InspectAPedia ®

Building & Environmental Inspection, Testing, Diagnosis, Repair, & Problem Prevention Advice
InspectAPedia
Home
| Air
Conditioning
| Electrical | Indoor
Environment
| Exteriors | Heating | Home
Inspection
| Insulate
Ventilate
| Interiors | Mold
Inspect/Test
| Plumbing
Water
Septic
| Roofing | Structure | Contact Us
Directory of Professionals to Inspect or Test a Building


OIL TANK HOME
ABANDONING OIL TANKS
ABOVE GROUND OIL TANK INSPECTIONS
BURIED OIL TANK ADVICE
BURIED OIL TANKS, FINDING
FLOATING UP OIL STORAGE or SEPTIC TANKS
FUEL OIL TYPES & CHARACTERISTICS
HEATING OIL EXPOSURE HAZARDS, LIMITS
HEATING OIL SHELF LIFE
OIL TANK ABANDONING PROCEDURE
OIL TANK FAILURE CAUSES
OIL TANK FAILURE RATES
OIL TANK GAUGES
OIL TANK INSPECTION REPORTS
OIL TANK LEGAL ISSUES
OIL TANK LEAK ADVICE
OIL TANK LIFE
OIL TANK PIPING DEFECTS
OIL TANK PRESSURE
OIL TANK REGULATIONS
OIL TANK REMOVAL COs
OIL TANK REMOVAL FINANCIAL AID
OIL TANK SLUDGE
OIL TANK STANDARDS
OIL TANK SUPPORT
OIL TANK TESTING
OIL TANK TESTING COs
OIL TANK WATER CONTAMINATION

More Information

InspectAPedia.comInspectAPedia ® Home & Site Map
InspectAPedia Blog - News Updates
Air Conditioning & Heat Pumps
Bookstore
Electrical
Environment
Exteriors
Heating
Home Inspection
Insulate Ventilate
Interiors
Mold Inspect/Test
Plumbing Water Septic
Roofing
Structure
Accuracy & Privacy Policies
Contact Us



Photograph of  an oil tank with seepage around the filler pipe and a too-small vent pipe.

Residential Oil Tank Pressures During Testing & During Oil Tank Fill-up
InspectAPedia®  -  

  • How Much Pressure is There on a Home Heating Oil Tank During an Oil Delivery?
  • What causes overpressure conditions in home heating oil tanks above ground or underground
  • How to avoid over-pressurizing a heating oil tank
Our site offers impartial, unbiased advice without conflicts of interest. We will block advertisements which we discover or readers inform us are associated with bad business practices, false-advertising, or junk science. Our contact info is at InspectAPedia.com/appointment.htm.

Here we explain the typical oil tank test pressure at the factory, the pressures that an oil tank is subjected to during oil tank fill-up, and the cause and prevention of excessive pressures that can cause leaks at oil tanks. This series of articles discusses the causes of leaks at oil tank fill or vent piping, what the leak and other hazards are, and what to do about oil tank piping leaks.

We also answer the question of the amount of pressure to which an oil tank is subjected during an oil delivery, providing pressure limits, calculation of oil tank pressure changes, and listing both causes and steps to prevent over pressurizing a home heating oil tank. Thanks to David Hollen, Applications & Technical Support, at pump manufacturer and distributor Yamada America for help with this data. We discuss pressure testing of oil tanks at OIL TANK TESTING. Readers should also see LEAKY OIL TANK FILL PIPES as well as LEAKY OIL TANK FILL PIPES and as OIL TANK LEAK CAUSES.

© Copyright 2009 Daniel Friedman, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use links at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

Factory Test Pressures on Steel Heating Oil Tanks

Oil tank pressure test label (C) Daniel Friedman Oil tank pressure test label (C) Daniel Friedman

Residential above ground steel heating oil tanks are typically factory tested to 5 psi to 7 psi by the manufacturer, as our two photographs of oil tank labels show (above).

Oil tank pressure test limits (C) Daniel FriedmanIn fact, as the labels show on oil tanks we photographed early in 2009 (at left and at the top of this page), some steel oil tank manufacturers specifically advise against further pressure testing of their oil tanks.

