InspectAPedia ®

Building & Environmental Inspection, Testing, Diagnosis, Repair, & Problem Prevention Advice
InspectAPedia
Home
| Air
Conditioning
| Electrical | Indoor
Environment
| Exteriors | Heating | Home
Inspection
| Insulate
Ventilate
| Interiors | Mold
Inspect/Test
| Plumbing
Water
Septic
| Roofing | Structure | Contact Us
Directory of Professionals to Inspect or Test a Building


Mobile Phone/PDA website viewMobile View
HEATING SYSTEMS
ANODES & DIP TUBES on WATER HEATERS
ANTI SCALD VALVES
BOILERS, HEATING
  BOILER OPERATION DETAILS
  BOILER CONTROLS & SWITCHES
  Air Bleeder Valves
  Air-bound boilers & radiators
  Air-bound heating systems part-2
  Aquastat Functions
    Aquastat control HI LO settings
    Aquastat control DIFF settings
    Single Function Limit Switches
  BOILER LEAKS CORROSION STAINS
  BOILER OPERATING PROBLEMS
  BOILER PARTS LIST
  Boiler Pressure Controls & Settings
  Cad Cell Relay Switch Flame Sensors
  Circulator Pumps & Relays
  Draft Regulators, Dampers
  Expansion Tanks
  Gauges on Heating Equipment
  Limit Switches, Boilers
  Low Water Cutoff Valves, Boilers
  Mixing Valves
  Relief Valves - TP Valves
  Reset Switch - Primary Control
  Reset Switch - electric motors
  Spill Switches
  Stack Relay Switch
  Thermostats
  Water Feeder Valves, Hydronic Boiler
  Zone Valves
  WATER HEATERS
ZONE VALVES
CARBON MONOXIDE/DIOXIDE
CARBON MONOXIDE WARNING
CHIMNEY INSPECTION DIAGNOSIS REPAIR
CHIMNEYS & Flues - Asbestos Transite Pipe
COMBUSTION GASES & PARTICLE HAZARDS
COMBUSTION PRODUCTS & IAQ
DEFINITION of Heating & Cooling Terms
DRAFT HOODS - gas fired
DRAFT REGULATORS - barometric dampers
DUCT SYSTEMS
DUCT INSULATION, Asbestos Paper
DUCTS, Asbestos Transite Pipe
DUST FROM HVAC?
ELECTRIC HEAT
ELECTRICAL POWER SWITCH FOR HEAT
ENERGY SAVINGS in BUILDINGS
ENERGY SAVINGS PRIORITIES
ENERGY SAVINGS RETROFIT CASE STUDY
ENERGY SAVINGS RETROFIT LEAK SEALING GUIDE
ENERGY SAVINGS RETROFIT OPTIONS
FLUE VENT CONNECTORS
FREEZE-PROOF A BUILDING
FURNACES, HEATING
  DUCT SYSTEM DEFECTS
  FAN LIMIT SWITCH
  FURNACE CONTROLS & SWITCHES
  FURNACE OPERATION DETAILS
  HEAT EXCHANGER LEAKS
  STACK RELAY SWITCHES
GAS PIPING, VALVES, CONTROLS
GAUGES ON HEATING EQUIPMENT
HEAT LOSS in BUILDINGS
HEAT LOSS DETECTION TOOLS
HEAT LOSS INDICATORS
HEAT LOSS R U & K VALUE CALCULATION
HOUSEWRAP AIR & VAPOR BARRIERS
HEATING COST SAVINGS METHODS
HEATING LOSS DIAGNOSIS-BOILERS
HEATING LOSS DIAGNOSIS-FURNACES
HEATING OIL CLOUD WAX GEL POINT
HEATING OIL EXPOSURE HAZARDS, LIMITS
HEATING OIL SLUDGE
HEATING SMALL LOADS
HEAT PUMPS
HEATING SYSTEM INSPECTION PROCEDURE
  HEATING INSPECTION CONCEPTS
  HEATING INSPECTION PROCEDURE
HOT WATER HEATERS
HOT WATER IMPROVEMENT
INSULATION & VENTILATION INSPECTION & IMPROVEMENT
MIXING VALVES
NO HEAT - BOILER / FURNACE DIAGNOSIS
OIL BURNERS
OIL BURNER INSPECTION GUIDE
OIL BURNER NOISE SMOKE ODORS
OIL BURNER SOOT & PUFFBACKS
OIL FUEL TYPES & CHARACTERISTICS
Oil Odors: Leaky Oil Tank Piping
OIL SAFETY VALVES
OIL TANKS
OIL TANK GAUGES
OIL TANK LEAKS
OIL TANK SLUDGE
OIL TANK TESTING
OIL TANKS, BURIED
PLASTIC HEATER VENT
RADIANT HEAT
RADIANT HEAT Floor Mistakes to Avoid
RADIANT SLAB FLOORING CHOICES
RADIANT SLAB TUBING & FLUID CHOICES
RADIATORS
RELIEF VALVES - TP Valves on Boilers
Relief Valves - Water Heaters
SAFETY DURING HEATING INSPECTION
Safety Recalls
  BLUERAY Recall
  CHIMNEYS & Flues - Asbestos Transite
  Goodman HTPV RECALL
  Heat Recovery Ventilator RECALL
  Lennox Furnace Manuals
  Lennox WARNING
  Weil McLain RECALL
SAFETY DURING HEATING INSPECTION
SOOT on OIL FIRED HEATING EQUIPMENT
SPILL SWITCHES - Flue Gas Detection
STAIN DIAGNOSIS on Indoor Surfaces
STEAM HEATING SYSTEMS
  Cad Cell Relay Switch Flame Sensors
  Low Water Cutoff Valves, Boilers
  Mixing Valves
  Relief Valves - TP Valves
  Sight Glass, Steam Boiler
  Pressure Switch, Steam Boiler
  Spill Switches
  Stack Relay Switch
  Steam Vents
  LOW WATER CUTOFF CONTROLS
  Water Feeder Valves, Steam
TANKLESS COILS
  Tankless Coil Leaks
THERMAL EXPANSION of MATERIALS
THERMAL MASS in BUILDINGS
THERMAL MASS in UPSTAIRS
THERMAL TRACKING & HEAT LOSS
THERMOSTATS
Transite Pipe Chimneys & Flues
WATER HEATERS
ZONE VALVES

