InspectAPedia.com InspectAPedia®
Google
InspectAPedia
 

Free Encyclopedia of Building & Environmental Inspection, Testing, Diagnosis, Repair

Ask a Question or Search InspectAPedia

  • HOME
  • AIR CONDITIONING
  • ELECTRICAL
  • EXTERIORS
  • HEATING
  • HOME INSPECTION
  • INTERIORS
  • PLUMBING
  • ROOFING
  • SEPTIC SYSTEMS
  • STRUCTURE
  • WATER SUPPLY
  • ENERGY SAVINGS
  • ENVIRONMENT
  • INDOOR AIR IAQ
  • INSULATION
  • MOLD INSPECT TEST REMOVE
  • NOISE
  • ODORS
  • SOLAR ENERGY
  • VENTILATION
  • EXPERTS DIRECTORY
  • CONTACT US



Mobile Phone or PDA view of this websiteMobile View
HEATING SYSTEMS

AFUE DEFINITION, RATINGS
AGE of AIR CONDITIONERS & HEAT PUMPS
AGE of HEATERS, BOILERS, FURNACES
AIR CONDITIONING & HEAT PUMP SYSTEMS
AIR FILTERS for HVAC SYSTEMS

AIR HANDLER / BLOWER UNITS
AIRBOUND HEAT SYSTEM REPAIRS
ANODES & DIP TUBES on WATER HEATERS
ANTI SCALD VALVES
ANIMAL ALLERGENS / PET DANDER
ANIMAL ENTRY POINTS in buildings
ANIMAL ODORS IN buildings
ANODES & DIP TUBES on WATER HEATERS
APPLIANCE EFFICIENCY RATINGS
ASBESTOS IDENTIFICATION IN buildings

BACKDRAFTING HEATING EQUIPMENT
BACKFLOW PREVENTER VALVE, HEATING SYS
BACKFLOW PREVENTER, HEATER WATER FEEDER
BACKUP HEAT for HEAT PUMPS
BANGING HEATING PIPES RADIATORS
BAROMETRIC DAMPERS
BIOGAS PRODUCTION & USE
BLEVE EXPLOSIONS
BLOWER DOORS & AIR INFILTRATION
BLOWER FAN CONTINUOUS OPERATION
BLOWER FAN OPERATION & TESTING
BLUE vs YELLOW COMBUSTION FLAMES
BLUERAY Recall

BOILERS, HEATING
BOILER CHEMICALS
BOILER COMPONENTS & PARTS
BOILER CONTROLS & SWITCHES
BOILER LEAKS CORROSION STAINS
BOILER LEAKS, HOW TO LOCATE
BOILER NOISE SMOKE ODORS
BOILER OPERATING PROBLEMS
BOILER OPERATION DETAILS
BOILER PRESSURE & TEMPERATURE SETTINGS
BUILDING SAFETY HAZARDS GUIDE

CAPACITORS for HARD STARTING MOTORS
CARBON DIOXIDE - CO2
CARBON MONOXIDE - CO
CARBON MONOXIDE WARNING
CHIMNEY INSPECTION DIAGNOSIS REPAIR
CHIMNEYS & Flues - Asbestos Transite Pipe
CHINESE DRYWALL HAZARDS
COOL OFF HEAT, Thermostat Switch
COMBUSTION AIR
COMBUSTION AIR for TIGHT buildings
COMBUSTION GASES & PARTICLE HAZARDS
COMBUSTION PRODUCTS & IAQ
COMPLETE COMBUSTION, Stoichiometric
CREOSOTE FIRE HAZARDS
COMBUSTION GASES & PARTICLE HAZARDS
COMBUSTION PRODUCTS & IAQ
COMPLETE COMBUSTION, Stoichiometric
CONDENSING BOILERS/FURNACES
CONDENSING BOILERS/FURNACES DAMAGE
CONVECTOR HEATERS - HYDRONIC COILS
CREOSOTE FIRE HAZARDS

DEFINITION of Heating & Cooling Terms
DIAGNOSE & FIX AIR CONDITIONER / HEAT PUMP
DIAGNOSE & FIX HEATING PROBLEMS-BOILER
DIAGNOSE & FIX HEATING PROBLEMS-FURNACE
DIRECT VENTS / SIDE WALL VENTS
DIRECTORY of OIL TANK EXPERTS
DRAFT HOODS - gas fired
DRAFT MEASUREMENT, CHIMNEYS & FLUES
DRAFT REGULATORS, DAMPERS, BOOSTERS
DUCT SYSTEM & DUCT DEFECTS
DUST CONTAMINATION FROM HVAC?