If you need to know the condition of an above-ground home heating oil tank after it has been installed, ask your heating oil company to perform a metal thickness scan of the oil tank. The technician will use a sonic test instrument to measure the thickness of the steel at a number of locations on the lower portion of the tank.

The reason the technician tests the lower tank areas is that it is there that corrosion and thus thinning of the tank steel most often occurs. This inspection procedure will not, however, detect a faulty tank weld nor piping errors in the heating oil handling system.

If you are concerned about the chances that a buried oil tank has leaked, you'll need to locate the tank and have appropriate soil tests performed. We discuss pressure testing of oil tanks at OIL TANK TESTING. Also see OIL TANK LEAK ADVICE and TANK TESTING COs.

Effects and Amounts of Oil Tank Pressures During a Home Heating Oil Delivery

How Much Pressure is There on a Home Heating Oil Tank During an Oil Delivery?

But what is the pressure to which a heating oil tank is subjected during an oil delivery? The pressure experienced by the oil tank during fill from the home heating oil delivery truck is expected to be less than the oil tank manufacturer's tank test pressure (5-7 psi) if the oil tank is adequately vented. A more detailed answer to the question of oil tank pressures is that it depends on several factors including the two main oil tank pressure factors listed below.

  • The pressure at which oil is pumped into the oil tank from the home heating oil delivery truck. A typical home heating oil delivery truck pumps oil into the heating oil tank at 20 to 40 gpm and at less than 10 to 15 psi.
    -- Thanks to David Hollen, Applications & Technical Support, at pump manufacturer and distributor Yamada America for help with this data.
  • The condition of the oil tank vent piping on the home heating oil tank receiving the oil. If a heating oil tank is not vented at all or if it is not vented properly, the pressures to which the oil tank are subjected can be substantial, as we explain in detail below.

Home heating oil is delivered under pressure at many buildings: the oil delivery truck's hose nozzle latches onto a special fitting at the top of the oil tank fill-valve. When this type of connection is made, the driver can fill the oil tank more rapidly than otherwise, and also can avoid spillage around the oil tank fill pipe.

Just how much pressure an oil tank is subjected to during filling varies as follows:

Normal oil tank fill tank pressure: less than 5 psi on a properly vented heating oil tank (the presumed tank pressurization must be less than the manufacturer's factory tested tank pressure)

Totally-blocked or missing oil tank venting: pressures up to 280 psi - this would be an unusual condition such as an oil tank vent that has not only become totally blocked, but the vent blockage is not "blown out" by pressures created during the tank filling operation.

Anticipated partially-blocked oil tank venting: as oil tank pressure increases due to compressed air in the tank pressing against an obstruction in the oil tank vent pipe (such as an oil slug blocking the vent line or a cap blockage by an insect nest or a painted-over vent cap screen) the pressure may be sufficient to "blow out" a transient blockage of that type. The pressure required depends on the solidity and adhesion of the blocking oil tank vent line debris. Our opinion is that considering the range of possible oil tank pressures, between 0 psi and over 200 psi (with a totally obstructed vent), it should be quite easy for an oil tank pressure to exceed the manufacturer's factory-test pressure of 5 to 7 psi.

Calculation of Increase in Oil Tank Pressure During Fill-up

If an oil tank is NOT vented, depending on how empty the tank was (how much air it contained), when the tank is filled it could be subjected to quite high pressure. Using Boyle's Law (P1V1 = P2V2), if we assume that a 275 gallon oil tank contained only 75 gallons at the start of fill up (200 gallons of air at 1 atmosphere pressure (14.7 psi)), and if the tank had absolutely no exit venting, and if the tank is filled to leave just 10 gallons of air remaining (actually it may be filled to the top if the tank lacks overfill protection or if the driver is not paying attention) then the pressure would increase from atmospheric (14.7 psi) to 294 psi. If we subtract out our starting 14.7 psi that means we've pressurized the tank to about 280 psi.

