InspectAPedia.com InspectAPedia®
 

Free Encyclopedia of Building & Environmental Inspection, Testing, Diagnosis, Repair

Ask a Question or Search InspectAPedia

  • HOME
  • AIR CONDITIONING
  • ELECTRICAL
  • EXTERIORS
  • HEATING
  • HOME INSPECTION
  • INTERIORS
  • PLUMBING
  • ROOFING
  • SEPTIC SYSTEMS
  • STRUCTURE
  • WATER SUPPLY
  • ENERGY SAVINGS
  • ENVIRONMENT
  • INDOOR AIR IAQ
  • INSULATION
  • MOLD INSPECT TEST REMOVE
  • NOISE
  • ODORS
  • SOLAR ENERGY
  • VENTILATION
  • EXPERTS DIRECTORY
  • CONTACT US


Mobile Phone/PDA website viewMobile View
INTERIORS of buildings

ACOUSTICAL SEALANT CHOICES
AGE of a BUILDING - how to determine
AIR BYPASS LEAKS
AIR LEAK DETECTION TOOLS
AIR LEAK MINIMIZATION
AIR LEAK SEALING PROCEDURE
AIR SEALING STRATEGIES
ANIMAL ALLERGENS
ANIMAL ENTRY POINTS in buildings
ANIMAL ODORS IN buildings
APPLIANCE EFFICIENCY RATINGS
ARCHITECTURE & BUILDING COMPONENT ID
ASBESTOS FLOORING HAZARD REDUCTION
ASBESTOS-FREE INSULATION MATERIALS
ASBESTOS IDENTIFICATION IN buildings
ASBESTOS ROOFING / SIDING DUST
ASBESTOS REMOVAL, Wetting Guidelines

ATTIC LEAKS, CONDENSATION & ATTIC MOLD
  Air Bypass Leaks, Thermal Tracking
  Blocked Soffit Intake Vents
  CATHEDRAL CEILING INSULATION
  CATHEDRAL CEILING VENTILATION
  Comparing Two Houses
  Heat Tapes: Use on Roofs for Ice
  HEAT TAPES & CABLES on Roofs for Ice Dams
  HOT ROOF DESIGNS: Un-Vented Roof Solutions
  HOUSEWRAP AIR & VAPOR BARRIERS
  HUMIDITY LEVEL TARGET
  ICE DAM PREVENTION
  ICE DAM CURE: Comparing Two Houses
  Inspect Attics for Moisture or Mold
  Inspect Attics for Blocked Soffit Intake Vents
  Inspect Basements for Moisture or Mold
  Cold Pour Joint Leaks
  Form Tie Leaks
  Wall Crack Leaks
  Floor-Wall Joint Leaks
  Inspect Building Exterior - Roof Venting
  Inspect the Ridge Vent System from the Attic
  Inspect the Soffit Vent System from the Attic
  ROOF VENTILATION SPECIFICATIONS
  Roof Venting: Intake - Outlet Area Ratios
  Roof Venting: Proper Locations
  Roof Venting: Both Ridge & Eaves Venting Needed
  Roof Venting: Eaves Intake if no Overhang
  Roof Venting: Soffit Intake Vent-Continuous
  Roof Venting: Un-Vented Hot Roof Solutions
  ROOF VENTING ENERGY SAVING DETAILS
  ROOF VENTING NEEDED?
  SKYLIGHT VENTILATION DETAILS
  Soffit Ventilation

ATTIC VENTILATION

BASEMENT CEILING VAPOR BARRIER
BASEMENT HEAT LOSS
BASEMENT LEAKS, INSPECT FOR
BASEMENT WATERPROOFING

BATH & KITCHEN DESIGN GUIDE
BATHROOM VENTILATION
BEST CONSTRUCTION PRACTICES GUIDE
Best Interior Finish Practices

BLOWER DOORS & AIR INFILTRATION
BLOWER FAN CONTINUOUS OPERATION
BLOWER FAN OPERATION & TESTING
BLOWN-IN INSULATION

BOOKSTORE - INTERIORS

BRICK LINED WALLS
BRICK VENEER WALL INSULATION
BRICK VENEER WALL Loose, Bulged
BRICK WALL DRAINAGE WEEP HOLES
BUCKLED FOUNDATIONS due to INSULATION?
BUILDING NOISE DIAGNOSIS & CURE

CARPET DUST IDENTIFICATION
CARPET MOLD CONTAMINATION
CARPET PADDING ASBESTOS, MOLD, ODORS
CARPET FUNGICIDAL SPRAY
CARPET STAIN DIAGNOSIS
CARPET & other STAIN TESTS
CARPET TEST GUIDE
CARPETING & INDOOR AIR QUALITY
CARPETING, SELECTION & INSTALLATION

