InspectAPedia.com InspectAPedia ®
Building & Environmental Inspection, Testing, Diagnosis, Repair
HOME | AIR CONDITION| ELECTRICAL
ENERGY SAVE
| ENVIRONMENT| EXTERIOR| HEAT| HOME INSPECT| INSULATE
VENTILATE
| INTERIOR| MOLD TEST| PLUMBING
WATER
SEPTIC
| ROOF| SOLAR| STRUCTURE| CONTACT
DIRECTORY OF BUILDING INSPECTION & TESTING PROFESSIONALS


Mobile Phone/PDA website viewMobile View
HEATING SYSTEMS
AIRBOUND HEAT SYSTEM REPAIRS
ANODES & DIP TUBES on WATER HEATERS
ANTI SCALD VALVES
BOILERS, HEATING
  BOILER OPERATION DETAILS
  BOILER CONTROLS & SWITCHES
  Air Bleeder Valves
  Air-bound boilers & radiators
  Air Scoops Purgers Separators
  Aquastat Control Functions
  Boiler Pressure Controls & Settings
  Cad Cell Relay Switch Flame Sensors
  Check Valves Flow Control Valves Flo Control
  Circulator Pumps & Relays
  Draft Regulators, Dampers
  ELECTRIC MOTOR OVERLOAD RESET SWITCH
  ELECTRICAL POWER SWITCH FOR HEAT
  Expansion Tanks
  FIRE SAFETY CONTROLS
  Gauges on Heating Equipment
  Limit Switches, Boilers
  Low Water Cutoff Valves, Boilers
  Mixing Valves
  Relief Valves - TP Valves
  Reset Switch - Primary Control
  Reset Switch - electric motors
  Spill Switches
  Stack Relay Switch
  THERMOSTATS
  Water Feeder Valves, Hydronic Boiler
  Zone Valves
BOILER LEAKS CORROSION STAINS
BOILER LEAKS, HOW TO LOCATE
BOILER NOISE SMOKE ODORS
BOILER OPERATING PROBLEMS
BOILER OPERATION DETAILS
BOILER PRESSURE & TEMPERATURE SETTINGS
BUILDING SAFETY HAZARDS GUIDE
CARBON MONOXIDE/DIOXIDE
CARBON MONOXIDE WARNING
CHIMNEY INSPECTION DIAGNOSIS REPAIR
CHIMNEYS & Flues - Asbestos Transite Pipe
COMBUSTION GASES & PARTICLE HAZARDS
COMBUSTION PRODUCTS & IAQ
COMPLETE COMBUSTION, Stoichiometric
DEFINITION of Heating & Cooling Terms
DRAFT HOODS - gas fired
DRAFT REGULATORS - barometric dampers
DUCT SYSTEM & DUCT DEFECTS
DUCT INSULATION, Asbestos Paper
DUCTS, Asbestos Transite Pipe
DUST FROM HVAC?
ELECTRIC HEAT
ELECTRIC MOTOR DIAGNOSTIC GUIDE
ELECTRIC MOTOR OVERLOAD RESET SWITCH
ELECTRICAL POWER SWITCH FOR HEAT
ENERGY SAVINGS in BUILDINGS
EVAPORATIVE COOLING SYSTEMS
FAN CONVECTOR HEATERS - HYDRONIC COILS
FIRE SAFETY CONTROLS
FIREPLACE Damage & Unsafe Hearths - Settlement
FLUE VENT CONNECTORS
FREEZE-PROOF A BUILDING
FUEL OIL TYPES & CHARACTERISTICS
FURNACES, HEATING
FURNACE CONTROLS & SWITCHES
FURNACE OPERATION DETAILS
GAS PIPING, VALVES, CONTROLS
GAUGES ON HEATING EQUIPMENT
HEAT LOSS in BUILDINGS
HEAT LOSS DETECTION TOOLS
HEAT LOSS INDICATORS
HEAT LOSS PREVENTION PRIORITIES
