InspectAPedia®   -   Search InspectApedia

Leaky oil tank piping - oil line leak at the burner leads to smoky operation and risks loss of heat Heating Oil Line Feed Piping Leaks

  • POST a QUESTION or COMMENT about leaks or installation problems in heating oil piping for oil-fired heating equipment & water heaters

Heating oil piping leaks in the oil burner supply & return piping: causes & effects of leaks in heating oil supply piping at fittings, valves, or other locations.

Heating oil pipe leaks out (fuel oil leaks), oil piping leaks in (air in the system) are dangerous in several regards, as a leak in oil burner feed piping can cause a puffback or complete loss of heat.

This document lists other important safety or oil-fired equipment operational defects in home and light commercial heating oil storage and piping systems.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

Heating Oil Line Leaks - Oil Line leaks found - can lead to oil heat system puffback and loss of heat

Heating oil filter at the oil burner (C) Daniel FriedmanThis article discusses leaks in the oil piping line(s) between an oil storage tank and the oil burner(s) that it supplies.

Watch out: leaks in heating oil appliance piping or filters can be much more serious than just a drip spot on the floor.

The same leak that allows oil to drip out of the oil filter or piping connections allows air to be drawn into the system when the oil fuel unit (oil pump for the water heater, oil fired boiler or furnace) is running.

That air leak into the system results in improper oil burner operation, soot clogging, and even a loud bang at oil burner start-up or worse, a dangerous puffback.

[Click to enlarge any image]

A separate article

at OIL TANK FILL / VENT PIPE LEAK REPAIRS discusses leaks in the oil tank fill and vent pipes.

How to spot heating oil line piping leaks by eye

Look for a drip area below heating oil piping, connectors, the oil filter, anywhere from the oil tank to the oil burner. To make detection of oil line leaks easier, be sure that surfaces below these areas are clean of loose dirt and debris.

To confirm that a suspected leak is dripping it may help to place a clean paper towel on the floor below the suspected drip point. Monitor for oil drops on the paper towel.

Oil piping leak at the fire safety valve on an oil fired steam boiler (C) Daniel Friedman

In our photo above, the oil line leak is a bit obvious as the property owner has left an aluminum pie plate to catch dripping heating oil!

The oil leak at the oil safety valve (below left) was present on the oil line supplying the oil burner whose smoky operation could be seen from outdoors (below right).

Oil burner smoky operation visible outdoors (C) Daniel Friedman

While the smoky chimney visible at above right cleared up after an hour or so of oil burner operation, we suspect that because the smoky operation went on for at least fifteen minutes after initial oil burner start-up, the oil burner was not operating properly.

Further investigation by a heating service tech might trace the burn-off of oil accumulated in the combustion chamber to that leaky OSV shown at above left.

Heating oil leak at oil safety valve (C) Daniel Friedman

Why would this happen? It may come as a surprise but drawing air into the oil burner from a leak in the oil line can leave an air bubble in the oil burner nozzle.

When the oil burner shuts down the pressure inside the nozzle area drops from 100 psi or more down to ambient pressure of just a few pounds.

Photo at left: close-up shows heating oil seeping out at the very top of the oil safety valve (red arrow) and at the valve stem base (blue arrow).

Locating the highest point at which heating oil is visible on an oil-soaked component usually is a good clue about the actual point of leakage.

This oil line safety valve (OSV) is leaking through the valve core. It needs to be replaced. [Click to enlarge any image]

The reduction in pressure causes that little air bubble to expand, pushing extra oil out of the oil burner nozzle where it dribbles into the oil heating system boiler or furnace combustion chamber.

The next time the oil burner starts-up this un-burned oil residue forms a mini explosion - you may hear a sort of "bang" when the oil burner starts.

Watch out: This malfunction can lead to a serious puff back blowing soot into the home, or worse.

This is an unsafe condition caused by what looks like a tiny innocent drip such as the one we show in our photo above.

This item should be checked/corrected by your service person promptly.

See details at PUFFBACKS, OIL BURNER

Heating Oil Leaks in the Heating Oil Line at the Oil Filter

Heating oil leak points at the oil filter (C) Daniel Friedman

In detail at OIL FILTER LEAK POINTS we describe the sources of leaks at and around the heating oil filter. Excerpts are below.

Leaks at the heating oil filter can occur at a variety of locations - everywhere that there is a threaded fitting or connector, including:

Oil piping leak at the copper piping flare fitting

Heating oil pipeline leaks (C) Daniel Friedman

As we explain in this article, and as we elaborate

at OIL BURNER INSPECTION & REPAIR

as well, oil leaks in the oil piping and filter system can not only spill oil, but can lead to loss of heat, improper oil burner operation and even a puffback.

At left we illustrate an active oil leak at a flare fitting.

We don't know without further investigation if this leak is because the flare nut is loose or if it's because the copper flare was cracked or improperly made, or finally, if it's because of a notch or scratch on the brass mating surface of the flare.

Try gently tightening the fitting and then clean it thoroughly and check for leaks.

What to Do About Heating Oil Line Leaks: How Urgent is Repair?

