InspectAPedia.com InspectAPedia®

Question? Just ask us!

Google
InspectAPedia

Free Encyclopedia of Building & Environmental Inspection, Testing, Diagnosis, Repair

  • HOME
  • AIR CONDITIONING
  • DAMAGE ASSESSMENT
  • ELECTRICAL
  • EXTERIORS
  • HEATING
  • HOME INSPECTION
  • INTERIORS
  • PLUMBING
  • ROOFING
  • SEPTIC SYSTEMS
  • STRUCTURE
  • WATER SUPPLY
  • ENERGY SAVINGS
  • ENVIRONMENT
  • INDOOR AIR IAQ
  • INSULATION
  • MOLD INSPECT TEST REMOVE
  • NOISE
  • ODORS
  • SOLAR ENERGY
  • VENTILATION
  • EXPERTS DIRECTORY
  • CONTACT US



InspectAPedia ® Home

HEATING SYSTEMS

AFUE DEFINITION, RATINGS
AGE of CHIMNEYS & FIREPLACES
AGE of HEATERS, BOILERS, FURNACES

BACKDRAFTING HEATING EQUIPMENT
BAROMETRIC DAMPERS
BLUERAY Recall
BOILERS, HEATING
BOILER COMPONENTS & PARTS
BOILER CONTROLS & SWITCHES
BOILER NOISE SMOKE ODORS
BOILER OPERATING PROBLEMS
BOOKSTORE - InspectAPedia

CARBON DIOXIDE - CO2
CARBON MONOXIDE - CO
CHIMNEY INSPECTION DIAGNOSIS REPAIR
COMBUSTION AIR
COMBUSTION AIR for TIGHT buildings
COMBUSTION GASES & PARTICLE HAZARDS
COMBUSTION PRODUCTS & IAQ
COMPLETE COMBUSTION, Stoichiometric
CREOSOTE FIRE HAZARDS
CONDENSING BOILERS/FURNACES

DEFINITION of Heating & Cooling Terms
DIAGNOSE & FIX HEATING PROBLEMS-BOILER
DIAGNOSE & FIX HEATING PROBLEMS-FURNACE
DIRECT VENTS / SIDE WALL VENTS
DRAFT HOODS - gas fired
DRAFT MEASUREMENT, CHIMNEYS & FLUES
DRAFT REGULATORS, DAMPERS, BOOSTERS

FIRE SAFETY CONTROLS
FIREPLACES & HEARTHS
FLAME COLOR, BLUE vs YELLOW COMBUSTION
FLOODED HEATING EQUIPMENT REPAIR
FLUE SIZE SPECIFICATIONS
FLUE VENT CONNECTORS
FUEL OIL TYPES & CHARACTERISTICS
FUEL UNIT, HEATING OIL PUMPS
FURNACES, HEATING
FURNACE CONTROLS & SWITCHES

GALVANIC SCALE & METAL CORROSION
GAS BURNER Flame & Noise Defects
GAS FIRED WATER HEATERS
GAS PIPING, VALVES, CONTROLS

HEATING LOSS DIAGNOSIS-BOILERS
HEATING LOSS DIAGNOSIS-FURNACES
HEATING OIL PIPING TROUBLES
HEATING OIL TANKS
HEATING SYSTEM NOISES
HEATING SYSTEM TYPES
HIGH EFFICIENCY BOILERS/FURNACES
HOT WATER HEATERS

LOW VOLTAGE BUILDING WIRING
LOW VOLTAGE TRANSFORMER TEST
LP & Natural Gas Safety Hazards

MANUALS & PARTS GUIDES - HVAC

Natural Gas Combustion
NO HEAT - BOILER
NO HEAT - FURNACE
NOISE, DUCT VIBRATION DAMPENERS
NOISE, HEATING SYSTEMS
NOISE, WATER HEATER

ODORS & SMELLS DIAGNOSIS & CURE
ODORS FROM HEATING SYSTEMS
OIL BURNERS
OIL BURNER FUEL UNIT
OIL BURNER INSPECTION & REPAIR
OIL BURNER NOISE SMOKE ODORS
OIL BURNER SOOT & PUFFBACKS
OIL FILTERS on HEATING EQUIPMENT
OIL FUEL TYPES & CHARACTERISTICS
OIL HEAT FIRE SAFETY CONTROLS
OIL LINE CLOGGING FIX
OIL LINE QUICK STOP VALVES
OIL LINE SAFETY VALVES
OIL ODORS, LEAKY OIL TANK PIPING
OIL PUMP FUEL UNIT
OIL TANKS

