InspectAPedia.com InspectAPedia®
Google
InspectAPedia
 

Free Encyclopedia of Building & Environmental Inspection, Testing, Diagnosis, Repair

Ask a Question or Search InspectAPedia

  • HOME
  • AIR CONDITIONING
  • DAMAGE ASSESSMENT
  • ELECTRICAL
  • EXTERIORS
  • HEATING
  • HOME INSPECTION
  • INTERIORS
  • PLUMBING
  • ROOFING
  • SEPTIC SYSTEMS
  • STRUCTURE
  • WATER SUPPLY
  • ENERGY SAVINGS
  • ENVIRONMENT
  • INDOOR AIR IAQ
  • INSULATION
  • MOLD INSPECT TEST REMOVE
  • NOISE
  • ODORS
  • SOLAR ENERGY
  • VENTILATION
  • EXPERTS DIRECTORY
  • CONTACT US



InspectAPedia ® Home

HEATING SYSTEMS

AGE of AIR CONDITIONERS & HEAT PUMPS
AGE of HEATERS, BOILERS, FURNACES
AGE of WATER HEATERS
AIR CONDITIONING & HEAT PUMP SYSTEMS
AIR FILTERS for HVAC SYSTEMS
ANODES & DIP TUBES on WATER HEATERS
AIR HANDLER / BLOWER UNITS
AIRBOUND HEAT SYSTEM REPAIRS
ANODES & DIP TUBES on WATER HEATERS
ANTIFREEZE for BOILERS
ANTI SCALD VALVES
ANIMAL ALLERGENS / PET DANDER
ANIMAL ENTRY POINTS in buildings
ANIMAL ODORS IN buildings
APPLIANCE EFFICIENCY RATINGS
ASBESTOS IDENTIFICATION IN buildings

BACKDRAFTING HEATING EQUIPMENT
BACKFLOW PREVENTER VALVE, HEATING SYS
BACKFLOW PREVENTER, HEATER WATER FEEDER
BACKUP HEAT for HEAT PUMPS
BANGING HEATING PIPES RADIATORS
BAROMETRIC DAMPERS
BIOGAS PRODUCTION & USE
BLEVE EXPLOSIONS
BLOWER DOORS & AIR INFILTRATION
BLOWER FAN CONTINUOUS OPERATION
BLOWER FAN OPERATION & TESTING
BLUE vs YELLOW COMBUSTION FLAMES
BLUERAY Recall
BOILERS, HEATING
BOILER CONTROLS & SWITCHES
BOILER LEAKS CORROSION STAINS
BOILER LEAKS, HOW TO LOCATE
BOILER NOISE SMOKE ODORS
BOILER OPERATING PROBLEMS
BOILER OPERATION DETAILS
BOILER PRESSURE & TEMPERATURE SETTINGS
BOOKSTORE - InspectAPedia
BTU USAGE MONITORS
BUILDING SAFETY HAZARDS GUIDE

CAPACITORS for HARD STARTING MOTORS
CARBON DIOXIDE - CO2
CARBON MONOXIDE - CO
CARBON MONOXIDE WARNING
CHIMNEY INSPECTION DIAGNOSIS REPAIR
CHIMNEYS & Flues - Asbestos Transite Pipe
CHINESE DRYWALL HAZARDS
CIRCULATOR PUMPS & RELAYS
COOL OFF HEAT, Thermostat Switch
COMBUSTION AIR
COMBUSTION AIR for TIGHT buildings
COMBUSTION GASES & PARTICLE HAZARDS
COMBUSTION PRODUCTS & IAQ
COMPLETE COMBUSTION, Stoichiometric
CONDENSING BOILERS/FURNACES
CONDENSING BOILERS/FURNACES DAMAGE
CONVECTOR HEATERS - HYDRONIC COILS
CREOSOTE FIRE HAZARDS
Curved Brick Chimneys - Sulphation

