InspectAPedia.com InspectAPedia®
 

Free Encyclopedia of Building & Environmental Inspection, Testing, Diagnosis, Repair

Ask a Question or Search InspectAPedia

  • HOME
  • AIR CONDITIONING
  • ELECTRICAL
  • EXTERIORS
  • HEATING
  • HOME INSPECTION
  • INTERIORS
  • PLUMBING
  • ROOFING
  • SEPTIC SYSTEMS
  • STRUCTURE
  • WATER SUPPLY
  • ENERGY SAVINGS
  • ENVIRONMENT
  • INDOOR AIR IAQ
  • INSULATION
  • MOLD INSPECT TEST REMOVE
  • NOISE
  • ODORS
  • SOLAR ENERGY
  • VENTILATION
  • EXPERTS DIRECTORY
  • CONTACT US


Mobile Phone or PDA view of this websiteMobile View
HEATING SYSTEMS

AFUE DEFINITION, RATINGS
AGE of AIR CONDITIONERS & HEAT PUMPS
AGE of HEATERS, BOILERS, FURNACES
AIR CONDITIONING & HEAT PUMP SYSTEMS
AIR FILTERS for HVAC SYSTEMS

AIR HANDLER / BLOWER UNITS
AIRBOUND HEAT SYSTEM REPAIRS
ANODES & DIP TUBES on WATER HEATERS
ANTI SCALD VALVES
APPLIANCE EFFICIENCY RATINGS
ASBESTOS IDENTIFICATION IN buildings

BLUE vs YELLOW COMBUSTION FLAMES
BLUERAY Recall

BOILERS, HEATING
  BOILER OPERATION DETAILS
  BACKDRAFTING HEATING EQUIPMENT
  BOILER COMPONENTS & PARTS
  BOILER CONTROLS & SWITCHES
  BOILER LEAKS CORROSION STAINS
  BOILER LEAKS, HOW TO LOCATE
  BOILER OPERATING PROBLEMS
CARBON MONOXIDE - CO
CARBON MONOXIDE WARNING

CHIMNEY INSPECTION DIAGNOSIS REPAIR
CHIMNEYS & Flues - Asbestos Transite Pipe
COMBUSTION AIR
COMBUSTION AIR for TIGHT buildings
COMBUSTION GASES & PARTICLE HAZARDS
COMBUSTION PRODUCTS & IAQ
COMPLETE COMBUSTION, Stoichiometric
DUCT INSULATION - Asbestos Paper
DUCTS - Asbestos Transite Pipe
DUST CONTAMINATION FROM HVAC?

ELECTRIC HEAT
ELECTRIC MOTOR DIAGNOSTIC GUIDE
ELECTRIC MOTOR OVERLOAD RESET SWITCH
ELECTRICAL POWER SWITCH FOR HEAT

ENERGY SAVINGS in buildings
EVAPORATIVE COOLING SYSTEMS

FAN, AIR HANDLER BLOWER UNIT
FAN AUTO ON Thermostat Switch
FAN, COMPRESSOR/CONDENSER UNIT
FAN CONVECTOR HEATERS - HYDRONIC COILS
FAN LIMIT SWITCH
FAN NOISES

FILTERS, AIR for HVAC SYSTEMS
FILTERS, OIL on HEATING EQUIPMENT

FIRE SAFETY CONTROLS
FIREPLACE Damage & Unsafe Hearths - Settlement
FLAME COLOR, BLUE vs YELLOW COMBUSTION
FLOODED HEATING EQUIPMENT REPAIR
FLOODED WATER HEATER REPAIR
FLUE VENT CONNECTORS
FREEZE-PROOF A BUILDING
FUEL OIL TYPES & CHARACTERISTICS
FUEL UNIT, HEAING OIL PUMPS

FURNACES, HEATING
  DUCT SYSTEM DEFECTS
  ALLOY SYSTEMS FLEXDUCT
  DUCT & AIR HANDLER ODORS
  DUCT INSULATION, Asbestos Paper
  FURNACE CONTROLS & SWITCHES
  FURNACE OPERATION DETAILS
FURNACE OPERATING TEMPERATURES
  HEAT EXCHANGER LEAKS
GALVANIC SCALE & METAL CORROSION
GAS BURNER Flame & Noise Defects
GAS FIRED WATER HEATERS

