Forced air heating or cooling air handler troubleshooting: blower fan won't shut off:
This article describes what to check if the furnace or forced air blower fan does not stop when you expect it to do so.
These same diagnostics also aid in air conditioning blower assembly diagnosis when an A/C blower continues running. We explain what switches or controls may be set improperly or what else, such as a shorted wire, can cause continuous HVAC fan operation.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
These diagnostic steps are for an air handler, blower, or furnace fan that just won't quit running.
Other heating system problems that can cause a furnace (or boiler) to refuse to stop are given
First, confirm that the room thermostat is not calling for heating or cooling.
In the heating season, just set the thermostat(s) to the lowest setting and confirm that room temperature is above that point. In the cooling season do the opposite - set the thermostat to its highest setting and confirm that room temperature is below that point.
You have told the thermostat to turn off the HVAC equipment.
If the equipment was running give it three to four minutes to shut down.
Next: If the blower just keeps running no matter what, there are two places to check switch settings before calling your heating or air conditioning service company in response to a furnace fan or air conditioning fan that just keeps running without stopping:
1.CHECK the FAN-AUTO setting - At the room thermostat: the FAN-AUTO-OFF or FAN ON/OFF switch on the room thermostat should be checked.
The fan control should be set to AUTO. You can try turning the switch to OFF too.
Details of checking the thermostat's FAN-AUTO-OFF or FAN-ON switch position when the furnace (or air conditioning) fan won't stop running are
at FAN WONT STOP - THERMOSTAT SWITCH
Other snafus such as a shorted thermostat wire can also cause the A/C or warm air furnace fan to run continuously.
Those problems are explained
2. CHECK for a MANUAL - ON Switch - At the furnace or air conditioner air handler or blower unit: the fan limit switch may include a switch that manually keeps the fan running.
We discuss this switch right here. If you don't know where to find the limit control switch on your furnace or air handler,
see FAN LIMIT SWITCH.
Some models of Fan Limit Controls such as the Honeywell L4046B229& Universal Fan and Limit Controler, in particular the Honeywell L4064B,W, and R models have a manual fan switch that overrides the fan control to keep the fan running continuously. The white knob and white arrow in our photo point to this manual fan switch.
Take a look at the fan limit control switch. Before pulling the cover off of the switch, just see if the switch includes a control such as the white push-pull switch like the white device shown at the lower left in our photo.
Depending on the position of this switch (pushed-in or pulled out) the fan may be on manual override - causing the fan motor to run continuously.
Check the printing on the switch face to see if you should push the switch in or pull it out to leave the blower on "Auto". ("Man" or "Manual" would be forcing the fan to run.)
Usually: "Push-in" position on this (Honeywell) fan limit switch is for continuous fan operation and "Pull out" position is for automatic fan operation.
There are some reasons (explained
at BLOWER FAN CONTINUOUS OPERATION)
to leave the blower fan on continuously for long periods, such as to use an air filtering system to improve indoor air quality.
And in some buildings we may run the blower continuously for more even or better conditioned (heated or cooled) air distribution.
On the off chance that someone has inadvertently mis-connected or shorted fan control wires at the fan limit switch, also check
out FAN LIMIT SWITCH INSTALLATION & WIRING.
On the chance that there is a shorted thermostat wire, a problem that can also cause the A/C or warm air furnace fan to run continuously
see THERMOSTAT WON'T TURN OFF.
Details about the manual FAN ON or FAN AUTO ON switch right at the furnace or air handler at the manual
at BLOWER FAN CONTINUOUS OPERATION.
This article series answers most questions about central heating system troubleshooting, inspection, diagnosis, and repairs.
We describe how to inspect, troubleshoot and repair heating and air conditioning systems to inform home owners, buyers, and home inspectors of common heating system defects.
Contact us to suggest text changes and additions and, if you wish, to receive online listing and credit for that contribution.
2015/10/22 Anonymous said:
My fan keeps running with no heat on furnace. What can I do?
If the furnace does not even try to run, that is if it never even starts, then follow these steps:
If the furnace tries to start but cannot keep running then there is a different problem such as no fuel or an unsafe condition.