DEFINITION of Heating & Cooling Terms
DIAGNOSE & FIX AIR CONDITIONER / HEAT PUMP
DIAGNOSE & FIX HEATING PROBLEMS-BOILER
DIAGNOSE & FIX HEATING PROBLEMS-FURNACE
DIRECT VENTS / SIDE WALL VENTS
DIRECTORY of OIL TANK EXPERTS
DRAFT HOODS - gas fired
DRAFT MEASUREMENT, CHIMNEYS & FLUES
DRAFT REGULATORS, DAMPERS, BOOSTERS
DUCT SYSTEM & DUCT DEFECTS
DUST, HVAC CONTAMINATION STUDY
DUST SAMPLING PROCEDURE

ELECTRIC HEAT, DIAGNOSIS, REPAIR
ELECTRIC MOTOR DIAGNOSTIC GUIDE
ELECTRIC MOTOR OVERLOAD RESET SWITCH
ELECTRICAL POWER SWITCH FOR HEAT
EVAPORATIVE COOLING SYSTEMS

FAN, AIR HANDLER BLOWER UNIT
FAN AUTO ON Thermostat Switch
FAN, COMPRESSOR/CONDENSER UNIT
FAN CONVECTOR HEATERS - HYDRONIC COILS
FAN LIMIT SWITCH
FAN NOISES
FILTERS, AIR for HVAC SYSTEMS
FILTERS, OIL on HEATING EQUIPMENT
FIRE SAFETY CONTROLS
FIREPLACES & HEARTHS
FLAME COLOR, BLUE vs YELLOW COMBUSTION
FLOODED HEATING EQUIPMENT REPAIR
FLUE SIZE SPECIFICATIONS
FLUE VENT CONNECTORS
FREEZE-PROOF A BUILDING
FUEL OIL TYPES & CHARACTERISTICS
FUEL UNIT, HEATING OIL PUMPS
FURNACES, HEATING
FURNACE CONTROLS & SWITCHES
FURNACE HEAT EXCHANGER LEAKS
FURNACE OPERATION DETAILS
FURNACE OPERATING TEMPERATURES

GALVANIC SCALE & METAL CORROSION
GAS BURNER Flame & Noise Defects
GAS FIRED WATER HEATERS
GAS PIPING, VALVES, CONTROLS
GAUGES ON HEATING EQUIPMENT
GEOTHERMAL HEATING SYSTEMS

HEAT EXCHANGER LEAK TEST
HEAT LOSS in BUILDINGS
HEAT LOSS DETECTION TOOLS
HEAT LOSS INDICATORS
HEAT LOSS PREVENTION PRIORITIES
HEATING COST FUEL & BTU Cost Table
HEATING COST SAVINGS
HEATING LOSS DIAGNOSIS-BOILERS
HEATING LOSS DIAGNOSIS-FURNACES
HEATING OIL CLOUD WAX GEL POINT
HEATING OIL EXPOSURE HAZARDS, LIMITS
HEATING OIL - OLD, USEABLE?
HEATING OIL PIPING TROUBLES
HEATING OIL SHELF LIFE
HEATING OIL SLUDGE
HEATING OIL USAGE RATE
HEATING SYSTEM INSPECT DIAGNOSE REPAIR
HOT WATER HEATERS
HOT WATER IMPROVEMENT

INSULATION INSPECTION & IMPROVEMENT

LOW VOLTAGE BUILDING WIRING
LOW VOLTAGE TRANSFORMER TEST
LP & Natural Gas Safety Hazards

MANUALS & PARTS GUIDES - HVAC
MIXING / ANTI-SCALD VALVES
MOTOR OVERLOAD RESET SWITCH

Natural Gas Combustion
NO HEAT - BOILER
NO HEAT - FURNACE
NOISE / SOUND DIAGNOSIS & CURE
NOISE AIR CONDITIONER / HEAT PUMP
NOISE, DUCT VIBRATION DAMPENERS
NOISE, HEATING SYSTEMS
NOISE, PLUMBING
NOISE, WATER HEATER

