InspectAPedia.com InspectAPedia®
 

Free Encyclopedia of Building & Environmental Inspection, Testing, Diagnosis, Repair

Ask a Question or Search InspectAPedia

  • HOME
  • AIR CONDITIONING
  • ELECTRICAL
  • EXTERIORS
  • HEATING
  • HOME INSPECTION
  • INTERIORS
  • PLUMBING
  • ROOFING
  • SEPTIC SYSTEMS
  • STRUCTURE
  • WATER SUPPLY
  • ENERGY SAVINGS
  • ENVIRONMENT
  • INDOOR AIR IAQ
  • INSULATION
  • MOLD INSPECT TEST REMOVE
  • NOISE
  • ODORS
  • SOLAR ENERGY
  • VENTILATION
  • EXPERTS DIRECTORY
  • CONTACT US


Mobile Phone/PDA website viewMobile View
HEATING SYSTEMS

AFUE DEFINITION, RATINGS
AGE of AIR CONDITIONERS & HEAT PUMPS
AGE of HEATERS, BOILERS, FURNACES
AIR CONDITIONING & HEAT PUMP SYSTEMS
AIR FILTERS for HVAC SYSTEMS

AIR HANDLER / BLOWER UNITS
AIRBOUND HEAT SYSTEM REPAIRS
ANODES & DIP TUBES on WATER HEATERS
ANTI SCALD VALVES
APPLIANCE EFFICIENCY RATINGS
ASBESTOS IDENTIFICATION IN buildings

BACKDRAFTING HEATING EQUIPMENT
BACKFLOW PREVENTERS
BACKUP HEAT for HEAT PUMPS
BAROMETRIC DAMPERS
BASEBOARD HEAT

BIOGAS PRODUCTION & USE
BLEVE EXPLOSIONS
BLOWER DOORS & AIR INFILTRATION
BLOWER FAN CONTINUOUS OPERATION
BLOWER FAN OPERATION & TESTING
BLUE vs YELLOW COMBUSTION FLAMES
BLUERAY Recall

BOILERS, HEATING
BOILER LEAKS CORROSION STAINS
BOILER LEAKS, HOW TO LOCATE
BOILER NOISE SMOKE ODORS
BOILER OPERATING PROBLEMS
BOILER OPERATION DETAILS
BOILER PRESSURE & TEMPERATURE SETTINGS
BOOKSTORE - InspectAPedia
BUILDING SAFETY HAZARDS GUIDE

CAPACITORS for HARD STARTING MOTORS
CARBON DIOXIDE - CO2
CARBON MONOXIDE - CO
CARBON MONOXIDE WARNING

CHIMNEY INSPECTION DIAGNOSIS REPAIR
CHIMNEYS & Flues - Asbestos Transite Pipe
CHINESE DRYWALL HAZARDS
CIRCULATOR PUMPS & RELAYS
COOL OFF HEAT, Thermostat Switch

COMBUSTION AIR
COMBUSTION AIR for TIGHT buildings
COMBUSTION GASES & PARTICLE HAZARDS
COMBUSTION PRODUCTS & IAQ
COMPLETE COMBUSTION, Stoichiometric
COMBUSTION GASES & PARTICLE HAZARDS
COMBUSTION PRODUCTS & IAQ
COMPLETE COMBUSTION, Stoichiometric

CONDENSING BOILERS/FURNACES
CONDENSING BOILERS/FURNACES DAMAGE
CONVECTOR HEATERS - HYDRONIC COILS

DEFINITION of Heating & Cooling Terms

DIAGNOSE & FIX AIR CONDITIONER / HEAT PUMP
DIAGNOSE & FIX HEATING PROBLEMS-BOILER
DIAGNOSE & FIX HEATING PROBLEMS-FURNACE

DRAFT HOODS - gas fired
DRAFT MEASUREMENT, CHIMNEYS & FLUES
DRAFT REGULATORS / Barometric Dampers
  Purpose of Barometric Draft Regulator
  Measure Draft
  Barometric Damper Defect List
  How to Inspect a Barometric Damper
  Automatic Vent Dampers
  Define flue damper, duct damper, & fire damper
  Draft Inducer Fans
DUCT INSULATION, Asbestos Paper

DUCT SYSTEM & DUCT DEFECTS
DUCTS, Asbestos Transite Pipe
DUST CONTAMINATION FROM HVAC?

