InspectAPedia ®

Building & Environmental Inspection, Testing, Diagnosis, Repair, & Problem Prevention Advice
InspectAPedia
Home
| Air
Conditioning
| Electrical | Indoor
Environment
| Exteriors | Heating | Home
Inspection
| Insulate
Ventilate
| Interiors | Mold
Inspect/Test
| Plumbing
Water
Septic
| Roofing | Structure | Contact Us
Directory of Professionals to Inspect or Test a Building


Mobile Phone/PDA website viewMobile View
HEATING SYSTEMS
AIRBOUND HEAT SYSTEM REPAIRS
ANODES & DIP TUBES on WATER HEATERS
ANTI SCALD VALVES
APPLIANCE EFFICIENCY RATINGS
ASBESTOS in BUILDINGS
BOILERS, HEATING
  BOILER OPERATION DETAILS
  BOILER CONTROLS & SWITCHES
  Air Bleeder Valves
  Aquastat Functions
  BOILER LEAKS CORROSION STAINS
  BOILER OPERATING PROBLEMS
  BOILER PARTS LIST
  Boiler Pressure Controls & Settings
  Cad Cell Relay Switch Flame Sensors
  Circulator Pumps & Relays
  Draft Regulators, Dampers
  Expansion Tanks
  Gauges on Heating Equipment
  Limit Switches, Boilers
  Low Water Cutoff Valves, Boilers
  Mixing Valves
  Relief Valves - TP Valves
  Reset Switch - Primary Control
  Reset Switch - electric motors
  Spill Switches
  Stack Relay Switch
  WATER HEATERS
ZONE VALVES
CARBON MONOXIDE/DIOXIDE
CARBON MONOXIDE WARNING
CHIMNEY INSPECTION DIAGNOSIS REPAIR
CHIMNEYS & Flues - Asbestos Transite Pipe
COMBUSTION GASES & PARTICLE HAZARDS
COMBUSTION PRODUCTS & IAQ
DEFINITION of Heating & Cooling Terms
DRAFT HOODS - gas fired
DRAFT REGULATORS - barometric dampers
DUCT SYSTEMS
DUCT INSULATION, Asbestos Paper
DUCTS, Asbestos Transite Pipe
DUST FROM HVAC?
ELECTRIC HEAT
ELECTRICAL POWER SWITCH FOR HEAT
ENERGY SAVINGS in BUILDINGS
ENERGY SAVINGS PRIORITIES
ENERGY SAVINGS RETROFIT CASE STUDY
ENERGY SAVINGS RETROFIT LEAK SEALING GUIDE
ENERGY SAVINGS RETROFIT OPTIONS
FAN CONVECTOR HEATERS - HYDRONIC COILS
FLUE VENT CONNECTORS
FREEZE-PROOF A BUILDING
FURNACES, HEATING
  DUCT SYSTEM DEFECTS
  DUCT & AIR HANDLER ODORS
  FAN LIMIT SWITCH
  FURNACE CONTROLS & SWITCHES
  FURNACE OPERATION DETAILS
  HEAT EXCHANGER LEAKS
  STACK RELAY SWITCHES
GAS PIPING, VALVES, CONTROLS
GAUGES ON HEATING EQUIPMENT
HEAT LOSS in BUILDINGS
HEAT LOSS DETECTION TOOLS
HEAT LOSS INDICATORS
HEAT LOSS PREVENTION PRIORITIES
HEAT LOSS R U & K VALUE CALCULATION
HOUSEWRAP AIR & VAPOR BARRIERS
HEATING COST SAVINGS METHODS
HEATING LOSS DIAGNOSIS-BOILERS
HEATING LOSS DIAGNOSIS-FURNACES
HEATING OIL CLOUD WAX GEL POINT
HEATING OIL EXPOSURE HAZARDS, LIMITS
HEATING OIL SLUDGE
HEATING SMALL LOADS
HEAT PUMPS
HEATING SYSTEM INSPECTION PROCEDURE
  HEATING INSPECTION CONCEPTS
  HEATING INSPECTION PROCEDURE
HOT WATER HEATERS
HOT WATER IMPROVEMENT
INSULATION & VENTILATION INSPECTION & IMPROVEMENT
MIXING VALVES
NO HEAT - BOILER / FURNACE DIAGNOSIS
OIL BURNERS
OIL BURNER INSPECTION GUIDE
OIL BURNER NOISE SMOKE ODORS
OIL BURNER SOOT & PUFFBACKS
OIL FUEL TYPES & CHARACTERISTICS
Oil Odors: Leaky Oil Tank Piping
OIL SAFETY VALVES
OIL TANKS
OIL TANK GAUGES
OIL TANK LEAKS
OIL TANK SLUDGE
OIL TANK TESTING
OIL TANKS, BURIED
PLASTIC HEATER VENT
RADIANT HEAT
RADIANT HEAT Floor Mistakes to Avoid
RADIANT SLAB FLOORING CHOICES
RADIANT SLAB TUBING & FLUID CHOICES
RADIATORS
RELIEF VALVES - TP Valves on Boilers
Relief Valves - Water Heaters
Reset Switch - Heater Primary Control
Reset Switch - Electric Motors
Reset Switch - Stack Relays
SAFETY DURING HEATING INSPECTION
Safety Recalls
  BLUERAY Recall
  CHIMNEYS & Flues - Asbestos Transite
  Goodman HTPV RECALL
  Heat Recovery Ventilator RECALL
  Lennox Furnace Manuals
  Lennox WARNING
  Weil McLain RECALL
SAFETY DURING HEATING INSPECTION
SOOT on OIL FIRED HEATING EQUIPMENT
SPILL SWITCHES - Flue Gas Detection
STAIN DIAGNOSIS on Indoor Surfaces
STEAM HEATING SYSTEMS
  Cad Cell Relay Switch Flame Sensors
  Low Water Cutoff Valves, Boilers
  Mixing Valves
  Relief Valves - TP Valves
  Sight Glass, Steam Boiler
  Pressure Switch, Steam Boiler
  Spill Switches
  Stack Relay Switch
  Steam Vents
  LOW WATER CUTOFF CONTROLS
  Water Feeder Valves, Steam
TANKLESS COILS
  Tankless Coil Leaks
THERMAL EXPANSION of MATERIALS
THERMAL MASS in BUILDINGS
THERMAL MASS in UPSTAIRS
THERMAL TRACKING & HEAT LOSS
THERMOSTATS
Transite Pipe Chimneys & Flues
WATER HEATERS
ZONE VALVES