ODORS & SMELLS DIAGNOSIS & CURE
ODORS FROM HEATING SYSTEMS
OIL BURNERS
OIL BURNER FUEL UNIT
OIL BURNER INSPECTION & REPAIR
OIL BURNER NOISE SMOKE ODORS
OIL BURNER NOZZLE & ELECTRODES
OIL BURNERS, RETENTION HEAD
OIL BURNER SOOT & PUFFBACKS
OIL FILTERS on HEATING EQUIPMENT
OIL FILTER MISSING
OIL FUEL TYPES & CHARACTERISTICS
OIL HEAT FIRE SAFETY CONTROLS
OIL LINE CLOGGING FIX
OIL LINE QUICK STOP VALVES
OIL LINE SAFETY VALVES
OIL ODORS, LEAKY OIL TANK PIPING
OIL PUMP FUEL UNIT
OIL SPILL CLEANUP / PREVENTION
OIL TANKS

PLASTIC HEATER VENT
PULSE COMBUSTION HEATERS
PASCAL CALCULATIONS
PRESSURE REDUCING VALVES
PRESSURE REGULATOR, WATER
PUFFBACKS, OIL BURNER
PUMPS, PONY PUMPS

RADIANT BARRIERS
RADIANT HEAT
RADIANT HEAT Floor Mistakes to Avoid
RADIANT HEAT TEMPERATURES
RADIANT SLAB FLOORING CHOICES
RADIANT SLAB TUBING & FLUID CHOICES
RADIATORS
REFRIGERANTS & PIPING
RELIEF VALVE LEAKS
RELIEF VALVES - TP Valves on Boilers
RELIEF VALVES - STEAM TP VALVES
RELIEF VALVES - Water Heaters
RELIEF VALVES - Water Tanks
Reset Switch - Heater Primary Control
Reset Switch Broken - Quick Repair
RESET SWITCH - ELECTRIC MOTOR
Reset Switch - Stack Relays

SAFETY HAZARDS & INSPECTIONS
SAFETY HAZARDS GUIDE
SAFETY, HEATING INSPECTION
SAFETY RECALLS, Chimneys, Vents, Heaters
SOOT on OIL FIRED HEATING EQUIPMENT
SPILL SWITCHES - Flue Gas Detection
SPLIT SYSTEM AIR CONDITIONERS & HEAT PUMPS
STACK RELAY SWITCHES
STAIN DIAGNOSIS on BUILDING INTERIORS
STEAM HEATING SYSTEMS

TANKLESS COILS
Thermal Expansion Cracking of Brick
THERMAL EXPANSION of HOT WATER
THERMAL EXPANSION of MATERIALS
THERMAL IMAGING, THERMOGRAPHY
THERMAL IMAGING MOLD SCANS
THERMAL MASS in BUILDINGS
THERMAL TRACKING & HEAT LOSS
THERMOSTATS, HEATING / COOLING
  Types of Building & Room Thermostats
  How Thermostats Work
  How to Set the Thermostat
  COOL OFF HEAT, Thermostat Switch
  FAN ON AUTO Thermostat Switch
  HEAT ANTICIPATOR Adjustment
  HEAT ANTICIPATOR Mini Ammeter to Check
  HEAT PUMP Thermostats - Outdoors
  THERMOSTAT WIRE CONNECTIONS
  LOW VOLTAGE TRANSFORMER TEST
  SWITCH FUNCTIONS on a Room Thermostat
  TEMPERATURE RESPONSE of Room Thermostats
THERMOSTATS, WATER HEATER
THERMOSTATIC EXPANSION VALVES
Transite Pipe Chimneys & Flues

VIDEO GUIDES: Heating System Videos
VIDEO GUIDES - InspectAPedia.com

WATER HEATERS
WATER HEATER SAFETY
WATER HEATERS for HOME HEATING USE?
WATER HEATER NOISES
WATER HEATER SCALE - De-Liming Procedure
WATER HEATER SCALE PREVENTION
WATER SOFTENERS & CONDITIONERS

WINTERIZE A BUILDING
WOOD, COAL STOVES & FIREPLACES
WOOD STOVE SAFETY

ZONE DAMPERS
ZONE VALVES

More Information

Low voltage transformer for heating or air conditioning (C) Daniel FriedmanTroubleshoot Low Voltage Transformers for Heating & Air Conditioning Systems
     

