InspectAPedia ® | ||||||||||||||||||||||||||
| Building & Environmental Inspection, Testing, Diagnosis, Repair, & Problem Prevention Advice |
| |||||||||||||||||||||||||
| InspectAPedia Home |
| | Air Conditioning |
| | Electrical | | | Indoor Environment |
| | Exteriors | | | Heating | | | Home Inspection |
| | Insulate Ventilate |
| | Interiors | | | Mold Inspect/Test |
| | Plumbing Water Septic |
| | Roofing | | | Structure | | | Contact Us |
| Directory of Professionals to Inspect or Test a Building | ||||||||||||||||||||||||||
Mobile View HEATING SYSTEMS AIR FILTERS for HVAC SYSTEMS AIRBOUND HEAT SYSTEM REPAIRS ANODES & DIP TUBES on WATER HEATERS ANTI SCALD VALVES BACKFLOW PREVENTERS BAROMETRIC DAMPERS BLOWER DOORS & AIR INFILTRATION BLUERAY Recall BOILERS, HEATING BOILER LEAKS CORROSION STAINS BOILER NOISE SMOKE ODORS BOILER OPERATING PROBLEMS BOILER OPERATION DETAILS BOILER PARTS LIST BOILER PRESSURE SETTINGS CARBON MONOXIDE/DIOXIDE CARBON MONOXIDE WARNING CHIMNEY INSPECTION DIAGNOSIS REPAIR CHIMNEYS & Flues - Asbestos Transite Pipe COOL OFF HEAT Thermostat Switch DRAFT REGULATORS - barometric dampers DUCT SYSTEMS DUCT SYSTEM DEFECTS DUCT INSULATION - Asbestos Paper DUCTS - Asbestos Transite Pipe DUST FROM HVAC? ELECTRIC HEAT ELECTRICAL POWER SWITCH FOR HEAT ENERGY SAVINGS in BUILDINGS ENERGY SAVINGS PRIORITIES ENERGY SAVINGS RETROFIT CASE STUDY ENERGY SAVINGS RETROFIT LEAK SEALING GUIDE ENERGY SAVINGS RETROFIT OPTIONS FLUE VENT CONNECTORS FREEZE-PROOF A BUILDING FURNACES, HEATING FURNACE CONTROLS & SWITCHES CAD CELL RELAYS DRAFT HOODS DRAFT REGULATORS FAN AUTO ON CONTROLS FAN LIMIT SWITCH What is a Fan & Limit Switch? Sensing Furnace Temperatures How to Set the Fan & Limit Control How to Test the Fan & Limit Control How to Install the Fan & Limit Control How to Wire the Fan & Limit Control SPILL SWITCHES STACK RELAYS THERMOSTATS ZONE DAMPER CONTROLS FURNACE OPERATION DETAILS GAS PIPING, VALVES, CONTROLS HEAT EXCHANGER LEAKS HEAT LOSS in BUILDINGS HEAT LOSS DETECTION TOOLS HEAT LOSS INDICATORS HEAT LOSS R U & K VALUE CALCULATION HOUSEWRAP AIR & VAPOR BARRIERS HEATING COST SAVINGS METHODS HEATING LOSS DIAGNOSIS-BOILERS HEATING LOSS DIAGNOSIS-FURNACES HEATING OIL CLOUD WAX GEL POINT HEATING OIL EXPOSURE HAZARDS, LIMITS HEATING OIL SLUDGE HEATING SMALL LOADS HEAT PUMPS HEATING SYSTEM INSPECTION PROCEDURE HIGH EFFICIENCY BOILERS/FURNACES INSULATION & VENTILATION INSPECTION & IMPROVEMENT MOTOR OVERLOAD RESET SWITCH NO HEAT - BOILER / FURNACE DIAGNOSIS ODORS FROM HEATING SYSTEMS OIL BURNERS OIL BURNER INSPECTION GUIDE OIL BURNER NOISE SMOKE ODORS OIL BURNER SOOT & PUFFBACKS OIL FUEL TYPES & CHARACTERISTICS Oil Odors: Leaky Oil Tank Piping OIL SAFETY VALVES OIL TANKS OIL TANK LEAKS & SMELLS OIL TANK PIPING DEFECTS OIL TANK PRESSURE OIL TANK SLUDGE OIL TANK TESTING OIL TANKS, BURIED PLASTIC HEATER VENT PULSE COMBUSTION HEATERS RADIANT HEAT RADIANT HEAT Floor Mistakes to Avoid RADIANT SLAB FLOORING CHOICES RADIANT SLAB TUBING & FLUID CHOICES RADIATORS RELIEF VALVES - TP Valves on Boilers Relief Valves - Water Heaters SAFETY DURING HEATING INSPECTION Safety Recalls BLUERAY Recall CHIMNEYS & Flues - Asbestos Transite Goodman HTPV RECALL Heat Recovery Ventilator RECALL Lennox Furnace Manuals Lennox WARNING Weil McLain RECALL SPILL SWITCHES STACK RELAY SWITCHES STEAM HEATING SYSTEMS TANKLESS COILS THERMAL EXPANSION of MATERIALS THERMAL MASS in BUILDINGS THERMAL MASS in UPSTAIRS THERMAL TRACKING & HEAT LOSS THERMOSTATS Transite Pipes, Chimneys & Flues WINTERIZE A BUILDING More Information InspectAPedia Blog - News Updates Air Conditioning & Heat Pumps Bookstore Electrical Environment Exteriors Heating Home Inspection Insulate Ventilate Interiors Mold Inspect/Test Plumbing Water Septic Roofing Structure Contact Us |
|
|
|
The rust on the exterior around the gas burners of this gas fired furnace could be due to improper and unsafe operation. Expert inspection should be ordered to assure that this system is safe and functional. If the furnace turns on immediately when the thermostat is turned-on or up from the living area what does this mean? Normally a hot air furnace oil or gas burner will turn on immediately when the thermostat calls for heat. However the blower or fan unit that delivers warm air to the living area will not turn on until the fan limit switch in the hot air supply plenum or furnace top senses that the air in that area is warm. This prevents blowing cold air on building occupants. |
