InspectAPedia ®

Building & Environmental Inspection, Testing, Diagnosis, Repair, & Problem Prevention Advice
InspectAPedia
Home
| Air
Conditioning
| Electrical | Indoor
Environment
| Exteriors | Heating | Home
Inspection
| Insulate
Ventilate
| Interiors | Mold
Inspect/Test
| Plumbing
Water
Septic
| Roofing | Structure | Contact Us
Directory of Professionals to Inspect or Test a Building


Mobile Phone or PDA view of this websiteMobile View
HEATING SYSTEMS
BLUERAY Recall
BOILERS, HEATING
  BOILER CONTROLS & SWITCHES
  BOILER LEAKS CORROSION STAINS
  BOILER NOISE SMOKE ODORS
  BOILER OPERATING PROBLEMS
  BOILER OPERATION DETAILS
  BOILER PARTS LIST
BOILER PRESSURE SETTINGS
CARBON MONOXIDE/DIOXIDE
CARBON MONOXIDE WARNING
CHIMNEY INSPECTION DIAGNOSIS REPAIR
CHIMNEYS & Flues - Asbestos Transite Pipe
COMBUSTION AIR DEFECTS
COMBUSTION PRODUCTS & IAQ
DUCT INSULATION - Asbestos Paper
DUCTS - Asbestos Transite Pipe
DUST FROM HVAC?
ELECTRIC HEAT
ELECTRICAL POWER SWITCH FOR HEAT
ENERGY SAVINGS in BUILDINGS
ENERGY SAVINGS PRIORITIES
ENERGY SAVINGS RETROFIT CASE STUDY
ENERGY SAVINGS RETROFIT LEAK SEALING GUIDE
ENERGY SAVINGS RETROFIT OPTIONS
FLUE VENT CONNECTORS
FREEZE-PROOF A BUILDING
FURNACES, HEATING
GAS PIPING, VALVES, CONTROLS
HEAT LOSS in BUILDINGS
HEAT LOSS DETECTION TOOLS
HEAT LOSS INDICATORS
HEAT LOSS R U & K VALUE CALCULATION
HOUSEWRAP AIR & VAPOR BARRIERS
HEATING COST SAVINGS METHODS
HEATING LOSS DIAGNOSIS-BOILERS
HEATING LOSS DIAGNOSIS-FURNACES
HEATING OIL CLOUD WAX GEL POINT
HEATING OIL EXPOSURE HAZARDS, LIMITS
HEATING OIL SLUDGE
HEATING SMALL LOADS
HEAT PUMPS
HEATING SYSTEM INSPECTION PROCEDURE
INSULATION & VENTILATION INSPECTION & IMPROVEMENT
MOTOR OVERLOAD RESET SWITCH
NO HEAT - BOILER / FURNACE DIAGNOSIS
OIL BURNERS
OIL BURNER INSPECTION GUIDE
OIL BURNERS, RETENTION HEAD
OIL BURNER SOOT & PUFFBACKS
OIL BURNER NOISE SMOKE ODORS
OIL BURNER NOZZLE & ELECTRODES
OIL PUMP FUEL UNIT PRESSURE SETTING TIPS
OIL SAFETY VALVES
OIL FUEL TYPES & CHARACTERISTICS
Oil Odors: Leaky Oil Tank Piping
OIL SAFETY VALVES
OIL TANKS
OIL TANK GAUGES
OIL TANK LEAKS
OIL TANK SLUDGE
OIL TANK TESTING
OIL TANKS, BURIED
PLASTIC HEATER VENT
RADIANT HEAT
RADIANT HEAT Floor Mistakes to Avoid
RADIANT SLAB FLOORING CHOICES
RADIANT SLAB TUBING & FLUID CHOICES
Safety Recalls
  BLUERAY Recall
  CHIMNEYS & Flues - Asbestos Transite
  Goodman HTPV RECALL
  Heat Recovery Ventilator RECALL
  Lennox Furnace Manuals
  Lennox WARNING
  Weil McLain RECALL
SAFETY DURING HEATING INSPECTION
STEAM HEATING SYSTEMS
  Cad Cell Relay Switch Flame Sensors
  Mixing Valves
  Relief Valves - TP Valves
  Sight Glass, Steam Boiler
  Pressure Switch, Steam Boiler
  Spill Switches
  Stack Relay Switch
  Steam Vents
  Low Water Cutoff Controls
  Water Feeder Valves, Steam
TANKLESS COILS
THERMAL EXPANSION of MATERIALS
THERMAL MASS in BUILDINGS
THERMAL MASS in UPSTAIRS
THERMAL TRACKING & HEAT LOSS
THERMOSTATS
Transite Pipes, Chimneys & Flues

