Federal Pacific Electric FPE Stab-Lok Class Action Settlement InspectAPedia® -
THIS IS A LEGAL NOTICE AND IS NOT AN ADVERTISEMENT
ATTENTION NEW
JERSEY HOMEOWNERS WITH FEDERAL PACIFIC
ELECTRIC CIRCUIT BREAKERS
InspectAPedia offers impartial, unbiased advice without conflicts of interest.
We will block advertisements which we discover or readers inform us are associated with bad business practices,
false-advertising, or junk science. Our contact info is at
InspectAPedia.com/Contact.htm.
Serag Yacout, Satish Chaudhary and 432
Owners, Inc., on behalf of themselves and all others similarly
situated,
Federal Pacific Electric
Company, Reliance Electric Company,
Defendants
CLASS ACTION NOTICE
To: ALL PERSONS OR ENTITIES IN THE STATE OF NEW JERSEY WHO CURRENTLY OWN, UTILIZE OR
POSSESS ANY CIRCUIT BREAKER SOLD OR MANUFACTURED BY FEDERAL PACIFIC ELECTRIC CO. DURING THE PERIOD 1965 TO 1980, WHICH
BEARS LABELING INDICATING THE BREAKER IS "UL LISTED" OR CONTAINS A SIMILAR CERTIFICATION THAT THE BREAKER COMPORTS WITH
APPLICABLE UL STANDARDS, AND ANY PERSONS OR ENTITIES WHO HAVE REPLACED SAID BREAKERS SINCE
1991.
1. Why should I Read This Notice?
If you own Federal Pacific circuit breakers or have
replaced Federal Pacific circuit breakers, please read this notice. It contains
important information. You may be entitled to monetary damage and/or other
relief. This Notice arises out of a class action lawsuit pending in
New
Jersey. The Court has directed that all claimants and
prospective claimants must identify themselves in response to this notice on or before April 20, 2005. If you do not respond, you will lose your rights.
2. What Is This Lawsuit About?
This Notice affects many persons who have Federal Pacific
circuit breakers. The Court has already determined that Federal Pacific violated
the New Jersey Consumer Fraud Act. The violation occurred because FPE cheated
during its testing of circuit breakers in order to obtain Underwriters Laboratories (UL) approval. The Court has already certified this action as a class action, but in order for your
claim to be considered you must act now. If you qualify as outlined below, you
may be entitled to monetary damage and/or other relief. The relief may include
three times the cost of replacing your circuit breakers.
3. Am I Eligible to Pursue a Claim?
Based on the Court's rulings, you may be eligible to pursue a claim if
you meet the following criteria:
·You own a home or building in
the State of
New Jersey;
·You must be the owner at the
time that FPE Stab-lok circuit breakers manufactured and sold between June 29, 1971 and July 1, 1980 were installed as
original equipment in your home or building; or you had renovations or additions done which included circuit breakers
made and sold in that period while you were the owner;
·The home or building contains
original FPE Stab-Lok circuit breakers (If you do, the circuit breaker panel box will have the name and logo of Federal
Pacific Electric Company and the words Stab-Lok on the breaker panel box) or you replaced the breakers since 1991. DO NOT ATTEMPT TO REMOVE ANY OF THE CIRCUIT
BREAKERS – you will be able to determine whether you have Federal Pacific Electric Company circuit breakers by looking
at the outside of the panel box and/or the inside of the door to the box. Please note that if your panel box or the circuit breakers within the panel box refer to "Federal
Pacific Equipment Inc." it is referring to a different company from Federal Pacific Electric Company. If you have Federal Pacific Equipment Inc. circuit breakers they are not included in
this claim;
·You are not one of the
defendants, any entity in which any of the defendants have a controlling interest, any of the defendants' past or
present parents, subsidiaries, affiliates, officers and directors; or a retail or wholesale dealer who sold Federal
Pacific circuit breakers and panel boxes.
4. What Do I Need To Do To Continue To Pursue a Potential Claim?
If you believe you are eligible to recover and you wish to
remain eligible, you must respond to this Notice by completing the coupon form below and mailing it to the FPE
Administrator. THE COMPLETED COUPON MUST BE POSTMARKED NO LATER THAN APRIL 20,
2005 or you may go directly to www.yacoutclassaction.com to respond to this Notice; if you do so, you must do that
by April 20, 2005. If you fail to DO SO, YOUR CLAIM WILL BE BARRED.
The FPE Administrator will then mail you an FPE Stab-lok
Circuit Breaker Information Form or you can obtain the Information Form on the website. The completed Information Form and any documentation requested therein
must be mailed to the third party administrator AND must be postmarked BY A DATE SPECIFIED THEREIN. IF YOU FAIL TO submit a complete Information
Form BY THE DATE SPECIFIED IN THE MATERIALS TO BE FURNISHED, you will be barred from further participating in this
litigation.
Your claim may be subject to verification and investigation, including
an inspection of the circuit breaker panel board and giving testimony with respect to your claim.
5. Where Do I Get Additional Information?
This Notice provides only a summary of matters regarding the
litigation and is not deemed an admission by any party. You may seek the advice
and guidance of your own private attorney, at your own expense, if you wish. For
more detailed information, you may review the pleadings, records, and other papers on file in this litigation, which may
be inspected during regular business hours at the Clerk's Office, Superior Court of New Jersey, Law Division, located at
One JFK Square,
New Brunswick,
New Jersey.
