InspectAPedia ®

Building & Environmental Inspection, Testing, Diagnosis, Repair, & Problem Prevention Advice
InspectAPedia
Home
| Air
Conditioning
| Electrical | Indoor
Environment
| Exteriors | Heating | Home
Inspection
| Insulate
Ventilate
| Interiors | Mold
Inspect/Test
| Plumbing
Water
Septic
| Roofing | Structure | Contact Us
Directory of Professionals to Inspect or Test a Building


HEATING SYSTEMS
AIR FILTERS for HVAC SYSTEMS
AIRBOUND HEAT SYSTEM REPAIRS
ANODES & DIP TUBES on WATER HEATERS
ANTI SCALD VALVES
BACKFLOW PREVENTERS
BAROMETRIC DAMPERS
BLOWER DOORS & AIR INFILTRATION
BLUERAY Recall
BOILERS, HEATING
BOILER LEAKS CORROSION STAINS
BOILER NOISE SMOKE ODORS
BOILER OPERATING PROBLEMS
BOILER OPERATION DETAILS
BOILER PARTS LIST
BOILER PRESSURE SETTINGS
CARBON MONOXIDE/DIOXIDE
CARBON MONOXIDE WARNING
CHIMNEY INSPECTION DIAGNOSIS REPAIR
CHIMNEYS & Flues - Asbestos Transite Pipe
COOL OFF HEAT Thermostat Switch
DRAFT REGULATORS - barometric dampers
DUCT SYSTEMS
DUST FROM HVAC?
ELECTRIC HEAT
ELECTRICAL POWER SWITCH FOR HEAT
ENERGY SAVINGS in BUILDINGS
ENERGY SAVINGS PRIORITIES
ENERGY SAVINGS RETROFIT CASE STUDY
ENERGY SAVINGS RETROFIT LEAK SEALING GUIDE
ENERGY SAVINGS RETROFIT OPTIONS
FLUE VENT CONNECTORS
FREEZE-PROOF A BUILDING
FURNACES, HEATING
FURNACE CONTROLS & SWITCHES
FURNACE OPERATION DETAILS
GAS PIPING, VALVES, CONTROLS
HEAT EXCHANGER LEAKS
HEAT LOSS in BUILDINGS
HEAT LOSS DETECTION TOOLS
HEAT LOSS INDICATORS
HEAT LOSS R U & K VALUE CALCULATION
HOUSEWRAP AIR & VAPOR BARRIERS
HEATING COST SAVINGS METHODS
HEATING LOSS DIAGNOSIS-BOILERS
HEATING LOSS DIAGNOSIS-FURNACES
HEATING OIL CLOUD WAX GEL POINT
HEATING OIL EXPOSURE HAZARDS, LIMITS
HEATING OIL SLUDGE
HEATING SYSTEM INSPECTION DIAGNOSIS REPAIR
  HEATING INSPECTION CONCEPTS
  HEATING INSPECTION PROCEDURE-GENERAL
DETAILED HEATING SYSTEM INSPECTION PROCEDURE
  PREPARATION for Heating System Inspection
  ATTENTION CONTROL During Heating Inspection
  OUTDOOR INSPECTION of HEATING SYSTEM
  INDOOR INSPECTION of HEATING SYSTEM
  HEATING BOILER INSPECTION GUIDE
    HEATING SYSTEM INSPECTION SEQUENCE
    INSPECT HEATING CONTROLS
    INSPECT FOR HEATING BOILER LEAKS
    HEATING SYSTEM DEFECT SIGNIFICANCE
  ALTERNATE HEATING INSPECTION SEQUENCE
  FUNCTIONAL UNDERSTANDING of HEATERS
  HEATING FURNACE INSPECTION GUIDE
  FINAL BOILER ROOM INSPECTION CHECKS
  >OIL BURNER INSPECTION GUIDE
  OPERATE THE HEATING SYSTEM
  HEATER OPERATING DEFECTS REPORT
  IMPLICATIONS OF HEATING CLUES
  FINAL HEATER INSPECTION REVIEW
  SET HEATING REPAIR PRIORITIES
HIGH EFFICIENCY BOILERS/FURNACES
INSULATION & VENTILATION INSPECTION & IMPROVEMENT
MOTOR OVERLOAD RESET SWITCH
NO HEAT - BOILER / FURNACE DIAGNOSIS
ODORS FROM HEATING SYSTEMS
OIL BURNERS
OIL BURNER INSPECTION GUIDE
OIL BURNER NOISE SMOKE ODORS
OIL BURNER SOOT & PUFFBACKS
OIL FUEL TYPES & CHARACTERISTICS
Oil Odors: Leaky Oil Tank Piping
OIL SAFETY VALVES
OIL TANKS
OIL TANK LEAKS & SMELLS
OIL TANK PIPING DEFECTS
OIL TANK PRESSURE
OIL TANK SLUDGE
OIL TANK TESTING
OIL TANKS, BURIED
PLASTIC HEATER VENT
PULSE COMBUSTION HEATERS
RADIANT HEAT
RADIANT HEAT Floor Mistakes to Avoid
RADIANT SLAB FLOORING CHOICES
RADIANT SLAB TUBING & FLUID CHOICES
RADIATORS
RELIEF VALVES - TP Valves on Boilers
Relief Valves - Water Heaters
SAFETY DURING HEATING INSPECTION
Safety Recalls
  BLUERAY Recall
  CHIMNEYS & Flues - Asbestos Transite
  Goodman HTPV RECALL
  Heat Recovery Ventilator RECALL
  Lennox Furnace Manuals
  Lennox WARNING
  Weil McLain RECALL
SPILL SWITCHES
STACK RELAY SWITCHES
STEAM HEATING SYSTEMS
TANKLESS COILS
THERMAL EXPANSION of MATERIALS
THERMAL MASS in BUILDINGS
THERMAL MASS in UPSTAIRS
THERMAL TRACKING & HEAT LOSS
THERMOSTATS
Transite Pipes, Chimneys & Flues
WINTERIZE A BUILDING

