InspectAPedia ® | ||||||||||||||||||||||||||||
| Building & Environmental Inspection, Testing, Diagnosis, Repair, & Problem Prevention Advice |
| |||||||||||||||||||||||||||
| Home | | | Air Conditioning |
| | Electrical - Energy Saving |
| | Environment Indoor |
| | Exteriors | | | Heating | | | Home Inspection |
| | Insulate - Ventilate |
| | Interiors | | | Mold Inspect/Test |
| | Plumbing Water Septic |
| | Roofing | | | Solar Energy |
| | Structure | | | Contact Us |
| Directory of Professionals to Inspect or Test a Building | ||||||||||||||||||||||||||||
|
INTERIORS of BUILDINGS ACOUSTICAL SEALANTS AGE of a BUILDING - how to determine AIR BYPASS LEAKS AIR LEAK DETECTION TOOLS AIR LEAK MINIMIZATION AIR SEALING STRATEGIES ANIMAL ALLERGENS APPLIANCE EFFICIENCY RATINGS ASBESTOS IDENTIFICATION IN BUILDINGS ATTIC LEAKS, CONDENSATION & ATTIC MOLD ATTIC VENTILATION BASEMENT HEAT LOSS BASEMENT LEAKS Moisture or Mold BASEMENT WATERPROOFING BATHROOM VENTILATION BLOWER DOORS & AIR INFILTRATION BRICK LINED WALLS BUCKLED FOUNDATIONS due to INSULATION? BUILDING NOISE DIAGNOSIS & CURE CATHEDRAL CEILING INSULATION CHIMNEY INSPECTION DIAGNOSIS & REPAIR COMBUSTION AIR for TIGHT BUILDINGS CRAWL SPACES DEW POINT CALCULATION for WALLS DEW POINT TABLE - CONDENSATION POINT GUIDE ELECTRICAL INSPECTION, DIAGNOSIS, REPAIR ENVIRONMENTAL HAZARDS FIBERGLASS INSULATION FIREPLACE Damage & Unsafe Hearths - Settlement FLAT ROOF MOISTURE & CONDENSATION FLOOD DAMAGE ASSESSMENT, SAFETY & CLEANUP FLOODS IN BUILDINGS-mold FLOORING CHOICES OVER CONCRETE SLABS FLOORING TYPES & DEFECTS FOUNDATION WATERPROOFING FREEZE-PROOF A BUILDING HEAT LOSS in BUILDINGS HEAT LOSS DETECTION TOOLS HEAT LOSS INDICATORS HEAT LOSS PREVENTION PRIORITIES HEAT LOSS R U & K VALUE CALCULATION Heat Tapes: Use on Roofs for Ice HEATING COST SAVINGS METHODS HOUSEWRAP AIR & VAPOR BARRIERS HUMIDITY LEVEL TARGET ICE DAM PREVENTION Ice Dams: Comparing Two Houses INSULATION IDENTIFICATION GUIDE INSULATION LOCATION in BUILDINGS - WHERE TO INSULATE INSULATION CHOICES INSULATION FACT SHEET- DOE INSULATION LOCATION & QUANTITY for ATTICS INSULATION LOCATION for BASEMENT FLOORS INSULATION LOCATION for BASEMENT WALLS INSULATION LOCATION for BRICK VENEER WALLS INSULATION LOCATION for CAPES, CRAWLSPACES INSULATION LOCATION for CATHEDRAL CEILINGS INSULATION LOCATION for GREENHOUSE or SOLARIUM INSULATION LOCATION for PASSIVE SOLAR FLOOR SLAB INSULATION LOCATION for SOUND CONTROL in BUILDINGS INSULATION LOCATION for SWIMMING, INDOOR INSULATION MOLD INSULATION R-Values & Properties INSULATION INSPECTION & IMPROVEMENT ATTIC CONDENSATION CAUSE & CURE Air Bypass Leaks, Thermal Tracking Blocked Soffit Intake Vents BRICK VENEER WALL INSULATION CATHEDRAL CEILING INSULATION CATHEDRAL CEILING VENTILATION ENERGY SAVINGS in BUILDINGS FIBERGLASS DUCT, RIGID CONSTRUCTION FRAMING DETAILS for BETTER INSULATION FRAMING DETAILS for DOUBLE WALL HOUSES Inspect Attics for Moisture or Mold Inspect Basements for Moisture or Mold Inspect Building Exterior Inspect the Ridge Vent System from the Attic Inspect the Soffit Vent System from the Attic Insulation Air & Heat Leaks INSULATION R-Values & Properties LOG HOME WALL INSULATION VALUES PHENOLIC FOAM INSULATION POLYISOCYANURATE FOAM INSULATION POLYISOCYANURATE FOAM BELOW SLABS POLYSTYRENE FOAM INSULATION PASCAL CALCULATIONS RADIANT BARRIERS RIGID FOAM USE INDOORS Urea Formaldehyde Foam Insulation UFFI URETHANE FOAM Deterioration, Outgassing Vermiculite Insulation LOG HOME ENERGY EFFICIENCY LOG HOME GUIDE MOBILE HOME INSPECTIONS MOISTURE CONTROL in BUILDINGS MOLD INFORMATION CENTER NOISE / SOUND DIAGNOSIS & CURE ODORS & SMELLS DIAGNOSIS & CURE PAINT FALURE, DIAGNOSIS, CURE, PREVENTION PLASTER & BEAVERBOARD & DRYWALL PASCAL