InspectAPedia ®

Building & Environmental Inspection, Testing, Diagnosis, Repair, & Problem Prevention Advice
InspectAPedia
Home
| Air
Conditioning
| Electrical | Indoor
Environment
| Exteriors | Heating | Home
Inspection
| Insulate
Ventilate
| Interiors | Mold
Inspect/Test
| Plumbing
Water
Septic
| Roofing | Structure | Contact Us
Directory of Professionals to Inspect or Test a Building


HEATING SYSTEMS
AIR FILTERS for HVAC SYSTEMS
AIRBOUND HEAT SYSTEM REPAIRS
ANODES & DIP TUBES on WATER HEATERS
ANTI SCALD VALVES
APPLIANCE EFFICIENCY RATINGS
ASBESTOS in BUILDINGS
BACKFLOW PREVENTERS
BAROMETRIC DAMPERS
BLOWER DOORS & AIR INFILTRATION
BLUERAY Recall
BOILERS, HEATING
BOILER LEAKS CORROSION STAINS
BOILER NOISE SMOKE ODORS
BOILER OPERATING PROBLEMS
BOILER OPERATION DETAILS
BOILER PARTS LIST
BOILER PRESSURE SETTINGS
CARBON MONOXIDE/DIOXIDE
CARBON MONOXIDE WARNING
CHIMNEY INSPECTION DIAGNOSIS REPAIR
CHIMNEYS & Flues - Asbestos Transite Pipe
COOL OFF HEAT Thermostat Switch
DRAFT REGULATORS - barometric dampers
DUCT SYSTEMS
DUST FROM HVAC?
ELECTRIC HEAT
ELECTRICAL POWER SWITCH FOR HEAT
ENERGY SAVINGS in BUILDINGS
ENERGY SAVINGS PRIORITIES
ENERGY SAVINGS RETROFIT CASE STUDY
ENERGY SAVINGS RETROFIT LEAK SEALING GUIDE
ENERGY SAVINGS RETROFIT OPTIONS
FAN CONVECTOR HEATERS - HYDRONIC COILS
FLUE VENT CONNECTORS
FREEZE-PROOF A BUILDING
FURNACES, HEATING
FURNACE CONTROLS & SWITCHES
FURNACE OPERATION DETAILS
GAS PIPING, VALVES, CONTROLS
HEAT EXCHANGER LEAKS
HEAT LOSS in BUILDINGS
HEAT LOSS DETECTION TOOLS
HEAT LOSS INDICATORS
HEAT LOSS PREVENTION PRIORITIES
HEAT LOSS R U & K VALUE CALCULATION
HOUSEWRAP AIR & VAPOR BARRIERS
HEATING COST SAVINGS METHODS
HEATING LOSS DIAGNOSIS-BOILERS
HEATING LOSS DIAGNOSIS-FURNACES
HEATING OIL CLOUD WAX GEL POINT
HEATING OIL EXPOSURE HAZARDS, LIMITS
HEATING OIL SLUDGE
HEATING SYSTEM INSPECTION DIAGNOSIS REPAIR
  HEATING INSPECTION CONCEPTS
  HEATING INSPECTION PROCEDURE-GENERAL
DETAILED HEATING SYSTEM INSPECTION PROCEDURE
  PREPARATION for Heating System Inspection
  ATTENTION CONTROL During Heating Inspection
  OUTDOOR INSPECTION of HEATING SYSTEM
  INDOOR INSPECTION of HEATING SYSTEM
  HEATING BOILER INSPECTION GUIDE
    HEATING SYSTEM INSPECTION SEQUENCE
    INSPECT HEATING CONTROLS
    INSPECT FOR HEATING BOILER LEAKS
    HEATING SYSTEM DEFECT SIGNIFICANCE
  ALTERNATE HEATING INSPECTION SEQUENCE
  FUNCTIONAL UNDERSTANDING of HEATERS
  HEATING FURNACE INSPECTION GUIDE
  FINAL BOILER ROOM INSPECTION CHECKS
  >OIL BURNER INSPECTION GUIDE
  OPERATE THE HEATING SYSTEM
  HEATER OPERATING DEFECTS REPORT
  IMPLICATIONS OF HEATING CLUES
  FINAL HEATER INSPECTION REVIEW
  SET HEATING REPAIR PRIORITIES
HIGH EFFICIENCY BOILERS/FURNACES
INSULATION & VENTILATION INSPECTION & IMPROVEMENT
MOTOR OVERLOAD RESET SWITCH
NO HEAT - BOILER / FURNACE DIAGNOSIS
ODORS FROM HEATING SYSTEMS
OIL BURNERS
OIL BURNER INSPECTION GUIDE
OIL BURNER NOISE SMOKE ODORS
OIL BURNER SOOT & PUFFBACKS
OIL FUEL TYPES & CHARACTERISTICS
Oil Odors: Leaky Oil Tank Piping
OIL SAFETY VALVES
OIL TANKS
OIL TANK LEAKS & SMELLS
OIL TANK PIPING DEFECTS
OIL TANK PRESSURE
OIL TANK SLUDGE
OIL TANK TESTING
OIL TANKS, BURIED
PLASTIC HEATER VENT
PULSE COMBUSTION HEATERS
RADIANT HEAT
RADIANT HEAT Floor Mistakes to Avoid
RADIANT SLAB FLOORING CHOICES
RADIANT SLAB TUBING & FLUID CHOICES
RADIATORS
RELIEF VALVES - TP Valves on Boilers
Relief Valves - Water Heaters
SAFETY DURING HEATING INSPECTION
Safety Recalls
  BLUERAY Recall
  CHIMNEYS & Flues - Asbestos Transite
  Goodman HTPV RECALL
  Heat Recovery Ventilator RECALL
  Lennox Furnace Manuals
  Lennox WARNING
  Weil McLain RECALL
SPILL SWITCHES
STACK RELAY SWITCHES
STEAM HEATING SYSTEMS
TANKLESS COILS
THERMAL EXPANSION of MATERIALS
THERMAL MASS in BUILDINGS
THERMAL MASS in UPSTAIRS
THERMAL TRACKING & HEAT LOSS
THERMOSTATS
Transite Pipes, Chimneys & Flues
WINTERIZE A BUILDING