More Information

InspectAPedia.comInspectAPedia ® Home & Site Map
InspectAPedia Blog - News Updates
Air Conditioning & Heat Pumps
Bookstore
Electrical
Environment
Exteriors
Heating
Home Inspection
Insulate Ventilate
Interiors
Mold Inspect/Test
Plumbing Water Septic
Roofing
Structure
Accuracy & Bias Pledge
Contact Us



LARGER VIEW of an octopus furnaceDetailed Procedures for Inspecting Heating Systems
InspectAPedia®  -    

How to Inspect Heating Systems - as An Approach to the Forensic Inspection of Any Complex System

  • Final Actions in the Step by Step Guide to inspection of heating boilers & furnaces for operating & safety defects
  • Heating system step by step detailed inspection procedure
  • How to understand & report the significance of findings during a heating system inspection
Our site offers impartial, unbiased advice without conflicts of interest. We will block advertisements which we discover or readers inform us are associated with bad business practices, false-advertising, or junk science. Our contact info is at InspectAPedia.com/appointment.htm.

This document presents the final inspection steps and operating suggestions when inspecting residential heating systems . The heating system inspection methodology involved is intended to be generalized to the forensic diagnostic inspection of any complex system in order to have the highest probability of detecting important safety or operating defects.

This sounds fancier than intended. Our object is to use an organized procedure for inspecting for defects, without losing the ability to discover unexpected problems as well.

The methodology discussed includes both details specific to heating boilers (the full outline at "Contents") and more general complex-system inspection methods (listed immediately below). © Copyright 2009 Daniel Friedman, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use links at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

© Copyright Daniel Friedman 2008-1993 all rights reserved -- Tri-State ASHI Seminar -- Last update 05/25/2009 - first presentation November 6-7, 1993

Final heating system inspection checks in the boiler room:

Operate the Heating Equipment

After all visual inspection. Avoids running dangerous systems, permits explanation to client without background noise. Permits observations of operation anomalies. ASHI 9.2.B. The inspector shall operate the system using normal operating controls such as using the thermostat - see BOILER OPERATING PROBLEMS

Heating System Operating Defects

  • Noises, smoke, soot, back pressure at inspection port (watch out for burns and fires if this port is opened), sloppy startup, rumbling, sloppy or delayed shutdown-flame lingers (very dangerous).
  • Feeling piping (hot!) can indicate if circulator is running--quick change in temperature vs convection.
  • Some leaks occur only at peak operating temperature--eg at relief valve.
  • Startup problems: noises, puff back, flapping barometric damper, vibrations
  • Particularly in cold weather, if the system was on and running, observe and note that it was running normally when you last touched it. Witnessed. (Frost damage issues lurk here.)