Similarly, when the thermostat is satisfied (the room has reached the thermostat set temperature), the thermostat will "turn off" the furnace. What actually happens is that the oil or gas burner will turn off immediately, but on most hot air furnace systems, the blower will continue to run, perhaps even for several minutes, as it extracts the remaining heat from the furnace heat exchanger and hot air supply plenum.
Two reasons for this continued operation of the furnace blower fan past burner shutdown include:
Make a thorough visual inspection for signs of damage or improper operation, missing parts, water damage, rust, mechanical damage, soot, smoke, improper venting, missing or damaged safety controls, etc. We detail these topics in articles listed below. Thanks to reader Cyrus for editing suggestions.
For details about the setting, re-setting, or function of the controls and switches commonly found on hot air heating systems see these articles:
A technical note is necessary about determining what kind of heat or what type of heating system is installed: some heating systems combine both hot water and hot air to heat a building, such as water to air systems which use a heating boiler (oil, gas, or electric) to heat water which circulates through (and inside of) a heat exchanger (that looks like a car radiator).
The heat exchanger in a water to air heating system is then placed inside of an air handler or blower compartment where a blower fan circulates building air from return ducts to a plenum where air is blown across the heat exchanger and then the warmed air is delivered to the occupied space through additional warm air ducts or radiators.
Some buildings are heated by a combination of separate hot water systems (circulating hot water through radiating devices like baseboards or radiators in some areas) and hot air systems (circulating warm air through ductwork into the occupied space in other areas). These buildings will have both a hot air furnace and a completely separate hot water heating boiler installed. In this case these are completely separate heating systems and usually each serves different building areas.
Some heating systems combine both hot water and hot air to heat a building, such as water to air systems which use a heating boiler (oil, gas, or electric) to heat water which circulates through (and inside of) a heat exchanger (that looks like a car radiator). The heat exchanger in a water to air heating system is then placed inside of an air handler or blower compartment where a blower fan circulates building air from return ducts to a plenum where air is blown across the heat exchanger and then the warmed air is delivered to the occupied space through additional warm air ducts or radiators.
Water-to-air heating systems will use both a separate water heating boiler and a blower or air handler system.
...
Search InspectAPedia |
Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.
|
|
![]() The Mold Information Center: What to Do About Mold in Buildings, When and How to Inspect for Mold, Clean Up Mold, or Avoid Mold Problems |
![]() Use this simple, economical mold test kit by following our instructions on how to collect and mail mold samples to our lab |
Environmental Inspection, Testing, & Diagnosis On-Site IAQ, Gas, Air Testing, Mold Investigation, Sick Building Diagnosis, Lab Services, & Remediation Plan Preparation - indoor air quality testing, problem source determination, supporting lab work, written remediation plan addressing removal of environmental and other hazards and prevention of their recurrence.
|
![]() Building Inspection, Problem Diagnosis, Forensic Investigation & Testing, Repair Consulting |
|
|
05/25/2009 - 09/05/1999 - InspectAPedia.com/heat/HeatFurnaceOperation.htm - © 2009 - 1988 Copyright Daniel Friedman All Rights Reserved - InspectAPedia® is a Registered U.S. Trademark