InspectAPedia®   -   Search InspectApedia

Honeywell room thermostatHeat Won't Turn OFF: troubleshoot the thermostat
4 Steps to take if the heating system won't turn off

Diagnose & fix heat that won't turn off when it should: here we discuss various causes of too much heat or of a heating system that does not shut off when it should.

We explain how to diagnose and fix thermostat switch settings, switch settings right at the air conditioner or furnace air handler, and we review thermostat wiring problems that cause a heating system or cooling system to stay ON when it should not.

We provide a sequence of diagnostic steps that determine if the problem is at the thermostat, the thermostat wiring, or at other heating or cooling system controls.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

Thermostat Troubleshooting: heating or cooling system won't turn OFF

Honeywell digital room thermostat (C) Daniel FriedmanHere we discuss how to diagnose & fix a thermostat that keeps calling for heating or cooling when it should not.

A separate article, HEAT WON'T TURN OFF, gives diagnostic procedures for other reasons why building heat wont' turn off besides problems at the thermostat itself.

Article Contents

First Step: Change the thermostat setting up or down

If the heating system won't turn OFF, that is if heat keeps being delivered even when you don't want it, set the thermostat to its lowest temperature setting and wait three to five minutes.

Or if your thermostat has a HEAT OFF COOL or FAN AUTO OFF control, set the control to OFF or COOL.

For help locating these thermostat switches see THERMOSTAT SWITCHES, EXTERNAL.

Watch out: for warm air heat blower units behave differently than hot water or steam heat systems: to avoid damage to the heat exchanger the air handler or blower unit will normally keep running for a minute or even a few minutes after the thermostat has stopped calling for heat. So for warm air heating systems, give the system a few minutes to shut down.

If the air handler, blower unit, or fan won't stop,

see FAN WONT STOP - THERMOSTAT SWITCH

For hot water and steam heating systems, because the heating baseboards, convectors, or radiators will be hot and because they have some thermal mass, heat continues to be delivered for a longer interval even after the heating system itself has stopped.

Therefore to check whether or not setting the thermostat temperature down to its lowest setting (or to OFF) has turned OFF the heating system you need to listen to the heating unit itself to observe that it has stopped.

If the cooling system wont' turn OFF, that is if cool air keeps being delivered even when you don't want it, we do the opposite: set the thermostat to its highest temperature, or if your thermostat has a HEAT OFF COOL or FAN AUTO OFF control, set the control to OFF or HEAT.

Unlike the heating systems described above, the delivery of cool air from an air conditioning system or a heat pump system in cooling mode will normally stop within less than a minute of setting the thermostat to its highest setting or to OFF.

Step 2: confirm that the problem is in the thermostat or its wiring

Forced Warm Air Heat Won't Stop

Programmable thermostat

If your heating system is by forced warm air (a furnace system) then check two switches that can cause the blower fan to run continuously even if the furnace is not heating the air:

furnace fan limit switch

While you may find good reason to keep the blower fan running continuously for now, to diagnose the problem make sure that both of these switches are set to FAN OFF.

See details

at BLOWER FAN CONTINUOUS OPERATION

Watch out: not all forced warm air furnace heating systems have a Manual-On switch on the limit switch, and not all thermostats include a FAN-ON switch on the thermostat.

All Heating Systems: forced air, warm air, hot water, steam, heat pump, electric: stuck "on" step 2 - continued

Aquastat showing wiring connections (C) Daniel FriedmanDisconnect the thermostat from the heating or cooling system - at the heating or cooling equipment.

It's easy to isolate the room thermostat and its wiring from the heating or cooling system: we simply remove the two thermostat wires right at the primary control for the heating or cooling system involved. Typically the two thermostat wires are red and white and are connected in the controller to terminals T1 and T2.

Our photo (left) shows the red and white thermostat wires connected to a heating boiler aquastat control - look at the top left corner of the photo. [Click to enlarge this or any photo or chart seen at InspectApedia.com]

Zone valve wire connections (C) Daniel FriedmanOK so it's not always as trivial as I just said. Multi-zoned heating systems may mean you have to follow the individual thermostat's wires to find just which control they operate.

If you are diagnosing a heating system that is controlled by a single room thermostat, then there will be one wall thermostat, one pair of wires that run between the thermostat and a primary heater or air conditioner controller, and one primary controller at the heater or air conditioner.

Typically these are

AQUASTAT CONTROLS for hot water heat (heating boilers),

or a FAN LIMIT SWITCH for warm air heat (furnaces).

An air conditioner or heat pump will be controlled by thermostat wires connected to a control board or relay in the air handler and/or compressor/condenser unit.

But in multi-zoned heating systems there may be multiple hot water zone valves or multiple air duct zone dampers. In those systems you will need to follow the individual problem thermostat wires to the specific controller such as an individual hot water heating zone valve to make the disconnection we discuss here.