CALCULATIONS RADIANT BARRIERS RADIANT HEAT RADIANT HEAT Floor Mistakes to Avoid RADIANT SLAB FLOORING CHOICES RADIANT SLAB TUBING & FLUID CHOICES ROOF VENTILATION SPECIFICATIONS ATTIC VENTILATION CATHEDRAL CEILING VENTILATION Inspect the Ridge Vent System from the Attic Inspect the Soffit Vent System from the Attic Insulation Air & Heat Leaks Roof Venting: Intake - Outlet Area Ratios Roof Venting: Proper Locations Roof Venting: Both Ridge & Eaves Venting Needed Roof Venting: Eaves Intake if no Overhang Roof Venting: Soffit Intake Vent-Continuous Roof Venting: Un-Vented Roof Solutions ROOF VENTING ENERGY SAVING DETAILS ROOF VENTING NEEDED? Soffit Ventilation ROT, FUNGUS, TERMITES TERMITE SHIELDS vs TERMITICIDE ROT, TIMBER FRAME SAFETY HAZARDS & INSPECTIONS SEARS KIT HOUSES SOLAR ENERGY SYSTEMS PASSIVE SOLAR DESIGN METHOD PASSIVE SOLAR ENERGY MONITORING PASSIVE SOLAR FLOOR TILES, PHASE CHANGE PASSIVE SOLAR HEAT PERFORMANCE PASSIVE SOLAR HOME, LOW COST PHOTOVOLTAIC POWER SYSTEMS SLAB INSULATION, PASSIVE SOLAR SOLAR COLLECTOR AIR or GAS COLLECTION SOLAR COLLECTOR EFFICIENCY COMPARISONS SOLAR COLLECTOR FILMS SOLAR COLLECTOR WOOD HOUSINGS SOLAR HEATING SYSTEMS SOLAR HOT WATER HEATERS SOLAR HOUSE EVALUATION SOLAR SHADES & SUNSCREENS SUNGAIN, FILMS, LOW-E GLASS SWIMMING POOL SOLAR HEAT, INDOOR SWIMMING POOL SOLAR HEAT, OUTDOOR DIAGNOSIS SOUND CONTROL in BUILDINGS STAIN DIAGNOSIS STAIRS, RAILINGS, LANDINGS, RAMPS - INSPECTIONS, CODES STUCCO OVER FOAM INSULATION STUCCO PAINT FAILURES STRUCTURAL INSPECTIONS & DEFECTS SUMP PUMPS GUIDE THERMAL EXPANSION of MATERIALS THERMAL MASS in BUILDINGS THERMAL MASS FLOOR SLABS THERMAL MASS in UPSTAIRS THERMAL MASS WALL DESIGN THERMAL TRACKING Indicates Heat Loss VAPOR BARRIERS & AIR SEALING at BAND JOISTS VAPOR BARRIERS & CONDENSATION in BUILDINGS VAPOR BARRIERS & HOUSEWRAP VAPOR CONDENSATION & BUILDING SHEATHING VENTILATION in BUILDINGS Air Bypass Leaks, Thermal Tracking ATTIC CONDENSATION CAUSE & CURE BATHROOM VENTILATION Blocked Soffit Intake Vents BLOWER DOORS & AIR INFILTRATION BRICK VENEER WALL INSULATION CATHEDRAL CEILING VENTILATION CRAWL SPACE VENTING & Dryout Procedures HEAT LOSS: How to Calculate Heat Loss in a Building HOUSEWRAP AIR & VAPOR BARRIERS HUMIDITY LEVEL TARGET ICE DAM PREVENTION Inspect Attics for Moisture or Mold Inspect Basements for Moisture or Mold Inspect Building Exterior for Moisture Problems Inspect the Ridge Vent System from the Attic Inspect the Soffit Vent System from the Attic Insulation Air & Heat Leaks MOISTURE CONTROL in BUILDINGS MOISTURE CALCULATIONS MOISTURE PROBLEMS: CAUSE & CURE ROOF VENTILATION SPECIFICATIONS Roof Venting: Intake - Outlet Area Ratios Roof Venting: Proper Locations Roof Venting: Both Ridge & Eaves Venting Needed Roof Venting: Eaves Intake if no Overhang Roof Venting: Soffit Intake Vent-Continuous Roof Venting: Un-Vented Roof Solutions ROOF VENTING ENERGY SAVING DETAILS ROOF VENTING NEEDED? Soffit Ventilation VENTILATION DESIGN PROBLEMS & SOLUTIONS WHOLE HOUSE VENTILATION Strategies WATER ENTRY in BUILDINGS WIND TURBINES WINDOWS & DOORS SKYLIGHT LEAK DIAGNOSIS & REPAIR SITE BUILT DOUBLE GLAZED WINDOWS SLOPED GLAZING DETAILS SUNGAIN, FILMS, LOW-E GLASS VERTICAL GLAZING DETAILS WINDOW / DOOR ENERGY EFFICIENT, DOE WINDOW LEAKS INTO BASEMENT WINTERIZE A BUILDING WOOD Burning Heaters Fireplaces Stoves More Information InspectAPedia Blog - News Updates Air Conditioning & Heat Pumps Bookstore Electrical Environment Exteriors Heating Home Inspection Insulate Ventilate Interiors Mold Inspect/Test Plumbing Water Septic Roofing Structure Accuracy & Bias Pledge Contact Us |
