2020-08-14 - by (mod) -
Marie
Thank you for the interesting photos and question about mortar deterioration in your brick veneer wall.
I think we have a combination of leaks into the wall
(see those openings in the mortar joints in your photo at top left?)
and perhaps variations in the mortar mix.
Start by finding and sealing leaks into the veneer wall.
On 2020-08-11 by Marie
Why only in a couple of area of our home but both under cover do i have the mortar turning to dust and in some places turning green.
Also a brick is turning white.
Please help, How can I treat this.
On 2020-07-09 - by (mod) -
There are several commercial iron-stain removers such as Iron-Out that may work. Try first in an unobtrusive spot.
On 2020-07-09 by Tim
Iron water stain on brick(boat house). What is the safest chemical and environmentally friendly with plants by the wall?
On 2020-06-14 - by (mod) -
Liz
After cleaning off the soot or creosote,
and having the flue inspected for fire-safety,
be sure the chimney is tall enough - 2 ft. above the ridge or 2 ft above point of contact with roof surface of a horizontal line drawn from chimney top to touch the nearest roof surface;
Ask your chimney sweep if your chimney has the right type of cap - preventing downdrafts;
I'm reluctant to rely on a larger cap since we'll just move the stain from the chimney to the roof surface, so we're left with taking care to burn dry, low-sap wood at sufficient temperature.
On 2020-06-13 by Liz
How can I prevent a black stain on the outside of my house just below the chimney I have a wood burning stove
On 2020-05-18 by Anonymous
Thank you
On 2020-05-18 - by (mod) -
Gabriel
Two approaches to removing the reddish stain on your brick are
1. try some masonry cleaners or iron removers as discussed in the article above
2. check out the list of likely causes of red stains on brick - also in the article above - to see if, by narrowing down the probable cause of the reddish stains in your photo we can home in on the most-effective cleaner
3. inspect the building, rooftop to siding bottom, including interior, plumbing, mechanical systems, to find the leak or defect that is causing this stain to appear in this particular location.
In my view this is an important step as otherwise we don't know that the stain isn't just a telltale of a more-serious hidden problem.
On 2020-05-18 by Gabriel
It seems that my aluminum siding has run into my bricks. Not sure if it’s rust or just the siding color. Hi do I safely take off without compromising the brick color?
Thanks
Hi, it seems that my brown aluminium siding is running down on my bricks. I’m not sure if it’s rust or just the color of the siding. Any suggestions how to take it off without compromising the color of the bricks
...
Continue reading at STONE, STUCCO & BRICK CLEANING METHODS for cleaning approaches useful for brick or stone surfaces, or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see STAINS on BRICK SURFACES FAQs - questions and answers posted originally on this page.
Or see these
STAINS on BRICK SURFACES at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
Our Comment Box is provided by Countable Web Productions countable.ca
In addition to any citations in the article above, a full list is available on request.