OIL STORAGE TANKS

ABANDONING OIL TANKS
ABOVE GROUND OIL TANK INSPECTIONS
AFUE DEFINITION, RATINGS
AGE of OIL TANK
ANODES & DIP TUBES on WATER HEATERS

BIOGAS PRODUCTION & USE
BOILERS, HEATING

BURIED OIL TANK ADVICE
BURIED OIL TANKS, FINDING

COMBUSTION PRODUCTS & IAQ

DEFINITION of Heating & Cooling Terms
DIAGNOSE & FIX HEATING PROBLEMS-BOILER
DIAGNOSE & FIX HEATING PROBLEMS-FURNACE

FILTERS, OIL on HEATING EQUIPMENT
FIRE SAFETY CONTROLS
FLAME COLOR, BLUE vs YELLOW COMBUSTION
FLOATING UP OIL STORAGE or SEPTIC TANKS
FLOODED HEATING EQUIPMENT REPAIR
FLOODED WATER HEATER REPAIR
FUEL OIL TYPES & CHARACTERISTICS
FUEL UNIT, HEAING OIL PUMPS

GALVANIC SCALE & METAL CORROSION
GAUGES ON HEATING EQUIPMENT

HEAT LOSS in buildings
HEAT TAPES, Heat, Insulation prevent Freeze-Up

HEATING COST FUEL & BTU Cost Table
HEATING COST SAVINGS METHODS

HEATING OIL CLOUD WAX GEL POINT
HEATING OIL EXPOSURE HAZARDS, LIMITS
HEATING OIL - OLD, USEABLE?
HEATING OIL PIPING TROUBLES
HEATING OIL SHELF LIFE
HEATING OIL SLUDGE
HEATING OIL TANKS
HEATING OIL USAGE RATE

HEATING SYSTEM INSPECT DIAGNOSE REPAIR
HEATING SYSTEM NOISES

HOME BUYERS GUIDE TO OIL TANKS
HOT WATER HEATERS

NO HEAT - BOILER / FURNACE DIAGNOSIS
NOISE CONTROL for HEATING SYSTEMS
NOISES COMING FROM WATER HEATER

ODORS & SMELLS DIAGNOSIS & CURE
ODORS FROM HEATING SYSTEMS

OIL BURNERS
OIL BURNER INSPECTION GUIDE
OIL BURNER NOISE SMOKE ODORS
OIL BURNER SOOT & PUFFBACKS

OIL FILTERS on HEATING EQUIPMENT
OIL FILTER MISSING
OIL FUEL TYPES & CHARACTERISTICS

OIL LINE CLOGGING FIX
OIL LINE SAFETY VALVES
OIL ODORS, LEAKY OIL TANK PIPING
OIL PUMP FUEL UNIT

OIL SPILL CLEANUP / PREVENTION

OIL TANKS
OIL TANK ABANDONING PROCEDURE
OIL TANK AGE
OIL TANK, BURIED, ADVICE
OIL TANK, BURIED, FINDING

OIL TANK FAILURE CAUSES
OIL TANK FAILURE RATES
OIL TANK FLOATING UP

OIL TANK GAUGES
OIL TANK INSPECTION, ABOVE GROUND
OIL TANK INSPECTION REPORTS

OIL TANK LEAKS & SMELLS
  OIL TANK LEAK ENVIRONMENTAL ISSUES
  FREQUENCY of OIL TANK LEAKS
  HOME INSPECTOR OIL TANK REPORT
  OIL TANK LEAK IMPACTS
  OIL TANK LEAK CAUSES
  OIL TANK LEAK CLEANUP GUIDE
  OIL TANK LEAK REPORTING REGULATIONS - ALL
  OIL TANK REGULATIONS - CANADA
  OIL TANK LEAK REPORTING in NEW JERSEY
  OIL TANK LEAK & SIZE REPORTING REQUIREMENTS
  OIL TANK LEAK TESTING
  LEAKY OIL TANK FILL PIPES
  OIL TANK LEAK REPORTING BASICS
  WHAT IF AN OIL TANK IS LEAKING?