GAS PIPING, VALVES, CONTROLS
HEAT LOSS INDICATORS
HEAT LOSS PREVENTION PRIORITIES
HEATING COST FUEL & BTU Cost Table
HEATING COST SAVINGS
HEATING LOSS DIAGNOSIS-BOILERS
HEATING LOSS DIAGNOSIS-FURNACES

HEATING OIL CLOUD WAX GEL POINT
HEATING OIL SLUDGE
HOT WATER HEATERS
HOT WATER IMPROVEMENT

INSULATION INSPECTION & IMPROVEMENT

LP & Natural Gas Safety Hazards

MANUALS & PARTS GUIDES - HVAC
NO HEAT - BOILER / FURNACE DIAGNOSIS

NOISE / SOUND DIAGNOSIS & CURE
NOISE AIR CONDITIONER / HEAT PUMP
NOISE, DUCT VIBRATION DAMPENERS
NOISE CONTROL for HEATING SYSTEMS
NOISE CONTROL for PLUMBING
NOISES COMING FROM WATER HEATER

ODORS & SMELLS DIAGNOSIS & CURE
ODORS FROM HEATING SYSTEMS

OIL BURNERS
OIL BURNER INSPECTION GUIDE
OIL BURNER NOISE SMOKE ODORS
OIL BURNER NOZZLE & ELECTRODES
OIL BURNERS, RETENTION HEAD
OIL BURNER SOOT & PUFFBACKS

OIL FILTERS on HEATING EQUIPMENT
OIL FILTER MISSING
OIL FUEL TYPES & CHARACTERISTICS

OIL & GAS PIPING
  GAS PIPING, VALVES, CONTROLS
  OIL TANK PIPING & PIPING DEFECTS

OIL LINE CLOGGING FIX
OIL LINE SAFETY VALVES
OIL ODORS, LEAKY OIL TANK PIPING
OIL PUMP FUEL UNIT
OIL SPILL CLEANUP / PREVENTION

OIL TANKS
OIL TANK SAFETY
OIL TANK SLUDGE
OIL TANK TESTING
OIL TANKS, BURIED
OIL TANK WATER REMOVAL

PLASTIC HEATER VENT
PULSE COMBUSTION HEATERS
PASCAL CALCULATIONS

RADIANT BARRIERS
RADIANT HEAT
RADIANT HEAT Floor Mistakes to Avoid
RADIANT HEAT TEMPERATURES
RADIANT SLAB FLOORING CHOICES
RADIANT SLAB TUBING & FLUID CHOICES

RADIATORS

RELIEF VALVES - TP Valves on Boilers
RELIEF VALVES - STEAM TP VALVES
RELIEF VALVES - Water Heaters
RELIEF VALVES - Water Tanks

Reset Switch - Heater Primary Control
Reset Switch - Electric Motors
Reset Switch - Stack Relays

SAFETY HAZARDS & INSPECTIONS
SAFETY HAZARDS GUIDE
SAFETY, HEATING INSPECTION
SAFETY,HOME HEATING TIPS
Safety Recalls, Chimneys, Vents, Heaters
  BLUE vs YELLOW COMBUSTION FLAMES
  BLUERAY Recall
  CHIMNEYS & Flues - Asbestos Transite
  Goodman HTPV RECALL
  Heat Recovery Ventilator RECALL
  Lennox Furnace Manuals
  Lennox SAFETY WARNING
  PLASTIC Plexvent / Ultravent RECALL
  Weil McLain RECALL
SAFETY, HEATING INSPECTION
SAFETY,HOME HEATING TIPS

STEAM HEATING SYSTEMS
  AQUASTAT CONTROL Functions
  BACKDRAFTING HEATING EQUIPMENT
  BANGING HEATING PIPE NOISES
  CAD CELL RELAY SWITCH
  Check Valves Flow Control Valves Flo Control
  Chemical treatments, Boiler
  Circulator Pumps & Relays
  COMBUSTION GASES & PARTICLE HAZARDS
  CONDENSATE RETURN PIPES, PUMPS, STEAM
  DIAGNOSE & FIX BOILER
  DRAFT HOODS - gas fired
  DRAFT MEASUREMENT, CHIMNEYS & FLUES
  DRAFT REGULATORS, DAMPERS, BOOSTERS
  ELECTRIC MOTOR OVERLOAD RESET SWITCH
  ELECTRICAL POWER SWITCH FOR HEAT
  Expansion Tanks
  FIRE SAFETY CONTROLS
  Gauges on Heating Equipment
  Limit Switches, Boilers
  Low Water Cutoff Valves, Boilers
  MIXING / ANTI-SCALD VALVES
  Pressure & Temperature Settings, Controls
  Pressure Switch, Steam Boiler
  RELIEF VALVES - STEAM TP VALVES
  Sight Glass, Steam Boiler
  Spill Switches
  Stack Relay Switch
  Steam Pressure Gauge
  Steam Vents
  THERMOSTATS, HEATING / COOLING
  LOW WATER CUTOFF CONTROLS
  Water Feeder Valves, Steam

