InspectAPedia.com InspectAPedia®
 

Free Encyclopedia of Building & Environmental Inspection, Testing, Diagnosis, Repair

Ask a Question or Search InspectAPedia

  • HOME
  • AIR CONDITIONING
  • ELECTRICAL
  • EXTERIORS
  • HEATING
  • HOME INSPECTION
  • INTERIORS
  • PLUMBING
  • ROOFING
  • SEPTIC SYSTEMS
  • STRUCTURE
  • WATER SUPPLY
  • ENERGY SAVINGS
  • ENVIRONMENT
  • INDOOR AIR IAQ
  • INSULATION
  • MOLD INSPECT TEST REMOVE
  • NOISE
  • ODORS
  • SOLAR ENERGY
  • VENTILATION
  • EXPERTS DIRECTORY
  • CONTACT US


Mobile Phone/PDA website viewMobile View
INTERIORS of buildings

ACOUSTICAL SEALANT CHOICES
AGE of a BUILDING - how to determine
AIR BYPASS LEAKS
AIR LEAK DETECTION TOOLS
AIR LEAK MINIMIZATION
AIR LEAK SEALING PROCEDURE
AIR SEALING STRATEGIES
ANIMAL ALLERGENS
ANIMAL ENTRY POINTS in buildings
ANIMAL ODORS IN buildings
APPLIANCE EFFICIENCY RATINGS
ARCHITECTURE & BUILDING COMPONENT ID
ASBESTOS FLOORING HAZARD REDUCTION
ASBESTOS-FREE INSULATION MATERIALS
ASBESTOS IDENTIFICATION IN buildings
ASBESTOS ROOFING / SIDING DUST
ASBESTOS REMOVAL, Wetting Guidelines

ATTIC LEAKS, CONDENSATION & ATTIC MOLD
  Air Bypass Leaks, Thermal Tracking
  Blocked Soffit Intake Vents
  CATHEDRAL CEILING INSULATION
  CATHEDRAL CEILING VENTILATION
  Comparing Two Houses
  Heat Tapes: Use on Roofs for Ice
  HEAT TAPES & CABLES on Roofs for Ice Dams
  HOT ROOF DESIGNS: Un-Vented Roof Solutions
  HOUSEWRAP AIR & VAPOR BARRIERS
  HUMIDITY LEVEL TARGET
  ICE DAM PREVENTION
  ICE DAM CURE: Comparing Two Houses
  Inspect Attics for Moisture or Mold
  Inspect Attics for Blocked Soffit Intake Vents
  Inspect Basements for Moisture or Mold
  Cold Pour Joint Leaks
  Form Tie Leaks
  Wall Crack Leaks
  Floor-Wall Joint Leaks
  Inspect Building Exterior - Roof Venting
  Inspect the Ridge Vent System from the Attic
  Inspect the Soffit Vent System from the Attic
  ROOF VENTILATION SPECIFICATIONS
  Roof Venting: Intake - Outlet Area Ratios
  Roof Venting: Proper Locations
  Roof Venting: Both Ridge & Eaves Venting Needed
  Roof Venting: Eaves Intake if no Overhang
  Roof Venting: Soffit Intake Vent-Continuous
  Roof Venting: Un-Vented Hot Roof Solutions
  ROOF VENTING ENERGY SAVING DETAILS
  ROOF VENTING NEEDED?
  SKYLIGHT VENTILATION DETAILS
  Soffit Ventilation

ATTIC VENTILATION

BASEMENT CEILING VAPOR BARRIER
BASEMENT HEAT LOSS
BASEMENT LEAKS, INSPECT FOR
BASEMENT WATERPROOFING

BATH & KITCHEN DESIGN GUIDE
BATHROOM VENTILATION
BEST CONSTRUCTION PRACTICES GUIDE
Best Interior Finish Practices

BLOWER DOORS & AIR INFILTRATION
BLOWER FAN CONTINUOUS OPERATION
BLOWER FAN OPERATION & TESTING
BLOWN-IN INSULATION

BOOKSTORE - INTERIORS

BRICK LINED WALLS
BRICK VENEER WALL INSULATION
BRICK VENEER WALL Loose, Bulged
BRICK WALL DRAINAGE WEEP HOLES
BUCKLED FOUNDATIONS due to INSULATION?
BUILDING NOISE DIAGNOSIS & CURE