More Information

InspectAPedia.comInspectAPedia ® Home & Site Map
InspectAPedia Blog - News Updates
Air Conditioning & Heat Pumps
InspectAPedia Bookstore
ELECTRICAL INSPECTION, DIAGNOSIS, REPAIR
Environment
Exteriors
Heating
Home Inspection
Insulate Ventilate
Interiors
Mold Inspect/Test
Plumbing Water Septic
Roofing
Structure
Contact Us



Photograph of  a modern oil-fired heating boiler How to Diagnose Oil Burner Noise, Smoke, Odors
InspectAPedia®  -    

  • How to Diagnose Oil Burner Noise, Smoke, Odors
  • Diagnose & repair oil burner soot, puffback, rumbling, hard-starting
  • Flue gas exposure hazards, smells, odors
  • How to diagnose loss of heat, heating boiler noises, leaks, odors, or smoke
  • Troubleshooting heating boiler oil or gas burners & controls
  • How to inspect & repair central hot water heating boilers - hydronic heating
Our site offers impartial, unbiased advice without conflicts of interest. We will block advertisements which we discover or readers inform us are associated with bad business practices, false-advertising, or junk science. Our contact info is at InspectAPedia.com/appointment.htm.

Here we discuss how to recognize & diagnose oil fired heating boiler noises, leaks, odors, or smoke. This website answers most questions about central hot water heating system troubleshooting, inspection, diagnosis, and repairs. We describe how to inspect residential heating systems to inform home owners, buyers, and home inspectors of common heating system defects.

The articles at this website describe how to recognize common oil-fired heating appliance operating or safety defects, and how to save money on home heating costs. Also see CHIMNEY INSPECTION & REPAIR GUIDE for details of chimney inspection, diagnosis, and repair, including blocked chimney flues, chimney backdrafting, leaks, and odors from flues. Separately we discuss CARBON MONOXIDE hazards in buildings. Readers concerned with LP gas or natural gas combustion flue gas products and hazards should also see Natural Gas Combustion Products and also LP & Natural Gas Safety Hazards.

© Copyright 2009 Daniel Friedman, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use links at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

How to Diagnose Noises & Odors During Heating System & Oil Burner Operation

What Oil Fired Heating System Noises are Normal and What are the Noise Sources?

Oil burner schematic (C) Carson DunlopSome heating system and heating oil burner noises are considered normal. These include noises coming from the following items:(The sketch is courtesy of Carson Dunlop. )

  • Electric motor noise: The electric motor which operates the oil unit and blower unit on the oil burner, or an electric motor which may operate a furnace blower fan or a flue-vent draft inducer fan. However some electric motor noises are "normal" while others indicate trouble, as we will elaborate below.
  • Combustion air fan noise: The combustion air blower, usually a squirrel cage fan on oil burners is spun by a shaft extending out of the oil burner's electric motor. The blower itself produces noise as it spins and moves air into the combustion chamber. Unless the oil burner blower is damaged you probably won't hear it over the other noises produced at the burner.
  • Warm air furnace blower noise: Furnace blower fan units: A bad furnace fan blower motor or assembly may produce noise you would indeed hear above the noises coming from the oil burner itself.
  • Heating oil pump noises: The oil burner's heating oil pump or "fuel unit" is usually driven by a shaft (and couplings) which begin at the electric motor on the oil burner, extend through the combustion air blower, and connect to a drive shaft protruding from the oil pump. Unless there is an internal problem with the pump, these units are pretty quiet compared with other normal oil burner noises.
  • Draft inducer fan noises: A flue vent connector-mounted or chimney-mounted combustion gas vent draft inducer fan if one is used, is usually audible, and in a typical installation you'll hear this fan turn on up 15 seconds or so before the oil burner itself begins to operate.
  • Oil burner combustion noise: Oil burner flame or combustion noise is usually the loudest "normal" noise coming from an oil burner. The fuel unit pumps heating oil to 100 psi or higher, then sprays it through an oil burner nozzle where the oil is ignited by electrodes mounted in the oil burner's tube at the entry to the combustion chamber. The "roar" that you hear at a normally operating heating system oil burner is usually produced mostly by this combustion process.
  • High speed oil burner noise compared with low speed oil burner noise: High speed oil burners noises: older traditional oil burners used on heating boilers and furnaces were driven by an electric motor spinning at 1725 rpm. Modern "high speed" heating system oil burners usually run at 3450 rpm. The higher speed permits more air flow and greater oil burner efficiency. But in buildings where an older low-speed oil burner is swapped out for a new "high speed" oil burner unit, the occupants are often surprised to hear that the new equipment is noticeably noisier than the old unit. This is normal, and your heating installer would have been smart to tell you to expect this change so you don't think something's wrong with the new heating system. You're tolerating more noise for lower heating system operating costs.