PLASTIC HEATER VENT
PULSE COMBUSTION HEATERS

RADIANT HEAT
RADIATORS
RELIEF VALVE LEAKS
RELIEF VALVES - TP Valves on Boilers
RELIEF VALVES - STEAM TP VALVES
RELIEF VALVES - Water Heaters
Reset Switch - Heater Primary Control
Reset Switch Broken - Quick RepaiR
RESET SWITCH - ELECTRIC MOTOR
Reset Switch - Stack Relays

SAFETY, HEATING INSPECTION
SAFETY RECALLS, Chimneys, Vents, Heaters
SOOT on OIL FIRED HEATING EQUIPMENT
SPILL SWITCHES - Flue Gas Detection
STACK RELAY SWITCHES
STAIN DIAGNOSIS on BUILDING INTERIORS
STEAM HEATING SYSTEMS

TANKLESS COILS
THERMAL EXPANSION of HOT WATER
THERMAL EXPANSION of MATERIALS
THERMAL MASS in BUILDINGS
THERMOSTATS, HEATING / COOLING
THERMOSTATS, WATER HEATER
Transite Pipe Chimneys & Flues

VIDEO GUIDES: Heating System Videos

WATER HEATERS
WINTERIZE A BUILDING
WOOD, COAL STOVES & FIREPLACES
WOOD STOVE SAFETY

ZONE DAMPERS
ZONE VALVES

More Information

Draft measurement example (C) D FriedmanDraft Measurement Guide for Chimneys & Flues
InspectAPedia®  -    

  • How & where do we measure the draft in a chimney or flue for heating appliances?
    • What are the right or specified draft measurements we should see in a chimney or flue?
  • AUTOMATIC VENT DAMPERS - separate article
  • BACKDRAFTING HEATING EQUIPMENT & CARBON MONOXIDE - CO - separate articles
  • CHIMNEY DRAFT & PERFORMANCE - separate article
  • COMBUSTION AIR DEFECTS - separate article
  • COMBUSTION AIR for TIGHT buildings - separate article
  • COMBUSTION GASES & PARTICLE HAZARDS & COMBUSTION PRODUCTS & IAQ - separate articles
  • COMPLETE COMBUSTION, Stoichiometric - separate article
  • DIRECT VENTS / SIDE WALL VENTS - separate article
  • DRAFT HOODS - gas fired - separate article
  • DRAFT MEASUREMENT, CHIMNEYS & FLUES
  • DRAFT REGULATORS, DAMPERS, BOOSTERS - separate article
  • DRAFT REGULATOR SOOT INSPECTION - separate article
  • DRAFT INDUCER FANS - separate article
  • Questions & Answers about inspecting and adjusting the barometric damper or draft regulator on oil fired heating equipment
  • References

Click to Show or Hide Related Topics

  • HEATING SYSTEMS - home
  • AGE of HEATERS, BOILERS, FURNACES
  • AIR FILTERS for HVAC SYSTEMS
  • AIR HANDLER / BLOWER UNITS
  • BOILERS, HEATING - home
  • BOILER OPERATING PROBLEMS
  • BOILER CONTROLS & SWITCHES
  • CIRCULATOR PUMPS & RELAYS
  • CONDENSING BOILERS/FURNACES
  • DIAGNOSE & FIX AIR CONDITIONER / HEAT PUMP
  • DIAGNOSE & FIX HEATING PROBLEMS-BOILER
  • DIAGNOSE & FIX HEATING PROBLEMS-FURNACE
  • DUCT SYSTEM & DUCT DEFECTS
  • ELECTRIC HEAT, DIAGNOSIS, REPAIR
  • FURNACES, HEATING - home
  • FURNACE CONTROLS & SWITCHES
  • GAS BURNER Flame & Noise Defects
  • GAUGES ON HEATING EQUIPMENT
  • HEATING COST SAVINGS METHODS
  • HEAT PUMPS, DIAGNOSIS, REPAIR
  • NOISE DIAGNOSIS, HEATING SYSTEM
  • ODORS FROM HEATING SYSTEMS
  • OIL BURNER INSPECTION & REPAIR
  • OIL TANKS - home
  • OIL TANK PIPING & PIPING DEFECTS - home
  • PULSE COMBUSTION HEATERS
  • RADIANT HEAT
  • RADIATORS
  • RELIEF VALVES, BOILERS
  • RELIEF VALVES, STEAM BOILERS
  • RESET SWITCH, Primary
  • RESET SWITCH, ELECTRIC MOTOR
  • RESET SWITCH, STACK RELAY
  • STEAM HEATING SYSTEMS & Controls - home
  • THERMOSTATS, HEATING / COOLING
  • WOOD, COAL STOVES & FIREPLACES
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