CARPET DUST IDENTIFICATION
CARPET MOLD CONTAMINATION
CARPET PADDING ASBESTOS, MOLD, ODORS
CARPET FUNGICIDAL SPRAY
CARPET STAIN DIAGNOSIS
CARPET & other STAIN TESTS
CARPET TEST GUIDE
CARPETING & INDOOR AIR QUALITY
CARPETING, SELECTION & INSTALLATION

CABINETS & COUNTERTOPS
CATHEDRAL CEILING INSULATION
CATHEDRAL CEILING VENTILATION
CEILING FINISHES INTERIOR
CEILINGS, DROP or SUSPENDED PANEL
CEILINGS, PLASTER TYPES
CEILINGS, PLASTER, LOOSE HAZARDS
CEILING TILES - Asbestos-Containing

CHIMNEY INSPECTION DIAGNOSIS & REPAIR
CHINESE DRYWALL HAZARDS
COMBUSTION AIR for TIGHT buildings
COOLING LOAD REDUCTION by ROOF VENTS

CRAWL SPACES
CONDENSATION or SWEATING PIPES, TANKS
CONDENSATION on WINDOWS & SKYLIGHTS

DECK & PORCH CONSTRUCTION
DEW POINT CALCULATION for WALLS
DEW POINT TABLE - CONDENSATION POINT GUIDE
DOORS, INTERIOR
DRYER VENTING
ELECTRICAL INSPECTION, DIAGNOSIS, REPAIR

ENERGY SAVINGS in buildings
ENGINEERED WOOD Flooring
ENGINEERED WOOD Products

ENVIRONMENTAL HAZARDS - INSPECT, TEST, REMEDY

FIBERGLASS INSULATION
FIREPLACES & HEARTHS
FLAT ROOF MOISTURE & CONDENSATION

FLOOD DAMAGE ASSESSMENT, SAFETY & CLEANUP
FLOODS IN buildings-mold

FLOOR TYPES & DEFECTS
  FLOOR, CERAMIC TILE
  FLOOR, CONCRETE SLAB CHOICES
  FLOOR, CONCRETE SLAB POURED FINISH
  FLOOR DAMAGE DIAGNOSIS
  FLOOR, ENGINEERED WOOD & LAMINATES
  FLOOR FRAMING & SUBFLOOR for TILE
  FLOOR, KITCHEN & BATH OPTIONS
  FLOOR, LAMINATE PLASTIC
  FLOOR RADIANT HEAT Mistakes to Avoid
  FLOOR, RESILIENT VINYL or CORK
  FLOOR, STONE, GRANITE, MARBLE, AGGLOMER
  FLOOR & SUBFLOOR MOLD, HIDDEN
  FLOOR TILE ASBESTOS IDENTIFICATION
  FLOOR TILE HISTORY & INGREDIENTS
  FLOOR WOOD AGE TYPES HISTORY
  FLOOR WOOD, DAMAGE DIAGNOSIS
  FLOOR, WOOD ENGINEERED, LAMINATE, INSTALL
  FLOOR, WOOD FINISHES
  FLOOR, WOOD INSTALLATION GUIDE
  FLOOR, WOOD MOISTURE
  FLOOR, WOOD RADIANT HEAT
  FLOOR, WOOD SOLID STRIP, PLANK
  FLOOR, WOOD TYPES
  FLOORING MATERIALS, Age, Types

FORMALDEHYDE HAZARDS

FOUNDATION BULGE or LEAN MEASUREMENTS
FOOTING & FOUNDATION DRAINS

FOUNDATION CRACKS & DAMAGE GUIDE
FOUNDATION WATERPROOFING
FRENCH DRAINS
FREEZE-PROOF A BUILDING
FROST HEAVES, FOUNDATION, SLAB

GREEN BUILDING CONSTRUCTION CODES GUIDES
GREENHOUSE DESIGN for SOLAR HEATING
GREENHOUSE / SUNSPACE GLARE

HEAT LOSS RATE CALCULATIONS
HEAT LOSS in buildings
HEAT LOSS DETECTION TOOLS
HEAT LOSS INDICATORS
HEAT LOSS PREVENTION PRIORITIES
HEAT LOSS R U & K VALUE CALCULATION