CABINETS & COUNTERTOPS
CATHEDRAL CEILING INSULATION
CATHEDRAL CEILING VENTILATION
CEILING FINISHES INTERIOR
CEILINGS, DROP or SUSPENDED PANEL
CEILINGS, PLASTER TYPES
CEILINGS, PLASTER, LOOSE HAZARDS
CEILING TILES - Asbestos-Containing

CHIMNEY INSPECTION DIAGNOSIS & REPAIR
CHINESE DRYWALL HAZARDS
COMBUSTION AIR for TIGHT buildings
COOLING LOAD REDUCTION by ROOF VENTS

CRAWL SPACES
CONDENSATION or SWEATING PIPES, TANKS
CONDENSATION on WINDOWS & SKYLIGHTS

DECK & PORCH CONSTRUCTION
DEW POINT CALCULATION for WALLS
DEW POINT TABLE - CONDENSATION POINT GUIDE
DOORS, INTERIOR
DRYER VENTING
ELECTRICAL INSPECTION, DIAGNOSIS, REPAIR

ENERGY SAVINGS in buildings
ENGINEERED WOOD Flooring
ENGINEERED WOOD Products

ENVIRONMENTAL HAZARDS - INSPECT, TEST, REMEDY

FIBERGLASS INSULATION
FIREPLACES & HEARTHS
FLAT ROOF MOISTURE & CONDENSATION

FLOOD DAMAGE ASSESSMENT, SAFETY & CLEANUP
FLOODS IN buildings-mold

FLOOR TYPES & DEFECTS
  FLOOR, CERAMIC TILE
  FLOOR, CONCRETE SLAB CHOICES
  FLOOR, CONCRETE SLAB POURED FINISH
  FLOOR DAMAGE DIAGNOSIS
  FLOOR, ENGINEERED WOOD & LAMINATES
  FLOOR FRAMING & SUBFLOOR for TILE
  FLOOR, KITCHEN & BATH OPTIONS
  FLOOR, LAMINATE PLASTIC
  FLOOR RADIANT HEAT Mistakes to Avoid
  FLOOR, RESILIENT VINYL or CORK
  FLOOR, STONE, GRANITE, MARBLE, AGGLOMER
  FLOOR & SUBFLOOR MOLD, HIDDEN
  FLOOR TILE ASBESTOS IDENTIFICATION
  FLOOR TILE HISTORY & INGREDIENTS
  FLOOR WOOD AGE TYPES HISTORY
  FLOOR WOOD, DAMAGE DIAGNOSIS
  FLOOR, WOOD ENGINEERED, LAMINATE, INSTALL
  FLOOR, WOOD FINISHES
  FLOOR, WOOD INSTALLATION GUIDE
  FLOOR, WOOD MOISTURE
  FLOOR, WOOD RADIANT HEAT
  FLOOR, WOOD SOLID STRIP, PLANK
  FLOOR, WOOD TYPES
  FLOORING MATERIALS, Age, Types

FORMALDEHYDE HAZARDS

FOUNDATION BULGE or LEAN MEASUREMENTS
FOOTING & FOUNDATION DRAINS

FOUNDATION CRACKS & DAMAGE GUIDE
FOUNDATION WATERPROOFING
FRENCH DRAINS
FREEZE-PROOF A BUILDING
FROST HEAVES, FOUNDATION, SLAB

GREEN BUILDING CONSTRUCTION CODES GUIDES
GREENHOUSE DESIGN for SOLAR HEATING
GREENHOUSE / SUNSPACE GLARE

HEAT LOSS RATE CALCULATIONS
HEAT LOSS in buildings
HEAT LOSS DETECTION TOOLS
HEAT LOSS INDICATORS
HEAT LOSS PREVENTION PRIORITIES
HEAT LOSS R U & K VALUE CALCULATION

HEAT TAPES & CABLES on Roofs for Ice Dams
HEATING COST SAVINGS METHODS

HOT ROOF DESIGNS: Un-Vented Roof Solutions
HOUSEWRAP AIR & VAPOR BARRIERS
HOUSE DOCTOR, how-to be
HUMIDITY LEVEL TARGET

ICE DAM PREVENTION
Ice Dams: Comparing Two Houses

INDOOR AIR QUALITY & HOUSE TIGHTNESS
INDOOR AIR QUALITY IMPROVEMENT GUIDE
INDOOR HOUSE DUST & DEBRIS

INSULATION CHOICES
Insulation Air & Heat Leaks
INSULATION FACT SHEET- DOE
INSULATION for GREENHOUSE or SOLARIUM
INSULATION IDENTIFICATION GUIDE