This article explains the methods of measurement and proper adjustment settings for draft regulators or barometric dampers on oil fired heating equipment. This website answers most questions about central heating system troubleshooting, inspection, diagnosis, and repairs. We describe how to inspect, troubleshoot and repair heating and air conditioning systems to inform home owners, buyers, and home inspectors of common heating system defects.

Green links show where you are. © Copyright 2013 InspectAPedia.com, All Rights Reserved. Author Daniel Friedman.

Where & How Do We Measure Chimney Draft or Heating Appliance Flue Draft?

Photograph of a draft regulator

Barometric dampers used on oil-fired heating appliances (furnaces, boilers, water heaters) are discussed in detail beginning at DRAFT REGULATORS, DAMPERS, BOOSTERS. Details about draft control for gas fired heating systems, including furnaces or boilers, are discussed at Furnace Draft Hood on gas fired equipment. Readers should also see CHIMNEY INSPECTION DIAGNOSIS REPAIR and Flue Vent Connectors - Boilers, Furnaces for inspection, defect identification, and repair suggestions for chimneys and flues. Contact us to suggest text changes and additions and, if you wish, to receive online listing and credit for that contribution.

As we explain at our home page for this topic, DRAFT REGULATORS, DAMPERS, BOOSTERS, a barometric draft control, also called a "damper" or barometric damper, is a hinged, weighted door on an opening at a heating flue.

The door opens or closes to let extra air into the flue to assure that the draft in the flue remains constant at the proper setting needed for proper heating system operation.

 

Where do we Measure Chimney or Flue Draft & What is the Correct Draft Measurement at Oil Fired Heaters?

Draft regulator, barometric damper schematic (C) Carson Dunlop

Normally we measure draft at two locations: over the fire or in the combustion chamber where typically we may see -0.02 to -0.03 inches of water column pressure, and in the breech or at the stack pipe (properly, the flue vent connector) measured just a few inches above the boiler or furnace top, and before the barometric damper itself.

Notice that we're using negative numbers for draft measurement - that's because gases in the flue are moving up, up, and away, like superman, and onwards out of the building - away from the heating equipment. The gas pressure in the chimney needs to be less than atmospheric pressure in the boiler room for gases to leave.

This sketch of a barometric damper used on oil fired heating equipment (heating boilers or water heaters) is provided courtesy of Carson Dunlop Associates.

In the breech we want to see about -0.05 inches WC pressure. If the breech draft is too low the combustion process and venting process may be inadequate, and if the draft measured in the breech is lower than the draft measured over the fire, the oil burner and combustion chamber are operating under pressure - which is often a problem on residential heating systems since few of them are designed to work this way. Thanks to L. - for correcting our WC pressure data.


Draft measurement example (C) D Friedman

We do not measure draft in the flue vent connector past the barometric damper since the damper is regulating the draft and we're not seeing what the oil burner is seeing at the fire. Lots of companies make draft gauge measurement devices, including Bachrach™, and including nice little pocket units that anyone can carry.

Our photo (left) shows a traditional Bachrach kit draft measurement gauge in use (green arrow) and its connection to the flue vent connector at the top of a boiler (red arrow) that in this case had no barometric damper installed.

This boiler had a poor draft, a history of sooting problems and a too-short chimney that we were in process of replacing when these photos of draft measurement procedure were made.

At this New York home (photos just above and below) the draft in the breech was running at about -0.02" w.c. - it should have been at least twice that amount. At below left you can see that the draft was hovering around 0.02" and at below right you can see our connection of the draft gauge sensing probe into the flue vent connector just above the boiler top.

Draft measurement instrument (C) D Friedman Draft measurement instrument (C) D Friedman

How Much Draft do we Want at an Oil Burner Fired Heating Boiler, Furnace, or Water Heater?