HEAT TAPES & CABLES on Roofs for Ice Dams
HEATING COST SAVINGS METHODS

HOT ROOF DESIGNS: Un-Vented Roof Solutions
HOUSEWRAP AIR & VAPOR BARRIERS
HOUSE DOCTOR, how-to be
HUMIDITY LEVEL TARGET

ICE DAM PREVENTION

INDOOR AIR QUALITY & HOUSE TIGHTNESS
INDOOR AIR QUALITY IMPROVEMENT GUIDE
INDOOR HOUSE DUST & DEBRIS

INSULATION CHOICES
Insulation Air & Heat Leaks
INSULATION FACT SHEET- DOE
INSULATION for GREENHOUSE or SOLARIUM
INSULATION IDENTIFICATION GUIDE

INSULATION INSPECTION & IMPROVEMENT
INSULATION LOCATION - WHERE TO PUT IT
INSULATION LOCATION for BRICK VENEER WALLS
INSULATION LOCATION for CAPES, CRAWLSPACES
INSULATION LOCATION for CATHEDRAL CEILINGS
INSULATION LOCATION for GREENHOUSE or SOLARIUM
INSULATION MOLD
INSULATION R-Values & Properties

INSULATION INSPECTION & IMPROVEMENT
INSULATION LOCATION - WHERE TO PUT IT
INSULATION LOCATION for BRICK VENEER WALLS
INSULATION LOCATION for CAPES, CRAWLSPACES
INSULATION LOCATION for CATHEDRAL CEILINGS
INSULATION LOCATION for GREENHOUSE or SOLARIUM
INSULATION MOLD
INSULATION R-Values & Properties

KITCHEN VENTILATION

LEED GREEN BUILDING CERTIFICATION
LEED Building Designation & IAQ
LOG HOME ENERGY EFFICIENCY
LOG HOME GUIDE

MOBILE HOME INSPECTIONS

MOISTURE CONTROL in buildings
MOLD INFORMATION CENTER
MOLD ACTION GUIDE - WHAT TO DO ABOUT MOLD
MOLD APPEARANCE - WHAT MOLD LOOKS LIKE
MOLD CLEANUP GUIDE- HOW TO GET RID OF MOLD
MOLD DETECTION & INSPECTION GUIDE

MOLD EXPERT, WHEN TO HIRE
MOLD KILLING GUIDE
MOLD LEVEL IN AIR, VALIDITY
MOLD PREVENTION GUIDE
MOLD SPRAYS, SEALANTS, PAINTS
MOLD TEST KITS
MOLD TESTING SERVICES

Nanomaterials Hazards
NOISE / SOUND DIAGNOSIS & CURE

ODORS & SMELLS DIAGNOSIS & CURE

PAINT FALURE, DIAGNOSIS, CURE, PREVENTION
PASCAL CALCULATIONS
PLASTER & BEAVERBOARD & DRYWALL
PLASTER BULGES & PILLOWS
PLASTER LATH, METAL
PLASTER, LOOSE FALL HAZARDS
PLASTER TYPE IDENTIFICATION
PLASTER VENEER Best Practices

RADIANT BARRIERS
RADIANT HEAT
RADIANT HEAT Floor Mistakes to Avoid
RADIANT HEAT TEMPERATURES
RADIANT SLAB FLOORING CHOICES
RADIANT SLAB TUBING & FLUID CHOICES

ROOF VENTILATION SPECIFICATIONS
  ATTIC VENTILATION
  CASEWORK, CABINETS, SHELVING INSTALLATION
  CATHEDRAL CEILING INSULATION
  CATHEDRAL CEILING VENTILATION
  HOT ROOF DESIGNS: Un-Vented Roof Solutions
  Inspect Attics for Moisture or Mold
  Inspect Attics for Blocked Soffit Intake Vent
  Inspect Basements for Moisture or Mold
  Inspect Building Exterior - Roof Venting
  Inspect the Ridge Vent System from the Attic
  Inspect the Soffit Vent System from the Attic
  Insects & Foam Insulation
  HOUSE DOCTOR, how-to be
  Insulation Air & Heat Leaks
  Roof Venting: Intake - Outlet Area Ratios
  Roof Venting: Proper Locations
  Roof Venting: Both Ridge & Eaves Venting Needed
  Roof Venting: Eaves Intake if no Overhang
  Roof Venting: Soffit Intake Vent-Continuous
  Roof Venting: Un-Vented Hot Roof Solutions
  ROOF VENTING ENERGY SAVING DETAILS
  ROOF VENTING NEEDED?
  SKYLIGHT VENTILATION DETAILS
  Soffit Ventilation