INSULATION INSPECTION & IMPROVEMENT
INSULATION LOCATION - WHERE TO PUT IT
INSULATION LOCATION for BRICK VENEER WALLS
INSULATION LOCATION for CAPES, CRAWLSPACES
INSULATION LOCATION for CATHEDRAL CEILINGS
INSULATION LOCATION for GREENHOUSE or SOLARIUM
INSULATION MOLD
INSULATION R-Values & Properties

INSULATION INSPECTION & IMPROVEMENT
INSULATION LOCATION - WHERE TO PUT IT
INSULATION LOCATION for BRICK VENEER WALLS
INSULATION LOCATION for CAPES, CRAWLSPACES
INSULATION LOCATION for CATHEDRAL CEILINGS
INSULATION LOCATION for GREENHOUSE or SOLARIUM
INSULATION MOLD
INSULATION R-Values & Properties

KITCHEN VENTILATION

LEED GREEN BUILDING CERTIFICATION
LEED Building Designation & IAQ
LOG HOME ENERGY EFFICIENCY
LOG HOME GUIDE

MOBILE HOME INSPECTIONS

MOISTURE CONTROL in buildings

MOLD INFORMATION CENTER
MOLD ACTION GUIDE - WHAT TO DO ABOUT MOLD
MOLD APPEARANCE - WHAT MOLD LOOKS LIKE
MOLD CLEANUP GUIDE- HOW TO GET RID OF MOLD
MOLD DETECTION & INSPECTION GUIDE

MOLD EXPERT, WHEN TO HIRE
MOLD KILLING GUIDE
MOLD LEVEL IN AIR, VALIDITY
MOLD PREVENTION GUIDE
MOLD SPRAYS, SEALANTS, PAINTS
MOLD TEST KITS
MOLD TESTING SERVICES

Nanomaterials Hazards
NOISE / SOUND DIAGNOSIS & CURE

ODORS & SMELLS DIAGNOSIS & CURE

PAINT FALURE, DIAGNOSIS, CURE, PREVENTION
PASCAL CALCULATIONS
PLASTER & BEAVERBOARD & DRYWALL
PLASTER BULGES & PILLOWS
PLASTER LATH, METAL
PLASTER, LOOSE FALL HAZARDS
PLASTER TYPE IDENTIFICATION
PLASTER VENEER Best Practices

RADIANT BARRIERS
RADIANT HEAT
RADIANT HEAT Floor Mistakes to Avoid
RADIANT HEAT TEMPERATURES
RADIANT SLAB FLOORING CHOICES
RADIANT SLAB TUBING & FLUID CHOICES

ROOF VENTILATION SPECIFICATIONS
  ATTIC VENTILATION
  CASEWORK, CABINETS, SHELVING INSTALLATION
  CATHEDRAL CEILING INSULATION
  CATHEDRAL CEILING VENTILATION
  HOT ROOF DESIGNS: Un-Vented Roof Solutions
  Inspect Attics for Moisture or Mold
  Inspect Attics for Blocked Soffit Intake Vent
  Inspect Basements for Moisture or Mold
  Inspect Building Exterior - Roof Venting
  Inspect the Ridge Vent System from the Attic
  Inspect the Soffit Vent System from the Attic
  Insects & Foam Insulation
  HOUSE DOCTOR, how-to be
  Insulation Air & Heat Leaks
  Roof Venting: Intake - Outlet Area Ratios
  Roof Venting: Proper Locations
  Roof Venting: Both Ridge & Eaves Venting Needed
  Roof Venting: Eaves Intake if no Overhang
  Roof Venting: Soffit Intake Vent-Continuous
  Roof Venting: Un-Vented Hot Roof Solutions
  ROOF VENTING ENERGY SAVING DETAILS
  ROOF VENTING NEEDED?
  SKYLIGHT VENTILATION DETAILS
  Soffit Ventilation

ROT, FUNGUS, TERMITES
ROT, TIMBER FRAME

SAFETY HAZARDS & INSPECTIONS
SEARS KIT HOUSES

SOLAR ENERGY SYSTEMS

SOUND CONTROL in buildings

STAIN & BIODETERIORATION AGENT CATALOG
STAINS on buildings - QUICK GUIDE
STAIN DIAGNOSIS on BUILDING EXTERIORS
STAIN DIAGNOSIS on BUILDING INTERIORS
STAIN DIAGNOSIS on ROOFS
STAIN DIAGNOSIS on STONE
STAINS & FINISHES, INTERIOR
STAINS on INDOOR SURFACES: PHOTO GUIDE