In sum the draft we typically see on oil fired heating equipment is

  • - 0.02" to 0.03" water column (w.c.) in the combustion chamber just over the fire
  • - 0.04" to 0.06" w.c. in the breech - the flue pipe area between the top of the boiler and the bottom of the barometric damper. Some oil burner models require higher draft than these numbers, and other oil burner models are actually tolerant of back-pressure in the combustion chamber (positive draft, or draft in the "wrong" direction").

Correcting Inadequate Chimney Draft - extending the flue height

Draft measurement instrument (C) D Friedman Replacing a too-short chimeny with a proper one (C) D Friedman

In the heating industry, traditionally draft measurements around -0.02" w.c. are considered "low", and around-0.06" w.c. are "high" draft levels. After we replaced the too-short chimney with one of proper height, and with a draft regulator (barometric damper) now installed at the boiler top, our measurement showed that we had a good draft in the flue vent connector - almost 0.06" w.c. in the breech (photo above left). In our chimney replacement photo (above right) the new chimney extending 24" above the roof of a new addition (green arrow) is much taller than the original 20" chimney (red arrow). That's how we got good draft in the new chimney set-up.

What are the recommended draft settings at a draft regulator / barometric damper?

Field Type AF Barometric Draft Control Adjustment (C) Daniel FriedmanBy moving a weight along a scale. You can see a weight and scale in our photo of the Field Type AF Draft Control.

In general the draft regulator is set to the lowest draft that gives good combustion and proper oil burner operation. Higher wastes energy.

While the heating equipment is operating at normal temperature, the draft is set to a number specified by the oil burner manufacturer, so we can only give approximate settings in this discussion. To find the proper weight setting to control the draft regulator, the heating service technician will make three measurements:

  1. Draft over the fire (typically set to 0.02" to 0.03" WC over the fire)
  2. Draft in the breech (always higher than the draft over the fire, and typically around 0.04 - 0.06" WC).
  3. CO2 measurements (which tells us how complete is the heating oil combustion process) - adjusting the draft affects the rate of combustion air movement into the combustion chamber.

It is the position of the weight along a moveable scale, usually by screwing the weight in or out, or by sliding the weight along a scale (see our photo), that adjusts how far the draft regulator door will open in response to these three conditions described above. It's basically a principle of leverage -the weight is moved closer to or farther out from the axis of rotation of the moving draft regulator door.

So do not change the barometric draft control's weight setting unless you're a trained service technician who knows when, where, how, and why to measure draft at an oil fired heating appliance.

Weight location & adjustment on barometric draft controls

Draft regulator installation instructions (C) Field Controls - D Friedman

Weight location & adjustment on barometric draft controls: the weight that is adjusted to regulate the operation of the draft control needs to be properly located as well as adjusted. T

he weight location switches on most regulators depending on whether the regulator is installed on a vertical flue or a horizontal flue. Field ships their draft regulators with the weight installed in position for a vertical flue.

The adjustment weight is in the right-hand slot when you are facing the control. If the damper is to be installed on a horizontal flue, the weight must be removed from the right-hand slot and attached to the left hand slot as shown in the illustration and sketches above.

Thanks to boiler expert Dirk Faegre for suggesting these additional details.

...


Frequently Asked Questions (FAQs) about measuring chimney draft

...

Ask a Question or Search InspectApedia

Questions & answers or comments about the procedure for measuring chimney or flue draft and the related settings for draft regulators and barometric dampers on heating equipment;

Ask a Question or Enter Search Terms in the InspectApedia search box just below.

Technical Reviewers & References

Related Topics, found near the top of this page suggest articles closely related to this one.