If you have any questions regarding this Notice, you can
contact class counsel:
Chase Kurshan Herzfeld & Rubin,
LLC
5N
Regent
Street,
Suite
508
Livingston,
New Jersey
07039-1617
Attn: Lisa Santana
Tel: (973) 535-8840
Email: lsantana@chaselaw.nj.com
PLEASE DO NOT CONTACT THE
COURT OR THE CLERK'S OFFICE.
The Honorable Bryan D. Garruto.
(CUT ALONG DOTTED LINE – PLEASE PRINT)
REQUEST FOR INFORMATION
FORM
I would like to have an FPE Stab-lok Circuit Breaker Information Form
mailed to:
City: ____________________________State
______ Zip Code________
CERTIFICATION: I HEREBY CERTIFY UNDER PENALTY OF PERJURY
THAT (1) I AM THE ORIGINAL OWNER OF A HOME OR PROPERTY WHERE FPE CIRCUIT BREAKERS ARE INSTALLED, (2) I CONTINUE TO OWN
THE PROPERTY AND (3) THE ABOVE INFORMATION IS TRUE AND CORRECT.
This REQUEST FOR INFORMATION FORM must be completed and
sent to the FPE Administrator in order to continue to remain a member of the class. THIS FORM OR YOUR EMAIL RESPONSE MUST BE POSTMARKED OR RECEIVED NO LATER THAN APRIL 20, 2005 in order to maintain
any rights you may have.
Critique, contributions wanted: Contact Us to suggest corrections or additions to articles at this website, and if you wish, to receive online listing and credit as a contributor. Particular thanks are due to the many experts and also consumers who read and critique technical articles at InspectAPedia.com.
Additional technical contributors & reference sources for this article are listed below.
Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.
Note: as we didn't add this reviewers list until 2007, this list of technical reviewers is incomplete; we have received comments and suggestions regarding this topic, edits and remarks included, from engineers and management from the US CPSC, electricians (many listed at our page on field reports of FPE failures), home inspectors, licensed electricians, and electrical engineers, and even a few attorneys and real estate agents, since 1986. Technical review, critique, content suggestions, questions, or clarifications are invited and where a contributor wishes, credit and links will be provided to that source. Contact us to provide feedback.
Dr. Jess Aronstein, electrical engineer, Poughkeepsie, NY, forensic engineering services, independent laboratory testing for various agencies protune@aol.com (independent electrical panel testing, including FPE Stab-Lok panels, to April 2010)
David Carrier, electrical engineer, 53 Henmond Blvd., Poughkeepsie, NY 12603 845-430-7527 davidwcarrier@earthlink.net (independent electrical panel testing, including FPE Stab-Lok panels, beginning 2010)
Alan Carson, Carson Dunlop, Associates, Toronto, Ontario. Mr. Carson is a home inspection professional, educator, researcher, writer, and a principal of Carson Dunlop Associates, a Toronto home inspection and education firm. Mr. Carson is a past president of ASHI, the American Society of Home Inspectors
Mark Cramer Inspection Services Mark Cramer, Tampa Florida, Mr. Cramer is a past president of ASHI, the American Society of Home Inspectors and is a Florida home inspector and home inspection educator. (727) 595-4211 mark@BestTampaInspector.com 11/06
Carl Grasso, Esq., Herzfeld & Rubin, New York, NY. Mr. Grasso is an attorney who managed a plaintiff's class action litigation against Federal Pacific Electric in New Jersey.
William King, US CPSC Director of Electrical Engineering (Ret).
Licensed Electricians: FPE Fire and Failure Reports includes electricians who have provided cases and photographs of field failures of FPE equipment at this website.
Homeowners, Home Inspectors, Electricians: Federal Pacific Electric (FPE) Panel Fires and other Failures includes anecdotal field reports provided by a range of contributors including electricians (and some home owners or home inspectors) who have provided cases and photographs of field failures of FPE equipment at this website.
Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair
Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.
Aluminum Wiring Information Website Aluminum Electrical Wiring Hazards and Repairs: in-depth authoritative info, photos, documents including selection of proper vs. ineffective repair methods. E.g.: Ideal 65 "Twister" purple connector fails in field and lab testing with aluminum wire.
Electrical Panels, How to Inspect in buildings, safety for electrical inspectors, electrical panel, fusing, wiring defects, defective products. Inspection Class Presentation
2007 FPE Stab-Lok TECHNICAL REPORT - an updated test report of independent testing (a large 1.2MB PDF file) using a larger pool of FPE Stab-Lok circuit breakers than the older CPSC and Wright Malta tests found significantly higher failure rates of FPE Stab-Lok circuit breakers, including a look at critical safety failures (breaker failed to trip at 200% of rated current or jammed) which found up to 80% failure rate for FPE Stab-Lok GFCI circuit breakers (n=4), 12% failure rate for double pole FPE Stab-Lok circuit breakers (n=120), and a 1% failure rate for FPE Stab-Lok single pole circuit breakers (n=345).
Replacement Panels for FPE Stab-Lok load centers - options include conventional complete panel replacement and a less costly replacement of the panel interior load center/bus assembly
1982 Reliance Electric Co. SEC Quarterly Report: Note C. reports litigation between Reliance and UV Liquidating Trust and contends that "... improper and deceptive practices were employed for many years to secure UL listings for Federal Pacific's circuit protective products..."
1980 Reliance Electric Co. Press Release: improper practices used to obtain UL Listing for most of FPE's circuit breakers and notes testing which indicates "possible defects." 1980, Reliance Electric Co.
1980 FPE - Exxon Buys A Scandal Along With A Company improper practices used to obtain UL Listing for most of FPE's circuit breakers and notes testing which indicates "possible defects." 1980, Reliance Electric Co.