  • Low voltage transformers: definition, wiring, troubleshooting, uses - what is a low-voltage transformer, what does it do & where is it found on heating furnaces, boilers, or air conditioners or thermostats?
    • How do you tell if a transformer is bad? How do you test a low voltage transformer?
    • How does a low voltage transformer work & how they are wired
    • How to test the low-voltage heating or air conditioning transformer to see if it's working
    • List of common uses of low voltage transformers in buildings & on building equipment
  • REPAIR / UPGRADE LOW VOLTAGE WIRING - separate article
  • Questions & Answers about wiring & testing low voltage transformers for HVAC equipment like air conditioners or heaters & in low voltage wiring systems
  • References

Click to Show or Hide Related Topics

  • THERMOSTATS, HEATING / COOLING
  • A/C - HEAT PUMP CONTROLS & SWITCHES
  • AQUASTAT CONTROL Functions
  • BOILER CONTROLS & SWITCHES
  • BTU USAGE MONITORS
  • COOL OFF HEAT, Thermostat Switch
  • FAN ON AUTO Thermostat Switch
  • FURNACE CONTROLS & SWITCHES
  • HEAT ANTICIPATOR Adjustment
  • HEAT ANTICIPATOR Mini Ammeter to Check
  • HEAT ANTICIPATOR Operation
  • HEAT PUMP Thermostats - Outdoors
  • LINE VOLTAGE THERMOSTATS
  • LOW VOLTAGE BUILDING WIRING
  • LOW VOLTAGE TRANSFORMER TEST
  • STEAM BOILER CONTROLS
  • TEMPERATURE RESPONSE of Room Thermostats
  • THERMOSTAT INSTALLATION STEPS
  • THERMOSTAT SWITCHES, EXTERNAL
  • THERMOSTAT SWITCHES, INTERNAL
  • THERMOSTAT WIRE CONNECTIONS
  • THERMOSTAT WIRE FUNCTIONS
  • THERMOSTATS, WATER HEATER
  • THERMOSTATIC EXPANSION VALVES
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

Low voltage (12-24 VAC) transformers guide for HVAC systems: this article explains how low-voltage transformers are used on heating, heat pumps, & air conditioning systems to provide power for thermostats, zone valves, and other relays and controls. We explain how a low voltage transformer is installed and wired, where the device is usually located, and how to test or troubleshoot & repair low voltage transformers using a VOM or DMM. Also see LOW VOLTAGE BUILDING WIRING.

Green links show where you are. © Copyright 2013 InspectAPedia.com, All Rights Reserved. Author Daniel Friedman.

How to Troubleshoot Low Voltage Transformers for Heating & Air Conditioning Systems

Question: How do you tell if a transformer is bad? How do you test a low voltage transformer?

Low voltage relay next to electrical panel (C) Daniel FriedmanHow do i tell if a transformer for thermostate is bad ?- Erwin 5/12/12

How do you test a low voltage transformer? - Den 7/16/12

Reply: how to test a low voltage transformer for heating or air conditioning

Erwin if you disconnect the low voltage wires connected to the transformer terminals and use a VOM you should find voltage, usually 14V. If the device looks burned, hot, or smells, don't even bother testing. If it has been buzzing that's another clue.

Den,

To test for a bad low voltage transformer you simply need a volt-ohm meter or a digital VOM. See USING DMMs VOMs SAFELY for advice on how to use a volt-ohm meter, and see Guide to Electrical Test Equipment for advice on ow to electrical test equipment safely. And of course you'll have to be sure you have found and are testing the right low voltage relay, as we will explain in the details below.

In our photo (above left) you can see a low voltage transformer mounted onto a 4-inch electrical box that is in turn secured to (and powered from) a gray-covered electrical panel. But as there are four circulator pumps shown in the photo, you can figure there will be more LV transformers and more circulator relay switches nearby, connected to other room thermostats in this building. Why? A typical residential-grade low voltage transformer cannot handle the total current draw (in Amps) to support multiple circulator pump relays or other controls.

Understand how your low voltage thermostat and its low voltage transformer work & how they are wired

Low Voltage Transformer (C) Daniel Friedman

It's usually pretty simple to understand the wiring and function of a low voltage relay on HVAC/R equipment. The low voltage transformer changes (transforms) house current (at 120V AC) to a lower voltage (usually around 14V to 24V AC) used to operate the room thermostats and possibly other heating or air conditioning controls.