ELECTRIC HEAT
ELECTRIC MOTOR DIAGNOSTIC GUIDE
ELECTRIC MOTOR OVERLOAD RESET SWITCH
ELECTRICAL POWER SWITCH FOR HEAT

ENERGY SAVINGS in buildings
EVAPORATIVE COOLING SYSTEMS

FAN, AIR HANDLER BLOWER UNIT
FAN AUTO ON Thermostat Switch
FAN, COMPRESSOR/CONDENSER UNIT
FAN CONVECTOR HEATERS - HYDRONIC COILS
FAN LIMIT SWITCH
FAN NOISES

FILTERS, AIR for HVAC SYSTEMS
FILTERS, OIL on HEATING EQUIPMENT

FIRE SAFETY CONTROLS
FIREPLACES & HEARTHS
FLAME COLOR, BLUE vs YELLOW COMBUSTION
FLOODED HEATING EQUIPMENT REPAIR
FLOODED WATER HEATER REPAIR
FLUE SIZE SPECIFICATIONS
FLUE VENT CONNECTORS
FREEZE-PROOF A BUILDING
FUEL OIL TYPES & CHARACTERISTICS
FUEL UNIT, HEAING OIL PUMPS

FURNACES, HEATING
FURNACE OPERATING TEMPERATURES

GALVANIC SCALE & METAL CORROSION
GAS BURNER Flame & Noise Defects
GAS FIRED WATER HEATERS

GAS PIPING, VALVES, CONTROLS

GAUGES ON HEATING EQUIPMENT

HEAT LOSS in buildings
HEAT LOSS DETECTION TOOLS
HEAT LOSS INDICATORS
HEAT LOSS PREVENTION PRIORITIES
HEAT LOSS R U & K VALUE CALCULATION

HEAT PUMPS, DiAGNOSIS, REPAIR
HEAT TAPES, Heat, Insulation prevent Freeze-Up

HEATING COST FUEL & BTU Cost Table
HEATING COST SAVINGS METHODS

HEATING LOSS DIAGNOSIS-BOILERS
HEATING LOSS DIAGNOSIS-FURNACES

HEATING OIL CLOUD WAX GEL POINT
HEATING OIL EXPOSURE HAZARDS, LIMITS
HEATING OIL - OLD, USEABLE?
HEATING OIL PIPING TROUBLES
HEATING OIL SHELF LIFE
HEATING OIL SLUDGE
HEATING OIL USAGE RATE

HEATING SMALL LOADS

HEATING SYSTEM NOISES
HEATING SYSTEM INSPECT DIAGNOSE REPAIR

HOT WATER HEATERS
HOT WATER IMPROVEMENT

INSULATION INSPECTION & IMPROVEMENT

LP & Natural Gas Safety Hazards

MANUALS & PARTS GUIDES - HVAC
MIXING / ANTI-SCALD VALVES

NO HEAT - BOILER / FURNACE DIAGNOSIS

NOISE / SOUND DIAGNOSIS & CURE
NOISE AIR CONDITIONER / HEAT PUMP
NOISE, DUCT VIBRATION DAMPENERS
NOISE CONTROL for HEATING SYSTEMS
NOISE CONTROL for PLUMBING
NOISES COMING FROM WATER HEATER

ODORS & SMELLS DIAGNOSIS & CURE
ODORS FROM HEATING SYSTEMS

OIL BURNERS
OIL BURNER INSPECTION GUIDE
OIL BURNER NOISE SMOKE ODORS
OIL BURNER NOZZLE & ELECTRODES
OIL BURNERS, RETENTION HEAD
OIL BURNER SOOT & PUFFBACKS