Heating Equipment Malfunction & Implications

What are the Implications of the Clues of Heating System Defects that You Observed?

  • Leaks are never acceptable, anywhere. Leaking relief valves need immediate attention and repair (Leaking relief valve could be due to water-logged expansion tank, improper control settings (temperature too high), improper automatic water feeder operation (pressure too high), or defective valve (leaky). True, you only have to report the valve. Did you miss problems at the other components?) Corroded relief valves also need test and repair/replacement
  • Relief Valves: Do not touch the heating boiler or water heater temperature or pressure relief valve - it may open and fail to shut down.
  • Corrosion on heating system parts: Do not pick at corrosion as you may start a catastrophic, un-stoppable leak requiring total system shut-down.
  • Tankless coils for making hot water: If there is different water pressure/flow observed in the kitchen in which the hot water pressure is significantly less than cold, even before examining the building's mechanical systems you may speculate that a tankless coil installed may be installed. What other clues suggest that the local water supply may be hard in minerals and that there may be a risk of clogged piping?

    When the water supply is high in minerals, the hot water pipes or tankless coils clog up before cold water piping. Is a water softener installed? Is there known "hard" water--have mineral deposits clogged the coil? Are there "cleanout" plumbing fittings on the tankless coil piping? Does this suggest a history of clogging and acid-flush treatments? Can a clogged coil be repaired or replaced? How severe was that rust you observed at the tankless coil mounting plate?

Remember that even a subtle clue like drips at the bottom of a relief valve discharge tube can have profound implications for the condition of the heating system. Clues make more sense when you understand how the equipment works, its operating cycle, and the function of each component.

See BOILER OPERATING PROBLEMS for an extensive list of heating system clues and what they mean for the safety, adequacy, or reliability of the heating system.

Thought Sequences for Final Heating System Check

  • Hot heating water movement from house supply into boiler, through circulating equipment.
  • Fuel movement from tank through burner up flue and chimney.
  • Air movement into house and to burner and up flue and chimney.
  • Air movement inside duct work (for furnaces)
  • Complete operation sequence reviewed?
  • Other building conditions observed which raise questions?
    wet basement, poor housekeeping, poor maintenance, extensive building additions may stretch boiler capacity, ...
  • What's missing ?
  • Did we leave the system operating normally?

Heating Inspections: Safety Concerns for the Home Inspector

This section contains examples of steps to protect the inspector. It does not address safety concerns for the client/occupant.ASHI 9.3.A. The inspector is not required to operate equipment when weather conditions or other circumstances may cause equipment damage [or in the opinion of the inspector, may cause any sort of unsafe condition (added by DJF, NOT ASHI Standards)
  • Do not turn on equipment which has been "shut down" - Possible open piping, unsafe wiring, leaks, unsafe chimney, fire risks.
  • Do not turn on equipment which has been switched off without explicit permission/instruction from a responsible party
  • Examine gauges (not entirely reliable) for unusual pressure or temperature conditions and do not permit such equipment to continue to operate
  • Do not operate equipment which does not appear to be vented properly; shut down equipment if, on operating it, you observe an apparently blocked flue
  • Do not operate equipment if the chimney is suspect--e.g. old single wythe unlined brick with visible damage in the attic or outside
  • Watch for flashback at inspection ports
  • Watch for electric shock at controls
  • Do not pick at corrosion
  • Do not test relief valve levers nor catch your sleeve on one
    ASHI 9.3.B. The inspector is not required to operate automatic safety controls
  • Do not light fires in coal or wood stoves to check draft, etc
    ASHI 9.3.C. The inspector is not required to ignite or extinguish solid fuel fires
  • Do not disassemble flue vent piping - risks of filth, unable to reassemble, etc.
    ASHI 9.3.D.1 The inspector is not required to observe the interior of flues [However often you can detect a blocked flue by looking through the barometric damper or by use of a mirror at the chimney cleanout. We recommend this step. -DJF]
    ASHI 9.3.D.2 The inspector is not required to observe fireplace insert flue connections [Normally not visible. Caution: there is frequently a hidden problem there.]
  • Be careful about disconnecting humidifiers to obtain access to furnace plenums: you may cut yourself on sheet metal, cause leaks in humidifier piping, cause spills.
    ASHI 9.3.D.3 The inspector is not required to observe humidifiers
  • But watch for humidifiers which leaked into and damaged duct work or onto and damaged a heat exchanger.
  • Avoid electric shock from the static charge at electronic air filters.
    ASHI 9.3.D.4 The inspector is not required to observe electronic air filters

Share this Article      

...

