InspectAPedia ® Home ENVIRONMENTAL HAZARDS - INSPECT, TEST, REMEDY ACCURACY vs PRECISION of MEASUREMENTS AIR CLEANER PURIFIER TYPES AIR LEAK DETECTION TOOLS AIR POLLUTANTS, COMMON INDOOR AIR QUALITY IMPROVEMENT STRATEGIES ANIMAL ODORS IN BUILDINGS BACKDRAFTING HEATING EQUIPMENT BIBLIOGAPHY for ENVIRONMENTAL HEALTH, MOLD, IAQ BIOGAS PRODUCTION & USE BIOLOGICAL POLLUTANTS BLOWER DOORS & AIR INFILTRATION BOOKSTORE - ENVIRONMENTAL BUILDING SAFETY HAZARDS GUIDE CARPETING & INDOOR AIR QUALITY CHINESE DRYWALL HAZARDS CHLORINE IN DRINKING WATER COMBUSTION PRODUCTS & IAQ COMBUSTION GASES & PARTICLE HAZARDS CONDENSATION or SWEATING PIPES, TANKS CPSC Indoor Air Pollution Book Online Copy DRAFT MEASUREMENT, CHIMNEYS & FLUES DUST SAMPLING PROCEDURE EMERGENCY RESPONSE, IAQ, GAS, MOLD ENVIRO-SCARE - PUBLIC FEAR CYCLES Fireplaces & Woodstove Contaminants FLAME COLOR, BLUE vs YELLOW COMBUSTION FORMALDEHYDE HAZARDS Formaldehyde Gas Hazard Reduction GAS DETECTION INSTRUMENTS GAS LP & Natural Gas Safety Hazards GAS LP & Natural Gas Pressures HEATING OIL EXPOSURE HAZARDS, LIMITS HOUSE DUST ANALYSIS HUMIDITY CONTROL & TARGETS INDOORS HYDROGEN SULFIDE GAS Indoor Air Pollution Book Online CPSC INDOOR AIR QUALITY & HOUSE TIGHTNESS INDOOR AIR QUALITY IMPROVEMENT GUIDE LP & Natural Gas Pressures LP & Natural Gas Safety Hazards MOLD ODORS, MUSTY SMELLS MSDS Material Safety Data Sheets MVOCs & MOLDY MUSTY ODORS Museum Artifact Preservation ODORS GASES SMELLS, DIAGNOSIS & CURE ODORS IN WATER OXYGEN - O2 OZONE HAZARDS PARTICLE SIZES & IAQ Pesticide Exposure Hazards PLASTIC ODORS-SCREENS, SIDING PLUMBING SYSTEM ODORS PVC - VINYL BUILDING PRODUCTS RADON HAZARD TESTS & MITIGATION SEPTIC METHANE GAS SEPTIC SYSTEM ODORS SMELL PATCH TEST to Track Down Odors SULPHUR & SEWER GAS SMELL SOURCES UFFI UREA FORMALDEHYDE FOAM INSULATION URETHANE FOAM Deterioration, Outgassing VAPOR CONDENSATION & BUILDING SHEATHING VENTILATION in BUILDINGS VINYL Siding or PLASTIC Window ODORS Volatile Organic Compounds VOCs WATER ODORS, CAUSE CURE More Information |
Carbon monoxide (CO) gas hazards home page: carbon monoxide alarms, effects, tests, exposure limits, medical effects. This article describes the toxicity and exposure limits for exposure to carbon monoxide gas (CO). In companion articles we also describe procedures for inspecting buildings for evidence of carbon monoxide hazards, including visual clues that may suggest a safety problem even if CO testing is not detecting carbon monoxide at the time of the inspection. We describe carbon monoxide testing methods, the medical effects of carbon monoxide exposure, and we cite authorities who set the limits on carbon monoxide exposure in different environments. We give references and explanation regarding Toxicity of Carbon Monoxide, based on literature search and including research on OSHA, NIOSH, and at the old Compuserve's Safety Forum. This is background information, obtained from expert sources. This text may assist readers in understanding these topics. Green links show where you are. © Copyright 2013 InspectAPedia.com, All Rights Reserved. Author Daniel Friedman. Guide to Inspecting buildings for Visible Evidence of Conditions Likely to Produce Dangerous Carbon Monoxide GasIF YOU SUSPECT CARBON MONOXIDE POISONING GO INTO FRESH AIR IMMEDIATELY and get others out of the building, then call your fire department or emergency services for help. Links on this page also direct the reader to carbon dioxide gas information in a separate document. Seek prompt advice from your doctor or health/safety experts if you have any reason to be concerned about exposure to toxic gases. Carbon monoxide poisoning can be fatal but exposure at lower limits can produce flu-like symptoms and headaches that are often mistaken for ordinary illness. Readers of this document should also see BACKDRAFTING HEATING EQUIPMENT and see HEAT EXCHANGER LEAKS. The fact that you cannot see nor smell dangerous carbon monoxide gas does not mean that there is nothing to look for when assessing the safety of heating equipment. Not only are there easily spotted installation errors (the first list below), there may be more subtle but easily visible errors if you know what to look for (the second list below). Safety Suggestions: Install Carbon Monoxide Detectors in addition to Smoke DetectorsCarbon monoxide detectors are inexpensive and readily available, both as a battery-operated unit and as a unit that plugs into an electrical outlet in the home. No home should be without this safety protection, and homes with gas-fired equipment (natural gas or LP propane), space heaters, or other sources of risk should be extra cautious. Smoke detectors do not protect against carbon monoxide poisoning, and the opposite is also true. Carbon monoxide detectors do not warn of smoke or fire. Examples of visible building conditions risking carbon monoxide hazardsThis is by no means the complete list of errors that can cause dangerous carbon monoxide exposure in buildings, but here are some common foul ups outside of the workplace that can cause dangerous levels of indoor carbon monoxide:
Other clues which can suggest a risk of carbon monoxide hazards in buildings
Procedures for Testing for Carbon Monoxide Gas Leaks, Exposure, HazardsIn addition to the installation of CO monitoring alarms in buildings, a variety of electronic and gas sampling equipment is available to make spot checks for hazardous gases. I have and have used a variety of these devices under a wide range of conditions. While a "positive" indication of a gas is an important indicator of a hazard, a "negative" or "not found" result is nothing to rely on. The fact that dangerous levels of CO are not present in a building at a particular instant is absolutely no guarantee that dangerous levels of CO (for example) may not occur even moments later. For example, opening a window, turning on a fan or clothes dryer, closing a door, and similar innocent acts can significantly change air flow, combustion air, and other building conditions. Therefore spot tests for dangerous gases should not be relied upon to guarantee building safety. This is why the list of visual inspection items and proper heating equipment maintenance are so important. Suggestions and content additions are invited. Contact me with items to add to these lists. More Reading:
CHIMNEY INSPECTION GUIDE contains detailed suggestions for inspecting building chimneys including the detection of blocked chimney flues or indications that a chimney may be blocked. MEDICAL EFFECTS of CO - Medical effects of Carbon Monoxide (CO) PoisoningMany sources I (DF) reviewed indicated that if carbon monoxide exposure was sub acute, that is if the person did not lose consciousness and was removed from the CO exposure before losing consciousness, then any medical effects were temporary. Indeed detection of CO exposure at a hospital is problematic since CO leaves the bloodstream quickly once a person is exposed to normal air. However there is evidence that lasting physical damage may occur from carbon monoxide exposure, though the popular press has not (2006) discussed the exposure level and duration necessary for these effects. Heart muscle damage occurs from Carbon Monoxide (CO) exposure, screening recommended31 January 2006 - The New York Times Science Section reports on a new study, released in JAMA's January 25 2006 Magazine Issue, and which indicated that people exposed to carbon monoxide suffer damage to their heart muscles and are at much greater risk for heart attacks in later years. The Times article asserted that CO Poisoning results in 40,000 emergency visits a year in the United States - the most common accidental poisoning event in the U.S. with an annual average accidental death rate of about 1000 people and average suicidal death rate of about 2400 people. [U.S. CDC] Five percent of such patients die in the hospital. Research was not cited regarding sub acute exposures and exposures which do not result in a visit to a hospital. -- New York Times Science Section, January 31, 2006 p. F6, "After Crisis, Carbon Monoxide Still Takes a Toll." The carbon monoxide exposure and heart muscle damage study was led by Christopher R. Henry, Minneapolis Heart Institute Foundation, in the current [Jan 2006] Journal of the American Medical Association The study examined the medical history of 230 people exposed to carbon monoxide and treated at hospital between 1994 and 2002, following their health to 2005. After 7 1/2 years, in this otherwise low risk (of heart failure) population, 25% of the originally-surviving patients had died - a rate about three times the average heart failure death rate statistic. For people who had suffered heart muscle damage the mortality rate was 38% with half of the mortalities being (apparently) traced to cardiovascular problems. The study concludes that people who are exposed to carbon monoxide should be screened for heart muscle damage. Heart muscle damage from CO poisoning (in the study) was characterized by elevated levels of cardiac troponin I (a type of protein) or creatine kinase-MB (a type of enzyme), and/or changes in