HEAT LOSS R U & K VALUE CALCULATION
HOUSEWRAP AIR & VAPOR BARRIERS
HEAT TAPES, Heat, Insulation prevent Freeze-Up
HEATING COST SAVINGS METHODS
HEATING LOSS DIAGNOSIS-BOILERS
HEATING LOSS DIAGNOSIS-FURNACES
HEATING OIL CLOUD WAX GEL POINT
HEATING OIL EXPOSURE HAZARDS, LIMITS
HEATING OIL SHELF LIFE
HEATING OIL SLUDGE
HEATING SMALL LOADS
HEAT PUMPS
HEATING SYSTEM INSPECTION DIAGNOSIS REPAIR
HOT WATER HEATERS
HOT WATER IMPROVEMENT
INSULATION INSPECTION & IMPROVEMENT
LP & Natural Gas Safety Hazards
MANUALS & PARTS GUIDES - HVAC
MIXING VALVES
NO HEAT - BOILER / FURNACE DIAGNOSIS
Nanotechnology & Carbon Nanotube Hazards
NOISE / SOUND DIAGNOSIS & CURE
NOISE CONTROL for PLUMBING
NOISES COMING FROM WATER HEATER
ODORS & SMELLS DIAGNOSIS & CURE
ODORS FROM HEATING SYSTEMS
OIL BURNERS
OIL BURNER INSPECTION GUIDE
OIL BURNER NOISE SMOKE ODORS
OIL BURNER NOZZLE & ELECTRODES
OIL BURNERS, RETENTION HEAD
OIL BURNER SOOT & PUFFBACKS
OIL FUEL TYPES & CHARACTERISTICS
Oil Odors: Leaky Oil Tank Piping
OIL PUMP FUEL UNIT PRESSURE SETTING TIPS
OIL SAFETY VALVES
OIL TANKS
OIL TANK GAUGES
OIL TANK INSPECTION REPORTS
OIL TANK LEAKS & SMELLS
OIL TANK PIPING DEFECTS
OIL TANK PRESSURE
OIL TANK SAFETY
OIL TANK SLUDGE
OIL TANK TESTING
OIL TANKS, BURIED
PLASTIC HEATER VENT
PULSE COMBUSTION HEATERS
PASCAL CALCULATIONS
RADIANT BARRIERS
RADIANT HEAT
RADIANT HEAT Floor Mistakes to Avoid
RADIANT SLAB FLOORING CHOICES
RADIANT SLAB TUBING & FLUID CHOICES
RADIATORS
RELIEF VALVES - TP Valves on Boilers
Relief Valves - Water Heaters
Reset Switch - Heater Primary Control
Reset Switch - Electric Motors
Reset Switch - Stack Relays
SAFE DECK CONSTRUCTION GUIDE
SAFETY HAZARDS & INSPECTIONS
SAFETY HAZARDS GUIDE
SAFETY DURING HEATING INSPECTION
Safety Recalls, Chimneys, Vents, Heaters
  BLUE vs YELLOW COMBUSTION FLAMES
  BLUERAY Recall
  CHIMNEYS & Flues - Asbestos Transite
  Goodman HTPV RECALL
  Heat Recovery Ventilator RECALL
  Lennox Furnace Manuals
  Lennox SAFETY WARNING
  PLASTIC Plexvent / Ultravent RECALL
  Weil McLain RECALL
SAFETY DURING HEATING INSPECTION
SOOT on OIL FIRED HEATING EQUIPMENT
SPILL SWITCHES - Flue Gas Detection
STACK RELAY SWITCHES
STAIN DIAGNOSIS on Indoor Surfaces
STEAM HEATING SYSTEMS
  Steam Vents
TANKLESS COILS
THERMAL EXPANSION of MATERIALS
THERMAL MASS in BUILDINGS
  THERMAL MASS FLOOR SLABS
  THERMAL MASS in UPSTAIRS
  THERMAL MASS WALL DESIGN
  THERMAL MASS in HOMES - STUDY
THERMAL TRACKING & HEAT LOSS
THERMOSTATS
Transite Pipe Chimneys & Flues
WATER HEATERS
ZONE VALVES