Examples of Causes of Excessive Pressures in a Heating Oil Tank

Restricted oil vent pipe (C) Daniel Friedman

  • A restricted oil tank vent pipe diameter, such as using too-small diameter oil tank vent piping (2" diameter is recommended in many jurisdictions, and a minimum of 1 1/2" diameter piping is common. Some older oil tank vent pipes may be just 1" in diameter and should be upgraded. Since 1902, NFPA, the National Fire Protection Association has provided oil burning equipment standards including dealing with oil tanks and tank vents. Many municipalities have adopted NFPA standards as part of their building codes. An under-sized oil fill pipe, a tipped one, and other defects may fail to meet NFPA or other building codes and certainly they increase the risk of an oil leak during an oil delivery.
  • Oil vent pipe clogged by a slug of oil or water: if an oil vent pipe is not properly sloped to drain back into the oil tank and if the tank is over-filled, oil may be pushed into a down-sloping section of piping, causing a blockage that increases tank pressure during fill-up.
  • Oil vent pipe cap clogged by insects or debris: we have found oil tank vent pipe caps that were totally blocked by insects, such as mud daubers who filled the vent with mud and nest materials. We've also see oil tank vent caps that include screens to keep out insects, but the screen has been blocked by paint or by grass clippings from the passage of a lawn mower.
  • Oil tank ball float valves - can cause an oil tank spill by malfunction.

Protection from Oil Tank Overfill - Methods

Because overfilling an oil tank might contribute to high oil tank pressures, we list some methods and products used to avoid over-filling a home heating oil tank:

  • Measure the oil level in the tank before filling to be sure that the tank really needs oil delivery. On occasion an oil tank gauge can stick and give erroneous readings.
  • Oil tank vent whistles are an old and traditional way to avoid tank overfilling. A whistle sounds as air is escaping the tank and stops when the tank is full. The oil tank delivery driver needs to stay close to the fill and vent piping to listen for this event. If the driver walks away from the building to have a smoke during oil tank fill-up there could be an overfill event. In some states such as Maine, state law requires that the delivery person remain present during oil tank fill-up.
  • Oil tank level alarms: can provide an audible signal when the tank is filled to a specified level, typically set at 90% full.
  • Spill buckets may be provided around the filler pipe for buried or underground oil storage tanks.
  • Remove un-used oil filler and vent piping: Never ever leave an oil and vent pipe installed at a home where the oil tank has been removed. There is a risk that a mistaken oil delivery driver will attempt to deliver to the wrong pipes, flooding and ruining the home with heating oil.

Share this Article      

...

Technical Reviewers & References

  • Daniel Friedman - principal author/editor of the InspectAPedia® Website
  • InspectAPedia Bookstore lists recommended books, organized by topic & available for purchase. Most of our articles also include a list of recommended books for the specific article topic as well as other references, and information sources.
  • Critique, contributions wanted: Contact Us to suggest corrections or additions to articles at this website, and if you wish, to receive online listing and credit as a contributor. Particular thanks are due to the many experts and also consumers who read and critique technical articles at InspectAPedia.com.
  • Additional technical contributors & reference sources for this article are listed below.

Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

OIL TANK HOME
ABANDONING OIL TANKS
ABOVE GROUND OIL TANK INSPECTIONS
BURIED OIL TANK ADVICE
BURIED OIL TANKS, FINDING
FLOATING UP OIL STORAGE or SEPTIC TANKS
FUEL OIL TYPES & CHARACTERISTICS
HEATING OIL EXPOSURE HAZARDS, LIMITS
HEATING OIL SHELF LIFE
OIL TANK ABANDONING PROCEDURE
OIL TANK FAILURE CAUSES
OIL TANK FAILURE RATES
OIL TANK GAUGES
OIL TANK INSPECTION REPORTS
OIL TANK LEGAL ISSUES
OIL TANK LEAK ADVICE
OIL TANK LIFE
OIL TANK PIPING DEFECTS
OIL TANK PRESSURE
OIL TANK REGULATIONS
OIL TANK REMOVAL COs
OIL TANK REMOVAL FINANCIAL AID
OIL TANK SLUDGE
OIL TANK STANDARDS
OIL TANK SUPPORT
OIL TANK TESTING
OIL TANK TESTING COs
OIL TANK WATER CONTAMINATION

