FPE Stab-Lok HAZARDS & REPAIRS WEBSITE
SUMMARY OF the FPE Stab-Lok PROBLEM
FPE HAZARD ARTICLES, STUDIES
FPE Stab-Lok TECHNICAL REPORT
HOW TO IDENTIFY FPE & FP
REPORTS OF FPE FAILURES
HOW TO REPORT FPE INCIDENTS
FPE REPAIR ELECTRICIANS
FPE REPLACEMENT BREAKERS
FPE REPLACEMENT PANELS

FEDERAL PIONEER in CANADA
  What Are Federal Pioneer Panel Concerns?
  Federal Pioneer Warranty Alert
  Federal Pioneer Circuit Breaker Recall
  Field Reports of Federal Pioneer Problems
  Other Federal Pioneer Concerns
  FEDERAL PIONEER PANEL PHOTOS
FPE Stab-lok: FIRES WAITING TO HAPPEN
FPE HISTORY
ADVICE TO HOME BUYERS w/ FPE PANELS
HOME INSPECTION LANGUAGE for FPE Stab-Lok
IAEI LETTER
FPE Stab-Lok Hazard Summary Page for Public Use

More Information

InspectAPedia.comInspectAPedia ® Home & Site Map
InspectAPedia Blog - News Updates
Air Conditioning & Heat Pumps
Bookstore
Electrical
Environment
Exteriors
Heating
Home Inspection
Insulate Ventilate
Interiors
Mold Inspect/Test
Plumbing Water Septic
Roofing
Structure
Accuracy & Privacy Policies
InspectAPedia ® Home & Site Map
Contact Us



Photograph of the interior of a Federal Pioneer electrical panel

Federal Pioneer / Federal Pacific NC015 and NC015CP Circuit Breakers Circuit Breaker Warrant Alert
InspectAPedia®  -    

  • Recall of Federal Pioneer NC015 and NC015CP Circuit Breakers in Canada
Our site offers impartial, unbiased advice without conflicts of interest. We will block advertisements which we discover or readers inform us are associated with bad business practices, false-advertising, or junk science. Our contact info is at InspectAPedia.com/appointment.htm.

In May 1999 we (DJF) have learned from Schneider Canada that Federal pioneer circuit breakers sold by that company are re-named from Federal Pacific circuit breakers and that two 15-amp single-pole models NC015 and NC015CP made between August 1, 1996 and June 11, 1997 have been recalled.

The Federal Pioneer electrical panel recall notice is available here. We asked the company to determine if Federal Pioneer and Federal Pacific components sold in Canada were made in the U.S. or if tooling used to produce them was identical with that used in the U.S. If this is the case (as one might expect based on economies of production) one should consider the possibility that other defects reported in the U.S. may also appear in Canadian installations. As of the latest date of this web page (see page bottom) no reply has been received.

The Federal Pioneer electric panel Warranty Alert was issued by the Ontario New Home Warranty program in October 1997 and provides for circuit breaker replacement. Schneider Canada is an electrical supplier whose product lines combine those previously marketed under the names Federal Pacific Electric, Federal Pioneer, Square-D, Tele Mechanique, Modicon, and Merlin Gerin.

© Copyright 2010 Daniel Friedman, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use links at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

Comparing the Canadian Warranty Alert for Federal Pioneer NC015/NC015CP circuit breakers and US CPSC and Industry Response to the performance of FPE Stab-Lok circuit breakers in the U.S. we comment:

This was a limited (to manufacturing date and breaker type) recall issued in Canada. But we emphasize  the point that is made in the recall notice, as it expresses a safety concern that applies to users of FPE Stab-Lok equipment in the US. The recall notice states "If the circuit breaker does not perform as intended, there is a potential for property damage and/or personal injury". That is what FPE denied, and a charge for which the U.S. CPSC did not have the resources to gather the evidence required to prevail in court.That statement is the most important part of the recall notice. 

Consumers whose properties receive electrical power supplied through an American-made FPE Stab-Lok panel should ask why it is that Stab-Lok breakers that don't trip properly in Canada pose a risk of property damage and/or injury, but Stab-Lok  breakers that don't trip properly in the USA do not?  Do we have less aggressive electrons in the USA.

Photos to assist in identification of Federal Pioneer electrical equipment are at FEDERAL PIONEER PANELS

The following Warranty Alert was issued by the Ontario New Home Warranty Program on October 14, 1997.