See DIAGNOSE & FIX HEATING PROBLEMS-FURNACE - home
A complete list of oil and gas fired furnace controls is
Below you will find questions and answers previously posted on this page at its page bottom reader comment box.
On 2020-12-05 - by (mod) - Trane air handler using snap-disc & control board for fan limit controls
Nathan
Good going on those diagnostic steps.
You're right that a furnace that uses "snap disc" controllers to manage the fan won't have a Honewyell dial-type fan limit control; but it's of course still performing those functions: fan ON OFF and HIGH limit settings are controlled by those snap-disc controls (whose wiring you may want to follow & check out)
With the thermostat wires completely disconnected at the air handler end, and when the fan won't stop, we rule out an issue with shorted TT wires as well as a bad thermostat or thermostat setting.
Of course "won't stop" bears some clarification: it is proper for the fan to continue running for a minute or so after a call for heat, to extract the remaining heat from the heat exchanger and thus avoid damaging it.
If you are absolutely certain that there is no FAN ON control anywhere on the furnace, and it's disconnected from the thermostat wires at the furnace end then there's not much left: I'd suspect a bad snap disc, (I hear that you tested it), a shorted wire in the air handler, or a bad relay in the air handler.
On 2020-12-05 by Nathan
Thank you. I have looked through your article extensively and tested at each place that is applicable to my system. Though I very well could have missed things as I get lost in the different types of systems.
It is an electric heating system with a heat pump and furnace.
1. Thermostat fan set to auto. Still runs all the time. Smart thermostat indicates that fan is off. Thermostat still calls for the fan when the furnace kicks on but when the furnace turns off and the fan is no longer called for at the thermostat it still runs.
2. It doesn’t seem as though there is a shorted wire as when I disconnect the thermostat from the furnace by disconnecting it’s wires at the Air Handler, the fan still runs.
3. There is no fan limit switch that I am aware of. It is a Trane and the furnace is BAY96X141502.
4. This system has a snap disk type limit switch. But I have checked it with a multimeter and it appears to be working correctly. Also the furnace is running as it should, just with constant blowing so if i understand correctly the limit switch would also be keeping the furnace from running normally.
Let me know if i’m missing checking something and I’ll check it out.
On 2020-12-05 - by (mod) -
Nathan
Let's start I asking you to review the causes of blower fan not stopping that are given in the article above on this page because that's more complete than if I try to make that up again in an off-the-cuff reply.
Please take a look and let me know what you think and let me know what questions remain.
On 2020-12-05 by Nathang
Hi looking for some technical help with our HVAC system. I just replaced the blower motor in our furnace and it is running constantly since the change. I’ve disconnected it from the thermostat to isolate the problem and it still fires up as soon as the power comes on and stays that way with or without the furnace engaged.
The furnace itself still turns on and off as normal so I don’t think it’s the furnace limit controller reading overheat or going bad. I suspect it could be a bad relay.
The thing that really confuses me is that every morning when I wake up it tends to be off and stays that way until triggered either by the thermostat, the fresh air exchange or even me cutting the power and turning it back on gets it going again. Then it stays running until the next morning again.
On 2020-12-04 by (mod) - my furnace will not shut off i have to use the breaker to shut it off
Keith
let's start by stepping through the Diagnostics given on the page above. Let me know what find or what questions remain.
On 2020-12-04 1 by keith
my furnace will not shut off i have to use the breaker to shut it off
i have a colman electric furnace that wont shut off
On 2020-11-13 by (mod) - important for the blower fan to continue running for a brief time after the thermostat stops calling for heat
thank you for that it, too. Your paragraph yes I agree and we discussed in this article series The observation that it's absolutely important for the blower fan to continue running for at least a brief time after the thermostat stops calling for heat. That's to extract the remaining heat out of a heat exchanger and thereby to avoid cracking the heat exchanger from high temperatures which in turn could make the furnace Unsafe and risk carbon monoxide poisoning.
So to be clear we should distinguish between the fan continuing to run for a brief interval typically 30 seconds or a minute after the call for heat of satisfied as distinct from the fan that just runs continuously.
If the fan runs continuously with never shutting off that's the situation discussed on this page and is not that he's purging cycle that you found in the instructions and that we also discussed in this article series
On 2020-11-13 by ovsa
Thanks.