STAIRS, RAILINGS, LANDINGS, RAMPS
STONE CLEANING METHODS

STUCCO WAll FAILURES DUE TO WEATHER
STUCCO WALL METHODS & INSTALLATION
STUCCO OVER FOAM INSULATION
STUCCO PAINT FAILURES

STRUCTURAL INSPECTIONS & DEFECTS
SUMP PUMPS GUIDE
SWEATING (CONDENSATION) on PIPES, TANKS

THERMAL EXPANSION of MATERIALS
THERMAL MASS in buildings
THERMAL TRACKING & HEAT LOSS

TRIM, INTERIOR INSTALLATION

TRUSS UPLIFT, ROOF
TRUSSES, Floor & Roof

VAPOR BARRIERS & CONDENSATION in buildings

VENTILATION in buildings
  Air Bypass Leaks, Thermal Tracking
  AIR CHANGE RATE ACH HEAT SAVINGS
  ATTIC CONDENSATION CAUSE & CURE
  BALANCED VENTILATION, HEAT COST SAVINGS
  BATH & KITCHEN DESIGN GUIDE
  BATHROOM VENTILATION
  Blocked Soffit Intake Vents
  BLOWER DOORS & AIR INFILTRATION
  BLOWN-IN INSULATION
  BRICK or BLOCK WALL CAVITY INSULATION
  BRICK VENEER WALL INSULATION
  CATHEDRAL CEILING INSULATION
  CATHEDRAL CEILING VENTILATION
  CLOTHES DRYER VENTING
  COOLING LOAD REDUCTION by ROOF VENTS
  CRAWL SPACE VENTING & Dryout Procedures
  HEAT LOSS: How to Calculate Heat Loss in a Building
  HOT ROOF DESIGNS: Un-Vented Roof Solutions
  HOUSEWRAP AIR & VAPOR BARRIERS
  HUMIDITY LEVEL TARGET
  ICE DAM PREVENTION
  Inspect Attics for Moisture or Mold
  Inspect Attics for Blocked Soffit Intake Vents
  Inspect Basements for Moisture or Mold
  Inspect Building Exterior - Roof Venting
  Inspect the Ridge Vent System from the Attic
  Inspect the Soffit Vent System from the Attic
  Insects & Foam Insulation
  HOUSE DOCTOR, how-to be
  Insulation Air & Heat Leaks
  KITCHEN VENTILATION
  MOISTURE CONTROL in buildings
  MOISTURE CALCULATIONS
  MOISTURE METER STUDY
  MOISTURE PROBLEMS: CAUSE & CURE
  ROOF VENTILATION SPECIFICATIONS
  ROOF VENTING ENERGY SAVING DETAILS
  ROOF VENTING NEEDED?
  SKYLIGHT VENTILATION DETAILS
  Soffit Ventilation
  VENTILATION, BALANCED HEAT COST SAVINGS
  VENTILATION DESIGN PROBLEMS & SOLUTIONS
  VENTILATION, WHOLE HOUSE STRATEGIES

WALL SIDING TRIM & FINISHES
WALL FINISHES INTERIOR

WATER BARRIERS, EXTERIOR BUILDING
WATER ENTRY in buildings

WIND WASHING INSULATION At EAVES
WINDOWS & DOORS

WINTERIZE A BUILDING
WOOD Burning Heaters Fireplaces Stoves
WOOD FLOOR DAMAGE

More Information

Severe ice dams, eaves to ground in Poughkeepsie NY Attic Condensation & Ice Dam Leaks in buildings
InspectAPedia®  -    

  • How to stop ice dams and roof leaks on buildings
  • How to detect & correct roof venting deficiencies, attic insulation defects, and attic moisture or condensation problems
  • How much attic ventilation is needed?
  • How to design effective attic or under-roof ventilation
  • Questions & answers about how to diagnose and fix attic moisture, condensation, and mold sources

This article series describes roof venting problems and solutions: ice dams, attic condensation, attic mold, and inspection methods and clues to detect roof venting deficiencies, insulation defects, and attic condensation problems in buildings. It describes proper roof ventilation placement, amounts, and other details.

InspectAPedia offers impartial, unbiased advice without conflicts of interest. We will block advertisements which we discover or readers inform us are associated with bad business practices, false-advertising, or junk science. Our contact info is at InspectAPedia.com/Contact.htm.