Warranty Alert - Ontario New Home Warranty Program

----------------------------------------------------
Schneider Canada NC015/NC015P Circuit Breaker Recall
----------------------------------------------------

IMPORTANT PRODUCT RECALL INFORMATION FOR BUILDERS

The Ontario New Home Warranty Program (ONHWP) wants to pass along important product recall information to all registered builders/ vendors from Schneider Canada.

Schneider Canada was recently made aware of a potential problem with their Federal Pioneer brand NC015 and NC015CP circuit breakers manufactured between August 1, 1996 and June 11, 1997.

In some circumstances these breakers may not trip. In other cases, the breakers will continue to protect anticipated overloads and short circuit currents. If the circuit breaker does not perform as intended, there is potential for property damage and/or personal injury. There have been no reports of injuries or fires as a result of the potential problem.

Schneider Canada is determined to make every effort to locate and replace these circuit breakers. Their plan is to notify homeowners in a number of ways, including utility bill stuffers, advertising and through channel and contractor notification. They expect to receive calls from concerned homeowners requesting replacement of their circuit breakers. Here is a summary of the process Schneider Canada has set up:

* There is a toll free call centre at 1-888-519- 5536 or 416-234-6407 (Metro Toronto) that homeowners can telephone for more information about the program and register their home for breaker replacement.

* The call centre has a list of authorized contractors and will refer up to three local contractors for the homeowner to call.

* Homeowners select one of the contractors and call to arrange a suitable date and time to visit and replace the breakers.

* The contractor makes a service call to remove and replace the affected breakers, invoices Schneider Canada for a service call and returns the circuit breakers to an authorized Schneider Canada distributor.

WHAT TO DO - Canadian FPE - Stab Lok Federal Pioneer Stab-Lok Equipment in Canada

Because Schneider Canada is taking charge of this product recall ONHWP does not expect to be involved.

You may want to check with your electrical contractor to determine if your homes and homeowners are affected.

FOR MORE INFORMATION on Canadian FPE Federal Pioneer Recall

More detailed information is available by calling your local Schneider Canada office or you can visit their website at www.schneider.ca

OFFICES OF THE ONTARIO NEW HOME WARRANTY PROGRAM

Head Office
5160 Yonge St. 6th Floor
North York ON M2N 6L9
(416) 229-9200
Toll Free 1-800-668-0124
E-Mail info@newhome.on.ca

Note: other Ontario New Home Warranty Program office addresses included in the above notice have been deleted for brevity. Otherwise the notice is quoted directly and verbatim from a copy faxed to me by Carson Dunlop & Associates in Toronto on 10/27/97 and verified by telephone call to Schneider Canada on 5/25/99.

Here is a copy of the original recall notice of Federal Pioneer NC015 and NC015CP circuit breakers for NC015 and NC015CP

Share this Article      

...

Technical Reviewers & References

Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

ELECTRICAL INSPECTION, DIAGNOSIS, REPAIR
FPE Stab-Lok HAZARDS & REPAIRS WEBSITE
SUMMARY OF the FPE Stab-Lok PROBLEM
FPE HAZARD ARTICLES, STUDIES
FPE Stab-Lok TECHNICAL REPORT
HOW TO IDENTIFY FPE & FP
REPORTS OF FPE FAILURES
HOW TO REPORT FPE INCIDENTS
FPE REPAIR ELECTRICIANS
FPE REPLACEMENT BREAKERS
FPE REPLACEMENT PANELS
FPE REPLACEMENT PANEL COSTS
CANADIAN VERSIONS of FPE Stab-Lok
FPE Stab-lok: FIRES WAITING TO HAPPEN
FPE HISTORY
ADVICE TO HOME BUYERS w/ FPE PANELS
HOME INSPECTION LANGUAGE for FPE Stab-Lok
IAEI LETTER