Keep in mind that a zone valve can become stuck in the OPEN position or it may even be manually latched "open" to continue to allow heat to flow.

See ZONE VALVES, HEATING

Our photo above shows a rats nest of wires at an older hot water heating system zone valve. Two of these, red and white, will be coming from the thermostat and will tell the zone valve to open on a call for heat. Additional wires from the zone valve tell the circulator pump to run.

Many room thermostats for heating and cooling have more than two wires connected to the thermostat. But in just about every case, just two wires are actually being used to turn the heater, air conditioner, or heat pump ON or OFF.

Help in sorting out thermostat wires is provided in our articles starting

at THERMOSTAT WIRE CONNECTIONS

and at THERMOSTAT WIRING COLOR CODES

and at SHORTING THERMOSTAT WIRES to ID R W B.In those articles you'll also find thermostat wiring diagrams and details for just about every type of room thermostat.

Step 3: check for damaged thermostat wiring

Room thermostat with unit removed to show the two thermostat wires (C) DanieL Friedman

Disconnect the thermostat wires at the thermostat:

when the heat is on and running and the thermostat is set to say 68F, when the room reaches 68F (measured at the thermostat on its scale), just disconnect the thermostat wires right there at the thermostat. (See our warning at Step 2.)

Our photo (left) shows the simplest case: a red and white wire from the wall thermostat turn a heating unit on (if they are connected by the thermostat or manually by touching them together) or off if they are disconnected.

Pulling the thermostat off of its mounting plate in this instance accomplishes "disconnect the thermostat wires at the thermostat" instruction.

Since a room thermostat is basically an ON-OFF switch that calls for heating or cooling in response to room temperature, when we disconnect the thermostat itself, that's the same as NOT calling for heating or cooling.

Step 4: what to do when the problem is not in the thermostat or thermostat wiring

Emergency electrical power OFF switch for heating equipment (C) Daniel FriedmanTurn Off Electrical Power

 to the Heating or Cooling Equipment. Call your heating or air conditioning service company for further diagnosis and repair help.

The equipment should STOP immediately.

Details about this switch are

at ELECTRICAL POWER SWITCH FOR HEAT

Watch out: Don't cycle heating or cooling equipment ON and OFF rapidly using the electrical power switch or any other control.

For heat troubleshooting, wait at least five minutes between on-off cycles;

For cooling system troubleshooting wait at least fifteen minutes to minimize the risk of equipment damage.

On rare occasions malfunctioning controls on heating equipment may continue to feed fuel to an oil or gas burner, requiring that fuel also be shut off. Turn off the fuel supply following instructions

at OIL or GAS FUELED HEATING EQUIPMENT SHUTOFFS.

Watch out: as we warned earlier, warm air heat blower units behave differently than hot water or steam heat systems: to avoid damage to the heat exchanger the air handler or blower unit will normally keep running for a minute or even a few minutes after the thermostat has stopped calling for heat.

For warm air heating systems, give the system a few minutes to shut down.

Examples of Diagnosing Too Much Heat or Heat Won't Turn Off - starting at the room thermostat

Reader Question: how do I fix a thermostat that I have to set lower than the level of heat I want?

My traditional honeywell simple dial-type thermostat on the wall has two pointers and two temp. scales. However I have to set it on 60 degrees to get heat temp to 70 degrees. What can I do? It was working fine until my condo changed the air/heating system this summer. - Jeannette 1/23/2013

Reply: check these reasons for a room thermostat that keeps calling for heat

Jeannette,

On most two-scale room thermostats, one scale reads the current or actual room temperature while the other scale is the set temperature - and is adjustable.

When you move or adjust the thermostat to call for a different room temperature you will see the scale pointer move to your new setting on the "set" scale.

You are describing having to set the thermostat lower (60F) than the desired temperature (70F) to get the proper level of heat in your home. In other words, you say that the room gets too hot - hotter than you asked-for. Here are some things that would cause that problem:

 




ADVERTISEMENT





Reader Comments, Questions & Answers About The Article Above

Below you will find questions and answers previously posted on this page at its page bottom reader comment box.

Reader Q&A - also see RECOMMENDED ARTICLES & FAQs

On 2022-08-14 by InspectApedia-911 (mod) - thermostat wiring problem means too much heat

@Chelsea,

If you loosen the thermostat on the wall and look on the back to see where the wires enter you should see a white and a red wire. If you follow those wires and disconnect either of them at the thermostat itself that will turn off the heat.

If the heat is still on after that then it's possible that the thermostat wires are shorted together somewhere enroute and need to be disconnected at their other end, at the controller on the heater.

On 2022-08-13 by Chelsea

Thermostat broke and I can’t figure out how to turn off the heat! Help!

broken thermostat won't turn off heat (C) InspectApedia.com Chelsea

On 2022-02-28 by Inspectapedia Com Moderator

@Anonymous,

Rather than re-writing our advice above, the best place to start is by going through the 4 steps listed above on this page for troubleshooting your thermostat. Not knowing anything about your heating system or wiring, that is the best first step.