More Information

InspectAPedia.comInspectAPedia ® Home & Site Map
InspectAPedia Blog - News Updates
Air Conditioning & Heat Pumps
Bookstore
Electrical
Environment
Exteriors
Heating
Home Inspection
Insulate Ventilate
Interiors
Mold Inspect/Test
Plumbing Water Septic
Roofing
Structure
Accuracy & Bias Pledge
Contact Us



LARGER VIEW of stack relay switch on an oil fired heater

Guide to Stack Relay Switches on Oil Fired Heating Equipment
InspectAPedia®  -    

  • Stack Relay Switches - Type RA 117A / RA116A Protectorelay Primary Controls on Oil Fired Heating Equipment, boilers, furnaces, water heaters: Stack Relay Troubleshooting & Repair Guide
  • How to use the primary controller reset button - how many times to press the red reset button on an oil burner
  • Oil burner puffbacks explained
  • Troubleshooting heating system furnace & boiler safety controls; when and how to service, test, & clean the stack relay switch primary control Type RA 116A Protectorelay Switch, Delco primary control (master control), Honey Primary controls on oil fired equipment
Our site offers impartial, unbiased advice without conflicts of interest. We will block advertisements which we discover or readers inform us are associated with bad business practices, false-advertising, or junk science. Our contact info is at InspectAPedia.com/appointment.htm.

Here we discuss how to inspect, test, reset, or clean the stack relay switch used as a flame detection/safety device for primary control on oil fired heating systems (boilers and furnaces). Readers will also find that this website answers most questions about central heating system troubleshooting, inspection, diagnosis, and repairs. We describe how to inspect residential heating systems to inform home owners, buyers, and home inspectors of common heating system defects.

The articles at this website describe the basic components of a home heating system, how to find the rated heating capacity of an heating system by examining various data tags and components, how to recognize common heating system operating or safety defects, and how to save money on home heating costs. We include product safety recall and other heating system hazards.