ELECTRIC HEAT, DIAGNOSIS, REPAIR
ELECTRIC MOTOR DIAGNOSTIC GUIDE
ELECTRIC MOTOR OVERLOAD RESET SWITCH
ELECTRICAL POWER SWITCH FOR HEAT
EVAPORATIVE COOLING SYSTEMS

FAN, AIR HANDLER BLOWER UNIT
FAN AUTO ON Thermostat Switch
FAN, COMPRESSOR/CONDENSER UNIT
FAN CONVECTOR HEATERS - HYDRONIC COILS
FAN LIMIT SWITCH
FAN NOISES

FILTERS, AIR for HVAC SYSTEMS
FILTERS, OIL on HEATING EQUIPMENT

FIRE SAFETY CONTROLS
FIREPLACES & HEARTHS
FLAME COLOR, BLUE vs YELLOW COMBUSTION
FLOODED HEATING EQUIPMENT REPAIR
FLOODED WATER HEATER REPAIR
FLUE VENT CONNECTORS
FREEZE-PROOF A BUILDING
FUEL OIL TYPES & CHARACTERISTICS
FUEL UNIT, HEATING OIL PUMPS

FURNACES, HEATING
FURNACE CONTROLS & SWITCHES
FURNACE EFFICIENCY, HIGH vs MID
FURNACE HEAT EXCHANGER LEAKS
FURNACE OPERATION DETAILS
FURNACE OPERATING TEMPERATURES

GALVANIC SCALE & METAL CORROSION
GAS BURNER Flame & Noise Defects
GAS FIRED WATER HEATERS
GAS PIPING, VALVES, CONTROLS
GAUGES ON HEATING EQUIPMENT
GEOTHERMAL HEATING SYSTEMS

HEAT EXCHANGER LEAKS
HEAT LOSS in buildings
HEAT LOSS DETECTION TOOLS
HEAT LOSS INDICATORS
HEAT LOSS PREVENTION PRIORITIES
HEAT LOSS R U & K VALUE CALCULATION
HEAT TAPES & CABLES on Roofs for Ice Dams
HEATING COST FUEL & BTU Cost Table

HEATING COST SAVINGS METHODS
HEATING LOSS DIAGNOSIS-BOILERS
HEATING LOSS DIAGNOSIS-FURNACES

HEATING SYSTEM INSPECT DIAGNOSE REPAIR
HEATING SYSTEM INSPECTION DETAILS
HEATING SYSTEM NOISES

HEATING SYSTEM TYPES

HEATING OIL CLOUD WAX GEL POINT
HEATING OIL EXPOSURE HAZARDS, LIMITS
HEATING OIL - OLD, USEABLE?
HEATING OIL PIPING TROUBLES
HEATING OIL SHELF LIFE
HEATING OIL SLUDGE
HEATING OIL USAGE RATE
HEATING SMALL LOADS

HEATING SYSTEM INSPECT DIAGNOSE REPAIR
HEATING SYSTEM NOISES
HEATING SYSTEM SERVICE & MAINTENANCE

HEATING SYSTEM TYPES

HIGH EFFICIENCY BOILERS/FURNACES

HOT WATER HEATERS
HOT WATER IMPROVEMENT

INSULATION INSPECTION & IMPROVEMENT

LP & Natural Gas Safety Hazards

MANUALS & PARTS GUIDES - HVAC
MIXING / ANTI-SCALD VALVES
MOTOR OVERLOAD RESET SWITCH

Natural Gas Combustion
NO HEAT - BOILER
NO HEAT - FURNACE
NOISE / SOUND DIAGNOSIS & CURE
NOISE AIR CONDITIONER / HEAT PUMP
NOISE, DUCT VIBRATION DAMPENERS
NOISE, HEATING SYSTEMS
NOISE, PLUMBING
NOISE, WATER HEATER