These recommendations are based on many years of building inspections, on the observation of the locations of moisture, mold, ice dams, condensation stains, and other clues in buildings, and on the correlation of these clues with the roof venting conditions at those properties, and frequent literature review and professional discussion. We have also measured changes in airflow, temperature, and moisture before and after installing roof venting.

Readers should see our detailed articles at ROOF VENTILATION SPECIFICATIONS.

© Copyright 2012 InspectAPedia.com, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use page top links to major topics or use links at the left of each page to navigate within topics and documents at this website. Green links show where you are in a document series or at this website.

Attic Condensation and Roof Leaks as a Source of Building Mold - Diagnosis and Cure

Frost on attic roof decking (C) Daniel FriedmanSources of Attic Mold: Roof leaks or, alternatively, high levels of attic moisture due to a combination of inadequate attic (soffit intake and ridge outlet) ventilation combine with building moisture sources (such as a chronic or even a single-event wet basement, plumbing leaks, or a leaky roof from roof failure or from ice dams) are likely to cause excessive moisture or actual wet conditions in an attic.

High attic moisture levels or actual wet attic conditions invite extensive mold growth. [Also see DEW POINT TABLE - CONDENSATION POINT GUIDE.]

Visible frost may appear on attic roof surfaces if the building is located in a freezing climate and high levels of moisture are trapped in a poorly vented attic or roof cavity (photo, left).

Visible mold may appear on wood surfaces in an attic such as on rafters or roof sheathing. Hidden mold may be present and may be even more of a problem if it forms in insulation or in the ducts and air handler of an air conditioning or heating/air conditioning system.

Typical building air convection currents tend to move air up and out from lower to upper building levels, so one would not think that much mold would move down from an attic into the living area. But important exceptions to this can quickly move problem mold from an attic into a living area.

Conditions that Cause Air Movement Upwards into an Attic or Roof Cavity Space

As home inspection expert Roger Hankey has pointed out,

"... attic bypasses are one of the primary causes of ice dams. You effectively discuss insulation and ventilation (at INSULATION INSPECTION & IMPROVEMENT and at VENTILATION in buildings) but if attic bypasses remain in an insulated and ventilated attic, then the result can be frost and moisture damage to the roof sheathing, and/or spot ice dams." - R. Hankey 01/28/2008.

Because warm air rises up through buildings by natural convection, tending to displace heavier cold air, warm building air leaks and forces its way into roof spaces primarily through small openings leaking from heated space into the roof cavity or attic space. The pressure difference between a warm interior ceiling and a cooler attic or cathedral ceiling space needs only to be slight for air to move from warm to cool spaces in a building.

Remarkably, the current of rising air in a two story or higher building can be quite adequate to even draw cool, moist, or possibly moldy air from a building's crawl space or basement too.

Details about air bypass leaks themselves can be read at AIR BYPASS LEAKS.

Readers who want to understand the significance of air bypass leaks and how this problem is corrected should see ENERGY SAVINGS RETROFIT CASE STUDY and ENERGY SAVINGS RETROFIT LEAK SEALING GUIDE.

Readers who want to find and fix un-wanted air bypass leaks should also see AIR LEAK DETECTION TOOLS and AIR LEAK MINIMIZATION as well as AIR SEALING STRATEGIES.

Conditions moving air and potentially moldy air downwards from an attic or roof space include

Toxic white attic mold (C) Daniel Friedman

  • Mold growth in heating and air conditioning HVAC ducts or air handlers found in an attic
  • Mold on any attic surface or in attic insulation if it is a species producing airborne spores (moldy attic photo at left) and if the building uses a whole house ventilating fan, especially if there is inadequate exit venting for the fan operation. This condition pressurizes the attic and moves mold down through various openings into the floors below.
  • Mold on building surfaces in an attic or attic knee wall space which opens onto or has a knee wall common with an upper floor living space such as a bedroom.
  • Ventilation fan or exhaust fan use causing downwards movement of air from upper building levels
  • Air conditioning use causing down-currents of air in buildings from an upper floor: heavier, cool air flows downwards in the structure and draws attic air into the upper floor from attic or roof cavity air bypass leak points (such as at light fixtures, stairs, attic hatch).

Building Exteriors Leaks and Mold vs Attic Ventilation & Moisture Troubles

No mold cleanup project will be successful unless you correct the conditions that caused mold growth in the first place. An expert inspection and report should find and suggest remedies for site and building exterior conditions that produce mold or for building areas that serve as a mold reservoir or as amplifiers for allergens, mold, mildew, excessive pollen or pet dander.