Technical Reviewers & References

  • Daniel Friedman - principal author/editor of the InspectAPedia® Website
  • InspectAPedia Bookstore lists recommended books, organized by topic & available for purchase. Most of our articles also include a list of recommended books for the specific article topic as well as other references, and information sources.
  • Critique, contributions wanted: Contact Us to suggest corrections or additions to articles at this website, and if you wish, to receive online listing and credit as a contributor. Particular thanks are due to the many experts and also consumers who read and critique technical articles at InspectAPedia.com.
  • Additional technical contributors & reference sources for this article are listed below.

Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

HEATING SYSTEM INSPECTION DIAGNOSIS REPAIR
  HEATING INSPECTION CONCEPTS
  HEATING INSPECTION PROCEDURE-GENERAL
DETAILED HEATING SYSTEM INSPECTION PROCEDURE
  PREPARATION for Heating System Inspection
  ATTENTION CONTROL During Heating Inspection
  OUTDOOR INSPECTION of HEATING SYSTEM
  INDOOR INSPECTION of HEATING SYSTEM
  HEATING BOILER INSPECTION GUIDE
    HEATING SYSTEM INSPECTION SEQUENCE
    INSPECT HEATING CONTROLS
    INSPECT FOR HEATING BOILER LEAKS
    HEATING SYSTEM DEFECT SIGNIFICANCE
  ALTERNATE HEATING INSPECTION SEQUENCE
  FUNCTIONAL UNDERSTANDING of HEATERS
  HEATING FURNACE INSPECTION GUIDE
  FINAL BOILER ROOM INSPECTION CHECKS
  >OIL BURNER INSPECTION GUIDE
  OPERATE THE HEATING SYSTEM
  HEATER OPERATING DEFECTS REPORT
  IMPLICATIONS OF HEATING CLUES
  FINAL HEATER INSPECTION REVIEW
  SET HEATING REPAIR PRIORITIES

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building design, inspection, and repair, and about indoor environment testing, diagnosis, and cleanup are at the InspectAPedia Bookstore.
  • ...
HEATING SYSTEMS
HEATING SYSTEM INSPECTION GUIDE

More Information

InspectAPedia.comInspectAPedia ® Home & Site Map
InspectAPedia Blog - News Updates
Air Conditioning & Heat Pumps
Bookstore
Electrical
Environment
Exteriors
Heating
Home Inspection
Insulate Ventilate
Interiors
Mold Inspect/Test
Plumbing Water Septic
Roofing
Structure
Accuracy & Bias Pledge
Contact Us