ODORS & SMELLS DIAGNOSIS & CURE
ODORS FROM HEATING SYSTEMS
OIL BURNERS
OIL BURNER FUEL UNIT
OIL BURNER INSPECTION & REPAIR
OIL BURNER NOISE SMOKE ODORS
OIL BURNER NOZZLE & ELECTRODES
OIL BURNERS, RETENTION HEAD
OIL BURNER SOOT & PUFFBACKS
OIL FILTERS on HEATING EQUIPMENT
OIL FILTER MISSING
OIL FUEL TYPES & CHARACTERISTICS
OIL & GAS PIPING
OIL LINE CLOGGING FIX
OIL LINE QUICK STOP VALVES
OIL LINE SAFETY VALVES
OIL ODORS, LEAKY OIL TANK PIPING
OIL PUMP FUEL UNIT
OIL SPILL CLEANUP / PREVENTION
OIL TANKS

PULSE COMBUSTION HEATERS

RADIANT HEAT
RADIANT HEAT Floor Mistakes to Avoid
RADIANT HEAT TEMPERATURES
RADIANT SLAB FLOORING CHOICES
RADIANT SLAB TUBING & FLUID CHOICES

RADIATORS
  BANGING HEATING PIPES RADIATORS
  BASEBOARD, CONVECTOR, RADIATOR TYPES
  COLD HOT WATER BASEBOARD / RADIATOR
  COLD STEAM HEAT RADIATORS
  LEAKS at BASEBOARD, CONVECTOR, RADIATOR
  RADIATOR or CONVECTOR COVERS
  RADIATOR or CONVECTOR INSULATION
  RADIATOR STEAM VENTS
  RADIATOR STEAM VENTS, AUTOMATIC
    Install Steam Vents to Control Heat
  RADIATOR VALVES & HEAT CONTROLS
    Radiator Control Valves & Vents
    Manual Radiator Valves
    Hot Water vs Steam Radiator Valves
    Adjust Level of Heat
    Automatic Radiator Valves
  STEAM TRAPS
  UNEVEN HEAT DIAGNOSIS

RELIEF VALVES - TP Valves on Boilers
RELIEF VALVES - Water Heaters
RELIEF VALVES - Water Tanks

SAFETY, HEATING INSPECTION
SAFETY,HOME HEATING TIPS
Safety Recalls, Chimneys, Vents, Heaters
SPILL SWITCHES
STACK RELAY SWITCHES
STAIN DIAGNOSIS on BUILDING INTERIORS

STEAM HEATING SYSTEMS

TANKLESS COILS
THERMAL EXPANSION of MATERIALS
THERMAL MASS in buildings
THERMAL TRACKING & HEAT LOSS
THERMOSTATS, HEATING / COOLING
Transite Pipe Chimneys & Flues

VIDEO GUIDES: Heating System Videos
VIDEO GUIDES - InspectAPedia.com

WATER HEATERS
WATER HEATER SAFETY
WATER HEATERS for HOME HEATING USE?
WATER HEATER NOISES
WATER HEATER SCALE - De-Liming Procedure
WATER HEATER SCALE PREVENTION
WINTERIZE A BUILDING
WOOD, COAL STOVES & FIREPLACES
WOOD STOVE SAFETY

ZONE VALVES

More Information

Steam vent on a radiator (C) Daniel Friedman Automatic Steam Vent Controls for Regulating Steam Heat
InspectAPedia®  -      

  • Automatic or Thermostatically Controlled Steam Vents for steam heat radiators
  • How to Adjust or Control the Level of Heat From Radiators
  • Guide to Choosing & Installing Adjustable or Thermostatically Controlled Steam Vents to Control Steam Heat
  • How to deal with radiator valves that are stuck or broken
  • Use of thermostatically controlled steam radiator valves for automatic room heat control
  • Use of thermostatically controlled steam vents to control steam radiators
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers nor with topics or services discussed at this website.

This article describes the use, adjustment, diagnosis & repair of automatic, thermostatically controlled steam heating radiator air vents or steam vents to control or balance steam heat in buildings. We provide articles that help in diagnosing and repairing no-heat problems with each types of hot water or steam or fan convector heat delivery systems.

This website answers most questions about all types of heating systems and gives important inspection, safety, and repair advice. If you don't know what kind of heat your building uses, we explain how to figure out the answer at HEATING SYSTEM TYPES. If your heating system is not working properly, see NO HEAT - BOILER or NO HEAT - FURNACE.

© Copyright 2010 Daniel Friedman, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use links at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

Automatic or Thermostatically Controlled Steam Vents

Steam vent on a radiator (C) Daniel Friedman

When steam is first rising in a one pipe or two pipe steam heating system, the steam heating radiator will be cool as will be the steam vent. Our photo (left) shows what looks like a Hoffman 1A float-type radiator steam vent. This is a residential low-pressure (1.5 psig) steam vent. Similar models include the Hoffman Model 40 (6 psig) and model 70A (11 psig).