diagnostic electrocardiogram (ECG). -- DJ Friedman paraphrasing the NY Times article and JAMA's news release regarding this study. More references for this study: Carbon Monoxide Poisoning Information From U.S. Army Field Manual 8-285:Pathology of CO poisoning: Asphyxiation is caused by the inactivation of blood hemoglobin through a combination with CO. The resultant anoxia may produce nervous system changes. Postmortem examinations reveal little beyond the characteristic cherry red color of the blood and hemorrhages in the brain Symptoms of CO poisoning: Carbon monoxide is very insidious in its action and poisoning may occur without appreciable initial signs. The symptoms progress from throbbing headaches, vertigo, yawning, and poor visual acuity, to the development of cherry red mucous membranes, weakness and coma, subnormal temperature, feeble pulse, and death. Diagnosis of CO poisoning: The diagnosis is made from the
circumstances of exposure and the appearance of Protection against CO poisoning: In general, exposure to CO should be avoided whenever possible. Adequate ventilation
should be provided for all enclosed spaces where CO
may be produced. The safety of air in the space for
people to breathe may be tested by standard CO indicator or detector devices. Individuals required to Treatment for Carbon Monoxide Poisoning: Remove the victim to pure air. If respirations are weak or absent, begin assisted ventilation at once. Oxygen, if available, should be given by a face mask, preferably under pressure (up to 3 atmospheres). The patient should be kept warm and at rest (sedated, if necessary). After resuscitation, initial supportive measures (such as the need for parenteral fluids and pressor drugs) can best be decided by the medical officer. Ordinarily, methylene blue solution, morphine, and atropine should NOT be used (TB MED 269). Prognosis for people exposed to carbon monoxide poisoning: The longer the period of the coma, CO EXPOSURE LIMITS - Carbon monoxide exposure limits PEL and TLV set by OSHA and NIOSHCarbon monoxide is a colorless, odorless, tasteless gas that, in its effects on humans, is a chemical asphyxiant - that is, it causes asphyxiation, or death by preventing a person from receiving adequate oxygen. When inhaled, carbon monoxide combines with hemoglobin in the blood more readily than oxygen does. Thus CO "displaces" or moves oxygen out from hemoglobin in the bloodstream. This interferes with oxygen transport by the blood. A person suffering from carbon monoxide (CO) intoxication may first experience euphoria (similar to the effect of a martini or two), then carbon monoxide poisoning effects lead to a headache, followed by nausea and possibly vomiting as the concentration of carboxyhemoglobin in the blood increases. To prevent these effects, OSHA has established a PEL of 50 ppm for an 8-hr exposure, identical to the TLV NIOSH, on the other hand, has decided to be more conservative and recommends a standard of 35 ppm. All of these concentrations refer to exposures with durations of 8 hr/day, 40 hr/week for a working lifetime and all are attempts to establish a "no effect" level. To prevent these effects, OSHA has established a PEL of 50 ppm for an 8-hr exposure, identical to the TLV. NIOSH, on the other hand, has decided to be more conservative and recommends a standard of 35 ppm. All of these carbon monoxide or other gas exposure limit concentrations refer to exposures with durations of 8 hr/day, 40 hr/week for a working lifetime and all are attempts to establish a "no effect" level. Here are some other exposure levels and effects of carbon monoxide exposure from various sources:
NOTES to the Carbon Monoxide Effects Table: sources include OSHA, EPA, www.transducertech.com ABBREVIATIONS: used with gas exposure limits:
Original document sourceThis carbon monoxide discussion file originated from a technical expert message board discussion on Carbon Monoxide and later Carbon Dioxide alarms, featuring comments by one of the leading authorities on CO, Jack Peterson, P.E., CIH, Ph.D., in May, 1987. NOTE: Daniel Friedman extracted CO and CO2 sections from that document, edited and added practical and field inspection-based information. Since its original publication this document has been expanded by reference materials from a variety of other sources. To convert between % and ppm concentration of carbon monoxide air see CONVERT PPM to % CONCENTRATIONCarbon Monoxide Hazards - Carboxyhemoglobin levels and related health effects on peopleQuoting from CPSC Indoor Air Pollution Book Online Copy Carbon