ROT, FUNGUS, TERMITES
ROT, TIMBER FRAME

SAFETY HAZARDS & INSPECTIONS
SEARS KIT HOUSES

SOLAR ENERGY SYSTEMS

SOUND CONTROL in buildings

STAIN & BIODETERIORATION AGENT CATALOG
STAINS on buildings - QUICK GUIDE
STAIN DIAGNOSIS on BUILDING EXTERIORS
STAIN DIAGNOSIS on BUILDING INTERIORS
STAIN DIAGNOSIS on ROOFS
STAIN DIAGNOSIS on STONE
STAINS & FINISHES, INTERIOR
STAINS on INDOOR SURFACES: PHOTO GUIDE

STAIRS, RAILINGS, LANDINGS, RAMPS
STONE CLEANING METHODS

STUCCO WAll FAILURES DUE TO WEATHER
STUCCO WALL METHODS & INSTALLATION
STUCCO OVER FOAM INSULATION
STUCCO PAINT FAILURES

STRUCTURAL INSPECTIONS & DEFECTS
SUMP PUMPS GUIDE
SWEATING (CONDENSATION) on PIPES, TANKS

THERMAL EXPANSION of MATERIALS
THERMAL MASS in buildings
THERMAL TRACKING & HEAT LOSS

TRIM, INTERIOR INSTALLATION

TRUSS UPLIFT, ROOF
TRUSSES, Floor & Roof

VAPOR BARRIERS & CONDENSATION in buildings

VENTILATION in buildings
  Air Bypass Leaks, Thermal Tracking
  AIR CHANGE RATE ACH HEAT SAVINGS
  ATTIC CONDENSATION CAUSE & CURE
  BALANCED VENTILATION, HEAT COST SAVINGS
  BATH & KITCHEN DESIGN GUIDE
  BATHROOM VENTILATION
  Blocked Soffit Intake Vents
  BLOWER DOORS & AIR INFILTRATION
  BLOWN-IN INSULATION
  BRICK or BLOCK WALL CAVITY INSULATION
  BRICK VENEER WALL INSULATION
  CATHEDRAL CEILING INSULATION
  CATHEDRAL CEILING VENTILATION
  CLOTHES DRYER VENTING
  COOLING LOAD REDUCTION by ROOF VENTS
  CRAWL SPACE VENTING & Dryout Procedures
  HEAT LOSS: How to Calculate Heat Loss in a Building
  HOT ROOF DESIGNS: Un-Vented Roof Solutions
  HOUSEWRAP AIR & VAPOR BARRIERS
  HUMIDITY LEVEL TARGET
  ICE DAM PREVENTION
  Inspect Attics for Moisture or Mold
  Inspect Attics for Blocked Soffit Intake Vents
  Inspect Basements for Moisture or Mold
  Inspect Building Exterior - Roof Venting
  Inspect the Ridge Vent System from the Attic
  Inspect the Soffit Vent System from the Attic
  Insects & Foam Insulation
  HOUSE DOCTOR, how-to be
  Insulation Air & Heat Leaks
  KITCHEN VENTILATION
  MOISTURE CONTROL in buildings
  MOISTURE CALCULATIONS
  MOISTURE METER STUDY
  MOISTURE PROBLEMS: CAUSE & CURE
  ROOF VENTILATION SPECIFICATIONS
  ROOF VENTING ENERGY SAVING DETAILS
  ROOF VENTING NEEDED?
  SKYLIGHT VENTILATION DETAILS
  Soffit Ventilation
  VENTILATION, BALANCED HEAT COST SAVINGS
  VENTILATION DESIGN PROBLEMS & SOLUTIONS
  VENTILATION, WHOLE HOUSE STRATEGIES