OIL FILTERS on HEATING EQUIPMENT
OIL FILTER MISSING
OIL FUEL TYPES & CHARACTERISTICS

OIL & GAS PIPING

OIL LINE CLOGGING FIX
OIL LINE SAFETY VALVES
OIL ODORS, LEAKY OIL TANK PIPING
OIL PUMP FUEL UNIT
OIL SPILL CLEANUP / PREVENTION

OIL TANKS
OIL TANKS, BURIED
OIL TANK GAUGES
OIL TANK INSPECTION REPORTS
OIL TANK LEAKS & SMELLS
OIL TANK PIPING & PIPING DEFECTS
OIL TANK PRESSURE
OIL TANK REGULATIONS
OIL TANK REMOVAL COs
OIL TANK REMOVAL FINANCIAL AID
OIL TANK SAFETY
OIL TANK SLUDGE
OIL TANK TESTING
OIL TANK TESTING COs
OIL TANK WATER CONTAMINATION
OIL TANK WATER REMOVAL

PLASTIC HEATER VENT
PULSE COMBUSTION HEATERS
PASCAL CALCULATIONS

RADIANT BARRIERS
RADIANT HEAT
RADIANT HEAT Floor Mistakes to Avoid
RADIANT HEAT TEMPERATURES
RADIANT SLAB FLOORING CHOICES
RADIANT SLAB TUBING & FLUID CHOICES

RADIATORS

RELIEF VALVES - TP Valves on Boilers
RELIEF VALVES - STEAM TP VALVES
RELIEF VALVES - Water Heaters
RELIEF VALVES - Water Tanks

Reset Switch - Heater Primary Control
Reset Switch - Electric Motors
Reset Switch - Stack Relays

SAFETY HAZARDS & INSPECTIONS
SAFETY HAZARDS GUIDE
SAFETY, HEATING INSPECTION
SAFETY,HOME HEATING TIPS
Safety Recalls, Chimneys, Vents, Heaters
SAFETY, HEATING INSPECTION
SAFETY,HOME HEATING TIPS
SOOT on OIL FIRED HEATING EQUIPMENT
SPILL SWITCHES - Flue Gas Detection
SPLIT SYSTEM AIR CONDITIONERS & HEAT PUMPS
STACK RELAY SWITCHES

STAIN DIAGNOSIS on BUILDING INTERIORS

STEAM HEATING SYSTEMS

TANKLESS COILS
TANKLESS WATER HEATERS
THERMAL EXPANSION of MATERIALS
THERMAL MASS in buildings
THERMAL TRACKING & HEAT LOSS

THERMOSTATS, HEATING / COOLING
Transite Pipe Chimneys & Flues

VIDEO GUIDES: Heating System Videos
VIDEO GUIDES - InspectAPedia.com

WATER HEATERS
WATER HEATER SAFETY
WATER HEATERS for HOME HEATING USE?
WATER HEATER NOISES
WATER HEATER SCALE - De-Liming Procedure
WATER HEATER SCALE PREVENTION

WINTERIZE A BUILDING
Wood Burning Heaters Fireplaces Stoves
Woodstove Safety

ZONE VALVES

More Information

Draft inducer fan installed (C) Daniel FriedmanGuide to Installing & Inspecting Draft Inducing Fans on Oil Fired Heating Equipment
InspectAPedia®  -         

  • Draft Boosting Fans - Draft Inducers on Oil Fired Boilers, Furnaces, Water Heaters: inspection, installation
  • When to install a draft inducer fan
  • When does the presence of a draft inducer fan suggest something else is wrong?
  • Questions & answers about bad draft on heating equipment & the use of draft inducer fans

Draft inducers guide: Here we explain Draft Inducers or Draft Booster Fans installed on oil fired heating equipment.

InspectAPedia offers impartial, unbiased advice without conflicts of interest. We will block advertisements which we discover or readers inform us are associated with bad business practices, false-advertising, or junk science. Our contact info is at InspectAPedia.com/Contact.htm.