OIL TANK LEGAL ISSUES
OIL TANK LIFE

OIL TANK PIPING & PIPING DEFECTS
OIL TANK PRESSURE

OIL TANK REGULATIONS
  BULK STORAGE OF PETROLEUM PRODUCTS
  OIL TANK LEAK REPORTING BASICS
  OIL TANK LEAK REPORTING REGULATIONS - ALL
  OIL TANK LEAK REPORTING, NEW JERSEY
  OIL TANK LEAK & SIZE REPORTING REQUIREMENTS
  OIL TANK LEGAL ISSUES
  OIL TANK REGULATIONS - CANADA
  OIL TANK LEAK & SIZE REPORTING REQUIREMENTS
OIL TANK REMOVAL COs
OIL TANK REMOVAL FINANCIAL AID
OIL TANK REPORT LANGUAGE

OIL TANK SAFETY
OIL TANK SLUDGE
OIL TANK STANDARDS
OIL TANK STANDARDS - Detailed List
OIL TANK SPILL CLEANUP / PREVENTION
OIL TANK SUPPORT

OIL TANK TESTING
OIL TANK TESTING COs

OIL TANK WATER CONTAMINATION
OIL TANK WATER REMOVAL

SOOT on OIL FIRED HEATING EQUIPMENT

STAIN DIAGNOSIS on BUILDING INTERIORS

WATER HEATERS

More Information

Photograph of - is this heating oil running across the basement floor? Notice the abandoned oil line at the furnace? Oil Storage Tank Standards - U.S. EPA listing of industry standards pertaining to oil tanks
InspectAPedia®  -    

  • Oil storage tank standards
  • Questions & answers about heating oil storage tank standards for installation, capacity, location, usage, piping, valves, controls, leaks, etc.
InspectAPedia offers impartial, unbiased advice without conflicts of interest. We will block advertisements which we discover or readers inform us are associated with bad business practices, false-advertising, or junk science. our contact info is at InspectAPedia.com/Contact.htm.

Here is a detailed list of industry standards pertaining to oil storage tanks, expanded from original information provided by the U.S. EPA. Readers should also see OIL TANK STANDARDS and see OIL TANK REGULATIONS.

The distance requirements for oil tanks to be set back from wells, property lines, etc. can be read at WELL CLEARANCES Qualified service providers may be listed at this website at no fee.

© Copyright 2012 InspectAPedia.com, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use page top links to major topics or use links at the left of each page to navigate within topics and documents at this website. Green links show where you are in a document series or at this website.

Industry Codes And Standards For UST Systems

Federal UST regulations often require that industry codes and standards be followed (where applicable) to ensure that the UST system works properly. For example, all UST systems must be designed, constructed, and protected from corrosion in accordance with a code of practice developed by a nationally recognized association or independent testing laboratory.

EPA has also included the use of industry codes for other sections of the rule, such as upgrading, repairing, and closing USTs. Industry codes and standards provide a means for improving methods or developing alternative methods of UST system management in a timely manner.

The UST regulations provide a flexible approach to codemaking by relying on nationally recognized organizations to develop new and improved codes and practices. EPA realizes that industry codes and standards may be updated periodically. EPA regulations do not require the use of a particular issue of any code. EPA encourages owners/operators to use the version of the code or standard that is current at the time the activity occurs.

Listed below are some industry codes and standards. Please be aware that there may be other codes or standards not listed here that may be used to meet regulatory requirements. Also be aware that inclusion on the list below does not necessarily imply EPA endorsement of either the code or the developing organization. You should refer to the current UST regulations to determine if a code of practice is required to be followed in order to meet regulatory requirements. For convenience, the industry codes and standards are arranged in two ways:

  1. by subject area, and
  2. by developing organization.

Note that industry codes and standards are copyrighted and are available only from the developing organization. These codes and standards must be purchased directly from the developing organization.