Also see GAS PIPING, VALVES, CONTROLS for more details on how to inspect and test LP and natural gas piping, controls, valves, and tanks. Contact us to suggest text changes and additions and, if you wish, to receive online listing and credit for that contribution. © Copyright 2010 Daniel Friedman, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use links at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

A Guide to Stack Relay Control Switches on Boilers, Furnaces, or Water Heaters

The stack relay switch shown in the photograph is attached at the flue vent connector which in turn passes flue gases from an old "octopus" type furnace to the chimney. (See the black box with its red reset button.) This same switch might also be found on some oil-fired heating boilers (hot water, hydronic, baseboard, or radiator heat) not just on furnaces (hot air heat).

Oil burner stack relay schematic (C) Carson Dunlop

Oil Burner Stack Relay Switches Explained Older oil burners used to heat a warm air furnace, a heating boiler, or a water heater may use a stack relay switch as a primary controller to prevent sending fuel into the oil burner if the oil burner flame has not been successfully ignited.

This sketch of a stack relay used as primary controller on oil fired heating equipment (heating boilers or water heaters) is provided courtesy of Carson Dunlop.

Stack relays are an older type of flame sensor than the Cad Cell Relays which we discussed above, but they accomplish the same purpose (turn off the oil burner if the flame is not established).

Mounting Location for the Primary Control Protecto Relay

Primary control stack relay skectch (C) Daniiel FriedmanThe "stack relay" uses a bimetallic spring (also called a bimetallic helix) inserted into the flue vent connector located usually quite close to the heating boiler between the boiler top and the chimney.

The round tube containing the bimetallic temperature sensing spring is inserted into the heating appliance flue stack so that it is located in the center of the path of flue gases. (Audel sketch at left, edited).

Taking advantage of the fact that two different metals laminated together will expand at different rates, the bimetallic spring moves in response to the presence or absence of heat inside of the flue vent connector ("smoke pipe" or "stack") of an oil fired boiler or furnace. Sensing heat in the stack is a means of assuring that the burner flame is present.

How Stack Relay Safety Switches Work on Oil Fired Heating Equipment

Type RA 116A primary control (C) Daniel Friedman AudelHow Stack Relay Switches Work: Older oil burners may use a Stack Relay to accomplish the same purpose (turn off the oil burner if the flame is not established). The "stack relay" is a bimetallic spring inserted into the flue vent connector located usually quite close to the heating boiler between the boiler top and the chimney.

If the oil burner fails to ignite or if the flame is intermittent, too small an cool, or lost entirely, this safety control will sense the loss of oil burner flame by sensing the drop of temperature in the flue. As the bimetallic spring changes shape in response to cooling, it mechanically operates a primary control safety-off switch to turn off the oil burner motor (so that we don't keep pumping un-burned heating oil into the combustion chamber).

Similarly to failure to ignite at boiler or furnace start-up, if the flame is lost during oil burner operation this control will also turn off the oil burner motor.

The Type RA 116A or Type RA117A primary control is also designed to automatically re-start the oil burner after a cool-down cycle of a minute to a minute and a half after an abnormal shutdown. If multiple re-start attempts fail to get the oil burner operating satisfactorily the system will shut down entirely in "SAFETY OFF" condition.

This control includes a red safety reset button (#8 in the drawing) that pops out if the control has caused a safety shut down of the oil burner. Here we discuss when, how, and how-often to press the red reset button to try re-starting the oil burner.

Our sketches (above) of a Type RA 116A / RA 117A Primary Control, also called a Stack Relay or a Protectorelay, shows the cover removed and identifies the principal components of this heating system control. Sketch from Audel. The Type RA 116A primary control was used on constant-ignition oil burners that fired heating boilers, warm air furnaces, and water heaters. You will still find this old control on older oil fired heating equipment, though not on newer oil-fired equipment which is more likely to use a  Cad Cell Relay Switch Flame Sensor to detect the successful ignition of the oil burner.

The bimetallic spring warms in response to hot oil burner exhaust, confirming that combustion is taking place. If combustion is not occurring a timer inside the stack relay turns off the oil burner to prevent flooding of the combustion chamber with un-burned oil.

The stack relay switch shown in the page top photograph and in the sketch above is attached at the flue vent connector which in turn passes flue gases from an old "octopus" type furnace (in our photograph) to the chimney. (See the black box with its red reset button.) This same switch might also be found on some oil-fired heating boilers (hot water, hydronic, baseboard, or radiator heat) not just on furnaces (hot air heat).