More Information


InspectAPedia.comInspectAPedia ® Home & Site Map
InspectAPedia Blog - News Updates
AIR CONDITIONING & HEAT PUMPS
BOOKSTORE
ELECTRICAL
ENERGY SAVINGS
ENVIRONMENT
EXTERIORS
HEATING
HOME INSPECTION
INSULATION
INTERIORS
MOLD INSPECT/TEST
PLUMBING
ROOFING
SEPTIC SYSTEMS
SOLAR ENERGY
STRUCTURE
VENTILATION
WATER SUPPLY
ACCURACY & PRIVACY POLICIES
CONTACT



LARGER VIEW of hot water heating air bleed valveHot Water Heat Air Bleeder Valves: a Guide to Air Bleeders for Radiators, Baseboards, Convectors
InspectAPedia®  -    

  • Guide to Air Bleeder Valves on Heating Systems: Heating System Radiator, Baseboard, or Convector Air Bleeder Valve Troubleshooting & Repair Guide
  • How to diagnose and fix heating system noises & air in hot water heating system pipes
  • Service Procedures to force air out of an air-bound hot water heating system
  • How to inspect & repair forced hot water heating systems
Our site offers impartial, unbiased advice without conflicts of interest. We will block advertisements which we discover or readers inform us are associated with bad business practices, false-advertising, or junk science. Our contact info is at InspectAPedia.com/Contact.htm.

Here we discuss how to diagnose and repair problems with air bleed valves and we describe methods used to remove un-wanted, air from noisy or air-bound hot water heating system pipes, radiators, convectors, and baseboards. If a hot water heating system develops too much air in the piping you may hear bubbling or gurgling in the heating pipes when the heating system is operating, or worse, so much air may be in the heating piping, radiators, or baseboards that heat may simply not circulate at all.

Here we explain how to locate, inspect, use, or replace automatic and manual air bleed valves on hot water heat, and we explain methods used to remove air from air-bound hot water heating systems by finding and repairing or using automatic or manual air bleeder valves, or by using two different service procedures to force air out of airbound pipes in a hot water heating system. This article is divided into these main sections:

Our discussion of radiators or baseboards that do not get hot when they should includes these key sections:

  1. Air Bleeder Valves - a Guide to Air Bleeder Valves for Hot Water Heating Systems: Radiators, Baseboards, Convectors - how to find and use manual and automatic air bleeders to fix noisy gurgling heating pipes or an airbound heating system.
  2. Air Scoops, Air Separators, Air Purgers: Since on many hot water heating systems a key air bleeding or air vent point is at the air scoop or air separator closer to the boiler, see Air Scoops Purgers Separators. Air purges for steam heating systems are discussed separately at Steam Vents.
  3. Airbound Heating System Relief Procedure #1 Using Water Feeder & Boiler Drain - how to use built-in controls and valves to force air out an air-bound heating system whose radiators, convectors, or baseboards are not warming up
  4. Airbound Heating System Relief Procedure #2 Using a Pony Pump - how to use a portable pump, short sections of garden hose, and heating system valves to force air out an air-bound heating system whose radiators, convectors, or baseboards are not warming up.
  5. Water Feeder Valves, Hydronic - a defective automatic water feeder valve on a hot water heating boiler can result in too little starting water pressure in the system - radiators on upper floors may fail to receive heat. On a steam heating boiler a defective automatic water feed valve can cause the heating system to shut down completely or can lead to boiler damage or even unsafe conditions. At BOILER PRESSURE & TEMPERATURE SETTINGS we discuss the pressures needed for hydronic or hot water heating systems - a taller building needs higher starting (cold) pressure in the heating boiler. At Water Feeder Valves, Hydronic we discuss problems with water feeder valves that also control water pressure in the boiler and we explain how to adjust the water feeder valve and thus boiler water pressure. If your heating system uses a steam boiler, see Water Feeder Valves, Steam.

Readers should also see Diagnose Oil Heat Noises for diagnosis and repair of other heating system noises on both oil and gas fired heating equipment. This website answers most questions about central heating system troubleshooting, inspection, diagnosis, and repairs. Contact us to suggest text changes and additions and, if you wish, to receive online listing and credit for that contribution.

If you don't know what kind of heat your building uses, see our introduction at BOILERS, HEATING. If your heating system is not working properly, see NO HEAT - BOILER / FURNACE DIAGNOSIS.This website answers nearly all questions about Heating System Boiler Controls on central heating systems to aid in troubleshooting, inspection, diagnosis, and repairs.