This website answers most questions about central heating system troubleshooting, inspection, diagnosis, and repairs. We describe how to inspect residential heating systems to inform home owners, buyers, and home inspectors of common heating system defects.

Details about draft control on oil fired heating systems (such as the oil fired heater shown in the photo above), including furnaces or boilers, are discussed right here at Draft Regulators barometric dampers on oil fired equipment. (Details about draft control for gas fired heating systems, including furnaces or boilers, are discussed at Furnace Draft Hood on gas fired equipment. Contact us to suggest text changes and additions and, if you wish, to receive online listing and credit for that contribution.

© Copyright 2012 InspectAPedia.com, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use page top links to major topics or use links at the left of each page to navigate within topics and documents at this website. Green links show where you are in a document series or at this website.

Types of chimney draft, natural, induced, forced (C) Carson Dunlop

Our sketch at left, courtesy of Carson Dunlop, illustrates the three types of draft that may be found at chimneys and heating appliances: natural draft, induced draft by a fan blowing up a chimney, and forced draft by a fan blowing combustion air into a burner assembly.

This article discusses the use of induced-draft equipment.

The articles at this website describe the basic components of a home heating system, how to find the rated heating capacity of an heating system by examining various data tags and components, how to recognize common heating system operating or safety defects, and how to save money on home heating costs. We include product safety recall and other heating system hazards.

Draft Inducer Fans for Problem Chimneys & Vents

Draft inducer fan from Tjernlund Products (C) Daniel FriedmanDraft inducers are special fans that are installed in the flue vent connector (or sometimes in the chimney) used to vent a heating boiler or furnace. Most often we see these installed on oil-fired systems at which the technician was unable to obtain sufficient natural draft for proper oil burner operation.

If an oil burner lacks adequate draft, as we discussed above, it will not operate properly, leading to soot clogging, more costly heating bills, back pressure in the combustion chamber, and possibly unsafe heater operation.

The draft inducer fan shown in our photo was found in our garage of left-over stock from our heating service days. This model, the Tjernlund DJ-3 Draft Inducer Fan is sold by Tjernlund in St. Paul, MN, and the photo shows the essential parts of this draft inducer:

  • An electric motor (this one made by Fasco)
  • A blower assembly of fan blades driven by the motor and designed to project into a metal flue pipe or flue vent connector
  • An electrical junction box to connect the motor to the oil burner controls to turn the fan on and off when needed
  • A metal shroud around the fan assembly

The draft inducer fan motor and wiring need to be adequately protected from the heat of the oil burner combustion gases, that's why you wouldn't try to make one of these at home out of an old computer fan or stereo system fan.

When is it not appropriate to install a draft inducer fan?

Draft inducer fan installed (C) Daniel FriedmanBe careful; it would be a mistake and possibly dangerous to install a draft inducing fan to boost oil burner draft to solve a venting or backpressure problem before the cause of that problem is accurately diagnosed.

For example, if the oil fired appliance draft is poor because the chimney is blocked, or because the appliance itself is blocked with soot and debris, or because there is inadequate combustion air, the draft inducer fan might make the problem seem to go away, but at the risk of creating unsafe conditions in the heating system.

In our photo of an oil fired heating boiler has a draft inducer fan installed. The draft boosting fan is that mechanism you see on the under-side of the flue vent connector to the left of the boiler.

If this boiler is venting into a chimney that is really right at the wall where the flue vent connector enters the block wall, it's a very short flue run and we would not expect a draft problem. Something must be seriously wrong with the boiler or with chimney itself to have induced the technician to install a draft inducer fan on this heating system.

 

When Might We Need to Install a Draft-boosting Draft Inducer Fan?

Long metal flue run - bad draft (C) Daniel FriedmanBut where the flue vent connector run-length is abnormally long or tortuous it may be difficult to get good draft, or where the chimney size itself (to which the flue vent connector joins) is too big or too small, the use of a draft inducer might be permitted. Check with the fan manufacturer and a qualified HVAC service technician before asking that one of these fans be installed.