More Information


InspectAPedia.comInspectAPedia ® Home & Site Map
InspectAPedia Blog - News Updates
Air Conditioning & Heat Pumps
Bookstore
Electrical
Environment
Exteriors
Heating
Home Inspection
Insulate Ventilate
Interiors
Mold Inspect/Test
Plumbing Water Septic
Roofing
Structure
Accuracy & Bias Pledge
Contact Us



Automatic water feed valve (C) Daniel FriedmanGuide to Fixing an Air-Bound Hot Water Heating System - Procedure#1, Using Built-In Controls & Valves
InspectAPedia®  -    

  • Service Procedures to force air out of an air-bound hot water heating system
  • Guide to Air Bleeder Valves on Heating Systems: Heating System Radiator, Baseboard, or Convector Air Bleeder Valve Troubleshooting & Repair Guide
  • Cold radiators: if your radiators won't get hot : how to check for an airbound radiator and other causes
  • How to diagnose and fix heating system noises & air in hot water heating system pipes
Our site offers impartial, unbiased advice without conflicts of interest. We will block advertisements which we discover or readers inform us are associated with bad business practices, false-advertising, or junk science. Our contact info is at InspectAPedia.com/appointment.htm.

Here we discuss how to remove un-wanted, air from noisy or air-bound hot water heating system pipes, radiators, convectors, and baseboards using the automatic water feed valve on a heating boiler. If a hot water heating system develops too much air in the piping you may hear bubbling or gurgling in the heating pipes when the heating system is operating, or worse, so much air may be in the heating piping, radiators, or baseboards that heat may simply not circulate at all.