This article discusses How to Specify the Proper Roof Intake and Outlet Vent Area Ratios to Stop Building Heat Loss and Provide Proper Attic Venting to Avoid Condensation, Ice Dam Leaks, Mold, & Roof Structure Damage. Adding under-roof ventilation is usually a great idea, but if the relative sizes of the intake and outlet vents are not proper, the building will suffer increased heat loss and thus an unnecessarily high home heating bill. This is a section the article series, Roof Venting: Correct Inadequate part of our discussion of ATTIC CONDENSATION CAUSE & CURE. This article describes inspection methods and clues to detect roof venting deficiencies, insulation defects, and attic condensation problems in buildings. It describes proper roof ventilation placement, amounts, and other details. These recommendations are based on roofing industry standards, roof covering manufacturer recommendations, and on review of the literature on building insulation and ventilation, as well as on 30 years of building inspections, on the observation of the locations of moisture, mold, ice dams, condensation stains, and other clues in buildings, and on the correlation of these clues with the roof venting conditions at those properties. We have also measured changes in airflow, temperature, and moisture before and after installing roof venting. © Copyright 2010 Daniel Friedman, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use links at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website. Vent Area Ratios: Attic Ventilation Soffit Intake to Ridge Outlet Air Flow or Square Inches RatioContinuous un-blocked soffit or eaves intake venting combined with continuous roof ridge venting (or equivalent area if the building framing does not permit a ridge vent) are needed to avoid ice dams, attic condensation, attic mold, rot, or insect damage from accumulating attic moisture. But the ratio of intake air to outlet air is of critical importance too. The ratio of soffit intake to roof outlet should be at least 2:1 to avoid unnecessary these heat losses from the building. A serious error is a roof outlet vent net free area that exceeds the air inlets at lower roof edges or eaves. When this occurs in a climate where building heating is needed during part of the year, warm air leaking into the attic or roof space and exiting at the ridge vent (or other vents high on the roof) creates a convection air current that draws excessive heat out of the building during the heating season, leading to unnecessarily high heating costs. But don't "fix" a bad intake to outlet air vent space ratio by reducing the ridge vent opening. Making this mistake can result in too little air flow under the roof surface, leading to indoor condensation and mold. Roof intake venting with no outlet vent openings won't work because there will be no air flow through the roof cavity. In a few cases, very wide, open soffit vents at building eaves seem to result in a dry attic, but the design relies on a prevailing wind pattern that sends air through the attic. Even in this case most air flow will be across the attic floor, and an inspection of the attic near the ridge may reveal evidence of unwanted condensation and moisture staining or even attic mold. Roof outlet venting with no intake venting won't work because the absence of sufficient intake of outside air to satisfy the negative pressure from air leaving at the ridge will cause draw warm air up from the building interior, increasing heating costs and possibly mold or allergen movement through the building. Providing more soffit or eaves intake venting than ridge outlet venting assures that the airflow required by attic air exiting at the ridge is satisfied by incoming outside air rather than by pulling air up from the building where it not only brings up building moisture, it also increases building heating or cooling costs. Table of Types of Ridge Vents and Net Free Venting Area per Linear Foot