The basic steps: find all unwanted moisture sources, correct appropriate building, site, landscaping, & construction details. 90% of the wet basements and crawl spaces I see are caused by bad or missing roof gutters and downspouts.

An IAQ investigator who has training and experience in building science, mycology (mold science), and IAQ, or in some cases an experienced ASHI-Certified home inspector or sick building investigator who is who has a similar in-depth understanding of construction failures can be helpful at this step.

How to Prevent Ice Dam Formations (and Ice Dam Leaks) on Roofs

As explained in Best Practices Guide to Residential Construction, chapter on BEST ROOFING PRACTICES:

Figure 2-54: Roof Ice Dam Formation (C) J Wiley, S Bliss

Ice dams form when heat leaking into attics or roof cavities from the building below, or from attic ductwork, melts the bottom layer of snow on the roof.

The melt water runs down the length of the roof to the eaves, where it refreezes, forming a dam and icicles.

In the worst cases, liquid water pools behind the dam and flows under the shingles and into the building (Figure 2-54 shown at left).

Research has indicated that the ice-dam risk is greatest when temperatures range between 15°F and 20°F— when it is warm enough for snow to melt but cold enough for it to refreeze at the eaves.

Also, the greater the depth of snow on the roof, the greater the risk of ice dams due to the insulating value of the snow itself.

Cold Roofs Prevent Ice Dams

Ventilation helps prevent ice dams by keeping the roof surface cold enough to limit uneven melting. Tests conducted in 1996 at the U.S. Army Corps of Engineers Cold Regions Research and Engineering Laboratory (CRREL), showed that the traditional 1:150 ventilation rule was sufficient to prevent ice dams on roofs with R-25 or greater ceiling insulation.

The 1:300 rule proved adequate for roofs with R-38 or greater insulation. Since most standard eave and ridge vents sold today meet the higher ventilation rates, most new homes are protected as long as there are no large heat leaks into the attic, or tricky sections of the roof with inadequate ventilation.

-- Adapted with permission from Best Practices Guide to Residential Construction.

Questions & Answers regarding this article

Questions & answers about how to diagnose and fix attic moisture, condensation, and mold sources

Ask a Question or Search InspectAPedia

HTML Comment Box is loading comments...

Share this Article      

...

Technical Reviewers & References

  • InspectAPedia.com® - Daniel Friedman - Publisher & Editor.
  • InspectAPedia Bookstore lists recommended books, organized by topic & available for purchase. Most of our articles also include a list of recommended books for the specific article topic as well as other references, and information sources.
  • Critique, contributions wanted: Contact Us to suggest corrections or additions to articles at this website, and if you wish, to receive online listing and credit as a contributor. Particular thanks are due to the many experts and also consumers who read and critique technical articles at InspectAPedia.com.
  • Additional technical contributors & reference sources for this article are listed below.

Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

ATTIC LEAKS, CONDENSATION & ATTIC MOLD
  Air Bypass Leaks, Thermal Tracking
  Blocked Soffit Intake Vents
  CATHEDRAL CEILING INSULATION
  CATHEDRAL CEILING VENTILATION
  Comparing Two Houses
  Heat Tapes: Use on Roofs for Ice
  HEAT TAPES & CABLES on Roofs for Ice Dams
  HOT ROOF DESIGNS: Un-Vented Roof Solutions
  HOUSEWRAP AIR & VAPOR BARRIERS
  HUMIDITY LEVEL TARGET
  ICE DAM PREVENTION
  ICE DAM CURE: Comparing Two Houses
  Inspect Attics for Moisture or Mold
  Inspect Attics for Blocked Soffit Intake Vents
  Inspect Basements for Moisture or Mold
  Cold Pour Joint Leaks
  Form Tie Leaks
  Wall Crack Leaks
  Floor-Wall Joint Leaks
  Inspect Building Exterior - Roof Venting
  Inspect the Ridge Vent System from the Attic
  Inspect the Soffit Vent System from the Attic
  ROOF VENTILATION SPECIFICATIONS
  Roof Venting: Intake - Outlet Area Ratios
  Roof Venting: Proper Locations
  Roof Venting: Both Ridge & Eaves Venting Needed
  Roof Venting: Eaves Intake if no Overhang
  Roof Venting: Soffit Intake Vent-Continuous
  Roof Venting: Un-Vented Hot Roof Solutions
  ROOF VENTING ENERGY SAVING DETAILS
  ROOF VENTING NEEDED?
  SKYLIGHT VENTILATION DETAILS
  Soffit Ventilation