A Guide to Air Bleeder Valves for Hot Water Heating Systems: Radiators, Baseboards, Convectors

Photograph of an oil fired heater stack relay

Heating Baseboard Air Bleeder Valves what are these valves for, where are they found, how do we use them?

Air bleeder valves are installed on hot water heating systems to remove unwanted air from the heating boiler, from hot water heat distribution piping, and from radiators, convectors, or baseboards.

Our photo (left) shows a manually operated air bleed valve at one end of a hot water heating baseboard. In this case freezing has caused the pipe connection to pop loose and leak - a different problem.

What Are the Functions of Hot Water Heating System (hydronic heat) Air Bleeder Valves?

Radiator air bleed valve (C) Carson DunlopAir bleeder valves, both manual and automatic, are used forced hot water heating systems to remove un-wanted air from the heating distribution pipes and radiators.

Carson Dunlop's sketch (left) shows a common location for the air bleed valve on a cast iron radiator. The advice to leave this valve alone is intended for home inspectors who don't want to risk spilling water on someone's floor or opening a valve to find that they can't close it again. But if your hot water radiator or convector is staying cold even though the heating boiler is running and hot, it may be air-bound and you'll need to bleed out the air.

Why is it necessary to get this air out of heating lines?

Air trapped in hot water heating piping, radiators, baseboards, or convectors makes the heating system noisy with gurgling or bubbling sounds if there is just a little air in the heating system.

But if the volume of air becomes too great, the heating system will simply stop delivering heat to the occupied spaces, some or all of them, in the building. Why? A heating circulator pump is capable of pushing water around in the loop of heating baseboard but is often not capable of overcoming a section of baseboard that contains a large bubble of air. It's necessary to remove such air blocks. If air blocking has been recurrent a previous owner may have installed air bleeders at strategic points.

See Air Bleeder Valves (this document) for details about how to get an individual cold radiator working again if it's air bound, and see AIRBOUND HEAT SYSTEM REPAIRS if the cold radiator, convector, or baseboard problem seems to affect all of the heating radiation devices on all or part of an individual heating piping loop or zone.

What are the Types of Air Bleeder Valves and Where are they Found on Hot Water Heat Systems?

Automatic air purge devices (photo at page top) are available and are usually installed right at the heating boiler but sometimes additional ones are needed at higher levels in the building.The two most common locations for automatic air bleeder valves on hot water heating systems are on top of the heating boiler itself (photo below right), or on a special air-scoop and air purging device found on the hot water heating piping just over or near the heating boiler (photo below left).

Air bleeder valve atop a hot water heating boiler (C) Daniel FriedmanAir scoop and air purge valve atop a heating boiler (C) Daniel Friedman

Manual air bleed valve on a heating baseboard (C) Daniel FriedmanManual air bleeder valves (photo above) can be opened slightly and carefully, to permit air to escape. Some heating convectors may have a tapping closed by a plug (photo at left) where an air bleeder valve can be installed - much more convenient than having to remove and replace the plug itself to get air out of the heating system piping.

As soon as water starts coming out of an air bleeder valve it can be closed.

The most common location for manual air bleeder valves on hot water heating systems are on heating radiators and convector units (every one), and at the ends of heating baseboard sections where there has been a previous problem with becoming air bound.

How to Diagnose and Repair Hot Water Heat Air Bleeder Valve Problems

Check hot water baseboards, radiators, or heating convectors: if some of these heating devices are hot and others cold, are they all on the same heating zone? Feel the hot water piping leaving the heating boiler - it should be hot when the boiler is running and the thermostat is calling for heat.

If the building has multiple heating zones each zone will be controlled by its own thermostat and each heating zone will either have its own hot water circulator pump (controlled by a thermostat and pump relay switch), or each hot water heating zone will have its own thermostat and a zone valve that opens to let a common circulator pump send hot water through that individual heating zone. Are all of the thermostats turned up high enough to call for heat in each heating zone?

If some heating baseboards or radiators are hot and others cold and we're sure that they're on the same heating zone, then the system is probably air-blocked.