  • Note: as we didn't add this reviewers list until 2007, this list of technical reviewers is incomplete; we have received comments and suggestions regarding this topic, edits and remarks included, from engineers and management from the US CPSC, electricians (many listed at our page on field reports of FPE failures), home inspectors, licensed electricians, and electrical engineers, and even a few attorneys and real estate agents, since 1986. Technical review, critique, content suggestions, questions, or clarifications are invited and where a contributor wishes, credit and links will be provided to that source. Contact us to provide feedback.
  • Dr. Jess Aronstein, electrical engineer, Poughkeepsie, NY, forensic engineering services, independent laboratory testing for various agencies
  • Alan Carson, Carson Dunlop, Associates, Toronto, Ontario. Mr. Carson is a home inspection professional, educator, researcher, writer, and a principal of Carson Dunlop Associates, a Toronto home inspection and education firm. Mr. Carson is a past president of ASHI, the American Society of Home Inspectors
  • Mark Cramer Inspection Services Mark Cramer, Tampa Florida, Mr. Cramer is a past president of ASHI, the American Society of Home Inspectors and is a Florida home inspector and home inspection educator. (727) 595-4211 mark@BestTampaInspector.com 11/06
  • Carl Grasso, Esq., Herzfeld & Rubin, New York, NY. Mr. Grasso is an attorney who managed a plaintiff's class action litigation against Federal Pacific Electric in New Jersey.
  • William King, US CPSC Director of Electrical Engineering (Ret).
  • Licensed Electricians: FPE Fire and Failure Reports includes electricians who have provided cases and photographs of field failures of FPE equipment at this website.
  • Homeowners, Home Inspectors, Electricians: Federal Pacific Electric (FPE) Panel Fires and other Failures includes anecdotal field reports provided by a range of contributors including electricians (and some home owners or home inspectors) who have provided cases and photographs of field failures of FPE equipment at this website.

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building design, inspection, and repair, and about indoor environment testing, diagnosis, and cleanup are at the InspectAPedia Bookstore.
  • ...
ELECTRICAL INSPECTION, DIAGNOSIS, REPAIR
FPE Stab-Lok HAZARDS & REPAIRS WEBSITE

More Information

InspectAPedia.comInspectAPedia ® Home & Site Map
InspectAPedia Blog - News Updates
Air Conditioning & Heat Pumps
Bookstore
Electrical
Environment
Exteriors
Heating
Home Inspection
Insulate Ventilate
Interiors
Mold Inspect/Test
Plumbing Water Septic
Roofing
Structure
Accuracy & Privacy Policies
Contact Us

More Information on Building Diagnostic Inspections and Repairs

InspectAPedia.comInspectAPedia® Home & Site Map - Building & Environmental Inspection, Testing, Diagnosis, Repair, & Problem Prevention Advice: In-depth research & advice on diagnosing, testing, correcting, & preventing building defects & indoor environmental hazards. Unbiased information, no conflicts of interest.
GO TO the MOLD and INDOOR ENVIRONMENT INFORMATION CENTER for in-depth advice on avoiding testing for or cleaning up mold and other indoor environmental hazards, odors, gases, contaminants
The Mold Information Center:
What to Do About Mold in Buildings, When and How to Inspect for Mold, Clean Up Mold, or Avoid Mold Problems
GO TO MOLD TEST KITS: This expert-recommended mold test kit is cheap and yet top performing *IF* you use a competent analysis laboratory!
Use this simple, economical mold test kit
by following our instructions on how to collect and mail mold samples to our lab
GO TO IAQ/MOLD-TEST LAB SERVICES: Mold, Pollen, indoor air quality, field and laboratory services by an expert.Environmental Inspection, Testing, & Diagnosis On-Site IAQ, Gas, Air Testing, Mold Investigation, Sick Building Diagnosis, Lab Services, & Remediation Plan Preparation - indoor air quality testing, problem source determination, supporting lab work, written remediation plan addressing removal of environmental and other hazards and prevention of their recurrence.
GO TO our PRE PURCHASE BUILDING INSPECTION SERVICES: Authoritative information for home buyers and home owners is included with your inspection.
Building Inspection, Problem Diagnosis
, Forensic Investigation & Testing, Repair Consulting

CONTACT Daniel Friedman - Dan is a senior ASHI home inspector, nationally recognized expert on building inspection, building failures, and sick building investigation
Contact Daniel Friedman for website content suggestions or for fee-paid consulting

02/04/2010 - 05/25/99 InspectAPedia.com/fpe/schneider.htm - © 2010 - 1988 Copyright Daniel Friedman All Rights Reserved - InspectAPedia® is a Registered U.S. Trademark

The Schneider Electric Recall notice is a public document.