ATTIC VENTILATION

  • Alan Carson Carson Dunlop Associates, Toronto, Ontario. Mr. Carson is a home inspection professional, educator, researcher, writer, and a principal of Carson Dunlop Associates, a Toronto home inspection and education firm. Mr. Carson is a past president of ASHI, the American Society of Home Inspectors Some great illustrations of the proper under-roof ventilation pathways are offered by Carson Dunlop.
  • Mark Cramer Inspection Services Mark Cramer, Tampa Florida, Mr. Cramer is a past president of ASHI, the American Society of Home Inspectors and is a Florida home inspector and home inspection educator. (727) 595-4211 mark@BestTampaInspector.com 11/06 & 12/08
  • John Annunziata, P.E. - NY Metro ASHI during informal chapter discussions about roof and attic ventilation options (1986-1996).
  • Roger Hankey is principal of Hankey and Brown home inspectors, Eden Prairie, MN. Mr. Hankey is a past chairman of the ASHI Standards Committee. Mr. Hankey has served in other ASHI professional and leadership roles. Contact Roger Hankey at: 952 829-0044 - rhankey@hankeyandbrown.com. Mr. Hankey is a frequent contributor to InspectAPedia.com.
  • The Smart Vent™ by DCI roof intake venting provides an intake at the lower edge of roof decking for difficult cases. See www.dciproducts.com/html/smartvent.htm
  • The AccuVent™ attic ventilation roof baffle produced by Berger permits insulation to extend over the top plate as far forward as possible. See www.bergerbuildingproducts.com/pdfs/AccuVentAtticVent.pdf
  • GAF Cobra® and other GAF roof ventilation products: see www.gaf.com/Content/GAF/RES1/ROOF/RS_whyuse_ventchart.asp?viewer=&module=

