InspectAPedia ®

Building & Environmental Inspection, Testing, Diagnosis, Repair, & Problem Prevention Advice
Home | Air
Conditioning
| Electrical
-
Energy Saving
| Environment
Indoor
| Exteriors | Heating | Home
Inspection
| Insulate
-
Ventilate
| Interiors | Mold
Inspect/Test
| Plumbing
Water
Septic
| Roofing | Solar
Energy
| Structure | Contact Us
Directory of Professionals to Inspect or Test a Building


Mobile Phone or PDA view of this websiteMobile View
HEATING SYSTEMS
APPLIANCE EFFICIENCY RATINGS
ASBESTOS in BUILDINGS
BLUERAY Recall
BOILERS, HEATING
CARBON MONOXIDE/DIOXIDE
CARBON MONOXIDE WARNING
CHIMNEY INSPECTION DIAGNOSIS REPAIR
CHIMNEYS & Flues - Asbestos Transite Pipe
DUCT INSULATION - Asbestos Paper
DUCTS - Asbestos Transite Pipe
DUST FROM HVAC?
FURNACES
GAS PIPING, VALVES, CONTROLS
HEAT LOSS in BUILDINGS
HEAT LOSS DETECTION TOOLS
HEAT LOSS INDICATORS
HEAT LOSS PREVENTION PRIORITIES
HEAT LOSS R U & K VALUE CALCULATION
HOUSEWRAP AIR & VAPOR BARRIERS
HEATING COST SAVINGS
HEATING LOSS DIAGNOSIS-BOILERS
HEATING LOSS DIAGNOSIS-FURNACES
HEATING OIL CLOUD WAX GEL POINT
HEATING OIL EXPOSURE HAZARDS, LIMITS
HEATING OIL SLUDGE
HEATING SYSTEM INSPECTION DIAGNOSIS REPAIR
HOT WATER IMPROVEMENT
INSULATION INSPECTION & IMPROVEMENT
NO HEAT - BOILER / FURNACE DIAGNOSIS
ODORS FROM HEATING SYSTEMS
OIL BURNERS
OIL BURNER INSPECTION GUIDE
OIL BURNER NOISE SMOKE ODORS
OIL BURNER SOOT & PUFFBACKS
OIL FUEL TYPES & CHARACTERISTICS
OIL TANK LEAKS
OIL TANK SLUDGE
OIL TANK TESTING
OIL TANKS, BURIED
PLASTIC HEATER VENT
RADIANT HEAT
RADIANT HEAT Floor Mistakes to Avoid
RADIANT SLAB FLOORING CHOICES
RADIANT SLAB TUBING & FLUID CHOICES
Safety Recalls
  BLUERAY Recall
  CHIMNEYS & Flues - Asbestos Transite
  Goodman HTPV RECALL
  Heat Recovery Ventilator RECALL
  Lennox Furnace Manuals
  Lennox WARNING
  Weil McLain RECALL
SAFETY DURING HEATING INSPECTION
STEAM HEATING SYSTEMS
TANKLESS COILS
THERMAL EXPANSION of MATERIALS
THERMAL MASS in BUILDINGS
  THERMAL MASS FLOOR SLABS
  THERMAL MASS in UPSTAIRS
  THERMAL MASS WALL DESIGN
THERMAL TRACKING & HEAT LOSS
THERMOSTATS
Transite Pipe Chimneys & Flues

More Information

InspectAPedia.comInspectAPedia ® Home & Site Map
InspectAPedia Blog - News Updates
Air Conditioning & Heat Pumps
Bookstore
Electrical
Environment
Exteriors
Heating
Home Inspection
Insulate Ventilate
Interiors
Mold Inspect/Test
Plumbing Water Septic
Roofing
Structure
Accuracy & Bias Pledge
Contact Us



Venmar heat recovery ventilatorHeat Recovery Ventilator System Product Recall Notice
InspectAPedia®  -    

  • Venmar product safety recall: heat recovery ventilators made between 1991 and 2001

This document describes safety hazards on certain models of heat recovery ventilators manufactured by Venmar Ventilationand sold under many other brands (listed below) and reports on safety recalls. Warning: not all heating equipment safety or other recalls issued by various agencies and countries are included in this article.

This document includes information from public safety notices from the US Consumer Product Safety Commision, from the Canadian Electrical Safety Authority, the Ontarion Fire Marshal's Office, or other sources. Information Accuracy & Bias Pledge is at below-left. Use the links at page left to navigate this document or to go to Other Website Topics. Readers of this document should also see HEAT EXCHANGER LEAKS.

Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

Our site offers impartial, unbiased advice without conflicts of interest. We will block advertisements which we discover or readers inform us are associated with bad business practices, false-advertising, or junk science. Our contact info is at InspectAPedia.com/appointment.htm.

Product Safety Alert: Heat Recovery Systems Present Potential Fire Hazards

Flair heat recovery ventilator model recalled19 January 2007 Product Safety Alert: this safety alert is an expansion to a previous safety alert issued by US and Canadian safety authorities in December 2006.

Consumers are urged to determine if their building has a heat recovery system installed under one of the product brands and model numbers listed below, because these products have the potential to overheat and catch fire. There are 232,753 affected heat recovery ventilator units in Canada and another 74,933 affected heat recovery units inthe U.S.

These products were manufactured by Venmar Ventilation. The company has implemented a Safety Upgrade Program for certain models of heat recovery ventilators produced between 1991 and 2001. Heat recovery ventilators manufactured before 1991 or after 2001 are not affected by this safety notice.