More Information

InspectAPedia.comInspectAPedia ® Home & Site Map
InspectAPedia Blog - News Updates
Air Conditioning & Heat Pumps
Bookstore
Electrical
Environment
Exteriors
Heating
Home Inspection
Insulate Ventilate
Interiors
Mold Inspect/Test
Plumbing Water Septic
Roofing
Structure
Accuracy & Bias Pledge
Contact Us



LARGER VIEW of an octopus furnaceAlternative Inspection Sequences for Heating Systems
InspectAPedia®  -    

How to Inspect Heating Systems - as An Approach to the Forensic Inspection of Any Complex System

Search InspectAPedia
  • Step by Step Guide to inspection of heating boilers & furnaces for operating & safety defects
  • Heating system step by step detailed inspection procedure
  • How to understand & report the significance of findings during a heating system inspection
Our site offers impartial, unbiased advice without conflicts of interest. We will block advertisements which we discover or readers inform us are associated with bad business practices, false-advertising, or junk science. Our contact info is at InspectAPedia.com/appointment.htm.

This document presents alternative sequences & methods inspecting residential heating systems with focus on heating boilers and furnaces, on assuring completeness, accuracy, and on maximum heating system defect detection. The heating system inspection methodology involved is intended to be generalized to the forensic diagnostic inspection of any complex system in order to have the highest probability of detecting important safety or operating defects.

This sounds fancier than intended. Our object is to use an organized procedure for inspecting for defects, without losing the ability to discover unexpected problems as well.

The methodology discussed includes both details specific to heating boilers (the full outline at "Contents") and more general complex-system inspection methods (listed immediately below). © Copyright 2009 Daniel Friedman, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use links at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

© Copyright Daniel Friedman 2008-1993 all rights reserved -- Tri-State ASHI Seminar -- Last update 01/20/2010 - first presentation November 6-7, 1993

Alternative Heating System Operating & Inspection Sequences

Eg: immediate burner on when the thermostat is turned-on from the living area.

Different Heating System Controls, more costly:

  • Air vents at radiators, RADIATORS and Air-bound radiators, baseboards, boilers
  • Pressure switch at boiler, typically set to .2 to .5 psi
  • Lower-pressure relief valve
  • Water feeder, manual or automatic. (Don't mess with either, they may open and be hard to shut off.)
  • Low Water Cutoff on some systems. (Also found on some hydronic boilers.)
  • Different piping on some systems - one-pipe vs two-pipe, easy to identify and very different implications for retrofit/conversion to other heating methods such as hot water.
  • Immediately recognized from the living area by presence of steam valves on radiators. Don't confuse steam valve with air bleeder valves found on hot water radiators.
  • Steam rises--hence no circulator pump - if you see a pump is it a separate HW zone? is it a condensate return pump?

Example of understanding function=understanding implications

A pressure control set to 10 PSI indicates some operating problem with system, addressed by a service person who's trying to "force" steam into the house rather than debugging a problem, probably with piping or steam valves. Service has been by someone unfamiliar with steam systems.