monoxide is an asphyxiant. An accumulation of this odorless, colorless gas may result in a varied constellation of symptoms deriving from the compound's affinity for and combination with hemoglobin, forming carboxyhemoglobin (COHb) and disrupting oxygen transport. The elderly, the fetus, and persons with cardiovascular and pulmonary diseases are particularly sensitive to elevated CO levels. Methylene chloride, found in some common household products, such as paint strippers, can be metabolized to form carbon monoxide which combines with hemoglobin to form COHb. The following chart shows the relationship between CO concentrations and COHb levels in blood. Tissues with the highest oxygen needs -- myocardium, brain, and exercising muscle -- are the first affected. Symptoms may mimic influenza and include fatigue, headache, dizziness, nausea and vomiting, cognitive impairment, and tachycardia. Retinal hemorrhage on funduscopic examination is an important diagnostic sign19, but COHb must be present before this finding can be made, and the diagnosis is not exclusive. Studies involving controlled exposure have also shown that CO exposure shortens time to the onset of angina in exercising individuals with ischemic heart disease and decreases exercise tolerance in those with chronic obstructive pulmonary disease (COPD)20. Note: Since CO poisoning can mimic influenza, the health care provider should be suspicious when an entire family exhibits such symptoms at the start of the heating season and symptoms persist with medical treatment and time.
Carboxyhemoglobin levels and related health effects on people
SOURCE: a U.S. EPA (1979); b U.S. EPA (1985) Nitrogen dioxide (NO) and sulfur dioxide (SO2) act mainly as irritants, affecting the mucosa of the eyes, nose, throat, and respiratory tract. Acute S02-related bronchial constriction may also occur in people with asthma or as a hypersensitivity reaction. Extremely high-dose exposure (as in a building fire) to N02 may result in pulmonary edema and diffuse lung injury. Continued exposure to high N02 levels can contribute to the development of acute or chronic bronchitis. The relatively low water solubility of N02 results in minimal mucous membrane irritation of the upper airway. The principal site of toxicity is the lower respiratory tract. Recent studies indicate that low-level N02 exposure may cause increased bronchial reactivity in some asthmatics, decreased lung function in patients with chronic obstructive pulmonary disease, and an increased risk of respiratory infections, especially in young children. The high water solubility of S02 causes it to be extremely irritating to the eyes and upper respiratory tract. Concentrations above six parts per million produce mucous membrane irritation. Epidemiologic studies indicate that chronic exposure to S02 is associated with increased respiratory symptoms and decrements in pulmonary function21. Clinical studies have found that some asthmatics respond with bronchoconstriction to even brief exposure to S02 levels as low as 0.4 parts per million22. Frequently Asked Questions (FAQs) about carbon monoxide gas exposure, hazards, testing, and regulations in homes and other buildingsQuestion: My furnace service tech shut down my gas fired unit and says I need a new one. He said he could smell the CO and he wouldn't let me see his CO detector meter. Am I getting scammed?I recently had a serviceman come to work on our natural gas furnace. When he was done he said that it was unsafe and needed to be replaced. He indicated that there was a high level of carbon monoxide (10,000 ppm) and shut the furnace off. I was made a little suspicious when he directed me to the exhaust pipe for the furnace and told me that the leak was so bad he could smell the CO. Since I always thought that CO is odourless that hit me a little strange. Plus the fact that he shoved the meter he was using under my nose for 3 seconds, not enough time for me to even read what was on the display. His sales pitch was that the heat exchanged was clogged and needed to be replaced. Would there really be a CO level that high with a blocked exchanger or would it need to have a leak? Is it possible he is just trying to get some work out of me and hoping that I won't know any better? - Matthew Reply: CO itself is odorless, but mixed in with combustion flue gases there would be a "flue gas" smell that someone might observe;Watch out: Because of very serious life safety issues, do not turn the equipment back on. But before replacing the gas furnace due to a carbon monoxide hazard I'd want an accurate diagnosis of just what the problem really is. Some problems might indeed justify a whole new heater, for example if the heat exchanger is perforated and if the cost to remove and replace the damaged heat exchanger is close to the cost of a whole new furnace, I'd consider going with the latter. Other problems can cause flue gas spillage, equally dangerous, but with different solutions such as