  • [1] "Instructions for Installing FIELD Type AF Barometric Draft Controls," Form No. 31 DC 30666, Field Corporation, Mendota, IL 61342, web search 04/02/2011, original source: http://www.fieldcontrols.com/pdfs/04592700.pdf, Field Controls, Kingston, North Carolina 28501, Tel: 919-522-3031
  • [2] Tjernlund Draft Controls, A Series (single action for oil, solid fuel, and fan-assisted gas burners) and B Series (double action for gas heating appliances), web search 04/02/1011, original source: http://www.tjernlund.com/Tjernlund_8500490.pdf , Tjernlund Products, Inc., 1601 Ninth Street, White Bear Lake MN 55110-6794, Tel: 651-426-2993 or 800-255-4208 website: www.tjernlund.com Email: fanmail@tjfans.com
  • Mark Cramer Inspection Services Mark Cramer, Tampa Florida, Mr. Cramer is a past president of ASHI, the American Society of Home Inspectors and is a Florida home inspector and home inspection educator. Mr. Cramer serves on the ASHI Home Inspection Standards. Contact Mark Cramer at: 727-595-4211 mark@BestTampaInspector.com
  • John Cranor is an ASHI member and a home inspector (The House Whisperer) is located in Glen Allen, VA 23060. He is also a contributor to InspectApedia.com in several technical areas such as plumbing and appliances (dryer vents). Contact Mr. Cranor at 804-747-7747 or by Email: johncranor@verizon.net
  • Carson, Dunlop &
Associates Ltd., TorontoCarson, Dunlop & Associates Ltd., 120 Carlton Street Suite 407, Toronto ON M5A 4K2. (416) 964-9415 1-800-268-7070 info@carsondunlop.com. The firm provides professional home inspection services & home inspection education & publications. Alan Carson is a past president of ASHI, the American Society of Home Inspectors. Thanks to Alan Carson and Bob Dunlop, for permission for InspectAPedia to use text excerpts from The Home Reference Book & illustrations from The Illustrated Home. Carson Dunlop Associates' provides:
    • Commercial Building Inspection Courses - protocol ASTM Standard E 2018-08 for Property Condition Assessments
    • Home Inspection Education Courses including home study & live classes at eleven colleges & universities.
    • Home Inspection Education Home Study Courses - ASHI@Home Training 10-course program.
      Special Offer: Carson Dunlop Associates offers InspectAPedia readers in the U.S.A. a 5% discount on these courses: Enter INSPECTAHITP in the order payment page "Promo/Redemption" space. InspectAPedia.com editor Daniel Friedman is a contributing author.
    • The Home Reference Book, a reference & inspection report product for building owners & inspectors.
      Special Offer: For a 10% discount on any number of copies of the Home Reference Book purchased as a single order. Enter INSPECTAHRB in the order payment page "Promo/Redemption" space. InspectAPedia.com editor Daniel Friedman is a contributing author.
    • The Home Reference eBook, an electronic version for PCs, the iPad, iPhone, & Android smart phones.
      Special Offer: For a 5% discount on any number of copies of the Home Reference eBook purchased as a single order. Enter inspectaehrb in the order payment page "Promo/Redemption" space.
    • The Illustrated Home illustrates construction details and building components, a reference for owners & inspectors.
      Special Offer: For a 5% discount on any number of copies of the Illustrated Home purchased as a single order Enter INSPECTAILL in the order payment page "Promo/Redemption" space.
    • The Horizon Software System manages business operations,scheduling, & inspection report writing using Carson Dunlop's knowledge base & color images. The Horizon system runs on always-available cloud-based software for office computers, laptops, tablets, iPad, Android, & other smartphones.
  • Lonny Steinke, Worland, WY USDA kindly corrected erroneous data we published on the proper draft numbers. - October 2008.
  • Dirk Faegre, Camden, Maine (207) 232-9494 is a certified  BPI  energy auditor and certified Envelope technician who kindly suggested draft regulator and flue vent connector inspection defect additions 6 Sept 09
  • Plastic Heating Vent Pipe & Other Heating Safety Recall Notices
  • Domestic and Commercial Oil Burners, Charles H. Burkhardt, McGraw Hill Book Company, New York 3rd Ed 1969.
  • National Fuel Gas Code (Z223.1) $16.00 and National Fuel Gas Code Handbook (Z223.2) $47.00 American Gas Association (A.G.A.), 1515 Wilson Boulevard, Arlington, VA 22209 also available from National Fire Protection Association, Batterymarch Park, Quincy, MA 02269. Fundamentals of Gas Appliance Venting and Ventilation, 1985, American Gas Association Laboratories, Engineering Services Department. American Gas Association, 1515 Wilson Boulevard, Arlington, VA 22209. Catalog #XHO585. Reprinted 1989.
  • The Steam Book, 1984, Training and Education Department, Fluid Handling Division, ITT [probably out of print, possibly available from several home inspection supply companies] Fuel Oil and Oil Heat Magazine, October 1990, offers an update,
  • Principles of Steam Heating, $13.25 includes postage. Fuel oil & Oil Heat Magazine, 389 Passaic Ave., Fairfield, NJ 07004.
  • The Lost Art of Steam Heating, Dan Holohan, 516-579-3046 FAX
  • Principles of Steam Heating, Dan Holohan, technical editor of Fuel Oil and Oil Heat magazine, 389 Passaic Ave., Fairfield, NJ 07004 ($12.+1.25 postage/handling).
  • "Residential Steam Heating Systems", Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
  • "Residential Hydronic (circulating hot water) Heating Systems", Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
  • "Warm Air Heating Systems". Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
  • Heating, Ventilating, and Air Conditioning Volume I, Heating Fundamentals,
  • Boilers, Boiler Conversions, James E. Brumbaugh, ISBN 0-672-23389-4 (v. 1) Volume II, Oil, Gas, and Coal Burners, Controls, Ducts, Piping, Valves, James E. Brumbaugh, ISBN 0-672-23390-7 (v. 2) Volume III, Radiant Heating, Water Heaters, Ventilation, Air Conditioning, Heat Pumps, Air Cleaners, James E. Brumbaugh, ISBN 0-672-23383-5 (v. 3) or ISBN 0-672-23380-0 (set) Special Sales Director, Macmillan Publishing Co., 866 Third Ave., New York, NY 10022. Macmillan Publishing Co., NY
  • Installation Guide for Residential Hydronic Heating Systems
  • Installation Guide #200, The Hydronics Institute, 35 Russo Place, Berkeley Heights, NJ 07922
  • The ABC's of Retention Head Oil Burners, National Association of Oil Heat Service Managers, TM 115, National Old Timers' Association of the Energy Industry, PO Box 168, Mineola, NY 11501. (Excellent tips on spotting problems on oil-fired heating equipment. Booklet.)