Heating oil pipeline leaks (C) Daniel FriedmanThis example of inspection report language where leaks or drips are found in heating oil piping is based on the inspection and photographs shown above.

Watch Out: unsafe condition and risk of loss of heat at the building:

We saw a heating oil line leak at oil line piping and fittings at the oil burner: the oil safety valve was wet with heating oil as were nearby oil piping fittings, and a pie plate on the floor contained about 1/2" of fresh heating oil. [Photo at left]

We also observed improper heating system operation: the burner ran very smoky (photos below) for a protracted interval after start-up, suggesting a quantity of un-burned oil in the combustion chamber.

That condition can be caused by air leaks into the heating oil piping system.

Oil leaks may be hazardous and also, as air may be drawn into the oil line when the fuel unit is pumping, they can lead to improper and unsafe system operation and even loss of heat in the building.

The urgency of this repair depends in part of other on-site observations such as the state of operation of the heating system. Given the smoky chimney (photo below) that was observed at oil burner startup and for a protracted interval after start-up, this system is not operating properly.

Action: A heating service call should be scheduled immediately.

This is a bit more detail than many home inspectors prefer to provide to their customer. I include this level of information to be sure that the reader understands the issue and is forewarned to reduce the risks of failure to act or failure to obtain a proper repair. The minimum that might be reported is below:

Watch Out: We saw evidence of a heating oil line leak at oil line piping and fittings at the oil burner:

A heating service call should be schedule immediately to reduce the chances of loss of heat and unsafe heating system operation.

Why do we call this heating oil line leak a safety concern?

Oil line leaks can lead to a dangerous puffback at the oil burner that in turn risks a very messy soot-up of the building interior and in less common but possible cases, a fire, or a blow-off of the flue vent connector between the heating appliance and the chimney, subsequently venting combustion gases (and possibly dangerous carbon monoxide) into the building.

See PUFFBACKS, OIL BURNER

Inspection & Pressure Tests (Vacuum Tests) of Heating Oil Piping

Reader Question: Is it normal practice to pressure test fuel lines when a new boiler has been fitted?

Is it normal practice to pressure test fuel lines when a new boiler has been fitted? We have an outdoor boiler that runs on a 2 pipe system as the storage tank is below the boiler.

The oil tank lines are buried as the distance between boiler & storage is 15-20 m. We reported a vast increase in oil consumption after installation, would it be the normal course of action to then pressure test 'supply & return' lines? - Mark 5/29/12

Reply: How pressure & vacuum gauges are used on heating oil lines to check for leaks or fuel unit troubles

Mark, it is normal practice to inspect oil piping for leaks at all of its fittings & connections for leaks after a new installation, and there are indeed vacuum measurement tests (not pressure tests) that can be conducted that indicate an air leak into the oil supply line line (or oil leaks out when the fuel unit is not running).

But in my experience oil line vacuum tests are not performed as a matter of course but rather when a problem is under diagnosis, such as improper oil burner operation. And in my experience oil supply & return lines between the oil tank and the oil burner are not pressure tested. As I explain here, pressure testing those lines runs into some practical difficulties.

Similarly, a vacuum gauge installed on the heating oil supply line, often at or near the oil filter assembly, can help diagnose a leak in the supply piping itself.

Unfortunately in a two-pipe system we don't install and cannot use a similar gauge on that second line to check for leaks.

In a two-pipe oil line system, the return line is never under vacuum, only under pressure when excess oil from the fuel unit is cycling back to the oil tank. Because the exit end of that pipe is open into the oil tank, it is not and cannot be "pressure tested" without some disassembly and the fitting of a plug at the line's outlet end.

At OIL PUMP FUEL UNIT we include a detailed explanation of how to read a pressure gauge on the oil piping system (at the fuel unit) to diagnose a leak or similar problem at the fuel unit.

De-Aerator Problems with Air Leaks in Oil Line Piping

This discussion has moved to OIL SUPPLY & RETURN LINE DE-AERATORS Tigerloop™


...

Continue reading at OIL LINE PIPING LEAK CAUSES or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see OIL LINE PIPING LEAK FAQs - questions & answers about finding and fixing oil piping leaks that were posted originally on this page.

Or see these

Recommended Articles

  • OIL LINE PIPING - home
  • OIL or GAS FUELED HEATING EQUIPMENT SHUTOFFS
  • OIL SPILL CLEANUP / PREVENTION
  • OIL TANK PIPING & PIPING DEFECTS - home
  • Suggested citation for this web page

    OIL SUPPLY LINE PIPING LEAKS at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.


    Or see this

    INDEX to RELATED ARTICLES: ARTICLE INDEX to HEATING OIL, OIL BURNERS, OIL FIRED HEATERS, OIL TANKS

    Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

    Ask a Question or Search InspectApedia

    Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.

    Search the InspectApedia website

    Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.

    Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
    You will not receive a notification
    when a response to your question has been posted.
    Please bookmark this page to make it easy for you to check back for our response.
    Our Comment Box is provided by Countable Web Productions countable.ca

    Comment Form is loading comments...

    Citations & References

    In addition to any citations in the article above, a full list is available on request.



    ADVERTISEMENT