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.
  • Home Reference Book - Carson Dunlop The Home Reference Book - the Encyclopedia of Homes, Carson Dunlop & Associates, Toronto, Ontario, 2010, $69.00 U.S., is available from Carson Dunlop. The Home Reference Book is a bound volume of more than 450 illustrated pages that assist home inspectors and home owners in the inspection and detection of problems on buildings. The text is intended as a reference guide to help building owners operate and maintain their home effectively. InspectAPedia.com ® author/editor Daniel Friedman is a contributing author. Field inspection worksheets are included at the back of the volume.
  • "The Elimination of Unsafe Guardrails, a Progress Report," Elliott O. Stephenson, Building Standards, March-April 1993
  • "Are Functional Handrails Within Our Grasp" Jake Pauls, Building Standards, January-February 1991
  • Access Ramp building codes:
    • UBC 1003.3.4.3
    • BOCA 1016.3
    • ADA 4.8.2
    • IBC 1010.2
  • Access Ramp Standards:
    • ADA (Americans with Disabilities Act), Public Law 101-336. 7/26/90 is very often cited by other sources for good design of stairs and ramps etc. even where disabled individuals are not the design target.
    • ANSI A117.4 Accessible and Usable buildings and Facilities (earlier version was incorporated into the ADA)
    • ASTM F 1637, Standard Practice for Safe Walking Surfaces, (Similar to the above standards)
  • "Energy Savers: Whole-House Supply Ventilation Systems [copy on file as /interiors/Energy_Savers_Whole-House_Supply_Vent.pdf ] - ", U.S. Department of Energy energysavers.gov/your_home/insulation_airsealing/index.cfm/mytopic=11880?print
  • "Energy Savers: Whole-House Exhaust Ventilation Systems [copy on file as /interiors/Energy_Savers_Whole-House_Exhaust.pdf ] - ", U.S. Department of Energy energysavers.gov/your_home/insulation_airsealing/index.cfm/mytopic=11870
  • "Energy Savers: Ventilation [copy on file as /interiors/Energy_Savers_Ventilation.pdf ] - ", U.S. Department of Energy
  • "Energy Savers: Natural Ventilation [copy on file as /interiors/Energy_Savers_Natural_Ventilation.pdf ] - ", U.S. Department of Energy
  • "Energy Savers: Energy Recovery Ventilation Systems [copy on file as /interiors/Energy_Savers_Energy_Recovery_Venting.pdf ] - ", U.S. Department of Energy energysavers.gov/your_home/insulation_airsealing/index.cfm/mytopic=11900
  • "Energy Savers: Detecting Air Leaks [copy on file as /interiors/Energy_Savers_Detect_Air_Leaks.pdf ] - ", U.S. Department of Energy
  • "Energy Savers: Air Sealing [copy on file as /interiors/Energy_Savers_Air_Sealing_1.pdf ] - ", U.S. Department of Energy
  • Falls and Related Injuries: Slips, Trips, Missteps, and Their Consequences, Lawyers & Judges Publishing, (June 2002), ISBN-10: 0913875430 ISBN-13: 978-0913875438
    "Falls in the home and public places are the second leading cause of unintentional injury deaths in the United States, but are overlooked in most literature. This book is unique in that it is entirely devoted to falls. Of use to primary care physicians, nurses, insurance adjusters, architects, writers of building codes, attorneys, or anyone who cares for the elderly, this book will tell you how, why, and when people will likely fall, what most likely will be injured, and how such injuries come about. "
  • Humidity: What indoor humidity should we maintain in order to avoid a mold problem?
  • Slips, Trips, Missteps and Their Consequences, Second Edition, Gary M. Bakken, H. Harvey Cohen,A. S. Hyde, Jon R. Abele, ISBN-13: 978-1-933264-01-1 or ISBN 10: 1-933264-01-2, available from the publisher, Lawyers ^ Judges Publishing Company,Inc., www.lawyersandjudges.com sales@lawyersandjudges.com and also from the InspectAPedia Bookstore (Amazon.com)
  • The Stairway Manufacturers' Association, (877) 500-5759, provides a pictorial guide to the stair and railing portion of the International Residential Code. [copy on file as http://www.stairways.org/pdf/2006%20Stair%20IRC%20SCREEN.pdf ] -
  • What Mold and Allergens Look Like: mold identification photos to help identify mold - choosing what to sample in buildings
  • How to Clean Moldy Wood Framing & Sheathing How to clean/seal mold from/on exposed lumber or plywood subfloor or roof sheathing indoors - some suggestions based on our field and laboratory research
  • Lighting, proper use of: proper aiming of a good flashlight can disclose hard to see but toxic light or white mold colonies on walls.
  • Mold spores in the Home - a Photo ID Library for detection and identification of mold allergens.
  • How to Find and Test For Mold in buildings A "how to" photo and text primer on finding and choosing the right spots to test for mold in buildings
  • Stuff that is not mold but is often mistaken for it - things you may not want to test. Also, not all "black mold" is toxic - here are examples of harmless black mold.
  • Simple Adhesive Tape Sampling of Moldy Surfaces - how to send a mold sample to our lab
  • Mold Sampling Methods in the Indoor Environment - In-depth article: detailed critique of popular mold testing methods - Is your mold test kit worth the bother?
  • Mold-Resistant Building Practices, advice from an expert on how to prevent mold after a building flood and how to prevent mold growth in buildings by selection of building materials and by anti-mold construction details.
  • Slips, Trips, Missteps and Their Consequences, Gary M. Bakken, H. Harvey Cohen, Jon R. Abele, Alvin S. Hyde, Cindy A. LaRue, Lawyers and Judges Publishing; 2 edition (April 2006), ISBN-10: 1933264012 ISBN-13: 978-1933264011
  • Steps and Stairways, Cleo Baldon & Ib Melchior, Rizzoli, 1989.
  • The Staircase, Ann Rinaldi
  • Common Sense Stairbuilding and Handrailing, Fred T. Hodgson
  • The Art of Staircases, Pilar Chueca
  • Building Stairs, by pros for pros, Andy Engel
  • A Simplified Guide to Custom Stairbuilding, George R. Christina
  • Basic Stairbuilding, Scott Schuttner
  • The Staircase (two volumes), John Templar, Cambridge: the MIT Press, 1992
  • The Staircase: History and Theories, John Templar, MIT Press 1995
  • Steps and Stairways, Cleo Baldon & Ib Melchior, Rizzoli, 1989.
  • "The Dimensions of Stairs", J. M. Fitch et al., Scientific American, October 1974.
  • "Weather-Resistive Barriers [copy on file as /interiors/Weather_Resistant_Barriers_DOE.pdf ] - ", how to select and install housewrap and other types of weather resistive barriers, U.S. DOE
  • Best Practices Guide to Residential Construction, by Steven Bliss. John Wiley & Sons, 2006. ISBN-10: 0471648361, ISBN-13: 978-0471648369, Hardcover: 320 pages, available from Amazon.com and also Wiley.com. See our book review of this publication.
  • Decks and Porches, the JLC Guide to, Best Practices for Outdoor Spaces, Steve Bliss (Editor), The Journal of Light Construction, Williston VT, 2010 ISBN 10: 1-928580-42-4, ISBN 13: 978-1-928580-42-3, available from Amazon.com
  • ...
Home About Us Accuracy Contact Us Content Use Policy Privacy Website Description © 2012 Copyright InspectAPedia.com