Two Pipe Steam Heat

In a two-pipe steam heat system, steam rises through the supply side of the radiator (where the radiator valve is found) and may push air and later condensate out through the return or condensate drain side of the radiator.

One-Pipe Steam Heat

On one-pipe steam heat systems the radiator valve is normally fully open (for the radiator to operate properly) or fully shut (no heat); you may find that some one-pipe steam heating system radiators will not work properly if the valve is left "in between" these positions.

Steam rises and enters each heating radiator through a single pipe, pushing air out of the radiator through its vent. Condensate returns to the boiler through the same pipe, passing out through a special passage in the radiator control valve.

Role of the steam vent on one pipe steam heat systems:

Unlike radiator valves that are closed manually or automatically to control the entry of hot water or steam into a heating radiator, steam vents are located at the opposite end of the radiator from the valve and are used to vent air out of a steam radiator so that steam can rise into and heat the unit. When steam reaches and heats the steam vent, the vent is designed to close and stop venting air (or steam), and the radiator will heat.

The steam vent opens, allowing air inside the radiator to be pushed out by rising steam that enters the radiator at the radiator bottom where a radiator valve is present and open.

The "hissing" sound you hear from the steam vent is air being pushed out of the radiator, and is normal. When the steam radiator and steam vent have become warm or hot, the steam vent closes (and is quiet).

Steam vents that won't open properly:

If a steam vent stops working and fails to open, rising steam cannot enter the radiator and it will be slow to heat or may not heat at all. If your one pipe steam radiator won't get hot, the air vent may be clogged or it may just be worn out and need replacement.

Steam vents that won't close properly:

If a steam vent stops working properly and fails to close, the vent will hiss and release steam (and sometimes produce condensate or water) continually all during the heating cycle, wasting heat, increasing heating cost, and in some cases creating a moisture problem or even a burn risk at the radiator.

At RADIATOR STEAM VENTS we discuss other steam vent problems such as spitting water, clogging, etc.

Guide to Choosing & Installing Adjustable or Thermostatically Controlled Steam Vents to Control Steam Heat

Types & Properties of Steam Radiator Vents

  • Thermostatically-controlled no-float steam vents
  • Float-type steam vents: an water+alcohol-filled float inside the steam vent heats, rises, and closes the vent as the radiator heats. The float also rises to prevent water from spitting out of the vent should condensate rise inside the radiator or vent. Rust or sediment can clog the float vent opening and interfere with its proper operation. Excessive steam pressure can also prevent the vent from operating properly.
  • Adjustable steam vents operate similarly to the float-type steam vents described above, but add the feature of adjustable air vent opening size so that the air venting rate can be better matched to the radiator size. (Larger steam radiators need a larger air vent opening.) Examples: Hoffman Model 1A (Part No. 401422) adjustable air valve with 6 settings (1-slow to 6-fast venting); VariValve® Quick-Vent. Those vents are designed for traditional steam radiators. If your steam heat is by a steam convector unit, different steam vents are required, such as the Hoffman Specialty Model 1B (Part No. 401425).
  • Adjustable-Thermostatically-operated steam vents (shown below) include an adjustable room temperature thermostat that allows the occupant to set the desired room temperature. Setting this control actually adjusts the rate at which the steam vent permits air to escape from the individual radiator, similar to the adjustable steam vents described above, but in this case once the thermostat is set, the automatically regulating steam vent is responding to the room temperature setting.

Each of these steam vent types is discussed below.

By controlling the rate at which a steam radiator gets hot, adjustable steam vents are a key instrument for balancing steam heat in a building.

Watch out: although adjustable steam vents can control the rate at which a steam radiator gets hot, these adjustable air vents are not identical in function and application nor is heat control using adjustable steam vents identical with that provided using thermostatically controlled radiator valves.

Thermostatically-controlled no-float steam vents

Hoffman specialty steam vent (C) Hoffman Specialty

Watch out: Some "thermostatically operated" steam vents include user-adjustable controls that permit the steam vent to operate as an individual room thermostat. But watch out: other "thermostatically operated" steam vents may be units that are not adjustable for controlling room temperature. These "thermostatically controlled" vents are describing how the vent works internally, not its function as an occupant-adjustable room temperature control.