WALL SIDING TRIM & FINISHES
WALL FINISHES INTERIOR

WATER BARRIERS, EXTERIOR BUILDING
WATER ENTRY in buildings

WIND WASHING INSULATION At EAVES
WINDOWS & DOORS

WINTERIZE A BUILDING
WOOD Burning Heaters Fireplaces Stoves
WOOD FLOOR DAMAGE

More Information

Photograph of frost in an attic - evidence of a source of attic mold and moisture damage How to Inspect Attics for Condensation & Moisture - to Detect & Correct Attic Condensation, Frost, Ice Dam Leaks & Attic Mold
InspectAPedia®  -    

  • How to inspect a building attic for evidence of ice dam leaks, condensation, frost, or moisture
  • How to detect roof venting deficiencies, attic insulation defects, and attic condensation problems
  • Questions & answers about detecting the cause of attic moisture, condensation, frost, leaks, or mold

This article describes inspection methods and clues to detect roof venting deficiencies, insulation defects, and attic condensation problems, in buildings. It describes proper roof ventilation placement, amounts, and other details.

InspectAPedia offers impartial, unbiased advice without conflicts of interest. We will block advertisements which we discover or readers inform us are associated with bad business practices, false-advertising, or junk science. Our contact info is at InspectAPedia.com/Contact.htm.

This chapter "How to Inspect in the Attic or Roof Cavity for Signs of an Under-roof Condensation Problem, is part of our artricle series on "Attic Condensation". Also see CATHEDRAL CEILING INSULATION.

These recommendations are based on 30 years of building inspections, on the observation of the locations of moisture, mold, ice dams, condensation stains, and other clues in buildings, and on the correlation of these clues with the roof venting conditions at those properties. I have also measured changes in airflow, temperature, and moisture before and after installing roof venting.

© Copyright 2012 InspectAPedia.com, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use page top links to major topics or use links at the left of each page to navigate within topics and documents at this website. Green links show where you are in a document series or at this website.

Inspecting in the Attic or Roof Cavity for Signs of an Under-roof Condensation Problem

After examining the eaves or lower roof edges, look up at the ridge for a continuous opening on either side of the ridge board, providing an exit vent path. On some buildings I've found that a ridge vent was installed but the installer just nailed it over the existing roof sheathing, forgetting to cut the necessary opening. "Spot vents" on lower roof slopes, or power vent fans are not as good a substitute for the year-round passive venting provided by a ridge vent.

You often will see many drip spots on the attic flooring or insulation (Left photo below). This is caused by moisture condensing on the roofing nails and dropping to the surface below. This is sure evidence of a condensation problem. The pattern of drip marks may be remarkably just like the pattern of roof shingle nails which protrude through the roof sheathing.

Winter condensation on the nails, even forming frost in freezing weather, rusts the nails and stains the roof sheathing around them. Frost later melts off of these nails and drips onto the floor below. The pattern may occur more on the cooler or north slope of the roof.

attic drip spots from attic condensation attic stains from roof leaks

If attic stains are from roof leaks, (right photo above) they will usually be much larger and will appear on the sides of rafters, on larger areas of the roof sheathing, and on larger areas of the attic floor.

If you see evidence of extensive roof leaks or condensation leaks, I'd also check the insulation and the attic side of the ceiling drywall for a hidden mold problem.

If you see condensation drip stains in the attic (left photo above), you'll be confirming what you suspected from outside -- inadequate ventilation.

attic stains from ice dams at eaves

Be careful and don't overlook viewing the roof eaves. There could be rotting fascia boards, decaying rafter ends, and delaminating plywood.

Look in that location for moisture-stained roof sheathing, and look carefully for ice dam leak stains into the eaves, such as the water marks shown in this photograph.

How to Inspect the Attic for Moisture - Stains Around Roofing Nails

Attic shows roof nails protrudingAttic shows condensation stains at roofing nails

Rust or stains around roofing nails that protrude through the attic sheathing (they're supposed to stick through) are a clear indication of high attic moisture.

Our photograph at above left shows roofing nails protruding through plywood roof sheathing visible in an attic where there is no under-roof condensation or moisture problem.

Our photograph at above right shows roofing nails which have rusted and stained the roof plywood in an attic where indoor moisture has risen through the building to condense on the under-side of the roof.

Attic condensation stains

Our photo at left shows the typical staining pattern in an attic where there has been modest condensation at the roofing nails.