If radiators of your building are not getting hot, the discussion here can help diagnose and cure that problem.

Here we explain how to locate, inspect, use, or replace automatic and manual air bleed valves on hot water heat, and we explain methods used to remove air from air-bound hot water heating systems by finding and repairing or using automatic or manual air bleeder valves, or by using two different service procedures to force air out of airbound pipes in a hot water heating system. This article is divided into these main sections:

Our discussion of radiators or baseboards that do not get hog when they should includes these key sections:

  1. Air Bleeder Valves - a Guide to Air Bleeder Valves for Hot Water Heating Systems: Radiators, Baseboards, Convectors - how to find and use manual and automatic air bleeders to fix noisy gurgling heating pipes or an airbound heating system. Air purges for steam heating systems are discussed separately at Steam Vents.
  2. Airbound Heating System Relief Procedure #1 Using Water Feeder & Boiler Drain - how to use built-in controls and valves to force air out an air-bound heating system whose radiators, convectors, or baseboards are not warming up
  3. Airbound Heating System Relief Procedure #2 Using a Pony Pump - how to use a portable pump, short sections of garden hose, and heating system valves to force air out an air-bound heating system whose radiators, convectors, or baseboards are not warming up.
  4. Water Feeder Valves, Hydronic - a defective automatic water feeder valve on a hot water heating boiler can result in too little starting water pressure in the system - radiators on upper floors may fail to receive heat. On a steam heating boiler a defective automatic water feed valve can cause the heating system to shut down completely or can lead to boiler damage or even unsafe conditions. At Boiler Pressure Settings we discuss the pressures needed for hydronic or hot water heating systems - a taller building needs higher starting (cold) pressure in the heating boiler. At Water Feeder Valves, Hydronic we discuss problems with water feeder valves that also control water pressure in the boiler and we explain how to adjust the water feeder valve and thus boiler water pressure. If your heating system uses a steam boiler, see Water Feeder Valves, Steam.

Readers should also see Diagnose Oil Heat Noises for diagnosis and repair of other heating system noises on both oil and gas fired heating equipment. This website answers most questions about central heating system troubleshooting, inspection, diagnosis, and repairs. Contact us to suggest text changes and additions and, if you wish, to receive online listing and credit for that contribution.

If you don't know what kind of heat your building uses, see our introduction at BOILERS, HEATING. If your heating system is not working properly, see NO HEAT - BOILER / FURNACE DIAGNOSIS.This website answers nearly all questions about Heating System Boiler Controls on central heating systems to aid in troubleshooting, inspection, diagnosis, and repairs.

Contact us to suggest text changes and additions and, if you wish, to receive online listing and credit for that contribution. © Copyright 2009 Daniel Friedman, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use links at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or Website.

Service Procedures to Fix an Air-Bound Hot Water Heating System

Here we describe the procedure that a heating service technician may use to remove un-wanted air in a hot water heating system in order to correct noisy gurgling pipes or to correct loss of heat due to an air-bound radiator, heating convector, or section of hot water heating baseboard.

If your hot water heating system has become air-bound (one or more sections of heating radiators or baseboards are staying cold even though the boiler is on and the circulator pump is running), and if your system does not have an air bleed valve to remove air blocking water flow, you probably need to call a heating service technician who will use one of the methods we describe here.

If your heating system does include both automatic and manual air-bleeder valves it is possible that you can correct a noisy or airbound heating system yourself. See Air Bleeder Valves and then How to Open Manual Air Bleeder Valves.

Airbound Heating System Relief Procedure #1 Using Water Feeder & Boiler Drain

LARGER VIEW of a heating boiler cad cell relay switchThe following procedure is the more simple of the two we describe for correcting an air-bound hot water (hydronic) heating system, and it avoids the need to use pumps or to install extra service drains that may have been omitted on the heating system. While this is the easiest and simplest procedure to remove air from an airbound heating system, you might not want to use this method if

  • The boiler is very hot and it is a cast iron unit that could be cracked by a sudden surge of incoming very cold water
  • The heating system has been filled with antifreeze.
  • The heating boiler drain (located at or near the bottom of the boiler) is in poor condition and may not be opened and then closed reliably.