Hoffman Specialty heating products offers thermostatically operated steam vents (such as the Hoffman Special Steam Vent Model 3 (Part No. 401419) no internal float, image at left) that can automatically regulate heat from individual steam radiators. These vents are used for Air Line or Paul Systems. The Hoffman Specialty Thermostatic Temperature Regulators (Series 1140 & 1141) are designed for commercial and institutional HVAC systems. These devices permit a set temperature ranging from 40degF. through 220 degF in increments of 40 degF. (no fine tuning).

Watch out: these steam regulators fail "open" (meaning heat fully on), so Hoffman warns that an alarm or cut-off must be installed where overheated water (or steam) could cause harm. Failure to follow this warning could cause serious burns, personal injury, or death.

For more conventional steam vents, take a look at the Hoffman Specialty series 2000 and the Hoffman Model 3 Steam Air Line Valve (Part No. 401419) for an example.

A Hoffman Vent, Model 3, is also thermostatically controlled, operates on temperature only, and does not close against water. Hoffman also produces conventional steam radiator vents such as their traditional Model 1A air valve, and also the Hoffman Model 74 float operated steam unit heater air valve. But these vents do not include a readily-accessible temperature adjustment. For steam heating convectors, different steam vent models are required due to the different operating pressures and vent locations that may be present.

Watch out: when replacing a steam vent be sure that you buy the proper vent for your heating radiator or convector type, or that the steam vent specifications of the new steam vent match the old one. Hoffman and other control manufacturers provide selection guidelines for steam vents as well as their other controls.

Float-type steam vents

As we introduced above, float type steam vents use a water+alcohol-filled float inside the steam vent heats, rises, and closes the vent as the radiator heats. The float also rises to prevent water from spitting out of the vent should condensate rise inside the radiator or vent. Rust or sediment can clog the float vent opening and interfere with its proper operation. Excessive steam pressure can also prevent the vent from operating properly.

Adjustable Steam Radiator Vents Permit Adjusting Radiator Vent & Heat-Up Rates

Also as we introduced above, manually adjustable steam vents operate similarly to the float-type steam vents described above, but add the feature of adjustable air vent opening size so that the air venting rate can be better matched to the radiator size. (Larger steam radiators need a larger air vent opening.)

Examples of manually adjustable vent-rate steam vents and their steam venting rates include:

  • Flair #101 steam vents (4 vent rate settings adjust vent rate from 0.00 to about 0.20 CFM
  • Gorton steam vents, adjustable depending on model from 0 to 0.4 CFM venting rate.
  • Hoffman Model 1A (Part No. 401422) adjustable air valve with 6 settings (1-slow to 6-fast venting); If your steam heat is by a steam convector unit, different steam vents are required, such as the Hoffman Specialty Model 1B (Part No. 401425). Hoffman steam vents handle 0.00 to about 0.20 CFM venting rates.
  • Hoffman #40 or #41 steam vents.
  • VariValve® Quick-Vent from Heat Timer (sliding vent rate adjuster). Those vents are designed for traditional steam radiators. According to Heat-Timer, their VariValve steam vent can be adjusted from 0 to 0.72 cubic feet per minute (CFM), faster than other steam vent valves. Radiator vent flow rates were tested at a gauge pressure of 1" W.C.

Notes:

  1. Steam radiator vent rates and system pressure: If your steam system pressures are lower than the 1" W.C. test data above, (as likely the case) the steam radiator vent rates will be slower, but the vent rate relationships among these valves probably will be the same.
  2. Main line air vents are also used on steam systems to quickly purge air from the main steam pipes ahead of the radiators. Hoffman, Gorton, and Heat-Timer also provide main line steam vents and automatic or adjustable steam vents for the main lines in steam heating systems.

Additional steam vents are listed at references below.

Especially in a single pipe steam heating system, the venting rate of radiators affects how the heating system works, how quickly heat rises in individual rooms, and the ability to balance the delivery of heat among different building areas.

Adjustable Thermostatically-operated steam vents

Thermostatically controled adjustable steam radiator ventThermostatically-operated steam vents (shown here) include an adjustable room temperature thermostat that allows the occupant to set the desired room temperature. Setting this control actually adjusts the rate at which the steam vent permits air to escape from the individual radiator, similar to the adjustable steam vents described above, but in this case once the thermostat is set, the automatically regulating steam vent is responding to the room temperature setting.