TANKLESS COILS
THERMAL EXPANSION of MATERIALS
THERMAL MASS in buildings
THERMAL TRACKING & HEAT LOSS

THERMOSTATS, HEATING / COOLING
Transite Pipe Chimneys & Flues

More Information

LARGER VIEW of an octopus furnaceHeating Inspection Safety Guide
InspectAPedia®  -         

  • Safety tips for inspecting & repairing central heating systems
  • Home inspection class: heating system inspection
  • Course on home inspection safety during heating system examination and testing
  • Questions & answers about safety hazards on and around residential heating equipment

Here we explain safety procedures and tips that are important during heating system inspections.

InspectAPedia offers impartial, unbiased advice without conflicts of interest. We will block advertisements which we discover or readers inform us are associated with bad business practices, false-advertising, or junk science. Our contact info is at InspectAPedia.com/Contact.htm.

This website answers most questions about central heating system troubleshooting, inspection, diagnosis, and repairs.

We describe how to inspect residential heating systems to inform home owners, buyers, and home inspectors of common heating system defects. The articles at this website describe the basic components of a home heating system, how to find the rated heating capacity of an heating system by examining various data tags and components, how to recognize common heating system operating or safety defects, and how to save money on home heating costs. We continue to add to and update this text as new details are provided. Contact us to suggest text changes and additions and, if you wish, to receive online listing and credit for that contribution.

© Copyright 2012 InspectAPedia.com, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use page top links to major topics or use links at the left of each page to navigate within topics and documents at this website. Green links show where you are in a document series or at this website.

Heating Inspection Safety Guide

This section describes examples of steps to protect the home or heating system inspector during the inspection of a heating system. It does not address safety concerns for the client/occupant or unsafe conditions on the heating equipment itself, though those are addressed in other articles at this website. ASHI 9.3.A. The inspector is not required to operate equipment when weather conditions or other circumstances may cause equipment damage [or in the opinion of the inspector, may cause any sort of unsafe condition (added by DJF, NOT ASHI Standards)

In order to be as thorough, accurate, and safe as possible, a heating system inspector should use a well-defined order of discovery which assures that s/he examines all important heating system components. Several possible heating system inspection "road maps" can be used for this purpose and are described at this website.