In these cases see Procedure #2 below.

The steps in airbound heat remedy #1 include: :

  1. Turn off the heating boiler, using the service switch. If necessary, see ELECTRICAL POWER SWITCH FOR HEAT.
  2. Confirm that the heating system appears to be air-bound: heat is on and boiler temperature is up and the circulator pump is running; by touch the technician confirms that one or more sections of radiator, convector, or heating baseboard remain cold even though all radiator or convector or other circulating system valves are in the open position.
  3. Heating boiler drain (C) Daniel Friedman
    Connect a garden hose to the boiler drain
    and run the end of the hose outside or to a convenient indoor building drain. Open this drain.

    Our photo (left) shows a typical boiler drain valve - this one has been leaking, as you can see by the stain on the floor and the mineral deposits on the drain valve.

    All boiler drains have threads that accept a standard garden hose.









     

  4. LARGER VIEW of a heating boiler cad cell relay switchOpen the water feeder bypass: Locate and open the bypass or "over-ride" on the automatic water-feeder pressure-reducer on the heating boiler.

    On a residential heating boiler the automatic water-feeder/pressure reducing valve that automatically provides makeup water to the heating boiler if pressure drops below 12 psi.

    Usually this valve has a lever that can be lifted to temporarily bypass the pressure-reducing function and feed water directly to the heating boiler at street water pressure (up to 70 psi). See Water Feeder Valves, Hydronic Boiler for details about how this valve works.

    Lift the lever to feed high pressure water into the heating boiler. This should also force high pressure water through the heating distribution pipes, radiators, convectors, or baseboards, forcing air out of those components.

    Pressure in the boiler should not exceed 30 psi (otherwise the pressure/temperature relief valve will begin to spill water). Let the water "run" through the heating system, watching the hose output end for evidence that air along with water is spurting out of the hose.

  5. Close the water feeder bypass and quickly move to step 6 just below. This will stop forcing higher-pressure water into the boiler and the heating system piping.
  6. Close the boiler drain valve. This will stop water from leaving the boiler.
  7. Set the proper boiler cold water pressure: The automatic water feeder will put additional water into the boiler until it reaches its starting pressure.

    If the boiler pressure is below its normal level the automatic water feeder should correct this problem. Watch the boiler pressure fill up to its normal cold pressure setting - typically this is around 12 psi on a two story home.

    If the boiler pressure is too high and the boiler is cold, use the boiler drain to drop the boiler pressure to the proper starting level.

    See Water Feeder Valves, Hydronic Boiler for a description of the typical pressures needed in residential hot water heating systems depending on the height of the highest radiator or baseboard above the heating boiler.
  8. Turn on the heating boiler and assure that the thermostat is calling for heat. When the system has reached normal operating temperature and pressure, check the radiators, convectors, or baseboard sections that were previously cold - they should now be warm.

    If the previously cold radiator (etc) still remains cold, either you have not removed enough air from the system or there is another problem causing loss of heat. In that case see HEATING LOSS DIAGNOSIS-BOILERS.
  9. Check the boiler drain valve to be sure it's not leaking. In an emergency we screw a garden hose cap on the end of a leaky heating boiler drain.
  10. Monitor heating system operation: we never leave a property where we have worked on the heating system without first checking for leaks, inspecting for obvious safety hazards (such as a bad relief valve, blocked flue, improper oil or gas burner operation), and confirming that the heating system runs through it's on-off cycle normally.

How Do we Know That the Air Bleed Valve Operation Has Been Successful?