Code/Standard Subject Areas

Assessing Tank Integrity, Repairing Tanks, and Interior Lining Of Tanks

API Recommended Practice 1631, "Interior Lining of Underground Storage Tanks"

ASTM G 158, "Standard Guide for Three Methods of Assessing Buried Steel Tanks"

ASTM E 1990, "Standard Guide for Performing Evaluations of Underground Storage Tank Systems for Operational Conformance with 40 CFR, Part 280 Regulations"

KWA "Recommended Practice for Inspecting Buried Lined Steel Tanks Using a Video Camera"

NACE Standard RP 0178, "Recommended Practice: Design, Fabrication, and Surface Finish of Metal Tanks and Vessels to be Lined for Chemical Immersion Service"

NACE Standard RP-0184, "Recommended Practice: Repair of Lining Systems"

NACE Standard RP0288, "Standard Recommended Practice: Inspection of Linings on Steel and Concrete"

NFPA 326, "Standard for the Safeguarding of Tanks and Containers for Entry, Cleaning, or Repair"

NLPA Standard 631, "Entry, Cleaning, Interior Inspection, Repair, and Lining of Underground Storage Tanks"

Closure

API Recommended Practice 1604, "Closure of Underground Petroleum Storage Tanks"

Corrective Action

API Publication 1628, "A Guide to the Assessment and Remediation of Underground Petroleum Releases"

API Publication 1629, "Guide for Assessing and Remediating Petroleum Hydrocarbons in Soils"

ASTM E 1599, "Standard Guide for Corrective Action for Petroleum Releases"

ASTM E 1739, "Standard Guide for Risk-Based Corrective Action Applied at Petroleum Release Sites"

ASTM E 1912, "Standard Guide for Accelerated Site Characterization for Confirmed or Suspected Petroleum Releases"

ASTM E 1943, "Standard Guide for Remediation of Ground Water by Natural Attenuation at Petroleum Release Sites"

NFPA 329, "Recommended Practice for Handling Releases of Flammable and Combustible Liquids and Gases"

Oil Storage Tank Corrosion Protection Standards

  • U.S. Environmental Protection Agency EPA Underground Oil Storage Tank Regulations include - Complete 40 CFR part 280 Technical Standards and Corrective Action Requirements for Owners and Operators of Underground Storage Tanks (UST) (454K byte PDF). This document defines dielectric material (coatings) used to protect underground oil storage tanks from corrosion: More about the galvanic scale and corrosion between dissimilar metals is at GALVANIC SCALE & METAL CORROSION.
  • API Recommended Practice 1632, "Cathodic Protection of Underground Petroleum Storage Tanks and Piping Systems"
  • NACE RP 0169, "Standard Recommended Practice: Control of External Corrosion on Underground or Submerged Metallic Piping Systems"
  • NACE RP 0285 "Standard Recommended Practice: Corrosion Control of Underground Storage Tank Systems by Cathodic Protection"
  • NACE Test Method TM 0101, "Measurement Techniques Related to Criteria for Cathodic Protection on Underground or Submerged Metallic Tank Systems"
  • NACE Test Method TM 0497, "Measurement Techniques Related to Criteria for Cathodic Protection on Underground or Submerged Metallic Piping Systems"
  • STI R892, "Recommended Practice for Corrosion Protection of Underground Piping Networks Associated with Liquid Storage and Dispensing Systems"
  • STI-R-972, "Recommended Practice for the Installation of Supplemental Anodes for STI-P3 USTs"
  • UL 1746, Standard for Safety: "External Corrosion Protection Systems for Steel Underground Storage Tanks"

General UST Topics

API Recommended Practice 2003, "Protection Against Ignitions Arising Out of Static, Lightning, and Stray Currents"

API Publication 2005, "Service Station Safety"

API Standard 2610, "Design, Construction, Operation, Maintenance, and Inspection of Terminal & Tank Facilities"

API Recommended Practice 1621, "Bulk Liquid Stock Control at Retail Outlets"

API Recommended Practice 1626, "Storing and Handling Ethanol and Gasoline-Ethanol Blends at Distribution Terminals and Service Stations"

API Recommended Practice 1627, "Storage and Handling of Gasoline-Methanol/Cosolvent Blends at Distribution Terminals and Service Stations"