I looked all through the duct work and there is defintely no controller in there. The stat is set at auto and it is a fairly new stat.
The manufactures data says,
"Time delay for blower activation:
60 seconds (std.)
130 deg. F Aquastat (w/optional aquastat).
So i think that 60 sec delay is just built into the board
I don't see any options or markings for time delay nor any DIP switches.
Anyway I can test it?
thanks for your help
Found a bit more info looking through the data sheets,
Units
without
Factory
Installed
Aquastats
or
Deactivated
Aquastats- A time delay of 60 seconds follows before the
circuit between R and G are complete activating the indoor
blower motor.
The
Air
Handler
fan
will
turn
off
30
seconds
after
the
Thermostat stops calling for heating.
On 2020-11-13 by (mod) - ADP Air Handler with heating/cooling coils: fan control
Ovsa
There is usually a fan limit control in the air handler that turns the fan on or off depending on air temperature sensed in the plenum just above the heater's heat exchanger.
If the fan won't stop on your unit look for one of the controls described above on this page and that can be used to manually turn the fan on for continuous operation. One of those is on the fan limit control, another is often on your room thermostat, and on occasion there may be a fan control right on the printed circuit board in the air handler.
Look furhter for a control board failure: if your air handler does not use a separate timer-containing fan limit control the time delay in fan shut-off may be controlled by dip switches on a control board or by a hard-wired timer.
If you don't have the manual for your unit see
ADP ADVANCED DISTRIBUTOR PROUCTS heating & cooling systems
Or this may be the IO Manual for your unit:
ADP B-Series Multi-Position & Hydronic Air Handlers IO Manual [PDF] (2017) Electric or Hot Water Heat, with available Variable-Speed High Efficiency ECM Motor
On 2020-11-13 by ovsa
I have a ADP air handler with a hot water heating coil and a refrigerant coil. My thermostat controls the HW recirc pump.
in heating mode after the recirc pump shuts off the fan keeps running, forever.
I do not see an aquastat or fan limit switch in the housing anywhere.
my question is what controls the fan on/off? Is it programmed right into the circuit board or am i missing something?
thanks
On 2020-10-19 - by (mod) -
Ed
Essentially, yes. IF your limit switch has no MAN-ON switch (found as a white push-pull knob or as a small metal slide left-right lever) then yeah that control is in automatic mode.
However some thermostats also include a FAN ON / AUTO / switch that can also control the fan.
If your fan NEVER turns off regardless of the thermostat setting then I suspect either one of the problems listed above on this page
OR
one of the situations described at FAN WONT STOP - THERMOSTAT SWITCH
On 2020-10-19 by Ed
If our honeywell fan limit switch does not have the auto/manual push/pull button for the fan, then is it safe to assume that it is always set for auto? Our limit switch does not have the hole for the button in the cover, but when opened, it looks like the image above except there is no white button.
Maybe it broke off? (we just bought the house and moved in so don't know).
I read another comment from someone who said that not all models have the button, but our's keeps running well after the temperature is reached. Any ideas on how to make sure the fan limit switch is set to auto?
On 2020-07-15 by Pam
Hello! My Honeywell digital thermostat is set on cooling currently and the fan is set on auto. Everything seems to be working fine, except every morning the blower fan comes on for a long time (an hour or more) even though the thermostat shows no activity (cooling ihas not come on)
The inside temp is already at set point and drops to a couple degrees below the set point within a few minutes of the fan coming on and stays there the whole time the fan is running. This does not seem to happen at other times of day. The thermostat seems to be working the way it should.
On 2020-07-15 by Steve (in GA) - clogged condensate drain causes intermittent shut down of the A/C system
Well, it turned out to be something verrrrrrrrry simple, but somewhat elusive!
I checked all wiring from tstat to airhandler, and from airhandler to compressor. All lines were
continuous, with no shorts to any other lines.
The compressor continued to run intermittently, with no icing seen on coils. The vent temps were65-66 degrees. After everything I tried (new airhandler fan delay/relay board, NOS tstat) got same
intermittent results, I figured the compressor was shutting down for some type of overheat situation.