Fire Safety Notes from Venmar Ventilation

Recalled heat recovery ventilatorTurn off the equipment and unplug it: Venmar asks owners of the heat recovery ventilators listed in the table above to immediately turn off and unplug the unit and to contacat Venmar as soon as possible at 1-866-441-4645, or at www.venmar.ca or by postal mail to SUP, 550 Lemire Blvd., Drummondville, QC, Canada J2C 7W9.

In Canada, for additional information contact Tatjana Dinic, Electrical Safety Authority, 905-712-5364.

If you do not know when your heat recovery ventilator was installed, check for it in the table of brand names and model numbers in the table above.

Odors or smells: if you detect strange odors or smells or observe smoke or smell burning in your home, call your fire department immediately (dial 911 in most areas), if possible, turn off electrical power to the equipment (or in an emergency simply turn off all electrical power if you can safely do so) and have the fire department determine the cause.

Heat Recovery Ventilator Brand

Heat Recovery Ventilator Model Numbers

Venmar AEXX, EARC, 1XX, 30X, 40X, 40XXXX
Venmar AVS 1.X, 2.X, 30XX, 55XX
vanEE 10, 1XX, 100X, 20, 20XX, 90
Conformax 300, 350, 400
NuTone NUTR130
Carrier, Bryant - Payne Day & Night VXXXXXXXXX
Bryant Carrier - Standard ERVXXXXXXX, HRVXXXXXXX
Heil HEILXXXX
York 5263554XXXX
Sears OPTIMUM
Broan - Guardian 100X, 200X
Rheem 84-ERV100, 84-ERV200
Rudd Protech - Weatherking 84-ERV100, 84-ERV200
NOTE: the X digit used in model numbers can be either a letter or a number.

Where to find the Heat Recovery Ventilator Model Number

The heat recovery ventilator (HRV) model number is located on a silver or black label which is positioned on the outside panel of the heat recovery ventilator unit.

Venmar's Recall Hotline: (866) 441-4645

Share this Article      

...

Technical Reviewers & References

  • InspectAPedia.com® - Daniel Friedman
  • InspectAPedia Bookstore lists recommended books, organized by topic & available for purchase. Most of our articles also include a list of recommended books for the specific article topic as well as other references, and information sources.
  • Critique, contributions wanted: Contact Us to suggest corrections or additions to articles at this website, and if you wish, to receive online listing and credit as a contributor. Particular thanks are due to the many experts and also consumers who read and critique technical articles at InspectAPedia.com.
  • Additional technical contributors & reference sources for this article are listed below.
  • US Consumer Product Safety Commission - CPSC notice: Release #07-143 29 March 2007 CPSC Recall Hotline: (800) 638-2772
  • Contact Us by email to suggest other product recall information that is appropriate for this website's readership. No listing fees are involved.

Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

HEATING SYSTEMS

More Information

InspectAPedia.comInspectAPedia ® Home & Site Map
InspectAPedia Blog - News Updates
Air Conditioning & Heat Pumps
Bookstore
Electrical
Environment
Exteriors
Heating
Home Inspection
Insulate Ventilate
Interiors
Mold Inspect/Test
Plumbing Water Septic
Roofing
Structure
Accuracy & Bias Pledge
Contact Us

More Information on Building Diagnostic Inspections and Repairs

InspectAPedia.comInspectAPedia® Home & Site Map - Building & Environmental Inspection, Testing, Diagnosis, Repair, & Problem Prevention Advice: In-depth research & advice on diagnosing, testing, correcting, & preventing building defects & indoor environmental hazards. Unbiased information, no conflicts of interest.
GO TO the MOLD and INDOOR ENVIRONMENT INFORMATION CENTER for in-depth advice on avoiding testing for or cleaning up mold and other indoor environmental hazards, odors, gases, contaminants
The Mold Information Center:
What to Do About Mold in Buildings, When and How to Inspect for Mold, Clean Up Mold, or Avoid Mold Problems
GO TO MOLD TEST KITS: This expert-recommended mold test kit is cheap and yet top performing *IF* you use a competent analysis laboratory!
Use this simple, economical mold test kit
by following our instructions on how to collect and mail mold samples to our lab
GO TO IAQ/MOLD-TEST LAB SERVICES: Mold, Pollen, indoor air quality, field and laboratory services by an expert.Environmental Inspection, Testing, & Diagnosis On-Site IAQ, Gas, Air Testing, Mold Investigation, Sick Building Diagnosis, Lab Services, & Remediation Plan Preparation - indoor air quality testing, problem source determination, supporting lab work, written remediation plan addressing removal of environmental and other hazards and prevention of their recurrence.
GO TO our PRE PURCHASE BUILDING INSPECTION SERVICES: Authoritative information for home buyers and home owners is included with your inspection.
Building Inspection, Problem Diagnosis
, Forensic Investigation & Testing, Repair Consulting

CONTACT Daniel Friedman - Dan is a senior ASHI home inspector, nationally recognized expert on building inspection, building failures, and sick building investigation
Contact Daniel Friedman for website content suggestions or for fee-paid consulting

10/01/2009 - 02/01/2007 - InspectAPedia.com/heat/VenmarRecall..htm - © 2010 - 1988 Copyright Daniel Friedman All Rights Reserved - InspectAPedia® is a Registered U.S. Trademark