In the photo shown here we have a long metal flue run - we cannot see the end of it, and the flue is shared, and there is no barometric damper installed - we suspect there is poor draft at this installation.

 

We've installed draft inducer fans in a few cases where the building chimney design was just too difficult to get good venting by natural draft.

For example we encountered a 12' long horizontal chimney run through masonry placing the boiler too far from the vertical chimney flue for good draft.

But in general, before installing a draft inducer we should make sure that the chimney is safe, not blocked, and that the heating equipment has been properly serviced and adjusted first.


Chimney cleanout left open (C) Daniel FriedmanYou might discover that someone simply left open the ash pit door on a heating system's chimney - all that may be needed to improve the draft could be closing that little door!

At the chimney cleanout shown here we see a bit of debris that has collected at the bottom - which could be normal depending on what flue is being served and how long since the chimney was cleaned.

But if leave this door open not only do you nearly eliminate the chimney draft needed by the heating equipment, you are also creating a fire hazard, a fire spread between floors hazard, and a possible point of release of combustion gases into the building.

Close the little door.

How is a draft inducer fan installed?

A rectangular opening is cut into the metal flue pipe at a suitable location - usually close to the heating equipment since that makes wiring easier. The draft inducing fan comes with a paper template showing the size of the opening to cut.

The fan is mounted to the opening on the metal chimney or flue pipe so that its blades project into the flue, and so that when the fan motor runs it's pushing exhaust air away from the heating equipment and towards the chimney.

We've seen people install these fans in fireplace chimney flues in an effort to improve a fireplace that has inadequate draft, but we can't say if the manufacturer would approve that installation. There may be hazards due to creosote and other deposits from a wood-burning fireplace when one of these fans is used.

A note from Tjernlund informs us that draft inducer fan model DJ-2 has been replaced by Model DJ-3 and that all references in instructions to DJ-2 fans apply to DJ-3 models too.

Questions & Answers regarding this article

Questions & answers about bad draft on heating equipment & the use of draft inducer fans

Ask a Question or Search InspectAPedia

HTML Comment Box is loading comments...

Share this Article      

...

Technical Reviewers & References

  • InspectAPedia.com® - Daniel Friedman - Publisher & Editor.
  • InspectAPedia Bookstore lists recommended books, organized by topic & available for purchase. Most of our articles also include a list of recommended books for the specific article topic as well as other references, and information sources.
  • Critique, contributions wanted: Contact Us to suggest corrections or additions to articles at this website, and if you wish, to receive online listing and credit as a contributor. Particular thanks are due to the many experts and also consumers who read and critique technical articles at InspectAPedia.com.
  • Additional technical contributors & reference sources for this article are listed below.

Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

DRAFT REGULATORS, DAMPERS, BOOSTERS
  Purpose of Barometric Draft Regulator what is a barometric damper and why do we need them
  Measure Draft - how when where and why we measure draft and how we set the draft regulator
  Barometric Damper Defect List
  How to Inspect a Barometric Damper - how to look into the flue, what you'll see, what it means about heating system economy and condition
  Automatic Vent Dampers - how an automatic vent damper saves heating cost
  Define flue damper, duct damper, & fire damper
  Draft Inducer Fans - for solving draft and chimney problems

  • Carson, Dunlop & Associates Ltd., 120 Carlton Street Suite 407, Toronto ON M5A 4K2. (416) 964-9415 1-800-268-7070 info@carsondunlop.com. Thanks to Alan Carson and Bob Dunlop, for permission to use illustrations from their publication, The Illustrated Home which illustrates construction details and building components. Carson Dunlop provides home inspection education including the ASHI-adopted Home Inspection Training Program (home study course), publications such as the Home Reference Book, report writing materials including the Horizon report writer, and home inspection services. Alan Carson is a past president of ASHI, the American Society of Home Inspectors.