The reality...was different....*facepalm*
Contractor came out, gauged compressor and looked at boards on compressor. He then
checked the airhandler, and the condensate float switch (here it comes!).
He saw some water in the switch cup, and said "you've got a clogged drainline. That's
what's shutting down the compressor." He blew out the line, and systems been running
like a top since then.
The clog must have been *partial*, with slow drainage. Between cycles, the line would drain
enough to let float switch drop, and enable the compressor to run.
The compressor would run, cool the coils, and condensate would begin accumulating--
until it began to back up in the slow drain, and lift the float switch--and shut down the
compressor. I did actually peek in the float switch cup several times, and never saw
anything. I must have been looking after it had drained down.
On 2020-07-13 - by (mod) -
Spiro
Let's start with the Diagnostics above on this page as that will be a more complete procedure than if I try to make it up again typing in an off-the-cuff reply here. Please look through those steps and let me know what you find.
On 2020-07-13 by Spiro
I have a Payne all in 1 blower condenser unit. My blower is staying on all the time.
On 2020-07-10 - by (mod) -
Right.
The simplest and most straightforward test is to disconnect a thermostat wires at both ends and then working from each end test for any continuity between any pair of them.
Let me know what you find
On 2020-07-10 by Steve (in GA)
thank you, I shall ohm out the control wires from thermostate mount plate, and check for shorts. Assumption: the W, Y and G should have no continuity
to C (ground), or to each other--correct?
I found a discussion in another forum with same symptoms (intermittent failure of airhandler to stop blowing after reaching setpoint temp), where poster found the G line was left 'floating' (as opposed to being grounded) at setpoint shutdown. He conjectured about putting a pull-down resistor across G and C, to bleed any stray/leftover voltage at setpoint shutdown. He mentioned a 5K.
I just installed a 100K across G and C. Should only load 24VAC transformer with an additional 24mA.
A cooling cycle just completed--system cooled to setpoint, thermostat clicked, and about a minute later, airhandler stopped blowing---good! Fingers crossed that this solved it!
On 2020-07-10 - by (mod) -
I got that, Steve, but I'm not clear on whether or not you found that by disconnecting the TT right at the air handler was done at a time when the AHU was running when you think it should not.
Taking that step not only rules out a bad thermostat but also mistakes in thermostat wiring and also the more-subtle problem of thermostat wires that are shorted together somewhere enroute.
On 2020-07-10 by Steve
I've already disconnected the thermostat, and replaced it with a brand new one...along with replacing the blower time delay relay board.
On 2020-07-10 - by (mod) -
Have you tried disconnecting the thermostat right at the air handler? That can rule the thermostat out.
On 2020-07-10 by Steve
I've got the same problem, as posted On 2020-03-04 by Forrest.
My Amana/Goodman ARUF3714C airhandler keeps blowing, even after thermostat reaches set-point; compressor shuts down, but airhandler keeps blowing. The problem is *intermittent*--sometimes airhandler shuts off, sometimes it just runs and runs (not the
65-second efficiency delay).
Figured it was the blower delay relay board; replaced it and all seemed ok for a few days. It started up again today. I called
Goodman and a tech suggested the thermostat might be defective. I had a new-in-box thermostat on hand, and wired it in.
It's doing same thing--seemingly random failure of airhandler to shut down, after reaching set-point temp.
I'm wondering about either the control wiring, or the 24 volt transformer. We had a power outage a few days before this
trouble started, and wonder if the transformer might have been zapped, and isn't putting out 24 VDC.
The other possibility is wiring--if there's some random short or open, responding to equipment vibration or...?
How to check the control wiring? Is "C"/blue the common ground? What wires should be 'shorted' to each other, or to ground, during different operating states?
On 2020-07-01 - by (mod) -
Bill
Your service tech might check for a bad control board or ice blocking on the cooling coil
On 2020-06-30 by Bill Harmon
I have a 15 sheer unit that blows strong and then weak, but continues to go up and down when activated at Temp setting. I mean it blows loud then soft then loud but maintains temp.
Whats happening can someone tell me what can I do ?
On 2020-05-24 - by (mod) -
If the blower previously would run in high speed then I suspect a failed relay or control board.