For possible reasons other than your thermostat for the heat not turning off, please see

HEAT WON'T TURN OFF

Sharing your location (city and country) and what type of thermostat you have may also be useful. Feel free to add a photo of your thermostat as well.

Please let us know if you have additional questions.

On 2022-02-28 by Anonymous

We have seperate thermostat in each room one will not shut off just keep running

On 2022-02-20 by Inspectapedia Com Moderator - How do I troubleshoot a mercury thermostat?

@Darlene V Quinn,

Actually the article above on this page describes things to do when your heat won't turn off and you suspect the problem is at the thermostat. Love usually anything to do with the mercury in the thermostat it's often dust and dirt making the thermostat stick or shorted thermostat wires.

Please do take a look at the advice given on the page above. Let me know how that works for you.

On 2022-02-19 by Darlene V Quinn

I have a mercury thermostat hooked to my hot-water boiler system. The temperature is reading 75 degrees in my basement on that thermostat and the boiler keeps turning on all day and night. How do I troubleshoot a mercury thermostat? It's over 40 years old but I read mercury thermostats usually don't go bad. Thanks.

On 2022-01-25 by Inspectapedia Com Moderator

@David Louis Wert,

More likely there is a wiring error or possibly a short between two thermostat wires.

Check out the Diagnostics given on the page above.

On 2022-01-25 by David Louis Wert

new thermostat. The heater will not shut down all the time. We have to manually shut it down at the breaker. We turn thermostat off and it still will not shut down. Could we possibly have brought a bad one?

On 2021-07-13 by danjoefriedman (mod) - step through diagnostics before replacing thermostat

@Denise,

Before replacing the thermostat - as it may be perfectly fine - try stepping through the diagnostic suggestions given on the page above. It would be a shame to toss a good thermostat only to discover, while installing its replacement, that the problem lies elsewhere, such as in shorted thermostat wires or a bad A/C control board.

On 2021-07-13 by Denise

My thermostat is on auto running my air conditioner it has reach 70 degrees and normally it will shut off once the house reach that temperature but it continues to run. Is it time for me to replace my thermostat?

On 2021-06-28 by danjoefriedman (mod) - Honeywell thermostat won't turn off heat

@sarah,

You landed on the correct page for this problem. Our best and most detailed advice is given above in a sequence of steps that you can follow. I will try those and let me know what happens

On 2021-06-28 by sarah

I have a Honeywell computer chip roter it does do anything and I cannot turn the heat off it is now 91d inside my apartment. I just do not know what to do next

On 2021-02-07 by danjoefriedman (mod) - ecobee thermostat display

Dan

Let's start with the diagnostic steps at NO HEAT - FURNACE (this assumes by "furnace" you mean that you have forced warm air heat.

If you have hot water (radiator, baseboard, steam) heat start at NO HEAT - BOILER

Let me know what you find.

On 2021-02-07 by Dan

My ecobee thermostat displays:There may be a problem with the furnace. For the past 2 hours the thermostat has been calling for heat, but the room temperature has decreased by 1.6C. Is there something wrong with the furnace?

Ecobee thermostat display (C) InspectApedia.com Dan

Reader Question: possible shorted thermostat wires

Our furnace thermostat failed after an adjacent water heater installation. I noticed that wires were pinched between the water heater and the gas pipe.

After I loosened the safety straps and freed the wire, the thermostat works. (I reset the furnace).

Were squished wires the cause of a temporary short and will the wires keep working if they are undisturbed? - Larry 8/2/11

Reply: check for shorted wires and for thermostat transformer damage as well as for blown fuse

Yes it's surely possible that your thermostat wires were shorted. Now a short in those wires sometimes lets you off the hook with no trouble, since the wires and thermostat are basically an "on-off" switch that calls for heat (or no heat).

But a thermostat wire short at the transformer could burn out the low voltage transformer that powers the thermostat and heating controls or maybe even damage the thermostat itself.

Find and check the low voltage transformer (often it's mounted near your furnace, on an electrical junction box, or it may be integral in your heater control unit).

See LOW VOLTAGE TRANSFORMER TEST


...

Continue reading at HEAT WON'T TURN OFF - topic home, or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see THERMOSTAT WON'T TURN OFF FAQs - questions & answers posted originally at this page

Or see these

Recommended Articles

Suggested citation for this web page

THERMOSTAT WON'T TURN OFF at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.


Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to HVAC THERMOSTATS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.

Search the InspectApedia website

Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.

Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification
when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
Our Comment Box is provided by Countable Web Productions countable.ca

Comment Form is loading comments...

Citations & References

In addition to any citations in the article above, a full list is available on request.



ADVERTISEMENT