  • Air Filter Shock Hazards: Avoid electric shock from the static charge at electronic air filters. - Home inspection standard example: ASHI 9.3.D.4 The inspector is not required to observe electronic air filter
  • Backpressure or Flashback: Watch for flashback or backpressure at inspection ports on heating equipment
  • Blocked heating flues: a blocked flue can cause the production of potentially fatal carbon monoxide gases in a building. A blocked flue case study is reported at UNLINED FLUE INSPECTIONS.
  • BLUE vs YELLOW COMBUSTION FLAMES - the Blueray history and blue flame vs. yellow flame combustion, flame color & combustion efficiency, & how oil competes with gas as a heating fuel.
  • Blueray Heating Boilers/Furnaces Safety Recall by the US CPSC, with additional history, photos, and technical details; Blue Flame Blue Ray
  • Carbon Dioxide Gas Toxicity
  • Carbon Monoxide Gas Toxicity, exposure limits, building inspection for CO hazards
  • Carbon Monoxide Poisoning Warning - Chimney Safety: US CPSC safety warning [Home Heating System Should Be Checked for proper venting and for CO Carbon Monoxide Hazards - clarifying notes by DJF]
  • Chimneys & Flues - Asbestos Transite Pipe - chimney movement, chimney cracks, chimney safety inspection, chimney cleaning, draft problem diagnosis & repair
  • Chimney Inspection Checklist - detailed articles on a wide variety of chimney safety and functional defects
  • CHINESE DRYWALL HAZARDS - corrosion risks to HVAC condensing and cooling or heating coils, possible corrosion risks to HVAC metal ductwork from corrosive gases produced by Chinese drywall.
  • Combustion air: make certain that all fuel burning equipment has adequate combustion air. See COMBUSTION AIR for additional details about the requirement for combustion air. COMBUSTION AIR for TIGHT buildings explains how to provide outside combustion air for tight buildings. See COMBUSTION GASES & PARTICLE HAZARDS for an explanation of the dangers of inadequate combustion air. See COMBUSTION PRODUCTS & IAQ for the relationship between fuel burning appliances and building indoor air quality. More about carbon monoxide - CO - is at CARBON MONOXIDE - CO and at CARBON MONOXIDE WARNING.
  • Confirm Heat Operation Before Leaving: To avoid a future dispute about having been the cause of lost heat in a building, particularly in cold weather, if the system was on and running, observe and note that it was running normally at the end of the inspection procedure. This is important if your inspection procedure includes any action that may temporarily shut off the system such as testing a shutoff switch.
  • Corrosion on Heating Systems Do not pick at corrosion on heating systems - you may cause a catastrophic leak that requires immediate system shut-down - which in freezing weather risks freeze-damage to the building.
  • DIAGNOSE DARK STAINS on Indoor Surfaces, how to diagnose stains on walls, floors, carpets, and how to determine the stain source
  • Disassembling flue vent connections: Do not disassemble flue vent piping - risks of filth, unable to reassemble, etc.
    Home inspection standard example: ASHI 9.3.D.1 The inspector is not required to observe the interior of flues [However often you can detect a blocked flue by looking through the barometric damper or by use of a mirror at the chimney cleanout. We recommend this step. -DJF]
    Home inspection standard example: ASHI 9.3.D.2 The inspector is not required to observe fireplace insert flue connections [Normally not visible. Caution: there is frequently a hidden problem there.]
  • DUCT SYSTEMS - air leaks, unsafe ductwork, inadequate supply or return air, other defects
  • DUCT & AIR HANDLER ODORS - how to find and cure smelly duct work or air handlers
  • Ducts - Asbestos Transite Pipe
  • DUST CONTAMINATION FROM HVAC? An Investigation of Indoor Dust Debris Blamed on a Heating/Cooling System Reveals Carpet Dust
  • FAN LIMIT SWITCH control on heating furnaces
  • NOISE / SOUND DIAGNOSIS & CURE includes a discussion of noises related to heating equipment
  • OIL BURNER NOISE SMOKE ODORS and also OIL BURNER SOOT & PUFFBACKS explain how to diagnose oil burner noises, smoke, odors, sooting, and which conditions are potentially dangerous, requiring prompt service or repair
  • Odors From Heating Systems - a list of articles addressing the sources of odors produced by various types of heating systems - how to find, diagnose, and correct these possibly dangerous conditions.
  • Safety Recalls, Chimneys, Vents, Heaters
      BLUE vs YELLOW COMBUSTION FLAMES
      BLUERAY Recall
      CHIMNEYS & Flues - Asbestos Transite
      Goodman HTPV RECALL
      Heat Recovery Ventilator RECALL
      Lennox Furnace Manuals
      Lennox SAFETY WARNING
      PLASTIC Plexvent / Ultravent RECALL
    US Consumer Product Safety Commission notices, contact information, claims
      Weil McLain RECALL
  • SOOT on OIL FIRED HEATING EQUIPMENT discusses sooty on or inside oil fired heating equipment and its effect on heating costs and heater operating problems. Also see OIL BURNER NOISE SMOKE ODORS.
  • STAIN DIAGNOSIS on BUILDING INTERIORS, how to diagnose stains on walls, floors, carpets, and how to determine the stain source
  • When to Shut Down Heating Systems: Turn off heating equipment immediately if you see conditions that appear to be unsafe, such as evidence of fire, smoke, puffback, or if you see safety controls such as relief valves, temperature limits, or flue gas spillage sensors which have been removed or modified, or if the equipment has already been "red-tagged" by a service technician.
  • When to Avoid Turning On Heating Systems: Do not turn on heating equipment if you see any condition that appears to be unsafe. Some examples are listed here.
    • Do not turn on equipment which has been "shut down" - Possible open piping, unsafe wiring, leaks, unsafe chimney, fire risks.
    • Do not turn on equipment which has been switched off without explicit permission/instruction from a responsible party
    • Examine gauges (not entirely reliable) for unusual pressure or temperature conditions and do not permit such equipment to continue to operate
    • Do not turn on, or turn off if already operating, any heating system whose temperature/pressure gauge shows abnormally high operating values
    • Do not operate equipment which does not appear to be vented properly; shut down equipment if, on operating it, you observe an apparently blocked flue
    • Do not operate equipment if the chimney is suspect--e.g. old single wythe unlined brick with visible damage in the attic or outside
    • Do not turn on, or turn off if already operating, any heating system that is not safely connected to a chimney
  • Humidifier Inspections: Be careful about disconnecting humidifiers to obtain access to furnace plenums: you may cut yourself on sheet metal, cause leaks in humidifier piping, cause spills.
    ASHI 9.3.D.3 The inspector is not required to observe humidifiers
    • But watch for humidifiers which leaked into and damaged duct work or onto and damaged a heat exchangers
  • Lighting test fires: Do not light fires in coal or wood stoves to check draft, etc
    Home inspection standard example: ASHI 9.3.C. The inspector is not required to ignite or extinguish solid fuel fires
  • Noises, smoke, soot, back pressure at inspection port (watch out for burns and fires if this port is opened), sloppy startup, rumbling, sloppy or delayed shutdown-flame lingers COULD indicate a very dangerous operating condition.
  • Relief Valve Testing on Heating Systems: Do not test relief valve levers nor catch your sleeve on one
    Home inspection standard example: ASHI 9.3.B. The inspector is not required to operate automatic safety controls
  • Shock Hazards at Heating Controls: Watch for electric shock at controls