  • If you open a manual air bleeder valve on a hot water heating system and air hisses out, there was air that needed removal. If only water comes out, that device was not the one that is air bound.
  • If the heating boiler is already running and hot, quite quickly, in a minute or three, the radiator or convector that was air bound will get hot to the touch. Feel first at the pipes that enter the radiator, convector or heating baseboard since that's where hot water will begin entering the previously air-bound device.

Contact us if you have other suggestions for improving this procedure. We are pleased to give credit and links to contributing reviewers, authors, or critics.

Share this Article      

...

Technical Reviewers & References

  • Daniel Friedman - principal author/editor of the InspectAPedia® Website
  • InspectAPedia Bookstore lists recommended books, organized by topic & available for purchase. Most of our articles also include a list of recommended books for the specific article topic as well as other references, and information sources.
  • Critique, contributions wanted: Contact Us to suggest corrections or additions to articles at this website, and if you wish, to receive online listing and credit as a contributor. Particular thanks are due to the many experts and also consumers who read and critique technical articles at InspectAPedia.com.
  • Additional technical contributors & reference sources for this article are listed below.

BOILERS, HEATING
  BOILER OPERATION DETAILS
  BOILER CONTROLS & SWITCHES
  Air Bleeder Valves
  Air-bound boilers & radiators
  Air-bound heating systems part-2

  • Thanks to reader Les Luka for pointing out that we needed to clarify step 5-6 in the air bleed procedure, 10/16/2009

For details about the setting, re-setting, or function of the controls and switches commonly found on hot air heating systems see these articles:

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building design, inspection, and repair, and about indoor environment testing, diagnosis, and cleanup are at the InspectAPedia Bookstore.
  • Carbon Dioxide Gas Toxicity
  • Carbon Monoxide Gas Toxicity, exposure limits, poisoning symptoms, and inspecting buildings for CO hazards
  • Dust from HVAC? An Investigation of Indoor Dust Debris Blamed on a Heating/Cooling System Reveals Carpet Dust
  • Goodman Furnace High Temperature Plastic Vent HTPV safety recall US CPSC notice
  • Home Heating System Should Be Checked [for proper venting and for CO Carbon Monoxide Hazards - DJF]
  • Inspection Procedures for Oil-Fired Heating Systems Detailed step by step approaches for inspecting complex systems]
  • Lennox Pulse Furnace Safety Inspection/Warranty Program: Carbon Monoxide Warning
  • Oil Tanks - The Oil Storage Tank Information Website: Buried or Above Ground Oil Tank Inspection, Testing, Cleanup, Abandonment of Oil Tanks
  • Oil Tanks Above Ground, UL Standards, guidance for home owners, buyers, and inspectors
  • Plastic Heating Vent Pipe & Other Heating Safety Recall Notices
  • Weil McLain Model GV Gas Boiler/gas valve CPSC recall/repair
  • Domestic and Commercial Oil Burners, Charles H. Burkhardt, McGraw Hill Book Company, New York 3rd Ed 1969.
  • National Fuel Gas Code (Z223.1) $16.00 and National Fuel Gas Code Handbook (Z223.2) $47.00 American Gas Association (A.G.A.), 1515 Wilson Boulevard, Arlington, VA 22209 also available from National Fire Protection Association, Batterymarch Park, Quincy, MA 02269. Fundamentals of Gas Appliance Venting and Ventilation, 1985, American Gas Association Laboratories, Engineering Services Department. American Gas Association, 1515 Wilson Boulevard, Arlington, VA 22209. Catalog #XHO585. Reprinted 1989.
  • The Steam Book, 1984, Training and Education Department, Fluid Handling Division, ITT [probably out of print, possibly available from several home inspection supply companies] Fuel Oil and Oil Heat Magazine, October 1990, offers an update,
  • Principles of Steam Heating, $13.25 includes postage. Fuel oil & Oil Heat Magazine, 389 Passaic Ave., Fairfield, NJ 07004.
  • The Lost Art of Steam Heating, Dan Holohan, 516-579-3046 FAX
  • Principles of Steam Heating, Dan Holohan, technical editor of Fuel Oil and Oil Heat magazine, 389 Passaic Ave., Fairfield, NJ 07004 ($12.+1.25 postage/handling).
  • "Residential Steam Heating Systems", Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
  • "Residential Hydronic (circulating hot water) Heating Systems", Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
  • "Warm Air Heating Systems". Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
  • Heating, Ventilating, and Air Conditioning Volume I, Heating Fundamentals,
  • Boilers, Boiler Conversions, James E. Brumbaugh, ISBN 0-672-23389-4 (v. 1) Volume II, Oil, Gas, and Coal Burners, Controls, Ducts, Piping, Valves, James E. Brumbaugh, ISBN 0-672-23390-7 (v. 2) Volume III, Radiant Heating, Water Heaters, Ventilation, Air Conditioning, Heat Pumps, Air Cleaners, James E. Brumbaugh, ISBN 0-672-23383-5 (v. 3) or ISBN 0-672-23380-0 (set) Special Sales Director, Macmillan Publishing Co., 866 Third Ave., New York, NY 10022. Macmillan Publishing Co., NY
  • Installation Guide for Residential Hydronic Heating Systems
  • Installation Guide #200, The Hydronics Institute, 35 Russo Place, Berkeley Heights, NJ 07922
  • The ABC's of Retention Head Oil Burners, National Association of Oil Heat Service Managers, TM 115, National Old Timers' Association of the Energy Industry, PO Box 168, Mineola, NY 11501. (Excellent tips on spotting problems on oil-fired heating equipment. Booklet.)
  • ...
HEATING SYSTEMS