  • Yamada Pumps, 800 990-7867, is a leading producer of industrial equipment since 1905, and of fluid handling products for over 60 years. Yamada America supports pump requirements for North, Central, and South America and has an assembly facility in the U.S. in Arlington Heights, IL. Special thanks to David Hollen, Applications & Technical Support, 847 631-9200 ext. 218, for technical consulting regarding pump selection and capacity.
  • Boyle's Law: this simple gas law explains the relation between pressure and volume when either of those changes - P1 • V1 = P2 • V2 A nice online calculator for Boyle's Law simple pressure and volume change operations is provided by 1728 Software Systems and can be found online at www.1728.com/boyle.htm
  • "Chapter 2, Operating Your Heating Oil Tank", Main Department of Environmental Protection, maine.gov/dep/rwm/ust/pdf/hotdoc2.pdf and see maine.gov/dep/rwm/ust/ for Maine's basic guide to oil storage tanks and maine.gov/dep/rwm/ust/statutesrules.htm for Maine's UST statutes and rules.
  • OIL TANK REGULATIONS lists oil tank regulations for all U.S. states and protectorates as well as Federal and some Canadian authorities on oil tank regulation and leak reporting

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building design, inspection, and repair, and about indoor environment testing, diagnosis, and cleanup are at the InspectAPedia Bookstore.
  • ...
OIL TANK HOME

More Information

InspectAPedia.comInspectAPedia ® Home & Site Map
InspectAPedia Blog - News Updates
Air Conditioning & Heat Pumps
Bookstore
Electrical
Environment
Exteriors
Heating
Home Inspection
Insulate Ventilate
Interiors
Mold Inspect/Test
Plumbing Water Septic
Roofing
Structure
Accuracy & Privacy Policies
Contact Us

More Information on Building Diagnostic Inspections and Repairs

    ...
InspectAPedia.comInspectAPedia® Home & Site Map - Building & Environmental Inspection, Testing, Diagnosis, Repair, & Problem Prevention Advice: In-depth research & advice on diagnosing, testing, correcting, & preventing building defects & indoor environmental hazards. Unbiased information, no conflicts of interest.
GO TO the MOLD and INDOOR ENVIRONMENT INFORMATION CENTER for in-depth advice on avoiding testing for or cleaning up mold and other indoor environmental hazards, odors, gases, contaminants
The Mold Information Center:
What to Do About Mold in Buildings, When and How to Inspect for Mold, Clean Up Mold, or Avoid Mold Problems
GO TO MOLD TEST KITS: This expert-recommended mold test kit is cheap and yet top performing *IF* you use a competent analysis laboratory!
Use this simple, economical mold test kit
by following our instructions on how to collect and mail mold samples to our lab
GO TO IAQ/MOLD-TEST LAB SERVICES: Mold, Pollen, indoor air quality, field and laboratory services by an expert.Environmental Inspection, Testing, & Diagnosis On-Site IAQ, Gas, Air Testing, Mold Investigation, Sick Building Diagnosis, Lab Services, & Remediation Plan Preparation - indoor air quality testing, problem source determination, supporting lab work, written remediation plan addressing removal of environmental and other hazards and prevention of their recurrence.
GO TO our PRE PURCHASE BUILDING INSPECTION SERVICES: Authoritative information for home buyers and home owners is included with your inspection.
Building Inspection, Problem Diagnosis
, Forensic Investigation & Testing, Repair Consulting

CONTACT Daniel Friedman - Dan is a senior ASHI home inspector, nationally recognized expert on building inspection, building failures, and sick building investigation
Contact Daniel Friedman for website content suggestions or for fee-paid consulting

04/09/2009- 10/25/2009 - InspectAPedia.com/oiltanks/Oil_Tank_Pressures.htm - © 2009 - 1988 Copyright Daniel Friedman All Rights Reserved - InspectAPedia® is a Registered U.S. Trademark