What oil fired heating system noises are abnormal and may indicate an operating problem or an unsafe condition?

Noises & soot buildup can lead to a potentially dangerous "puffback" which can damage the heating equipment and blow soot and smoke throughout the building. An experienced heating service technician may recognize the following diagnostic list of heating system or oil burner noises as well as perhaps other signs of trouble:

  • Chimney fires: DANGEROUS, IMMEDIATE ACTION NEEDED: Very loud noise like a roaring freight train coming from a chimney is likely to be a chimney fire- extremely dangerous, risking a house fire: turn off heat as you run out of the house: call the fire department from your cell phone or from a neighbor's house. A chimney fire moves fast, loud, and produces lots of smoke. In fact a quick look at the chimney serving a heater at any time can tell you how the heating system is operating. If the chimney top shows smoke or soot (without the freight train noise of a chimney fire) the burner is not operating properly. If you have a chimney fire (or any kind of fire) stop reading this Internet article, leave the building immediately, and call your fire department. See CHIMNEY INSPECTION & REPAIR GUIDE for details of chimney inspection, diagnosis, and repair, including blocked chimney flues, chimney backdrafting, leaks, and odors from flues. Separately we discuss CARBON MONOXIDE hazards in buildings.
  • Noises during oil burner startup - a "bang" or "puffback" which blows soot into the room through the barometric damper or through other equipment openings: the oil pump may not be shutting down properly at the end of an oil burn cycle, leaking incompletely burned oil into the combustion chamber. That oil ignites at startup causing a potentially dangerous puffback. Immediate service and repair are needed.
  • Noises during oil burner startup - a "rumbling" sound (which usually continues all during operation" or a "stumbling" sound in the combustion chamber probably indicates that the system needs inspection and cleaning very soon. Some noise is normal however, but the normal sounds tend to be more smooth and continuous.
  • Noises during oil burner shut-down - a stumbling or rumbling after the oil burner motor has stopped, indicate that oil is continuing to leak into the combustion chamber and risks a dangerous puffback - see "Noises during oil burner startup" above. Immediate service is recommended.
  • Oil burner noises of shrieks or grinding coming from the electric motor or oil pump on the oil burner mean that immediate service is needed - probably a bearing is failing.
  • Furnace noises of shrieks, whining, or grinding coming from the electric motor or blower assembly of a furnace air handler probably mean that the system has a bad bearing (or fan belt) and prompt repair service is needed. It's best to shut down such a system since certain failures, such as sucking a furnace filter into the blower assembly, can lead to overheating and cause a fire.
  • Oil Burner Startup problems: noises and clues of puff back: if you see flapping at the barometric damper or if you see or hear vibrations in the system, prompt service is needed
  • Noises from radiators or heating baseboards: clanking pipes or sharp snapping noises may be heard as a normal consequence of expansion of metals during the heating cycle. These noises can often be eliminated or reduced by careful routing of piping and by allowing room around heating pipes for expansion, but probably not eliminated in the case of hot water baseboards. Bubbling or rumbling noises in hot water heating piping can be caused by air in the heating lines. If the amount of air becomes excessive the system may be unable to circulate hot water and extra steps to bleed unwanted air will be required. Hissing sounds such as air escaping from radiators or other piping where air bleeder valves are installed are normal but should be brief and uncommon. If you constantly hear air hissing from radiator bleed valves double check that you understand what kind of heat you have - hissing from bleeder valves on steam heat radiators as heat is coming up in the building is normal.
  • Noises from Oil Tanks or Oil Piping: Vibrations of the heating oil piping, especially if installed passing overhead along building framing and if installed without sound isolation can use the ceiling as a giant speaker and may be quite loud.
  • Noises from air leaks: on furnaces (hot air systems) we sometimes find that an air leak in the duct system or air handler, or quite often around the air filter itself, can make lots of noise.