So the transformer has 12V wires connected to its inupt terminals (not visible in our photo at left as by code the 120V wires have to be inside of that 4" metal electrical box). The low voltage thermostat wires that bring operating current (14-12V VAC) to the thermostats are on the exposed surface of the transformer.

In the simplest applications, two wires, typically red and white, are connected at the transformer. A "C" or common terminal wire on the low voltage transformer is connected to the control relay that operates the heater or air conditioner, and an "R" terminal on the transformer is connected first to the thermostat (which acts as an "on-off" switcht) and from the thermostat onwards to a thermostat terminal found on the heater or air conditioner's primary control or circuit board. Details about thermostat wiring and low voltage control wiring are found at THERMOSTAT WIRE CONNECTIONS.

Testing the Low Voltage Heating or Air Conditioner Transformer

Low voltage transformer for heating or air conditioning (C) Daniel Friedman

When we think that there may be a problem with getting power to a thermostat (if it needs power) or to other low-voltage-operated controls in an HVAC system, the "test" of the low voltage HVAC transformer involves these very simple steps:

  1. Find the low voltage transformer that is operating the thermostat or other control device. Usually the transformer is visible, mounted on an electrical box in the utility area where the heater or air conditioner blower unit is installed (blue arrow in our photo, above left), may be mounted inside of the furnace or air handler itself (photo at left).

On some modern HVAC equipment the low voltage transformer may be harder to spot as it may be incorporated into a more complex circuit board or component. In all cases, however, if you follow the small gauge low-voltage wires from your thermostat back into the furnace or air handler cabinet you can find wires of this same dimension connected to a transformer.

  1. Check that all of the wires and connections are in fact intact, un-damaged, and properly connected. If you suspect that a thermostat wire has been damaged between the transformer and the thermostat, you can try a simple continuity test - disconnect the thermostat wires and connect them together at one end of the run - then test tor continuity between the wires using a VOM at the other, disconnected end of the pair.
  2. Check that the low voltage transformer is is providing power - using a VOM we test for voltage between 12-24V AC at the transformer's output screws. Here are the procedural details for testing a low voltage transformer for live output power:

    Remove all of the the low voltage wires from the two (or more) screws on the top of the transformer. Usually you'll see a small gauge red and white wire simply connected under two screws on the upper surface of the transformer itself.

    Some heating transformers for thermostats that use more than two wires will have more than two screws and more than two low voltge wires connected or there may even be multiple sets of thermostat wires connected if the transformer is powering more than one room thermostat. (photo above left).

    Check for output voltage: with power to the transformer "on", using the VOM on a low voltage scale (say 0-24VAC ) check for voltage between the two screw terminals. If the transformer itself is receiving 120V power but there is no voltage between the two low voltage output screws, then it is not working.
  3. Listen for buzzing: Also before a low voltage transformer fails you may hear it buzzing - a condition that can continue for some time but ultimately is likely to lead to failure.
  4. Inspect for overheating or burnup: Finally, by visual inspection you MIGHT see burn marks or evidence of overheating - but I wouldn't depend on visual inspection alone.

List of Low Voltage Transformers Found on HVAC/R Equipment and in Other Building Applications

LV relay used to operate a boiler primary control relay (C) Daniel Friedman

Watch out: there may be more than one low voltage thermostat, for example one controlling heating and another controlling air conditioning in your building. Or there may be additional low-voltage thermostats providing power to individual hydronic heating zone circulator pump relays and to the thermostats that control each of those zones (see our photo at the top of this page).

Watch out: there are other low voltage transformers found on air conditionres, boilers, furnaces, circulator relays, fan relays, etc. that are not the units providing low voltage to the room thermostat and main on-off HVAC/R controls.

  • Primary control LV transformer: The low voltage transformer found inside of a heating boiler primary control and used to operate circulator or other relays (transformer visible at lower left in our photo at left). The low voltage transformer shown in the lower left in this photo of a primary control is not the thermostat power supply. Other primary controls used on hydronic heating systems and boilers may have two of these relays, one for the oil burner circuit and one for a circulator pump.