I wouldn't insult the service tech when s/he may have been saving your life. But it's quite reasonable to ask that a carbon monoxide hazard be properly diagnosed and the evidence shown to you before you approve equipment replacement. After all, if you replace the gas furnace but leave an unsafe chimney in place a fatal carbon monoxide hazard could still be present. Question: what does a utility company gas furnace safety check red-tag placed on our heating equipment mean?When your Utility Company Technician performs a safety check of your gas furnace and determines it to be "unsafe/hazardous" plus "Shut off and capped due to recirculation," what exactly does this mean? - Chris Reply: significance of red-tagging heating equipment - serious safety hazards are present and the equipment cannot be safely used until repairedChris: details may vary by state or municipality, but in general you are describing what the industry calls "red tagging" - a utility company or a heating contractor or even a licensed plumber or other trades expert who inspects heating equipment and finds that it is in a condition that is unsafe to operate should leave the system turned off and red-tagged with - usually - an attached red safety tag that indicates the date, the identity of the inspector, and the unsafe condition. Question: asphyxiation hazards from gas fired water heaters?what asphyxiation statistics are available for water heaters and water heater venting? - Dan Lewis Reply:Dan that's an interesting way to put a carbon monoxide hazard question. Asphyxiation from CO depends on the concentration and exposure time, as we've published. One could calculate some theoretical carbon monoxide production rates from water heaters of various BTUH input ratings, but frankly in my opinion such data would be wild speculation. That's because the accumulation of a toxic gas in a building or any enclosed space depends on so many variables, such as: Question: how to conduct a carbon monoxide CO survey of CO from street traffic?I live on a residential street in the community of Glendale Ca. My street happens to be the only access to a regional park that was developed by the city. There are not only the hundreds of cars that access the park but also continual city large truck traffic and school busses that are creating high levels of CO. How can I get someone to take readings and correct this situation - Ken Steele Reply:Ken, different times of day and in different seasons
All of that data, collected and prepared with sufficient professionalism to be credible would be very expensive, surely thousands of dollars. Question: what might be causing a smell in my basement?aerosol smell in basement - what could be the cause - 6/26/2012 Anonymous Reply:Gee, Anon, I have no idea what an "aerosol" smell is. But you've posted the question on a carbon monoxide article - CO gas is odorless, though it can appear transported by gases from an oil or gas burner whose other combustion products may smell. For such a broad question, I suggest starting odor track-down at ODORS GASES SMELLS, DIAGNOSIS & CURE. Question: gas odors in my heating system - no leak was detected, why does it still smellI smell gas in my heating system.. I called for them to do a test... they said no alarm regeisterd a leak.. Reply:Jessie, CO alarms and detectors respond to that gas - Carbon Monoxide, but not necessarily to other combustion gases that would be present in escaping heating system exhaust. So if your chimney or heater is leaking - still potentiallyi dangerous including as a possible fire or as a possible inadequate draft equipment problem - relying on a CO detector alone would be nonsense. Ask your heating service manager to send an experienced technician to inspect your heating equipment for safe, proper operation. ... Ask a Question or Search InspectApediaQuestions & answers or comments about carbon monoxide gas exposure, hazards, testing, and regulations Ask a Question or Enter Search Terms in the InspectApedia search box just below. Technical Reviewers & ReferencesRelated Topics, found near the top of this page suggest articles closely related to this one.