Some adjustable automatic air vents for steam radiators include:

  • Gorton air vents - Tel: 908-276-1323 (size the vent to match the radiator)
  • Hoffman model 1A, also models Hoffman 40, Hoffman 41, and Hoffman 43 (different piping arrangements) have 6 port settings and operate at a maximum steam pressure of 10 psi (fine for residential systems). This type of steam valve allows you to adjust how quickly the radiator gets hot; it does not respond to room temperature.
  • VariValve® from Heat Timer Corporation, adjustable steam radiator vent for one pipe steam systems uses a sliding lever on the valve to speed or slow the venting from radiators. Useful in balancing steam heat distribution in buildings.
  • Vent-Rite #1 Adjustable Air Elimination Steam Vents (Barnes & Jones).
  • Watts Water Technologies, Model 0841005_SVA adjustable steam vent
  • Webstone air vent valves

Thanks to reader Paul Ruud for discussing improved steam heat controls and thermostatically operated steam radiator valves and air vents.

Watch out: If the radiator continually makes noises (whistling or wheezing) at the steam vent, there is a problem that needs to be fixed: a bad steam vent, steam piping problem, steam pressure set too high, or boiler oversized for the heating distribution system.

Watch out: to be sure your steam heating system and its controls are properly adjusted excessive steam pressure can be dangerous.

Questions & Answers regarding this article

.

Ask a Question or Search InspectAPedia

HTML Comment Box is loading comments...

Recommend / Share this Article            

...

Technical Reviewers & References

  • InspectAPedia.com® - Daniel Friedman - Publisher & Editor.
  • InspectAPedia Bookstore lists recommended books, organized by topic & available for purchase. Most of our articles also include a list of recommended books for the specific article topic as well as other references, and information sources.
  • Critique, contributions wanted: Contact Us to suggest corrections or additions to articles at this website, and if you wish, to receive online listing and credit as a contributor. Particular thanks are due to the many experts and also consumers who read and critique technical articles at InspectAPedia.com.
  • Additional technical contributors & reference sources for this article are listed below.

Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.


RADIATORS
  BANGING HEATING PIPES RADIATORS
  BASEBOARD, CONVECTOR, RADIATOR TYPES
  COLD HOT WATER BASEBOARD / RADIATOR
  COLD STEAM HEAT RADIATORS
  LEAKS at BASEBOARD, CONVECTOR, RADIATOR
  RADIATOR or CONVECTOR COVERS
  RADIATOR or CONVECTOR INSULATION
  RADIATOR STEAM VENTS
  RADIATOR STEAM VENTS, AUTOMATIC
    Install Steam Vents to Control Heat
  RADIATOR VALVES & HEAT CONTROLS
    Radiator Control Valves & Vents
    Manual Radiator Valves
    Hot Water vs Steam Radiator Valves
    Adjust Level of Heat
    Automatic Radiator Valves
  STEAM TRAPS
  UNEVEN HEAT DIAGNOSIS


STEAM HEATING SYSTEMS
  AQUASTAT CONTROL Functions
  BACKDRAFTING HEATING EQUIPMENT
  BACKFLOW PREVENTER VALVE, HEATING SYS
  BANGING HEATING PIPES RADIATORS
  CAD CELL RELAY SWITCH
  CHECK VALVES, HEATING SYSTEM
  Chemical treatments, Boiler
  Circulator Pumps & Relays
  COMBUSTION GASES & PARTICLE HAZARDS
  CONDENSATE RETURN PIPES, PUMPS, STEAM
  DIAGNOSE & FIX BOILER
  DRAFT HOODS - gas fired
  DRAFT MEASUREMENT, CHIMNEYS & FLUES
  DRAFT REGULATORS, DAMPERS, BOOSTERS
  ELECTRIC MOTOR OVERLOAD RESET SWITCH
  ELECTRICAL POWER SWITCH FOR HEAT
  EXPANSION TANKS
  FIRE SAFETY CONTROLS
  GAUGES, HEATING EQUIP.
  LIMIT SWITCH, BOILER
  LOW WATER CUTOFF VALVE
  MIXING / ANTI-SCALD VALVES
  PRESSURE, TEMPERTURE SETTINGS, CONTROLS
  PRESSURE SWITCH, STEAM BOILER
  RELIEF VALVES - STEAM TP VALVES
  SIGHT GLASS, STEAM BOILER
  SPILL SWITCHES
  STACK RELAY SWITCH
  STEAM PRESSURE GAUGE
  STEAM TRAPS
  STEAM VENTS
  THERMOSTATS, HEATING / COOLING
  WATER FEEDER Valves, Steam