    In our photo you can indeed see two thermostat control wires connected to the two screws marked "T" just below the LV relay. Those thermostat wires are carrying the "on-off" signal from the room thermostat.

    The relay itself operates a 120V relay found just above the LV transformer (center left on the control board) that is used to switch the heating boiler oil burner on or off.

Circulator relays (C) Daniel Friedman
  • Low voltage transformer operating one or more hot water heating circulator relays.

    The transformer in the primary control of most heating boilers also operates one circulator pump. But in a building with multiple hydronic heating zones that use individual circulator pumps, each additional circulator pump, presumably serving an individual heating zone, will be turned on or off by the room thermostat located in the zone the circulator pump serves. (see our photo at the top of this page).

    In our photo at left, you can see at center three red circulator pumps (two different models have been installed). At the upper left corner of the photo in those gray Honeywell labeled control boxes are individual circulator pump relay controls, each of which will be activated by an individual thermostat. We can see that we have a gas fired hyrdonic heating system boiler with three zones, but we don't know from the photo if all three are heating zones - one of those relays and circulators could be supplying heat to an indirect fired water heater.

    See Circulator Pumps & Relays and also INDIRECT FIRED WATER HEATERS for details.

Protectorelay oil burner control schematic
  • Low voltage transformer operating the oil burner circuit inside of a cad cell relay. Details are at CAD CELL RELAY SWITCH.
  • Low voltage transformer operating the control for a draft inducer fan found on flue vents on some heating equipment. See Draft Inducer Fans
  • Low voltage transformer in a stack relay or protectorelay that operates an oil burner - schematic at left. This control is detailed at STACK RELAY SWITCHES
  • Automatic Vent Dampers
  • LOW VOLTAGE BUILDING WIRING that controls lights, electrical receptacles
  • Doorbells
  • Many other relays, solenoids, and devices that operate equipment found in buildings

...


Frequently Asked Questions (FAQs)

...

Ask a Question or Search InspectApedia

Questions & answers or comments about installing, wiring, & repairing low-voltage HVAC/R transformers.

Ask a Question or Enter Search Terms in the InspectApedia search box just below.

Recommend / Share this Article          share button   

...

Technical Reviewers & References

Related Topics, found near the top of this page suggest articles closely related to this one.

  • [1] The ABC's of Retention Head Oil Burners, National Association of Oil Heat Service Managers, TM 115, National Old Timers' Association of the Energy Industry, PO Box 168, Mineola, NY 11501. (Excellent tips on spotting problems on oil-fired heating equipment. Booklet.)
  • [2] Domestic and Commercial Oil Burners, Charles H. Burkhardt, McGraw Hill Book Company, New York 3rd Ed 1969.
  • [3] National Fuel Gas Code (Z223.1) $16.00 and National Fuel Gas Code Handbook (Z223.2) $47.00 American Gas Association (A.G.A.), 1515 Wilson Boulevard, Arlington, VA 22209 also available from National Fire Protection Association, Batterymarch Park, Quincy, MA 02269. Fundamentals of Gas Appliance Venting and Ventilation, 1985, American Gas Association Laboratories, Engineering Services Department. American Gas Association, 1515 Wilson Boulevard, Arlington, VA 22209. Catalog #XHO585. Reprinted 1989.
  • [4] Fuel Oil & Oil Heating Magazine, 3621 Hill Rd., Parsippany, NJ 07054, 973-331-9545
  • [5] The Steam Book, 1984, Training and Education Department, Fluid Handling Division, ITT [probably out of print, possibly available from several home inspection supply companies] Fuel Oil and Oil Heat Magazine, October 1990, offers an update,
  • [6] Principles of Steam Heating, $13.25 includes postage. Fuel oil & Oil Heat Magazine, 389 Passaic Ave., Fairfield, NJ 07004.
  • [7] Principles of Steam Heating, Dan Holohan, technical editor of Fuel Oil and Oil Heat magazine, 389 Passaic Ave., Fairfield, NJ 07004 ($12.+1.25 postage/handling).
  • [8] "Residential Steam Heating Systems", Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
  • [9] "Residential Hydronic (circulating hot water) Heating Systems", Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
  • [10] "Warm Air Heating Systems". Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
  • [11] Heating, Ventilating, and Air Conditioning Volume I, Heating Fundamentals,
  • Boilers, Boiler Conversions, James E. Brumbaugh, ISBN 0-672-23389-4 (v. 1) Volume II, Oil, Gas, and Coal Burners, Controls, Ducts, Piping, Valves, James E. Brumbaugh, ISBN 0-672-23390-7 (v. 2) Volume III, Radiant Heating, Water Heaters, Ventilation, Air Conditioning, Heat Pumps, Air Cleaners, James E. Brumbaugh, ISBN 0-672-23383-5 (v. 3) or ISBN 0-672-23380-0 (set) Special Sales Director, Macmillan Publishing Co., 866 Third Ave., New York, NY 10022. Macmillan Publishing Co., NY
  • [12] Installation Guide for Residential Hydronic Heating Systems
  • [13] Installation Guide #200, The Hydronics Institute, 35 Russo Place, Berkeley Heights, NJ 07922
  • [14] Bob Scaringe, Ph.D., P.E., "Thermostatic Wiring Principles", QwikProducts by Mainstream Engineering, Rockledge FL, Tel: 800-866-3550, Website: http://www.mainstream-engr.com/, retrieved 7/17/2011, original source http://www.epatest.com/store/resources/images/misc/how-a-thermostat-operates.pdf, [copy on file as how-a-thermostat-operates.pdf ]
  • [15] Voltage Transformer, U.S. Patent No. 2,412,345, Dec. 10, 1946, Nils E. Lindenblad, Port Jefferson, NY, for Radio Corporation of America


Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.
  • Home Reference Book - Carson DunlopThe Home Reference Book - the Encyclopedia of Homes, Carson Dunlop & Associates, Toronto, Ontario, 25th Ed., 2012, is a bound volume of more than 450 illustrated pages that assist home inspectors and home owners in the inspection and detection of problems on buildings. The text is intended as a reference guide to help building owners operate and maintain their home effectively. Field inspection worksheets are included at the back of the volume. Special Offer: For a 10% discount on any number of copies of the Home Reference Book purchased as a single order. Enter INSPECTAHRB in the order payment page "Promo/Redemption" space. InspectAPedia.com editor Daniel Friedman is a contributing author.

    Or choose the The Home Reference eBook for PCs, Macs, Kindle, iPad, iPhone, or Android Smart Phones. Special Offer: For a 5% discount on any number of copies of the Home Reference eBook purchased as a single order. Enter INSPECTAEHRB in the order payment page "Promo/Redemption" space.

  • GO TO Carson Dunlop's Home Study Course Information - How to Become a Home Inspector: Carson Dunlop's nationally recognized Home Study Course, selected by ASHI the American Society of Home Inspectors and other professionals and associations. This website author is a contributor to this course.
  • GO TO Carson Dunlop's Home Study Course Information - How to Become a Home Inspector: Carson Dunlop's nationally recognized Home Study Course, selected by ASHI the American Society of Home Inspectors and other professionals and associations. This website author is a contributor to this course.
  • GO TO Carson Dunlop's Home Study Course Information - How to Become a Home Inspector: Carson Dunlop's nationally recognized Home Study Course, selected by ASHI the American Society of Home Inspectors and other professionals and associations. This website author is a contributor to this course.
    Building inspection education & report writing systems from Carson, Dunlop & Associates Ltd
  • Carson Dunlop, Associates, Toronto, have provided us with (and we recommend) Carson Dunlop Weldon & Associates' Technical Reference Guide to manufacturer's model and serial number information for heating and cooling equipment
    Special Offer
    : Carson Dunlop Associates offers InspectAPedia readers in the U.S.A. a 5% discount on any number of copies of the Technical Reference Guide purchased as a single order. Just enter INSPECTATRG in the order payment page "Promo/Redemption" space.

  • ...

HOME ABOUT CONTACT COPYING DESCRIPTION POLICIES PRINTING PRIVACY © 2013 Copyright InspectAPedia.com