What can we do to reduce heating system operating noises?

Heating equipment located well out of occupied space, in an unoccupied basement, for example, are not usually a source of noise complaints in a building, though there are a few exceptions for which we have suggestions.

  • Consult your heating service technician first to be sure that the heating system is operating normally and safely, before attempting any other steps to reduce noises coming from the heating system.
  • How to cure vibrations of the heating oil piping or oil tank: re-route piping between the oil tank and the oil burner to remove any contact points with overhead ceiling framing or flooring; if those contact points are necessary to support the line, be sure that the oil line is supported with noise-suppressing fittings (we use foam rubber and copper pipe clamps) and that the piping is well secured.
  • How to cure warm air heating system air duct or filter noises see
  • Oil Burner Noise Insulation: some of our readers suggest building an insulated box around the oil burner to reduce its noise. Watch out! If you constrict or reduce the amount of combustion air available to the oil burner it will not operate properly and the system could become unsafe. Be sure to discuss the design of any noise insulation scheme and its possible effects on combustion air or other heating system considerations with your heating service technician.

Share this Article      

...

Technical Reviewers & References

  • Daniel Friedman - principal author/editor of the InspectAPedia® Website
  • InspectAPedia Bookstore lists recommended books, organized by topic & available for purchase. Most of our articles also include a list of recommended books for the specific article topic as well as other references, and information sources.
  • Critique, contributions wanted: Contact Us to suggest corrections or additions to articles at this website, and if you wish, to receive online listing and credit as a contributor. Particular thanks are due to the many experts and also consumers who read and critique technical articles at InspectAPedia.com.
  • Additional technical contributors & reference sources for this article are listed below.

Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

OIL BURNERS
OIL BURNER INSPECTION GUIDE
OIL BURNERS, RETENTION HEAD
OIL BURNER SOOT & PUFFBACKS
OIL BURNER NOISE SMOKE ODORS
OIL BURNER NOZZLE & ELECTRODES
OIL PUMP FUEL UNIT PRESSURE SETTING TIPS
OIL SAFETY VALVES
OIL FUEL TYPES & CHARACTERISTICS
Oil Odors: Leaky Oil Tank Piping
OIL SAFETY VALVES
OIL TANKS
OIL TANK GAUGES
OIL TANK LEAKS
OIL TANK SLUDGE
OIL TANK TESTING
OIL TANKS, BURIED

  • Thanks to Alan Carson and Bob Dunlop, Carson Dunlop, Associates, Toronto, for permission to use illustrations from their publication, The Illustrated Home which illustrates construction details and building components. Carson Dunlop provides home inspection education, publications, report writing materials, and home inspection services. Alan Carson is a past president of ASHI, the American Society of Home Inspectors.

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building design, inspection, and repair, and about indoor environment testing, diagnosis, and cleanup are at the InspectAPedia Bookstore.
  • ...
HEATING SYSTEMS
HEATING SYSTEM INSPECTION DIAGNOSIS REPAIR

More Information

InspectAPedia.comInspectAPedia ® Home & Site Map
InspectAPedia Blog - News Updates
Air Conditioning & Heat Pumps
InspectAPedia Bookstore
ELECTRICAL INSPECTION, DIAGNOSIS, REPAIR
Environment
Exteriors
Heating
Home Inspection
Insulate Ventilate
Interiors
Mold Inspect/Test
Plumbing Water Septic
Roofing
Structure
Accuracy & Bias Pledge
Contact Us