  • Barnes & Jones Corporation, 91 Pacella Park Drive Randolph, MA 02368, Tel: 781-963-8000calibrated steam traps and vents, Email: bnesbitt@barnesandjones.com. Vent-Rite steam vents for radiator control.
  • Energy Savers: Heat Distribution Systems, Steam Radiators & Hot Water Radiators, U.S. Department of Energy, web search 12/27/2010, original source: http://www.energysavers.gov/your_home
    /space_heating_cooling/index.cfm/mytopic=12580
  • Gorton Heating Corporation, 546 South Avenue East, Cranford, New Jersey 07016, Tel: 908-276-1323, email: info@gorton-valves.com, fast venting valves for steam heating systems.
  • "Rv-4 One-Pipe Steam Radiator Valve", available from Armstrong International, 816 Maple Street, Three Rivers, MI 49093 USA, Tel: (269) 273-1415, Armstrong has offices in Beijing, China, Belgium, India and Mexico. Web search 12/27/2010, original source:
    http://www.armstronginternational.com/thermostatic-valves-rv-4-one-pipe.
  • "Special Steam Vents", Hoffman Specialty heating products, web search 12/27/2010, original source:
    http://www.hoffmanspecialty.com/pdf/hs900/HS900-3474.pdf
  • "Steam and Water Vents, Selection Guidelines - Steam Vents", Hoffman Specialty, web search 12/27/2010, original source:
    http://www.hoffmanspecialty.com/pdf/hs900/HS900-stvents.pdf
  • Hoffman 1A adjustable steam vents, available from Hoffman Specialty, ITT, web search 12/27/2010, original source:
    http://www.drillspot.com/products/51570/Hoffman_1A_Adjustable_Automatic_Air_Vent_For_Steam_Radiators
  • Hoffman Convector Steam Vents, available from Hoffman Specialty, ITT, web search 12/28/2010, original source:
    http://www.hoffmanspecialty.com/pdf/hs900/HS900-conv109.pdf
  • Report 95-14, PB96-198163 Thermostatic Radiator Valve (TRV) Demonstration Project, contact NYSERDA. 17 Columbia Circle, Albany, NY 12203-6399 Toll-Free: 1-866-NYSERDA, Tel:(518)465-6252, Ext. 241. Web Search 12/27/2010, original source: http://www.homeenergy.org/archive/hem.dis.anl.gov/eehem/96/960509.html
  • VariValve® Quick-Vent from Heat Timer, adjustable radiator and main line vent valves for one pipe steam systems, web search 12/27/2010, original source: http://www.heat-timer.com/enFiles/ProductDocument/literature/VariV056082C.pdf
  • "Care & Feeding of Air Vents", Dan Holohan, Old House Journal Online, November 2004
  • Steam Boiler Inspection, Diagnosis, Repair books at the InspectAPedia bookstore - Amazon.com
  • The Steam Book, 1984, Training and Education Department, Fluid Handling Division, ITT [probably out of print, possibly available from several home inspection supply companies] Fuel Oil and Oil Heat Magazine, October 1990, offers an update, (see next item in this list). ITT Fluid Technology, 1133 Westchester Avenue
    White Plains, NY 10604, tel +1 914 304 1700 fax +1 914 696 2950 www.ittfluidbusiness.com
  • Principles of Steam Heating, $13.25 includes postage. Fuel oil & Oil Heat Magazine, 389 Passaic Ave., Fairfield, NJ 07004.
  • The Lost Art of Steam Heating, Dan Holohan, 516-579-3046 FAX
  • Principles of Steam Heating, Dan Holohan, technical editor of Fuel Oil and Oil Heat magazine, 389 Passaic Ave., Fairfield, NJ 07004 ($12.+1.25 postage/handling).
  • "Residential Steam Heating Systems", Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
  • The Heat Efficiency of Steam Boilers, Bryan Donkin
  • Steam Boiler Operation, Principles & Practice, James J. Jackson
  • Thanks to reader Paul Ruud for discussing improved steam heat controls and thermostatically operated steam radiator valves and air vents, 12/27/2010.