More Information

InspectAPedia® Home & Site Map
Air Conditioning & Heat Pumps
Bookstore
Electrical
Environment
Exteriors
Heating
Home Inspection
Insulate Ventilate
Interiors
Mold Inspect/Test
Plumbing Water Septic
Roofing
Structure
Accuracy & Bias Pledge
Contact Us

More Information on Building Diagnostic Inspections and Repairs

  • ...
InspectAPedia.comInspectAPedia® Home & Site Map - Building & Environmental Inspection, Testing, Diagnosis, Repair, & Problem Prevention Advice: In-depth research & advice on diagnosing, testing, correcting, & preventing building defects & indoor environmental hazards. Unbiased information, no conflicts of interest.
GO TO the MOLD and INDOOR ENVIRONMENT INFORMATION CENTER for in-depth advice on avoiding testing for or cleaning up mold and other indoor environmental hazards, odors, gases, contaminants
The Mold Information Center:
What to Do About Mold in Buildings, When and How to Inspect for Mold, Clean Up Mold, or Avoid Mold Problems
GO TO MOLD TEST KITS: This expert-recommended mold test kit is cheap and yet top performing *IF* you use a competent analysis laboratory!
Use this simple, economical mold test kit
by following our instructions on how to collect and mail mold samples to our lab
GO TO IAQ/MOLD-TEST LAB SERVICES: Mold, Pollen, indoor air quality, field and laboratory services by an expert.Environmental Inspection, Testing, & Diagnosis On-Site IAQ, Gas, Air Testing, Mold Investigation, Sick Building Diagnosis, Lab Services, & Remediation Plan Preparation - indoor air quality testing, problem source determination, supporting lab work, written remediation plan addressing removal of environmental and other hazards and prevention of their recurrence.
GO TO our PRE PURCHASE BUILDING INSPECTION SERVICES: Authoritative information for home buyers and home owners is included with your inspection.
Building Inspection, Problem Diagnosis
, Forensic Investigation & Testing, Repair Consulting

CONTACT Daniel Friedman - Dan is a senior ASHI home inspector, nationally recognized expert on building inspection, building failures, and sick building investigation
Contact Daniel Friedman for website content suggestions or for fee-paid consulting

10/16/2009 - 09/05/1999 - InspectAPedia.com/heat/Air_Removal_1.htm - © 2009 - 1988 Copyright Daniel Friedman All Rights Reserved - InspectAPedia® is a Registered U.S. Trademark