Questions & Answers regarding this article

Questions & answers about safety hazards on and around residential heating equipment

Ask a Question or Search InspectAPedia

HTML Comment Box is loading comments...

Share this Article      

...

Technical Reviewers & References

  • InspectAPedia.com® - Daniel Friedman - Publisher & Editor.
  • InspectAPedia Bookstore lists recommended books, organized by topic & available for purchase. Most of our articles also include a list of recommended books for the specific article topic as well as other references, and information sources.
  • Critique, contributions wanted: Contact Us to suggest corrections or additions to articles at this website, and if you wish, to receive online listing and credit as a contributor. Particular thanks are due to the many experts and also consumers who read and critique technical articles at InspectAPedia.com.
  • Additional technical contributors & reference sources for this article are listed below.

Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

HEATING SYSTEMS
HEATING SYSTEM INSPECTION DIAGNOSIS REPAIR
HEATING SYSTEM INSPECTION DETAILS
HEATING SYSTEM NOISES
HEATING SYSTEM SERVICE & MAINTENANCE

HEATING SYSTEM TYPES

BOILERS, HEATING
  BACKDRAFTING HEATING EQUIPMENT
  BOILER COMPONENTS & PARTS
  BOILER OPERATION DETAILS
  BACKDRAFTING HEATING EQUIPMENT
  BOILER COMPONENTS & PARTS
  BOILER OPERATING PROBLEMS
BOOKSTORE - Heating Systems
CARBON MONOXIDE - CO
CHIMNEY INSPECTION DIAGNOSIS REPAIR
DUCT SYSTEM DEFECTS
  ALLOY SYSTEMS FLEXDUCT
  AIR HANDLER / BLOWER UNITS
  AIR FILTERS for HVAC SYSTEMS
  DUCT INSULATION - Asbestos Paper
  DUCTS - Asbestos Transite Pipe
PLASTIC HEATER VENT
GALVANIC SCALE & METAL CORROSION
GAS BURNER Flame & Noise Defects
GAS FIRED WATER HEATERS

GAS PIPING, VALVES, CONTROLS
HEAT LOSS
HEATING COST SAVINGS
OIL TANKS
RADIANT HEAT
RADIANT HEAT Floor Mistakes to Avoid
RADIANT HEAT TEMPERATURES
RADIANT SLAB FLOORING CHOICES
RADIANT SLAB TUBING & FLUID CHOICES

RADIATORS
Safety Recalls, Chimneys, Vents, Heaters
  BLUE vs YELLOW COMBUSTION FLAMES
  BLUERAY Recall
  CHIMNEYS & Flues - Asbestos Transite
  Goodman HTPV RECALL
  Heat Recovery Ventilator RECALL
  Lennox Furnace Manuals
  Lennox SAFETY WARNING
  PLASTIC Plexvent / Ultravent RECALL
  Weil McLain RECALL
SAFETY, HEATING INSPECTION
SAFETY,HOME HEATING TIPS