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.
  • Home Reference Book - Carson Dunlop The Home Reference Book - the Encyclopedia of Homes, Carson Dunlop & Associates, Toronto, Ontario, 2010, $69.00 U.S., is available from Carson Dunlop. The Home Reference Book is a bound volume of more than 450 illustrated pages that assist home inspectors and home owners in the inspection and detection of problems on buildings. The text is intended as a reference guide to help building owners operate and maintain their home effectively. InspectAPedia.com ® author/editor Daniel Friedman is a contributing author. Field inspection worksheets are included at the back of the volume.
  • Carbon Monoxide Gas Toxicity, exposure limits, poisoning symptoms, and inspecting buildings for CO hazards
  • DUST CONTAMINATION FROM HVAC? An Investigation of Indoor Dust Debris Blamed on a Heating/Cooling System Reveals Carpet Dust
  • Fuel Oil & Oil Heating Magazine, 3621 Hill Rd., Parsippany, NJ 07054, 973-331-9545
  • Goodman Furnace High Temperature Plastic Vent HTPV safety recall US CPSC notice
  • Home Heating System Should Be Checked [for proper venting and for CO Carbon Monoxide Hazards - DJF]
  • Inspection Procedures for Oil-Fired Heating Systems Detailed step by step approaches for inspecting complex systems]
  • Lennox Pulse Furnace Safety Inspection/Warranty Program: Carbon Monoxide Warning
  • Oil Tanks - The Oil Storage Tank Information Website: Buried or Above Ground Oil Tank Inspection, Testing, Cleanup, Abandonment of Oil Tanks
  • Oil Tanks Above Ground, UL Standards, guidance for home owners, buyers, and inspectors
  • Plastic Heating Vent Pipe & Other Heating Safety Recall Notices
  • Weil McLain Model GV Gas Boiler/gas valve CPSC recall/repair
  • Domestic and Commercial Oil Burners, Charles H. Burkhardt, McGraw Hill Book Company, New York 3rd Ed 1969.
  • National Fuel Gas Code (Z223.1) $16.00 and National Fuel Gas Code Handbook (Z223.2) $47.00 American Gas Association (A.G.A.), 1515 Wilson Boulevard, Arlington, VA 22209 also available from National Fire Protection Association, Batterymarch Park, Quincy, MA 02269. Fundamentals of Gas Appliance Venting and Ventilation, 1985, American Gas Association Laboratories, Engineering Services Department. American Gas Association, 1515 Wilson Boulevard, Arlington, VA 22209. Catalog #XHO585. Reprinted 1989.
  • The Steam Book, 1984, Training and Education Department, Fluid Handling Division, ITT [probably out of print, possibly available from several home inspection supply companies] Fuel Oil and Oil Heat Magazine, October 1990, offers an update,
  • Principles of Steam Heating, $13.25 includes postage. Fuel oil & Oil Heat Magazine, 389 Passaic Ave., Fairfield, NJ 07004.
  • The Lost Art of Steam Heating, Dan Holohan, 516-579-3046 FAX
  • Principles of Steam Heating, Dan Holohan, technical editor of Fuel Oil and Oil Heat magazine, 389 Passaic Ave., Fairfield, NJ 07004 ($12.+1.25 postage/handling).
  • "Residential Steam Heating Systems", Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
  • "Residential Hydronic (circulating hot water) Heating Systems", Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
  • "Warm Air Heating Systems". Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
  • Heating, Ventilating, and Air Conditioning Volume I, Heating Fundamentals,
  • Boilers, Boiler Conversions, James E. Brumbaugh, ISBN 0-672-23389-4 (v. 1) Volume II, Oil, Gas, and Coal Burners, Controls, Ducts, Piping, Valves, James E. Brumbaugh, ISBN 0-672-23390-7 (v. 2) Volume III, Radiant Heating, Water Heaters, Ventilation, Air Conditioning, Heat Pumps, Air Cleaners, James E. Brumbaugh, ISBN 0-672-23383-5 (v. 3) or ISBN 0-672-23380-0 (set) Special Sales Director, Macmillan Publishing Co., 866 Third Ave., New York, NY 10022. Macmillan Publishing Co., NY
  • Installation Guide for Residential Hydronic Heating Systems
  • Installation Guide #200, The Hydronics Institute, 35 Russo Place, Berkeley Heights, NJ 07922
  • The ABC's of Retention Head Oil Burners, National Association of Oil Heat Service Managers, TM 115, National Old Timers' Association of the Energy Industry, PO Box 168, Mineola, NY 11501. (Excellent tips on spotting problems on oil-fired heating equipment. Booklet.)
  • Links to our list of additional information on heating system inspection, repair, maintenance
  • ...

Home About Us Accuracy Contact Us Content Use Policy Printing Tips Privacy Website Description © 2012 Copyright InspectAPedia.com