More Information on Building Diagnostic Inspections and Repairs

  • Carbon Dioxide Gas Toxicity
  • Carbon Monoxide Gas Toxicity, exposure limits, poisoning symptoms, and inspecting buildings for CO hazards
  • Dust from HVAC? An Investigation of Indoor Dust Debris Blamed on a Heating/Cooling System Reveals Carpet Dust
  • Goodman Furnace High Temperature Plastic Vent HTPV safety recall US CPSC notice
  • Home Heating System Should Be Checked [for proper venting and for CO Carbon Monoxide Hazards - DJF]
  • Inspection Procedures for Oil-Fired Heating Systems Detailed step by step approaches for inspecting complex systems]
  • Lennox Pulse Furnace Safety Inspection/Warranty Program: Carbon Monoxide Warning
  • Oil Tanks - The Oil Storage Tank Information Website: Buried or Above Ground Oil Tank Inspection, Testing, Cleanup, Abandonment of Oil Tanks
  • Oil Tanks Above Ground, UL Standards, guidance for home owners, buyers, and inspectors
  • Plastic Heating Vent Pipe & Other Heating Safety Recall Notices
  • Weil McLain Model GV Gas Boiler/gas valve CPSC recall/repair
  • Domestic and Commercial Oil Burners, Charles H. Burkhardt, McGraw Hill Book Company, New York 3rd Ed 1969.
  • National Fuel Gas Code (Z223.1) $16.00 and National Fuel Gas Code Handbook (Z223.2) $47.00 American Gas Association (A.G.A.), 1515 Wilson Boulevard, Arlington, VA 22209 also available from National Fire Protection Association, Batterymarch Park, Quincy, MA 02269. Fundamentals of Gas Appliance Venting and Ventilation, 1985, American Gas Association Laboratories, Engineering Services Department. American Gas Association, 1515 Wilson Boulevard, Arlington, VA 22209. Catalog #XHO585. Reprinted 1989.
  • The Steam Book, 1984, Training and Education Department, Fluid Handling Division, ITT [probably out of print, possibly available from several home inspection supply companies] Fuel Oil and Oil Heat Magazine, October 1990, offers an update,
  • Principles of Steam Heating, $13.25 includes postage. Fuel oil & Oil Heat Magazine, 389 Passaic Ave., Fairfield, NJ 07004.
  • The Lost Art of Steam Heating, Dan Holohan, 516-579-3046 FAX
  • Principles of Steam Heating, Dan Holohan, technical editor of Fuel Oil and Oil Heat magazine, 389 Passaic Ave., Fairfield, NJ 07004 ($12.+1.25 postage/handling).
  • "Residential Steam Heating Systems", Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel,
  • CT 06801 800/227-1663 [home inspection training material] 1987 "Residential Hydronic (circulating hot water) Heating Systems", Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987 "Warm Air Heating Systems". Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987 Heating, Ventilating, and Air Conditioning Volume I, Heating Fundamentals, Boilers, Boiler Conversions, James E. Brumbaugh, ISBN 0-672-23389-4 (v. 1) Volume II, Oil, Gas, and Coal Burners, Controls, Ducts, Piping, Valves, James E. Brumbaugh, ISBN 0-672-23390-7 (v. 2) Volume III, Radiant Heating, Water Heaters, Ventilation, Air Conditioning, Heat Pumps, Air Cleaners, James E. Brumbaugh, ISBN 0-672-23383-5 (v. 3) or ISBN 0-672-23380-0 (set) Special Sales Director, Macmillan Publishing Co., 866 Third Ave., New York, NY 10022. Macmillan Publishing Co., NY
  • Installation Guide for Residential Hydronic Heating Systems and
  • Installation Guide #200, The Hydronics Institute, 35 Russo Place, Berkeley Heights, NJ 07922 The ABC's of Retention Head Oil Burners, National Association of Oil Heat Service Managers, TM 115, National Old Timers' Association of the Energy Industry, PO Box 168, Mineola, NY 11501. (Excellent tips on spotting problems on oil-fired heating equipment. Booklet.)
InspectAPedia.comInspectAPedia® Home & Site Map - Building & Environmental Inspection, Testing, Diagnosis, Repair, & Problem Prevention Advice: In-depth research & advice on diagnosing, testing, correcting, & preventing building defects & indoor environmental hazards. Unbiased information, no conflicts of interest.
GO TO the MOLD and INDOOR ENVIRONMENT INFORMATION CENTER for in-depth advice on avoiding testing for or cleaning up mold and other indoor environmental hazards, odors, gases, contaminants
The Mold Information Center:
What to Do About Mold in Buildings, When and How to Inspect for Mold, Clean Up Mold, or Avoid Mold Problems
GO TO MOLD TEST KITS: This expert-recommended mold test kit is cheap and yet top performing *IF* you use a competent analysis laboratory!
Use this simple, economical mold test kit
by following our instructions on how to collect and mail mold samples to our lab
GO TO IAQ/MOLD-TEST LAB SERVICES: Mold, Pollen, indoor air quality, field and laboratory services by an expert.Environmental Inspection, Testing, & Diagnosis On-Site IAQ, Gas, Air Testing, Mold Investigation, Sick Building Diagnosis, Lab Services, & Remediation Plan Preparation - indoor air quality testing, problem source determination, supporting lab work, written remediation plan addressing removal of environmental and other hazards and prevention of their recurrence.
GO TO our PRE PURCHASE BUILDING INSPECTION SERVICES: Authoritative information for home buyers and home owners is included with your inspection.
Building Inspection, Problem Diagnosis
, Forensic Investigation & Testing, Repair Consulting

CONTACT Daniel Friedman - Dan is a senior ASHI home inspector, nationally recognized expert on building inspection, building failures, and sick building investigation
Contact Daniel Friedman for website content suggestions or for fee-paid consulting

05/25/2009 - 09/05/2006 - InspectAPedia.com/heat/Heat_Inspection_Details5.htm - © 2009 - 1988 Copyright Daniel Friedman All Rights Reserved - InspectAPedia® is a Registered U.S. Trademark