If you perform this inspection step in winter in a freezing climate you may find frost on these nails. In other seasons or in non-freezing climates you will see rust on the roofing nails and often stains on the roof sheathing surrounding the nail. On an older home that has been re-roofed, you may see these nail-stains but no nails - the old nails may have been removed during re-roofing, leaving just the rust-marked roof sheathing.

Excessive attic moisture condenses on the cool metal surface of the roofing nails, causing corrosion or rust on the nails and stains on the surrounding wood materials. These same condensation points - the roofing nails - will often map exactly the drip stains found on the attic insulation or attic floor below each nail.

Because moisture may enter the attic more at some locations than others, for example over a bathroom or kitchen, nail staining and drip marks will not be uniformly distributed throughout an attic.

How to Spot Attic Mold Due to High Attic Moisture or Roof Leaks

Photo of brown mold in an attic Penicillium mold in an attic

These photos show mold on attic surfaces due to high moisture in that area. While many inspectors notice dark mold or mold-suspect material on roof framing or roof sheathing, it is at least as important, and often more important to spot the light-colored molds that may also be present - often these are the more hazardous, particularly if building conditions cause air movement downwards out of the attic into the living space or into an attic-located HVAC duct system.

The brown/black attic mold on plywood in the left-hand photo is easy to spot and is often an allergen or problematic attic fungus like Cladosporium sp., Pithomyces chartarum, Ulocladium sp., or Aureobasidium pullulans but the light colored mold on the tongue-and-groove pine roof sheathing in the right photo was found to be Penicillium sp. which is more likely to be airborne and transmitted in the building.

If you find significant levels or large areas of mold in your attic the mold should be cleaned - that is, removed. Do not rely on magic bullets like sprays alone. The spray approach does not remove the problem mold and it may spread it into otherwise uncontaminated materials like insulation.

Don't tear off the roof over a moldy attic: Unless the mold-causing conditions have also rotted framing or delaminated plywood roof sheathing, structural removal/replacement, such as a roof tear-off are unnecessary and inappropriate. But don't forget that if you see attic mold the insulation or ceiling drywall below may also be moldy.

See How to Find, Test For, & Remove Mold in Attics for details about where and how to look for attic mold and what to do about it.

Questions & Answers regarding this article

Questions & answers about detecting the cause of attic moisture, condensation, frost, leaks, or mold

Ask a Question or Search InspectAPedia

HTML Comment Box is loading comments...

Share this Article      

...

Technical Reviewers & References

  • InspectAPedia.com® - Daniel Friedman - Publisher & Editor.
  • Critique, contributions wanted: Contact Us to suggest corrections or additions to articles at this website, and if you wish, to receive online listing and credit as a contributor. Particular thanks are due to the many experts and also consumers who read and critique technical articles at InspectAPedia.com.
  • Alan Carson Carson Dunlop Associates, Toronto, Ontario. Mr. Carson is a home inspection professional, educator, researcher, writer, and a principal of Carson Dunlop Associates, a Toronto home inspection and education firm. Mr. Carson is a past president of ASHI, the American Society of Home Inspectors Some great illustrations of the proper under-roof ventilation pathways are offered by Carson Dunlop.
  • Mark Cramer Inspection Services Mark Cramer, Tampa Florida, Mr. Cramer is a past president of ASHI, the American Society of Home Inspectors and is a Florida home inspector and home inspection educator. (727) 595-4211 mark@BestTampaInspector.com 11/06 & 12/08
  • John Annunziata, P.E. - NY Metro ASHI during informal chapter discussions about roof and attic ventilation options (1986-1996).
  • Technical reviewers are invited to comment or ask questions - contact us

Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

ATTIC LEAKS, CONDENSATION & ATTIC MOLD
  Air Bypass Leaks, Thermal Tracking
  Blocked Soffit Intake Vents
  CATHEDRAL CEILING INSULATION
  CATHEDRAL CEILING VENTILATION
  Comparing Two Houses
  Heat Tapes: Use on Roofs for Ice
  HEAT TAPES & CABLES on Roofs for Ice Dams
  HOT ROOF DESIGNS: Un-Vented Roof Solutions
  HOUSEWRAP AIR & VAPOR BARRIERS
  HUMIDITY LEVEL TARGET
  ICE DAM PREVENTION
  ICE DAM CURE: Comparing Two Houses
  Inspect Attics for Moisture or Mold
  Inspect Attics for Blocked Soffit Intake Vents
  Inspect Basements for Moisture or Mold
  Cold Pour Joint Leaks
  Form Tie Leaks
  Wall Crack Leaks
  Floor-Wall Joint Leaks
  Inspect Building Exterior - Roof Venting
  Inspect the Ridge Vent System from the Attic
  Inspect the Soffit Vent System from the Attic
  ROOF VENTILATION SPECIFICATIONS
  Roof Venting: Intake - Outlet Area Ratios
  Roof Venting: Proper Locations
  Roof Venting: Both Ridge & Eaves Venting Needed
  Roof Venting: Eaves Intake if no Overhang
  Roof Venting: Soffit Intake Vent-Continuous
  Roof Venting: Un-Vented Hot Roof Solutions
  ROOF VENTING ENERGY SAVING DETAILS
  ROOF VENTING NEEDED?
  SKYLIGHT VENTILATION DETAILS
  Soffit Ventilation