On 2020-05-23 by Anonymous
Why won't the blower turn on high on my Goodman heat pump and Goodman furnace while in the cooling mode
On 2020-03-04 by (mod) - blower motor on air conditioner will not shut down.
Have you checked for shorted wires anywhere in the control circuit?
On 2020-03-04 by Forrest
blower motor on air conditioner will not shut down. I put in a new control board,that didn't work.put in a new contactor switch.that worked for 8 day's then stopped working.put in another contactor switch .the same. fan motor still runs constantly.
On 2020-02-04 - by (mod) -
Tab
Your heating service tech may find a bad switch or control or even a thermostat set wrong or shorted thermostat wires.
She might check the diagnostics above on this page first.
On 2020-02-01 by Tab
My furnace fan in my house won't turn off when my unit is off
On 2019-12-28 - by (mod) -
Jamie
Perhaps there is a defective fan limit control or fan relay control switch.
On 2019-12-28 by Jamie
Sometimes my blower fan won’t shut off for a while. It will work for half the day and then the other half of the day it will not shut off.If I flip the breaker off and right back on the fans stays off until the next cycle.
On 2019-12-05 - by (mod) - check dip switches or jumpers on fan controller
First let's identify the exact brand and model of heater and then look at the manual to see what settings are available.
On most equipment there's actually a user operable switch that will turn the fan to run continuously. But on some it might be a dip switch or jumper.
The other place to look of course is at the thermostat. You can rule out the thermostat by disconnecting the thermostat wires entirely at the heater. If the fan keeps running then it's not a thermostat setting.
On 2019-12-04 by Nemo
Thank you for getting back to me. You mean you think it's the ECM problem (bad or set that way) as well?
What do I need to do, if I don't want the fan constant blowing?
On 2019-12-04 - by (mod) -
I agree with you that typically there's either a switch set somewhere or a shorted wire or bad control
On 2019-12-04 by Nemo
Thank you for all the very very helpful information found on this website! I am a new homeowner and I found the blower fan (Genteq Endura ECM FM19, 1/2 hp, 230VAC) installed has been running constantly. This is what I have gathered so far:
1. if I disconnect 5-pin low voltage signaling on the ECM, the fan still runs.
2. I checked voltage on the 4-pin power supply to the ECM, they are all correct (C-0V, L-115V, G-0V, N-115V).
3. snap-disc thermo switch checked.
4. heat sequencer checked (I have a heat pump and electric heat).
5. fan relay is quite hard to reach, but when I call fan-on, the relay clicks and the fan blows a little bit stronger.
6. interior of ECM looks great, no dust, no rust, no busted capacitor, perfect rubbery seal.
I suspect the ECM module is programed to run the motor non-stop, by the builder or previous owner? Program # 604253-05. Or what else could be the problem here? Thank you again!
Regards,
Nemo
On 2019-11-15 - by (mod) -
This sounds as if the FAN ON switch is set to ON at the thermostat or on the fan limit controller inside the furnace air handler
AND
that your furnace is not working - that is the burner won't run. Depending on the fuel (oil, gas, electric) you'll find different diagnostic routines in the ARTICLE INDEX given in the Continue Reading section of this page
On 2019-11-15 by Jon tester
Blower fan continuously running while heat off switches on heat and on auto no fire in the box fan still runs
2019/11/04 Misty Lawhon
I think my air off and the fan off but my furnace keeps lighting up. I’m worried it with catch fire.
Misty
I can't tell what's happening with your furnace from your brief text: is the thermostat calling for heat?
Watch out: In any event if you have the slightest worry that the heater is unsafe then
I hope you simply shut down the system then called for repair;
2019/10/18 Henri Nseke
Can blower running constantly
2019/08/15 Rick asked
Why does the ac blow thru furnace
It's using the indoor furnace fan to blow cool air through the same duct system used for warm air heating.
...
Continue reading at FAN WONT STOP - THERMOSTAT SWITCH, or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see FURNACE FAN WONT STOP FAQs - questions & answers about why the furnace blower fan won't stop running
Or see these
FURNACE FAN WONT STOP at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
Our Comment Box is provided by Countable Web Productions countable.ca
In addition to any citations in the article above, a full list is available on request.