More Information on Building Diagnostic Inspections and Repairs

  • Carbon Monoxide Gas Toxicity, exposure limits, poisoning symptoms, and inspecting buildings for CO hazards
  • Home Heating System Should Be Checked [for proper venting and for CO Carbon Monoxide Hazards - DJF]
  • Inspection Procedures for Oil-Fired Heating Systems Detailed step by step approaches for inspecting complex systems]
  • Oil Tanks - The Oil Storage Tank Information Website: Buried or Above Ground Oil Tank Inspection, Testing, Cleanup, Abandonment of Oil Tanks
  • Domestic and Commercial Oil Burners, Charles H. Burkhardt, McGraw Hill Book Company, New York 3rd Ed 1969.
  • National Fuel Gas Code (Z223.1) $16.00 and National Fuel Gas Code Handbook (Z223.2) $47.00 American Gas Association (A.G.A.), 1515 Wilson Boulevard, Arlington, VA 22209 also available from National Fire Protection Association, Batterymarch Park, Quincy, MA 02269. Fundamentals of Gas Appliance Venting and Ventilation, 1985, American Gas Association Laboratories, Engineering Services Department. American Gas Association, 1515 Wilson Boulevard, Arlington, VA 22209. Catalog #XHO585. Reprinted 1989.
  • The Steam Book, 1984, Training and Education Department, Fluid Handling Division, ITT [probably out of print, possibly available from several home inspection supply companies] Fuel Oil and Oil Heat Magazine, October 1990, offers an update,
  • Principles of Steam Heating, $13.25 includes postage. Fuel oil & Oil Heat Magazine, 389 Passaic Ave., Fairfield, NJ 07004.
  • The Lost Art of Steam Heating, Dan Holohan, 516-579-3046 FAX
  • Principles of Steam Heating, Dan Holohan, technical editor of Fuel Oil and Oil Heat magazine, 389 Passaic Ave., Fairfield, NJ 07004 ($12.+1.25 postage/handling).
  • "Residential Steam Heating Systems", Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
  • "Residential Hydronic (circulating hot water) Heating Systems", Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
  • "Warm Air Heating Systems". Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
  • Heating, Ventilating, and Air Conditioning Volume I, Heating Fundamentals,
  • Boilers, Boiler Conversions, James E. Brumbaugh, ISBN 0-672-23389-4 (v. 1) Volume II, Oil, Gas, and Coal Burners, Controls, Ducts, Piping, Valves, James E. Brumbaugh, ISBN 0-672-23390-7 (v. 2) Volume III, Radiant Heating, Water Heaters, Ventilation, Air Conditioning, Heat Pumps, Air Cleaners, James E. Brumbaugh, ISBN 0-672-23383-5 (v. 3) or ISBN 0-672-23380-0 (set) Special Sales Director, Macmillan Publishing Co., 866 Third Ave., New York, NY 10022. Macmillan Publishing Co., NY
  • Installation Guide for Residential Hydronic Heating Systems
  • Installation Guide #200, The Hydronics Institute, 35 Russo Place, Berkeley Heights, NJ 07922
  • The ABC's of Retention Head Oil Burners, National Association of Oil Heat Service Managers, TM 115, National Old Timers' Association of the Energy Industry, PO Box 168, Mineola, NY 11501. (Excellent tips on spotting problems on oil-fired heating equipment. Booklet.)
InspectAPedia.comInspectAPedia® Home & Site Map - Building & Environmental Inspection, Testing, Diagnosis, Repair, & Problem Prevention Advice: In-depth research & advice on diagnosing, testing, correcting, & preventing building defects & indoor environmental hazards. Unbiased information, no conflicts of interest.
GO TO the MOLD and INDOOR ENVIRONMENT INFORMATION CENTER for in-depth advice on avoiding testing for or cleaning up mold and other indoor environmental hazards, odors, gases, contaminants
The Mold Information Center:
What to Do About Mold in Buildings, When and How to Inspect for Mold, Clean Up Mold, or Avoid Mold Problems
GO TO MOLD TEST KITS: This expert-recommended mold test kit is cheap and yet top performing *IF* you use a competent analysis laboratory!
Use this simple, economical mold test kit
by following our instructions on how to collect and mail mold samples to our lab
GO TO IAQ/MOLD-TEST LAB SERVICES: Mold, Pollen, indoor air quality, field and laboratory services by an expert.Environmental Inspection, Testing, & Diagnosis On-Site IAQ, Gas, Air Testing, Mold Investigation, Sick Building Diagnosis, Lab Services, & Remediation Plan Preparation - indoor air quality testing, problem source determination, supporting lab work, written remediation plan addressing removal of environmental and other hazards and prevention of their recurrence.
GO TO our PRE PURCHASE BUILDING INSPECTION SERVICES: Authoritative information for home buyers and home owners is included with your inspection.
Building Inspection, Problem Diagnosis
, Forensic Investigation & Testing, Repair Consulting

CONTACT Daniel Friedman - Dan is a senior ASHI home inspector, nationally recognized expert on building inspection, building failures, and sick building investigation
Contact Daniel Friedman for website content suggestions or for fee-paid consulting

10/31/2009- 09/05/1999 - InspectAPedia.com/heat/HeatBoilerDefectshtm - © 2009 - 1988 Copyright Daniel Friedman All Rights Reserved - InspectAPedia® is a Registered U.S. Trademark