How to Get Un-wanted Air out of a Hot Water Heating System

Virtually every hot water heating system has one or more air bleed valves installed. On most hot water heating systems there is at least one automatic air bleed valve, usually located on the heating boiler itself, or close to the heating boiler on a nearby check valve or flow controller.

Inspect and fix or replace the automatic air bleeder valves:

Air bleeder valve corrosion (C) Daniel Friedman

Is there a little cap on top of the air bleeder? many air bleeders use an internal float and an air valve stem that is about the same as the valve stem of an automobile tire valve or bicycle tire valve. The cap over these valves looks just like the cap on the valve stem on a tire (it is).

But on an air bleeder the valve cap is normally left loose so that when the valve has accumulated enough air to move the internal float the valve can open to expel the air.

If the valve cover is screwed down tightly, or if the valve cover has become clogged with mineral debris left by leaking water, air cannot be released. Loosen the valve cap.

If air escapes when you loosen the valve cap on the air bleed valve, that's good.

If the valve cap on your air bleeder is badly corroded (photo above left) the valve probably needs to be replaced.

Water leak at an air bleed purge valve on a heating system (C) Daniel Friedman

If water starts to leak out of the air bleeder valve continuously (photo at left) (it's ok for a drop or so to be expelled if the leak stops quickly) then screw the cap down tight again and ask your heating service technician to replace the valve.

If loosening the valve cap does not make water leak out, leave the cap loose.

Corroded air bleeder valve (C) Daniel Friedman

  • Is the air bleeder valve corroded? If the air bleeder is thick with corrosion or mineral deposits (photo at left) it has probably been leaking water when it should not, and it probably needs replacement.

    If the air bleeder valve is badly corroded or coated with mineral deposits it's safer to leave the valve alone. Picking at a corroded plumbing or heating component of any sort risks starting a leak that you cannot stop without having to shut the entire system down. Call your heating service technician.
  • Additional automatic air bleeder valves may be installed at other points on the hot water piping, usually at a higher spot near the boiler and sometimes on upper floors in the building. Look for and check the operation of these air bleeder valves too.

Inspect and use or replace manual air bleeder valves on the heat distribution piping:

  • Problem spot manual air bleed valves: If a building heating system has experienced previous problems with air blockage in the heating system a technician may have installed a manual bleed valve at a strategic location to get air out of a problem section of piping. Look for valves that resemble the one shown in our photo.
  • Problem spot air bleeder valves on hot water heating piping or baseboards can be hard to find, usually at the higher end of a section of heating baseboard that has become air-bound in the past. An example is show in our next photo (below).
  • Also see SOLAR COLLECTOR AIR or GAS COLLECTION for a discussion of automatic air bleed valves on solar collectors.

How to Open Manual Air Bleeder Valves on Heating Radiators and Baseboards to Bleed Out Air - step by step guide

Here we describe the procedure for using manual air bleeder valves to remove un-wanted air in a hot water heating system in order to correct noisy gurgling pipes or to correct loss of heat due to an air-bound radiator, heating convector, or section of hot water heating baseboard. If your hot water heating system has become air-bound (one or more sections of heating radiators or baseboards are staying cold even though the boiler is on and the circulator pump is running), and if your system does not have an air bleed valve to remove air blocking water flow, you probably need to call a heating service technician who will use one of the methods we describe at Airbound Heating System Relief Procedure.

Honeywell round thermostat (C) Daniel Friedman

Step 1: turn on and turn up the heat. First make sure that your thermostat is calling for heat and that the heating system boiler has been running for ten minutes or so - to insure that the system is warm and up to normal operating pressure.

This step is necessary to ensure that heating system pressure will easily push out air from the air-bound radiator or baseboard, and to subsequently force hot heating water into the previously cold radiator or baseboard, confirming that you have successfully removed air that was preventing heat from rising into that unit.

In our photo, the room temperature (bottom scale) is at about 70 degF and the thermostat is set to 65 deg. F - in this condition the heating system will be off and removing un-wanted air in the system would be more difficult.

Manual air bleed valve on a heating baseboard (C) Daniel Friedman

Step 2: find the air-bound radiator or baseboard: if you have not already done so, once the heating system is up to operating temperature and pressure, check each radiator, convector, or heating baseboard to see if it has warmed up. If you find one or more that remain cold, and provided that the cold heating radiator's valve is in the "open" position (counterclockwise), proceed to step 3 to see if that unit was air-bound.