How to Reset the Oil Burner Stack Relay - Using the Reset Button

A gray box with a red reset button housing the stack relay and its reset switch will be found mounted on the flue vent connector if this control is in use. The first is simply to press the red reset button that protrudes through the cover of the stack relay box itself.

Delco primary control stack relay (C) Daniel FriedmanThe primary control reset button on a Delco master control is labeled at the center right of the illustration at left. A primary control stack relay reset button is also pointed out by arrow #8 in our sketch above.

This red button should project through a small hole in the primary control's cover. If you don't see the red button but you see the hole in the control cover, it's possible that a plastic reset button extension has broken off and been lost, but the actual working reset button and switch can still be found inside the control cover and it can still be pressed.

Knowing how to reset the stack relay can avoid a costly "no heat" service call or it can keep the heating boiler running sufficiently to keep the building warm while waiting for the heating service technician.

There are actually two resets that can be performed on an oil burner stack relay.

A second stack control reset might be necessary - we discuss it at How to Reset the Oil Burner Stack Relay below.

How many times can I press the reset button on the oil burner primary controller?

Most heating technicians and inspectors will tell you to only press the reset button once. That's because we worry that a homeowner will keep pressing the button even though the oil burner flame is never igniting.

Where are all the heating system reset buttons? If you are looking for the main reset button on heating equipment you'll want to see: Aquastat Functions and Cad Cell Relay Switch Flame Sensors (hot water boilers and some water heaters), Stack Relay Switch on older oil fired boilers and furnaces, SPILL SWITCHES (gas fired equipment), and also Low Water Cutoff Controls on steam heating systems. At ELECTRIC MOTOR OVERLOAD RESET SWITCH we discuss the thermal overload switch and reset button that is found on many electric motors including those operating air conditioning fans, heating system oil burners, and furnace blowers and motors.

Below we discuss other reset functions peculiar to the Stack Relay Switch, also called the Primary Controller on older oil fired heating equipment.

Oil burner puffback problems

If you flood the heater's combustion chamber with un-burned oil which later does ignite, the result can be a dangerous puffback which blows soot and smoke into the building, can damage the equipment, is unsafe, and could even start a fire.

So as with cad cell relays and other heating system "reset" buttons, if the oil burner does not turn on and run continuously and normally (no smoke, no loud noises, etc.) for at least 5 or 10 minutes after resetting the relay or pressing the reset button, DO NOT keep resetting the system since doing so can flood the combustion chamber with un-burned heating oil - a dangerous condition as we just explained.

How to Reset the Oil Burner Stack Relay - Using the Internal Relay Stepping Lever

How to reset the primary control Protectorelay (C) Daniel FriedmanWhy might you need to remove the cover and look for a second, "internal" reset lever inside of this control? Sometimes simply pressing the reset button through the cover of the stack relay switch will not turn on the oil burner, but the problem could be in the switch itself, not the burner.

This procedure is called "re-stepping" the Protectorelay or Type RA 116A Primary Control (which we call the "stack relay" because its bimetallic spring sensor is inserted into the oil-fired boiler or furnace "stack pipe" (flue vent connector) where it senses the heat from a successful oil burner ignition and flame.

The second and more thorough reset of the stack relay can be accomplished by removing the cover on this control box (SAFETY WARNING LIVE VOLTAGE electrical connections are inside this box - a shock hazard). The stack relay bimetallic spring assembly can be "reset" by removing the cover of the assembly and pulling the (visually obvious) reset lever out away from the flue vent connector, and then carefully and gently releasing it again. Watch out for sensitive stack relays: sometimes these switches trip off during oil burner testing or operation and they can be trick to re-set.

If you're able to get the system running again by using this internal reset, but if the relay switch tends to trip off if you simply tap on the outside of the relay switch when its cover has been replaced, then there is a problem needing further investigation, either with an electrical connection in the switch, or with the switch itself. In this case the stack relay switch may need replacement, but before replacing it see our note below on cleaning the stack relay switch.