Comments & Opinion About Statements of Net Free Ventilation Area of Various Roof Venting ProductsBesides the rated air ventilation area described by various vent product manufacturers, other roof and vent opening details can significantly affect the actual airflow and level of under roof ventilation at a building. While roofing product companies give useful general guidance on the amount of roof ventilation are recommended as a function of the square feet of attic space, here are some factors that could significantly change the actual recommended under-roof ventilation for a specific building:
Looking at a linear foot of a typical thick mesh-type ridge vent and before considering that power-nailing compresses the mesh to further reduce airflow: If we cut a 1.5" gap between ridge board and remaining roof deck, 12" long, on each side of the ridge board, that's Suppose a roof vent product company indicates that their product is giving you 17 sq.in. of roof venting in a 12" length - roughly that's a 50% airflow restriction over the free opening, before allowing for other obstructions (rafters, air flowing downhill) - by this analysis. But another step is needed: This is how we think about vent area with a roll-out mesh ridge vent material: The exposed *edge* of the mesh vent is all that can possibly vent out - that's typically about 1/2" to 3/4" high between the roof surface and the underside of the cap shingles on the roofs we have walked recently. For a linear foot, after the cap shingles are installed, and counting both sides of the ridge, that's about 12 sq. in. of available space (1/2" x 12" x 2 sides), We then cut that area in half to factor in the 50% mesh-restricted air flow rate that we found above, so we're really seeing an effective vent outlet, in the best case, of 6 sq.in. per foot. Which is too little compared with the intake. The appeal of the low profile roll-out type mesh ridge vent materials that are covered with cap shingles is aesthetic - the ridge vent looks nicer from the ground, and it's convenient on the truck - doesn't get dented, rolls up and stores nicely for transport, and installs over a non-straight ridge line, something that's a problem with the old vent type. So we understand why it's a popular product. It just does not pass as much air as the older vent type. We asked one manufacturer's mesh-type roll-out ridge vent vent tech-ref-salesman about their actual airflow tests and airflow venting rates at a JLC conference in the 1980's: he was flabbergasted - replying that he had no idea about any actual tests or measured numbers. Happily most roofing product manufacturers such as the GAF are kind enough to provide their estimates of the amount of ventilation provided by each product. A low profile mesh type and some other plastic ridge vents do not pass much air compared to an older (uglier) higher-profile rigid aluminum ridge vent. Where we are having difficulty obtaining good airflow under a roof (such as where there is limited air space between insulation and the roof deck, aggressive intake venting and properly sized outlet venting at the ridge can help assure that the limited vent space under the roof would have adequate airflow. That's why we often suggest that uglier alternative exit vent, as well as suggest making sure that the roof decking slots for outlet venting at the ridge are cut correctly on both sides of the ridge board. In general, you want 2x as much intake venting (at the eaves) as outlet (at the ridge) but keep in mind that if you use a mesh type "ridge vent" the ridge opening is obstructed by the mesh and the air