Our photo (left) shows a manually-operated air bleeder on a heating baseboard.

In a building whose heat is delivered by hot water radiators or by hot water convector units every one of these may have its own individual manually-operated air bleeder valves installed.

If one radiator or convector is not heating up, find and open the air bleeder valve to let out air. Close the valve immediately when water begins to come out.

We hold a cup under the valve spout during this operation so we don't spill water in the living area. (Photo below.)

How to bleed air out of a heating system (C) Daniel FriedmanStep 3: bleed out excess air: Open the air bleed valve (turn it counter-clockwise) and listen for the hiss of escaping air. If no air comes out of the valve, just water, then the radiator or baseboard served by that valve is not air-bound.

A "roller skate key" like device may be needed to turn the recessed square end of older manual air bleeders on radiators and heating convectors.

But in pinch we've been able to open and close the valve using needle-nose pliers (photo at left) that have a point fine enough to reach into and grasp the square end of the valve control.

Step 4: close the air bleeder valve. When water begins to come out of the valve, close it.

Step 5: feel the heating pipes entering the baseboard, radiator or convector. In a minute or so the pipes and radiator should begin to warm up and eventually become hot. If this does not occur either the heating system is off, there is another airbound location, or there is a separate problem with the heating system. In that case see HEATING LOSS DIAGNOSIS-BOILERS.

Manual air bleeder valve on a heating convector (C) Daniel Friedman

Other air bleeder valves are opened using a simple flat-bladed screwdriver.

But if the manual, screwdriver-operated air bleeder valve is badly corroded such as the one shown in our photo of a manual air bleed valve at the bottom of a heating radiator (photo at left) chances are it has been leaking and it be stuck.

This particular valve was one we handled with great care. If it was not easy to open and shut it again with a screwdriver (without much force) we'd have chosen to leave the valve alone until it could be replaced.

How Do we Know That the Air Bleed Valve Operation Has Been Successful?

  • If you open a manual air bleeder valve on a hot water heating system and air hisses out, there was air that needed removal. If only water comes out, that device was not the one that is air bound.
  • If the heating boiler is already running and hot, quite quickly, in a minute or three, the radiator or convector that was air bound will get hot to the touch. Feel first at the pipes that enter the radiator, convector or heating baseboard since that's where hot water will begin entering the previously air-bound device.

.

Share this Article      

...

Technical Reviewers & References

Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

HEATING SYSTEMS
AGE of HEAT PUMPS
AGE of HEATERS, BOILERS, FURNACES
AIR FILTERS for HVAC SYSTEMS
AIR HANDLER UNIT
AIRBOUND HEAT SYSTEM REPAIRS
ANODES & DIP TUBES on WATER HEATERS
ANTI SCALD VALVES
ANIMAL ALLERGENS / PET DANDER
ANIMAL ODORS IN BUILDINGS
APPLIANCE EFFICIENCY RATINGS
ASBESTOS in BUILDINGS
BACKFLOW PREVENTERS
BACKUP HEAT for HEAT PUMPS
BAROMETRIC DAMPERS
BIOGAS PRODUCTION & USE
BLOWER DOORS & AIR INFILTRATION
BLOWER FAN OPERATION & TESTING
BLUE vs YELLOW COMBUSTION FLAMES
BLUERAY Recall
BOILERS, HEATING
  BOILER OPERATION DETAILS
  BOILER CONTROLS & SWITCHES
  Air Bleeder Valves

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

HOME | AIR CONDITION| ELECTRICAL
ENERGY SAVE
| ENVIRONMENT| EXTERIOR| HEAT| HOME INSPECT| INSULATE
VENTILATE
| INTERIOR| MOLD TEST| PLUMBING
WATER
SEPTIC
| ROOF| SOLAR| STRUCTURE| CONTACT
© 2010 Copyright InspectAPedia.com All Rights Reserved ABOUT USACCURACY POLICY ADVERTISING POLICY BOOKSTORE LINK EXCHANGE PRIVACY POLICY SEARCHWEBSITE CONTENT USE POLICYWEBSITE DESCRIPTION