Absence of any sign that the occupants ever drain and clean the automatic water feeder suggests risk of inoperative key safety device. Needs attention even if you see absolutely no problems. Modified piping? improperly sloped radiators?

Furnaces - Hot Air Heating System Inspection

Not examined in this seminar but a few notes: (See FURNACES, HEATING and also FURNACE OPERATION DETAILS)
  • A simpler, operating sequence
  • Different controls-- blower, fan/limit sw.
  • Working Definition: A furnace is a steel or cast iron "box" connected to a series of duct work which runs through the house bringing hot air to grilles (registers). A fan, usually at the furnace, circulates air from cold-air return grilles through duct work to the furnace where the air is heated and then returned through "supply ducts" to the living area.
  • Room cools, thermostat switch closes (calls for heat), oil burner is turned on, oil is pumped from tank to burner, ignited, burned,
  • Hot gases pass through a fire chamber (steel can) and out an exhaust flue, past a barometric damper to a chimney to outdoors.
  • ASHI 9.2.C. The inspector shall open readily open-able access panels provided by the manufacturer or installer for routine homeowner maintenance
  • Understanding functions=understanding implications: eg: wet basement, steel furnace, high CO risks from rusted heat exchanger.

Share this Article      

...

Technical Reviewers & References

Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

HEATING SYSTEM INSPECTION DIAGNOSIS REPAIR
  HEATING INSPECTION CONCEPTS
  HEATING INSPECTION PROCEDURE-GENERAL
DETAILED HEATING SYSTEM INSPECTION PROCEDURE
  PREPARATION for Heating System Inspection
  ATTENTION CONTROL During Heating Inspection
  OUTDOOR INSPECTION of HEATING SYSTEM
  INDOOR INSPECTION of HEATING SYSTEM
  HEATING BOILER INSPECTION GUIDE
    HEATING SYSTEM INSPECTION SEQUENCE
    INSPECT HEATING CONTROLS
    INSPECT FOR HEATING BOILER LEAKS
    HEATING SYSTEM DEFECT SIGNIFICANCE
  ALTERNATE HEATING INSPECTION SEQUENCE
  FUNCTIONAL UNDERSTANDING of HEATERS
  HEATING FURNACE INSPECTION GUIDE
  FINAL BOILER ROOM INSPECTION CHECKS
  >OIL BURNER INSPECTION GUIDE
  OPERATE THE HEATING SYSTEM
  HEATER OPERATING DEFECTS REPORT
  IMPLICATIONS OF HEATING CLUES
  FINAL HEATER INSPECTION REVIEW
  SET HEATING REPAIR PRIORITIES

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building design, inspection, and repair, and about indoor environment testing, diagnosis, and cleanup are at the InspectAPedia Bookstore.
  • ...
HEATING SYSTEMS
HEATING SYSTEM INSPECTION GUIDE

More Information

InspectAPedia.comInspectAPedia ® Home & Site Map
InspectAPedia Blog - News Updates
Air Conditioning & Heat Pumps
Bookstore
Electrical
Environment
Exteriors
Heating
Home Inspection
Insulate Ventilate
Interiors
Mold Inspect/Test
Plumbing Water Septic
Roofing
Structure
Accuracy & Bias Pledge
Contact Us