When to Clean the Oil Burner Stack Relay Switch

Since this oil burner relay switch depends on sensing the heat of the flue gases as they pass through the flue vent connector (or "stack pipe") from the oil burner/combustion chamber in a furnace or boiler up to the chimney, the sensor, a bimetallic spring, is exposed to soot in the oil burner exhaust. If the oil burner has been running poorly, perhaps itself needing cleaning or adjustment, the level of soot in the oil burner exhaust can be quite high.

Soot produced by oil combustion (or by poor or incomplete heating oil combustion) is itself an insulator. Not only do we need to remove this soot from inside of a furnace or boiler in order to get the most heat from our heating oil into the building's heating distribution system (hot air or hot water), but this same soot can collect on, clog, or insulate the oil burner stack relay switch.

Soot collected on the stack relay switch bimetallic sensor spring, acting as an insulator, can "fool" the switch into thinking that there is not good combustion (temperatures look too low at the sensor) and thus it might switch off on safety and need to be frequently "reset" to keep the heating system running. It may be necessary to clean the stack relay switch sensor.

During oil burner service for a boiler or furnace, if the heating system uses a stack relay switch (which in fact is rather obsolete), the switch should be removed during system cleaning (when you remove the flue vent connector piping), and its external parts or sensor should be cleaned (normally by light brushing).

Tips for Servicing and Testing the Oil Burner Primary Control: the Type RA116A Protectorelay Stack Relay

Do not lubricate the primary control parts with oil.

Keep the cover on the primary control - this protects the control from dust and from mechanical damage, either of which could make it stop working or make it unsafe.

Protectorelay scavenger timing and recycling timer (C) Daniel Friedman AudelCheck the safety lockout function of the oil burner primary control: with the oil burner running, close the manual oil valve at the oil burner - this simulates a flame failure of the oil burner. When the oil burner flame goes out, "hot contacts" (#6) should open after a the stack temperature begins to drop (and the bimetallic spring of the A 116A contracts). This should turn off the oil burner motor itself.

The burner should stay off until the stack relay RA116A cools down enough to re-make the cold contacts (#7) which should re-start the oil burner automatically. But as you have left the oil flow turned off, after 90 seconds or less the burner motor should stop again.

Pressing the red "reset" button while the oil burner is running normally will also interrupt or stop the oil burner.

Check the Scavenger Timing cycle of the primary control, using the procedure at Scavenger Cycle Restart Delay Time.

-- the above is paraphrased from Audel

When to Adjust the Oil Burner Scavenger Cycle Restart Delay Time on the RA 116A Protectorelay Switch

The following procedure, recommended by Frank Graham of Audel, tests the scavenger timing cycle of an oil burner that is controlled by a Type RA 116A Protectorelay or "stack relay" primary control.

Protectorelay scavenger timing and recycling timer (C) Daniel Friedman AudelWhen an oil burner is in proper adjustment and is working but has been shut off using the electrical power switch (line switch) to the oil burner, the scavenger timing is checked by turning on the oil burner at the line switch. (See ELECTRICAL POWER SWITCH FOR HEAT). The oil burner should start and operate normally.

Let the oil burner keep running, but watch the outer clutch finger (#3 in our sketch from Audel) in the contr9ol. You can see these parts easily when the control cover has been removed. (Watch out: Live Voltage!).

As the oil burner runs from the moment you've switched on its electrical power, you should see the clutch outer finger move outward until it engages the stop arm (#2). The drive shaft (#4) should continue to move outwards after the clutch finger reaches the stop arm. Only a small amount of movement is needed, but it's very important.

After letting the oil burner continue to run for about two to three minutes longer, open (turn off) and then immediately re-close (turn on) the electrical power to the oil burner (the line switch).
Look at the second hand on your watch when you flip the electrical switch on and off, and begin timing the number of seconds until the oil burner re-starts.

If the oil burner restarts in less than one minute it is re-starting too soon. Turn off the electrical power again, let the heating system cool down. Then adjust the scavenger time period as follows:

Move the recycle stop lever (#1) outwards one notch. (You'll see detent notches on the steel rim against which the stop lever arm slides).

Watch the clutch finger (#3) as it moves outwards.

The clutch finger (#3) should move outwards until it engages the stop arm. The drive shaft (#4) should continue to move outward after the clutch finger reaches the stop. This continued movement, as we said before, is a small but important amount.

Now again switch electrical power to the oil burner on, let the system run as above, and then switch the electrical power quickly off and back on as before.