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.
  • Home Reference Book - Carson Dunlop The Home Reference Book - the Encyclopedia of Homes, Carson Dunlop & Associates, Toronto, Ontario, 2010, $69.00 U.S., is available from Carson Dunlop. The Home Reference Book is a bound volume of more than 450 illustrated pages that assist home inspectors and home owners in the inspection and detection of problems on buildings. The text is intended as a reference guide to help building owners operate and maintain their home effectively. InspectAPedia.com ® author/editor Daniel Friedman is a contributing author. Field inspection worksheets are included at the back of the volume.
  • Carbon Monoxide Gas Toxicity, exposure limits, poisoning symptoms, and inspecting buildings for CO hazards
  • Fuel Oil & Oil Heating Magazine, 3621 Hill Rd., Parsippany, NJ 07054, 973-331-9545
  • Goodman Furnace High Temperature Plastic Vent HTPV safety recall US CPSC notice
  • Home Heating System Should Be Checked [for proper venting and for CO Carbon Monoxide Hazards - DJF]
  • Inspection Procedures for Oil-Fired Heating Systems Detailed step by step approaches for inspecting complex systems]
  • Lennox Pulse Furnace Safety Inspection/Warranty Program: Carbon Monoxide Warning
  • Plastic Heating Vent Pipe & Other Heating Safety Recall Notices
  • Domestic and Commercial Oil Burners, Charles H. Burkhardt, McGraw Hill Book Company, New York 3rd Ed 1969.
  • National Fuel Gas Code (Z223.1) $16.00 and National Fuel Gas Code Handbook (Z223.2) $47.00 American Gas Association (A.G.A.), 1515 Wilson Boulevard, Arlington, VA 22209 also available from National Fire Protection Association, Batterymarch Park, Quincy, MA 02269. Fundamentals of Gas Appliance Venting and Ventilation, 1985, American Gas Association Laboratories, Engineering Services Department. American Gas Association, 1515 Wilson Boulevard, Arlington, VA 22209. Catalog #XHO585. Reprinted 1989.
  • The Steam Book, 1984, Training and Education Department, Fluid Handling Division, ITT [probably out of print, possibly available from several home inspection supply companies] Fuel Oil and Oil Heat Magazine, October 1990, offers an update,
  • Principles of Steam Heating, $13.25 includes postage. Fuel oil & Oil Heat Magazine, 389 Passaic Ave., Fairfield, NJ 07004.
  • The Lost Art of Steam Heating, Dan Holohan, 516-579-3046 FAX
  • Principles of Steam Heating, Dan Holohan, technical editor of Fuel Oil and Oil Heat magazine, 389 Passaic Ave., Fairfield, NJ 07004 ($12.+1.25 postage/handling).
  • "Residential Steam Heating Systems", Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
  • "Residential Hydronic (circulating hot water) Heating Systems", Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
  • "Warm Air Heating Systems". Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
  • Heating, Ventilating, and Air Conditioning Volume I, Heating Fundamentals,
  • Boilers, Boiler Conversions, James E. Brumbaugh, ISBN 0-672-23389-4 (v. 1) Volume II, Oil, Gas, and Coal Burners, Controls, Ducts, Piping, Valves, James E. Brumbaugh, ISBN 0-672-23390-7 (v. 2) Volume III, Radiant Heating, Water Heaters, Ventilation, Air Conditioning, Heat Pumps, Air Cleaners, James E. Brumbaugh, ISBN 0-672-23383-5 (v. 3) or ISBN 0-672-23380-0 (set) Special Sales Director, Macmillan Publishing Co., 866 Third Ave., New York, NY 10022. Macmillan Publishing Co., NY
  • Installation Guide for Residential Hydronic Heating Systems
  • Installation Guide #200, The Hydronics Institute, 35 Russo Place, Berkeley Heights, NJ 07922
  • The ABC's of Retention Head Oil Burners, National Association of Oil Heat Service Managers, TM 115, National Old Timers' Association of the Energy Industry, PO Box 168, Mineola, NY 11501. (Excellent tips on spotting problems on oil-fired heating equipment. Booklet.)
  • ...
Home About Us Accuracy Contact Us Content Use Policy Privacy Website Description © 2012 Copyright InspectAPedia.com