ATTIC VENTILATION

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.
  • Home Reference Book - Carson Dunlop The Home Reference Book - the Encyclopedia of Homes, Carson Dunlop & Associates, Toronto, Ontario, 2010, $69.00 U.S., is available from Carson Dunlop. The Home Reference Book is a bound volume of more than 450 illustrated pages that assist home inspectors and home owners in the inspection and detection of problems on buildings. The text is intended as a reference guide to help building owners operate and maintain their home effectively. InspectAPedia.com ® author/editor Daniel Friedman is a contributing author. Field inspection worksheets are included at the back of the volume.
  • "The Elimination of Unsafe Guardrails, a Progress Report," Elliott O. Stephenson, Building Standards, March-April 1993
  • "Are Functional Handrails Within Our Grasp" Jake Pauls, Building Standards, January-February 1991
  • Access Ramp building codes:
    • UBC 1003.3.4.3
    • BOCA 1016.3
    • ADA 4.8.2
    • IBC 1010.2
  • Access Ramp Standards:
    • ADA (Americans with Disabilities Act), Public Law 101-336. 7/26/90 is very often cited by other sources for good design of stairs and ramps etc. even where disabled individuals are not the design target.
    • ANSI A117.4 Accessible and Usable buildings and Facilities (earlier version was incorporated into the ADA)
    • ASTM F 1637, Standard Practice for Safe Walking Surfaces, (Similar to the above standards)
  • "Energy Savers: Whole-House Supply Ventilation Systems [copy on file as /interiors/Energy_Savers_Whole-House_Supply_Vent.pdf ] - ", U.S. Department of Energy energysavers.gov/your_home/insulation_airsealing/index.cfm/mytopic=11880?print
  • "Energy Savers: Whole-House Exhaust Ventilation Systems [copy on file as /interiors/Energy_Savers_Whole-House_Exhaust.pdf ] - ", U.S. Department of Energy energysavers.gov/your_home/insulation_airsealing/index.cfm/mytopic=11870
  • "Energy Savers: Ventilation [copy on file as /interiors/Energy_Savers_Ventilation.pdf ] - ", U.S. Department of Energy
  • "Energy Savers: Natural Ventilation [copy on file as /interiors/Energy_Savers_Natural_Ventilation.pdf ] - ", U.S. Department of Energy
  • "Energy Savers: Energy Recovery Ventilation Systems [copy on file as /interiors/Energy_Savers_Energy_Recovery_Venting.pdf ] - ", U.S. Department of Energy energysavers.gov/your_home/insulation_airsealing/index.cfm/mytopic=11900
  • "Energy Savers: Detecting Air Leaks [copy on file as /interiors/Energy_Savers_Detect_Air_Leaks.pdf ] - ", U.S. Department of Energy
  • "Energy Savers: Air Sealing [copy on file as /interiors/Energy_Savers_Air_Sealing_1.pdf ] - ", U.S. Department of Energy
  • Falls and Related Injuries: Slips, Trips, Missteps, and Their Consequences, Lawyers & Judges Publishing, (June 2002), ISBN-10: 0913875430 ISBN-13: 978-0913875438
    "Falls in the home and public places are the second leading cause of unintentional injury deaths in the United States, but are overlooked in most literature. This book is unique in that it is entirely devoted to falls. Of use to primary care physicians, nurses, insurance adjusters, architects, writers of building codes, attorneys, or anyone who cares for the elderly, this book will tell you how, why, and when people will likely fall, what most likely will be injured, and how such injuries come about. "
  • Humidity: What indoor humidity should we maintain in order to avoid a mold problem?
  • Slips, Trips, Missteps and Their Consequences, Second Edition, Gary M. Bakken, H. Harvey Cohen,A. S. Hyde, Jon R. Abele, ISBN-13: 978-1-933264-01-1 or ISBN 10: 1-933264-01-2, available from the publisher, Lawyers ^ Judges Publishing Company,Inc., www.lawyersandjudges.com sales@lawyersandjudges.com and also from the InspectAPedia Bookstore (Amazon.com)
  • The Stairway Manufacturers' Association, (877) 500-5759, provides a pictorial guide to the stair and railing portion of the International Residential Code. [copy on file as http://www.stairways.org/pdf/2006%20Stair%20IRC%20SCREEN.pdf ] -
  • What Mold and Allergens Look Like: mold identification photos to help identify mold - choosing what to sample in buildings
  • How to Clean Moldy Wood Framing & Sheathing How to clean/seal mold from/on exposed lumber or plywood subfloor or roof sheathing indoors - some suggestions based on our field and laboratory research
  • Lighting, proper use of: proper aiming of a good flashlight can disclose hard to see but toxic light or white mold colonies on walls.
  • Mold spores in the Home - a Photo ID Library for detection and identification of mold allergens.
  • How to Find and Test For Mold in buildings A "how to" photo and text primer on finding and choosing the right spots to test for mold in buildings
  • Stuff that is not mold but is often mistaken for it - things you may not want to test. Also, not all "black mold" is toxic - here are examples of harmless black mold.
  • Simple Adhesive Tape Sampling of Moldy Surfaces - how to send a mold sample to our lab
  • Mold Sampling Methods in the Indoor Environment - In-depth article: detailed critique of popular mold testing methods - Is your mold test kit worth the bother?
  • Mold-Resistant Building Practices, advice from an expert on how to prevent mold after a building flood and how to prevent mold growth in buildings by selection of building materials and by anti-mold construction details.
  • Slips, Trips, Missteps and Their Consequences, Gary M. Bakken, H. Harvey Cohen, Jon R. Abele, Alvin S. Hyde, Cindy A. LaRue, Lawyers and Judges Publishing; 2 edition (April 2006), ISBN-10: 1933264012 ISBN-13: 978-1933264011
  • Steps and Stairways, Cleo Baldon & Ib Melchior, Rizzoli, 1989.
  • The Staircase, Ann Rinaldi
  • Common Sense Stairbuilding and Handrailing, Fred T. Hodgson
  • The Art of Staircases, Pilar Chueca
  • Building Stairs, by pros for pros, Andy Engel
  • A Simplified Guide to Custom Stairbuilding, George R. Christina
  • Basic Stairbuilding, Scott Schuttner
  • The Staircase (two volumes), John Templar, Cambridge: the MIT Press, 1992
  • The Staircase: History and Theories, John Templar, MIT Press 1995
  • Steps and Stairways, Cleo Baldon & Ib Melchior, Rizzoli, 1989.
  • "The Dimensions of Stairs", J. M. Fitch et al., Scientific American, October 1974.
  • "Weather-Resistive Barriers [copy on file as /interiors/Weather_Resistant_Barriers_DOE.pdf ] - ", how to select and install housewrap and other types of weather resistive barriers, U.S. DOE
  • Best Practices Guide to Residential Construction, by Steven Bliss. John Wiley & Sons, 2006. ISBN-10: 0471648361, ISBN-13: 978-0471648369, Hardcover: 320 pages, available from Amazon.com and also Wiley.com. See our book review of this publication.
  • Decks and Porches, the JLC Guide to, Best Practices for Outdoor Spaces, Steve Bliss (Editor), The Journal of Light Construction, Williston VT, 2010 ISBN 10: 1-928580-42-4, ISBN 13: 978-1-928580-42-3, available from Amazon.com
  • ...
Home About Us Accuracy Contact Us Content Use Policy Privacy Website Description © 2012 Copyright InspectAPedia.com