Again time the length of time until the burner re-starts. The oil burner should stop immediately and should not re-start until a minute or more has passed. If the scavenger period (the "down time" before the oil burner re-starts) is too short repeat this process, moving the stop lever one notch at a time until you've achieved more than a minute of scavenger time.

-- the above is paraphrased from Audel

Share this Article      

...

Technical Reviewers & References

  • InspectAPedia.com® - Daniel Friedman
  • InspectAPedia Bookstore lists recommended books, organized by topic & available for purchase. Most of our articles also include a list of recommended books for the specific article topic as well as other references, and information sources.
  • Critique, contributions wanted: Contact Us to suggest corrections or additions to articles at this website, and if you wish, to receive online listing and credit as a contributor. Particular thanks are due to the many experts and also consumers who read and critique technical articles at InspectAPedia.com.
  • Additional technical contributors & reference sources for this article are listed below.
  • Daniel Friedman - InspectAPedia® Website Author/Editor
  • Audels Oil Burner Guide, Installing, Servicing, Repairing, Frank D. Graham, Theo. Audel & Co., New York 1946, 1947, 1955 (out of print, copies occasionally available from antique book dealers and on EBay). Originally this 364 page guide to oil burner installation, operation, diagnosis, and repair sold for $1.00 - one dollar.
  • Thanks to Alan Carson and Bob Dunlop, Carson Dunlop, Associates, Toronto, for permission to use illustrations from their publication, The Illustrated Home which illustrates construction details and building components. Carson Dunlop provides home inspection education, publications, report writing materials, and home inspection services. Alan Carson is a past president of ASHI, the American Society of Home Inspectors.
  • Critique, contributions wanted: Contact Us to suggest text changes and additions and, if you wish, to receive online listing and credit for that contribution.

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building design, inspection, and repair, and about indoor environment testing, diagnosis, and cleanup are at the InspectAPedia Bookstore.
  • ...
HEATING SYSTEMS
HEATING SYSTEM INSPECTION DIAGNOSIS REPAIR

More Information

InspectAPedia.comInspectAPedia ® Home & Site Map
InspectAPedia Blog - News Updates
Air Conditioning & Heat Pumps
InspectAPedia Bookstore
ELECTRICAL INSPECTION, DIAGNOSIS, REPAIR
Environment
Exteriors
Heating
Home Inspection
Insulate Ventilate
Interiors
Mold Inspect/Test
Plumbing Water Septic
Roofing
Structure
Accuracy & Bias Pledge
Contact Us

