Unsafe return air input at furnace (C) D FriedmanFurnace Blower Fan Blows Cold Air or Alternates Blowing Warm then Cold Air

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

Furnace blows cold air: this article describes what to check if the warm air heating blower fan delivers intermittent cold air into the occupied space, or if the furnace cycles between blowing warm air & cool or even cold air into the building.

Green links show where you are. © Copyright 2015 InspectApedia.com, All Rights Reserved.

How to Diagnose & Fix a Blower Fan that Blows Alternating Hot then Cold Air

Question: forced air heating furnace blows COLD, HOT, COLD, then OFF - what's up with its fan limit control?

Fan limit control diagnosis suggestions (C) InspectAPedia JCFan Limit Switch Problem History

Two story 75 year old classic cape cod home. Gas forced air furnace is Lennox G16 24 years old, in good condition. With Honeywell fan limit switch, outside fresh air intake and draft motor. We have owned home 12 years. (has AC). Owner not a technician but understands mechanical/heating concepts.

Furnace operating problem

When heat called for and fan comes on it blows cold air, then heat, then cold, then off. It has always done this. Limit switch is at off 100, on 125 off 150.

Recent information

Changing set points on limit switch does not seem to change pattern. I do not dare force it. This winter local utility provider replaced burned out fan motor with same HP, number of speeds, etc. Since the draft motor was noisy we replaced that as well. Upon dissection of draft motor is was covered with white crusty minerals probably from the water from the humidifier mounted on the nearby cold air return. When we first owned this house we have removed the humidifier (and installed a whole house water filter).

My Theory

The fan limit switch sensor which protrudes into the burn area is crusted and therefore "locked" into a former position and now un adjustable. What do you think? - J.C. 4/15/2013

Reply: stuff to check when the fan is not turning on and off at reasonable temperatures

Thanks for the interesting question and the excellent photo. Unfortunately the photo you sent had a virus - we had to clean it up so what we display here is a bit different and at at lower resolution that your version. I don't know what's happening with your heating system but I can, from your note make a few diagnostic suggestions:

Watch out: you are quite right not to force the set point adjustments on a fan limit switch. Doing so can make the heating system unsafe, even risking overheating, heat exchanger damage, and fatal carbon monoxide poisoning of building occupants.

The furnace fan limit switch assembly is intended to be adjusted within a safe range by the heating service tech by moving the stops, but if you bend something the switch is damaged and unsafe, and if you set the switch incorrectly (for example fan coming on too late or turning off too early, or setting the upper limit too high) there is risk of overheating the heat exchanger, cracking it, risking fatal carbon monoxide poisoning at worst, or perhaps a costly heat exchanger or furnace replacement job.

I like Dan Holohan's expression "Keep your hands in your pockets" - my mom used to make me sit on my own hands. (No not recently.)

Take a look at the duct system itself for things that can make it cool down quickly blowing cold air sooner than one might expect, such as a long uninsulated run, missing insulation, air leaks at the return side.

Check that the air filter is clean and that the ductwork is not obstructed. (This is just on general principle).

Now about that pesky fan limit control, you could

  1. Test the operation of the fan limit switch following the instructions in the article above. Start reading
    at FAN LIMIT SWITCH TROUBLESHOOTING.

    A very simple "test" that most fellows do in the field before touching anything is to just watch the dial as the plenum heats up when the furnace is running. If the dial doesn't turn it's jammed. The installation instructions warn about installation mistakes (like a too-long or improperly-located sheet metal screw) or sensor in contact with ductwork etc. - stuff that can bind the switch operation.
  2. Inspect the limit switch temperature sensor for obstruction or clogging (as you suggest) - to do this you have to turn power off and completely remove the switch - carefully again so as not to get cut nor bend anything. If the helix and heat sensor look clean, then you can jump to step 3 which is probably where a less curious tech might start
  3. Replace the switch with a new unit, at its factory settings.

Keep us posted - what you learn will help other readers diagnosing a fan limit switch problem with their own furnace.

Other Causes for a Heating Furnace to Blow Cool or Cold Air into the Occupied Spaces

Check for air duct leaks

Check for an air duct leak, particularly, leaks from cold areas such as an un-heated crawl space or basement into the return air duct system. Such leaks not only increase heating costs unnecessarily, they also are unsafe.

Check for deliberate introduction of cold air into the HVAC system

In some buildings we like to run the blower fan continuously for more even heat distribution and improved air filtration - improvements to building indoor air quality. But in some buildings where heating ducts run through cold spaces and are not well insulated, or in installations in which the heating system is inducing cold outdoor air into the duct system, when the furnace burners are off the system will indeed blow cold air onto building occupants.

Check the following two switches to make sure that the furnace blower fan is not simply set to run continuously:

If you need to introduce outdoor air into a building for air quality reasons, consider an air to air heat exchange system to save on heating costs. Check out

...


Continue reading at FAN LIMIT SWITCH TROUBLESHOOTING or select a topic from the More Reading links or topic ARTICLE INDEX shown below.

Or see FAN WONT STOP - LIMIT SWITCH

Suggested citation for this web page

FURNACE BLOWS COLD AIR at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

More Reading

Green link shows where you are in this article series.

INDEX to RELATED ARTICLES: ARTICLE INDEX to HEATING FURNACES

OR use the Search Box found below at Ask a Question or Search InspectApedia

...

Frequently Asked Questions (FAQs)

Click to Show or Hide FAQs

Ask a Question or Search InspectApedia

Use the "Click to Show or Hide FAQs" link just above to see recently-posted questions, comments, replies, try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.

Search the InspectApedia website

HTML Comment Box is loading comments...

Technical Reviewers & References

Publisher's Google+ Page by Daniel Friedman

Click to Show or Hide Citations & References

Support InspectApedia.com & See Fewer Advertisements

From Google's Contributor website: Contribute a few dollars each month. See fewer ads. The money you contribute helps fund the sites you visit.

Google-Contributor supports websites while reducing advertisements. You can support InspectApedia with a contribution of any amount you wish. Or you can contribute nothing and we'll still keep our website free to all readers - supported by advertising. Either approach is OK.