More Information on Building Diagnostic Inspections and Repairs

  • Carbon Dioxide Gas Toxicity
  • Carbon Monoxide Gas Toxicity, exposure limits, poisoning symptoms, and inspecting buildings for CO hazards
  • Dust from HVAC? An Investigation of Indoor Dust Debris Blamed on a Heating/Cooling System Reveals Carpet Dust
  • Goodman Furnace High Temperature Plastic Vent HTPV safety recall US CPSC notice
  • Home Heating System Should Be Checked [for proper venting and for CO Carbon Monoxide Hazards - DJF]
  • Inspection Procedures for Oil-Fired Heating Systems Detailed step by step approaches for inspecting complex systems]
  • Lennox Pulse Furnace Safety Inspection/Warranty Program: Carbon Monoxide Warning
  • Oil Tanks - The Oil Storage Tank Information Website: Buried or Above Ground Oil Tank Inspection, Testing, Cleanup, Abandonment of Oil Tanks
  • Oil Tanks Above Ground, UL Standards, guidance for home owners, buyers, and inspectors
  • Plastic Heating Vent Pipe & Other Heating Safety Recall Notices
  • Weil McLain Model GV Gas Boiler/gas valve CPSC recall/repair
  • Domestic and Commercial Oil Burners, Charles H. Burkhardt, McGraw Hill Book Company, New York 3rd Ed 1969.
  • National Fuel Gas Code (Z223.1) $16.00 and National Fuel Gas Code Handbook (Z223.2) $47.00 American Gas Association (A.G.A.), 1515 Wilson Boulevard, Arlington, VA 22209 also available from National Fire Protection Association, Batterymarch Park, Quincy, MA 02269. Fundamentals of Gas Appliance Venting and Ventilation, 1985, American Gas Association Laboratories, Engineering Services Department. American Gas Association, 1515 Wilson Boulevard, Arlington, VA 22209. Catalog #XHO585. Reprinted 1989.
  • The Steam Book, 1984, Training and Education Department, Fluid Handling Division, ITT [probably out of print, possibly available from several home inspection supply companies] Fuel Oil and Oil Heat Magazine, October 1990, offers an update,
  • Principles of Steam Heating, $13.25 includes postage. Fuel oil & Oil Heat Magazine, 389 Passaic Ave., Fairfield, NJ 07004.
  • The Lost Art of Steam Heating, Dan Holohan, 516-579-3046 FAX
  • Principles of Steam Heating, Dan Holohan, technical editor of Fuel Oil and Oil Heat magazine, 389 Passaic Ave., Fairfield, NJ 07004 ($12.+1.25 postage/handling).
  • "Residential Steam Heating Systems", Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel,
  • CT 06801 800/227-1663 [home inspection training material] 1987 "Residential Hydronic (circulating hot water) Heating Systems", Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987 "Warm Air Heating Systems". Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987 Heating, Ventilating, and Air Conditioning Volume I, Heating Fundamentals, Boilers, Boiler Conversions, James E. Brumbaugh, ISBN 0-672-23389-4 (v. 1) Volume II, Oil, Gas, and Coal Burners, Controls, Ducts, Piping, Valves, James E. Brumbaugh, ISBN 0-672-23390-7 (v. 2) Volume III, Radiant Heating, Water Heaters, Ventilation, Air Conditioning, Heat Pumps, Air Cleaners, James E. Brumbaugh, ISBN 0-672-23383-5 (v. 3) or ISBN 0-672-23380-0 (set) Special Sales Director, Macmillan Publishing Co., 866 Third Ave., New York, NY 10022. Macmillan Publishing Co., NY
  • Installation Guide for Residential Hydronic Heating Systems and
  • Installation Guide #200, The Hydronics Institute, 35 Russo Place, Berkeley Heights, NJ 07922 The ABC's of Retention Head Oil Burners, National Association of Oil Heat Service Managers, TM 115, National Old Timers' Association of the Energy Industry, PO Box 168, Mineola, NY 11501. (Excellent tips on spotting problems on oil-fired heating equipment. Booklet.)
InspectAPedia.comInspectAPedia® Home & Site Map - Building & Environmental Inspection, Testing, Diagnosis, Repair, & Problem Prevention Advice: In-depth research & advice on diagnosing, testing, correcting, & preventing building defects & indoor environmental hazards. Unbiased information, no conflicts of interest.
GO TO the MOLD and INDOOR ENVIRONMENT INFORMATION CENTER for in-depth advice on avoiding testing for or cleaning up mold and other indoor environmental hazards, odors, gases, contaminants
The Mold Information Center:
What to Do About Mold in Buildings, When and How to Inspect for Mold, Clean Up Mold, or Avoid Mold Problems
GO TO MOLD TEST KITS: This expert-recommended mold test kit is cheap and yet top performing *IF* you use a competent analysis laboratory!
Use this simple, economical mold test kit
by following our instructions on how to collect and mail mold samples to our lab
GO TO IAQ/MOLD-TEST LAB SERVICES: Mold, Pollen, indoor air quality, field and laboratory services by an expert.Environmental Inspection, Testing, & Diagnosis On-Site IAQ, Gas, Air Testing, Mold Investigation, Sick Building Diagnosis, Lab Services, & Remediation Plan Preparation - indoor air quality testing, problem source determination, supporting lab work, written remediation plan addressing removal of environmental and other hazards and prevention of their recurrence.
GO TO our PRE PURCHASE BUILDING INSPECTION SERVICES: Authoritative information for home buyers and home owners is included with your inspection.
Building Inspection, Problem Diagnosis
, Forensic Investigation & Testing, Repair Consulting

CONTACT Daniel Friedman - Dan is a senior ASHI home inspector, nationally recognized expert on building inspection, building failures, and sick building investigation
Contact Daniel Friedman for website content suggestions or for fee-paid consulting

01/20/2010 - 09/05/2006 - InspectAPedia.com/heat/Heat_Inspection_Details4.htm - © 2010 - 1988 Copyright Daniel Friedman All Rights Reserved - InspectAPedia® is a Registered U.S. Trademark