More Information on Building Diagnostic Inspections and Repairs

  • Carbon Dioxide Gas Toxicity
  • Carbon Monoxide Gas Toxicity, exposure limits, poisoning symptoms, and inspecting buildings for CO hazards
  • Dust from HVAC? An Investigation of Indoor Dust Debris Blamed on a Heating/Cooling System Reveals Carpet Dust
  • Goodman Furnace High Temperature Plastic Vent HTPV safety recall US CPSC notice
  • Home Heating System Should Be Checked [for proper venting and for CO Carbon Monoxide Hazards - DJF]
  • Inspection Procedures for Oil-Fired Heating Systems Detailed step by step approaches for inspecting complex systems]
  • Lennox Pulse Furnace Safety Inspection/Warranty Program: Carbon Monoxide Warning
  • Oil Tanks - The Oil Storage Tank Information Website: Buried or Above Ground Oil Tank Inspection, Testing, Cleanup, Abandonment of Oil Tanks
  • Oil Tanks Above Ground, UL Standards, guidance for home owners, buyers, and inspectors
  • Plastic Heating Vent Pipe & Other Heating Safety Recall Notices
  • Weil McLain Model GV Gas Boiler/gas valve CPSC recall/repair
  • Domestic and Commercial Oil Burners, Charles H. Burkhardt, McGraw Hill Book Company, New York 3rd Ed 1969.
  • National Fuel Gas Code (Z223.1) $16.00 and National Fuel Gas Code Handbook (Z223.2) $47.00 American Gas Association (A.G.A.), 1515 Wilson Boulevard, Arlington, VA 22209 also available from National Fire Protection Association, Batterymarch Park, Quincy, MA 02269. Fundamentals of Gas Appliance Venting and Ventilation, 1985, American Gas Association Laboratories, Engineering Services Department. American Gas Association, 1515 Wilson Boulevard, Arlington, VA 22209. Catalog #XHO585. Reprinted 1989.
  • The Steam Book, 1984, Training and Education Department, Fluid Handling Division, ITT [probably out of print, possibly available from several home inspection supply companies] Fuel Oil and Oil Heat Magazine, October 1990, offers an update,
  • Principles of Steam Heating, $13.25 includes postage. Fuel oil & Oil Heat Magazine, 389 Passaic Ave., Fairfield, NJ 07004.
  • The Lost Art of Steam Heating, Dan Holohan, 516-579-3046 FAX
  • Principles of Steam Heating, Dan Holohan, technical editor of Fuel Oil and Oil Heat magazine, 389 Passaic Ave., Fairfield, NJ 07004 ($12.+1.25 postage/handling).
  • "Residential Steam Heating Systems", Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
  • "Residential Hydronic (circulating hot water) Heating Systems", Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
  • "Warm Air Heating Systems". Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
  • Heating, Ventilating, and Air Conditioning Volume I, Heating Fundamentals,
  • Boilers, Boiler Conversions, James E. Brumbaugh, ISBN 0-672-23389-4 (v. 1) Volume II, Oil, Gas, and Coal Burners, Controls, Ducts, Piping, Valves, James E. Brumbaugh, ISBN 0-672-23390-7 (v. 2) Volume III, Radiant Heating, Water Heaters, Ventilation, Air Conditioning, Heat Pumps, Air Cleaners, James E. Brumbaugh, ISBN 0-672-23383-5 (v. 3) or ISBN 0-672-23380-0 (set) Special Sales Director, Macmillan Publishing Co., 866 Third Ave., New York, NY 10022. Macmillan Publishing Co., NY
  • Installation Guide for Residential Hydronic Heating Systems
  • Installation Guide #200, The Hydronics Institute, 35 Russo Place, Berkeley Heights, NJ 07922
  • The ABC's of Retention Head Oil Burners, National Association of Oil Heat Service Managers, TM 115, National Old Timers' Association of the Energy Industry, PO Box 168, Mineola, NY 11501. (Excellent tips on spotting problems on oil-fired heating equipment. Booklet.)
InspectAPedia.comInspectAPedia® Home & Site Map - Building & Environmental Inspection, Testing, Diagnosis, Repair, & Problem Prevention Advice: In-depth research & advice on diagnosing, testing, correcting, & preventing building defects & indoor environmental hazards. Unbiased information, no conflicts of interest.
GO TO the MOLD and INDOOR ENVIRONMENT INFORMATION CENTER for in-depth advice on avoiding testing for or cleaning up mold and other indoor environmental hazards, odors, gases, contaminants
The Mold Information Center:
What to Do About Mold in Buildings, When and How to Inspect for Mold, Clean Up Mold, or Avoid Mold Problems
GO TO MOLD TEST KITS: This expert-recommended mold test kit is cheap and yet top performing *IF* you use a competent analysis laboratory!
Use this simple, economical mold test kit
by following our instructions on how to collect and mail mold samples to our lab
GO TO IAQ/MOLD-TEST LAB SERVICES: Mold, Pollen, indoor air quality, field and laboratory services by an expert.Environmental Inspection, Testing, & Diagnosis On-Site IAQ, Gas, Air Testing, Mold Investigation, Sick Building Diagnosis, Lab Services, & Remediation Plan Preparation - indoor air quality testing, problem source determination, supporting lab work, written remediation plan addressing removal of environmental and other hazards and prevention of their recurrence.
GO TO our PRE PURCHASE BUILDING INSPECTION SERVICES: Authoritative information for home buyers and home owners is included with your inspection.
Building Inspection, Problem Diagnosis
, Forensic Investigation & Testing, Repair Consulting

CONTACT Daniel Friedman - Dan is a senior ASHI home inspector, nationally recognized expert on building inspection, building failures, and sick building investigation
Contact Daniel Friedman for website content suggestions or for fee-paid consulting

01/20/2010 - 09/05/2006 - InspectAPedia.com/heat/StackRelaySwitch.htm - © 2010 - 1988 Copyright Daniel Friedman All Rights Reserved - InspectAPedia® is a Registered U.S. Trademark