flow will may be insufficient, so you can't just measure the sq.in. of vent opening, you have to also adjust the calculation for the degree to which the vent opening is obstructed by mesh, screening, and any other airflow obstructions such as under-sized cuts into the roof deck. On older homes where rafters are wider apart than standard modern framing specifications (16" o.c.), a baffle that extends the full width between the rafters is the best you're going to get unless the owners opt for the more labor intensive and thus more costly approach of a site-built vent path that uses furring strips alongside rafters and solid foam insulation sheets to give a deeper vent path under the roof than provided by a baffle. You'll want to look at the baffle selected to be sure it won't be compressed when insulation is added into the remaining roof space between the rafters. About ice dams and roof ventilationIncreased air flow under the roof will prevent, not cause, ice dams, provided that insulation is also completely installed. Take a look at Comparing Two Houses where we compare two under roof venting schemes on houses that happened to be side by side. We installed continuous soffit intake and ridge vent on the house at left; the house at right had almost no soffit intake venting. See ICE DAM PREVENTION for details about this topic. You'll want to be sure air FLOWS continuously from soffit to ridge- if the baffles compress or the air space is too little (say less than 1/2"), or if the ridge outlet is obstructed by low-flow plastic mesh, then the risk of ice dams is increased - not because of the soffit inlet but because of inadequate outlet. Put it another way, if you had no roof venting at all, heat lost into the roof cavity will cause ice dams. In sum the building design least likely to give ice dams includes
Last: don't forget the importance of also avoiding excessive interior moisture levels (a key factor in attic condensation and thus mold) - the dirt crawl space needs to be addressed. ... Technical Reviewers & References
Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website. INTERIORS of BUILDINGS
Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair
| |||||||||||||||||||||||||
|
INTERIORS of BUILDINGS AIR BYPASS LEAKS AIR LEAK DETECTION TOOLS AIR LEAK MINIMIZATION AIR SEALING STRATEGIES BATHROOM VENTILATION BASEMENT WATERPROOFING BLOWER DOORS & AIR INFILTRATION BRICK LINED WALLS BUCKLED FOUNDATIONS due to INSULATION? BUILDING NOISE DIAGNOSIS & CURE CATHEDRAL CEILING INSULATION CRAWL SPACE VENTING & Dryout Procedures MOISTURE, MOLD, ICE DAM LEAKS in ATTICS & ROOFS ATTIC CONDENSATION CAUSE & CURE HEAT LOSS: How to Calculate Heat Loss in a Building HOUSEWRAP AIR & VAPOR BARRIERS HUMIDITY LEVEL TARGET HOUSEWRAP AIR & VAPOR BARRIERS HOUSEWRAP - TYVEK INSTALLATION DETAILS ICE DAM PREVENTION INSULATION INSPECTION & IMPROVEMENT More Information InspectAPedia Blog - News Updates Air Conditioning & Heat Pumps Bookstore Electrical Environment Exteriors Heating Home Inspection Insulate Ventilate Interiors Plumbing Water Septic Roofing Structure Accuracy & Privacy Policies Contact Us |
More Information on Building Diagnostic Inspections and RepairsMore Reading about Dealing with Attic Mold, Identifying, Removing, and Preventing Mold in AtticsBe sure to review HOW TO FIND MOLD: How to Inspect Homes and Other Buildings for Mold - the Basics of How to Find Problem Mold Indoors in our Mold Action Guide. Here are other articles that will be helpful in evaluating attic mold presence, causes, and cures:
|
01/28/2010 - 06/02/1990 - InspectAPedia.com/interiors/atticcond10htm - © 2010 - 1988 Copyright Daniel Friedman All Rights Reserved - InspectAPedia® is a Registered U.S. Trademark