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.
  • Home Reference Book - Carson DunlopThe Home Reference Book - the Encyclopedia of Homes, Carson Dunlop & Associates, Toronto, Ontario, 25th Ed., 2012, is a bound volume of more than 450 illustrated pages that assist home inspectors and home owners in the inspection and detection of problems on buildings. The text is intended as a reference guide to help building owners operate and maintain their home effectively. Field inspection worksheets are included at the back of the volume. Special Offer: For a 10% discount on any number of copies of the Home Reference Book purchased as a single order. Enter INSPECTAHRB in the order payment page "Promo/Redemption" space. InspectAPedia.com editor Daniel Friedman is a contributing author.

    Or choose the The Home Reference eBook for PCs, Macs, Kindle, iPad, iPhone, or Android Smart Phones. Special Offer: For a 5% discount on any number of copies of the Home Reference eBook purchased as a single order. Enter INSPECTAEHRB in the order payment page "Promo/Redemption" space.

  • GO TO Carson Dunlop's Home Study Course Information - How to Become a Home Inspector: Carson Dunlop's nationally recognized Home Study Course, selected by ASHI the American Society of Home Inspectors and other professionals and associations. This website author is a contributor to this course.
  • GO TO Carson Dunlop's Home Study Course Information - How to Become a Home Inspector: Carson Dunlop's nationally recognized Home Study Course, selected by ASHI the American Society of Home Inspectors and other professionals and associations. This website author is a contributor to this course.
  • GO TO Carson Dunlop's Home Study Course Information - How to Become a Home Inspector: Carson Dunlop's nationally recognized Home Study Course, selected by ASHI the American Society of Home Inspectors and other professionals and associations. This website author is a contributor to this course.
    Building inspection education & report writing systems from Carson, Dunlop & Associates Ltd
  • Carson Dunlop, Associates, Toronto, have provided us with (and we recommend) Carson Dunlop Weldon & Associates' Technical Reference Guide to manufacturer's model and serial number information for heating and cooling equipment
    Special Offer
    : Carson Dunlop Associates offers InspectAPedia readers in the U.S.A. a 5% discount on any number of copies of the Technical Reference Guide purchased as a single order. Just enter INSPECTATRG in the order payment page "Promo/Redemption" space.

  • ...
HOME ABOUT CONTACT COPYING DESCRIPTION POLICIES PRINTING PRIVACY © 2013 Copyright InspectAPedia.com