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.
  • Home Reference Book - Carson Dunlop The Home Reference Book - the Encyclopedia of Homes, Carson Dunlop & Associates, Toronto, Ontario, 2010, $69.00 U.S., is available from Carson Dunlop. The Home Reference Book is a bound volume of more than 450 illustrated pages that assist home inspectors and home owners in the inspection and detection of problems on buildings. The text is intended as a reference guide to help building owners operate and maintain their home effectively. InspectAPedia.com ® author/editor Daniel Friedman is a contributing author. Field inspection worksheets are included at the back of the volume.
  • Carbon Monoxide Gas Toxicity, exposure limits, poisoning symptoms, and inspecting buildings for CO hazards
  • DUST CONTAMINATION FROM HVAC? An Investigation of Indoor Dust Debris Blamed on a Heating/Cooling System Reveals Carpet Dust
  • Fuel Oil & Oil Heating Magazine, 3621 Hill Rd., Parsippany, NJ 07054, 973-331-9545
  • Goodman Furnace High Temperature Plastic Vent HTPV safety recall US CPSC notice
  • Home Heating System Should Be Checked [for proper venting and for CO Carbon Monoxide Hazards - DJF]
  • Inspection Procedures for Oil-Fired Heating Systems Detailed step by step approaches for inspecting complex systems]
  • Lennox Pulse Furnace Safety Inspection/Warranty Program: Carbon Monoxide Warning
  • Oil Tanks - The Oil Storage Tank Information Website: Buried or Above Ground Oil Tank Inspection, Testing, Cleanup, Abandonment of Oil Tanks
  • Oil Tanks Above Ground, UL Standards, guidance for home owners, buyers, and inspectors
  • Plastic Heating Vent Pipe & Other Heating Safety Recall Notices
  • Weil McLain Model GV Gas Boiler/gas valve CPSC recall/repair
  • Domestic and Commercial Oil Burners, Charles H. Burkhardt, McGraw Hill Book Company, New York 3rd Ed 1969.
  • National Fuel Gas Code (Z223.1) $16.00 and National Fuel Gas Code Handbook (Z223.2) $47.00 American Gas Association (A.G.A.), 1515 Wilson Boulevard, Arlington, VA 22209 also available from National Fire Protection Association, Batterymarch Park, Quincy, MA 02269. Fundamentals of Gas Appliance Venting and Ventilation, 1985, American Gas Association Laboratories, Engineering Services Department. American Gas Association, 1515 Wilson Boulevard, Arlington, VA 22209. Catalog #XHO585. Reprinted 1989.
  • The Steam Book, 1984, Training and Education Department, Fluid Handling Division, ITT [probably out of print, possibly available from several home inspection supply companies] Fuel Oil and Oil Heat Magazine, October 1990, offers an update,
  • Principles of Steam Heating, $13.25 includes postage. Fuel oil & Oil Heat Magazine, 389 Passaic Ave., Fairfield, NJ 07004.
  • The Lost Art of Steam Heating, Dan Holohan, 516-579-3046 FAX
  • Principles of Steam Heating, Dan Holohan, technical editor of Fuel Oil and Oil Heat magazine, 389 Passaic Ave., Fairfield, NJ 07004 ($12.+1.25 postage/handling).
  • "Residential Steam Heating Systems", Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
  • "Residential Hydronic (circulating hot water) Heating Systems", Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
  • "Warm Air Heating Systems". Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
  • Heating, Ventilating, and Air Conditioning Volume I, Heating Fundamentals,
  • Boilers, Boiler Conversions, James E. Brumbaugh, ISBN 0-672-23389-4 (v. 1) Volume II, Oil, Gas, and Coal Burners, Controls, Ducts, Piping, Valves, James E. Brumbaugh, ISBN 0-672-23390-7 (v. 2) Volume III, Radiant Heating, Water Heaters, Ventilation, Air Conditioning, Heat Pumps, Air Cleaners, James E. Brumbaugh, ISBN 0-672-23383-5 (v. 3) or ISBN 0-672-23380-0 (set) Special Sales Director, Macmillan Publishing Co., 866 Third Ave., New York, NY 10022. Macmillan Publishing Co., NY
  • Installation Guide for Residential Hydronic Heating Systems
  • Installation Guide #200, The Hydronics Institute, 35 Russo Place, Berkeley Heights, NJ 07922
  • The ABC's of Retention Head Oil Burners, National Association of Oil Heat Service Managers, TM 115, National Old Timers' Association of the Energy Industry, PO Box 168, Mineola, NY 11501. (Excellent tips on spotting problems on oil-fired heating equipment. Booklet.)
  • Links to our list of additional information on heating system inspection, repair, maintenance
  • ...