NACE Standard RP 0177 Recommended Practice: "Mitigation of Alternating Current and Lightning Effects on Metallic Structures and Corrosion Control Systems'

NFPA 30, "Flammable and Combustible Liquids Code"

NFPA 30A, "Automotive and Marine Service Station Code"

PEI RP900 Recommended Practices for the Inspection and Maintenance of UST Systems

Filling Practices

API Recommended Practice 1007, "Loading and Unloading of MC306/DOT 406 Cargo Tank Motor Vehicles"

NFPA 385 "Standard for Tank Vehicles for Flammable and Combustible Liquids"

Installation

API Recommended Practice 1615, "Installation of Underground Petroleum Storage Systems"

PEI RP100, "Recommended Practices for Installation of Underground Liquid Storage Systems"

Release Detection

ASTM E 1430, "Standard Guide for Using Release Detection Devices with Underground Storage Tanks"

ASTM E 1526, "Standard Practice for Evaluating the Performance of Release Detection Systems for Underground Storage Tank Systems"

Tanks and Piping

FPTPI Recommended Practice T-95-02, "Remanufacturing of Fiberglass Reinforced Underground Storage Tanks"

STI-R922, "Specification for Permatank"

STI-P3, "STI-P3 Specification and Manual for External Corrosion Protection of Underground Steel Storage Tanks"

STI-F894, "ACT-100 Specification for External Corrosion Protection of FRP Composite Steel Underground Storage Tanks"

STI-F961, "ACT-100-U Specification for External Corrosion Protection of Composite Steel Underground Storage Tanks"

UL 58, Standard for Safety: "Steel Underground Tanks for Flammable and Combustible Liquids"

UL 971, Standard for Safety: "Non-Metallic Underground Piping for Flammable Liquids"

UL 1316, Standard for Safety: "Glass-Fiber-Reinforced Plastic Underground Storage Tanks for Petroleum Products"

Top of page


Code/Standard Developing Organizations

ANSI -- American National Standards Institute
11 West 42nd Street
New York, New York 10036
(212) 642-4900

AWWA -- American Water Works Association
6666 West Quincy Avenue
Denver, CO 80235
(303) 794-7711

API -- American Petroleum Institute
1220 L Street, N.W.
Washington, DC 20005
(202) 682-8000

2008 Catalog of API Publications, Programs, and Services (includes API standards) (PDF) (210 pp, 3.85 MB, About PDF)

  • API Recommended Practice 1007Loading and Unloading of MC306/DOT 406 Cargo Tank Motor Vehicles
  • API Recommended Practice 1604 Closure of Underground Petroleum Storage Tanks
  • API Recommended Practice 1615 Installation of Underground Petroleum Storage Systems
  • API Recommended Practice 1621 Bulk Liquid Stock Control at Retail Outlets
  • API Recommended Practice 1626 Storing and Handling Ethanol and Gasoline-Ethanol Blends at Distribution Terminals and Service Stations
  • API Recommended Practice 1627 Storage and Handling of Gasoline-Methanol/Cosolvent Blends at Distribution Terminals and Service Stations
  • API Publication 1628 A Guide to the Assessment and Remediation of Underground Petroleum Releases
  • API Publication 1629 Guide for Assessing and Remediating Petroleum Hydrocarbons in Soils
  • API Recommended Practice 1631 Interior Lining of Underground Storage Tanks
  • API Recommended Practice 1632 Cathodic Protection of Underground Petroleum Storage Tanks and Piping Systems
  • API Recommended Practice 1635 Management of Underground Petroleum Storage Systems at Marketing and Distribution Facilities [final edition, now out of print]
  • API Recommended Practice 2003 Protection Against Ignitions Arising Out of Static, Lightning, and Stray Currents
  • API Publication 2005 Service Station Safety
  • API Standard 2610 Design, Construction, Operation, Maintenance, and Inspection of Terminal & Tank Facilities

ASTM International -- formerly American Society for Testing and Materials
100 Barr Harbor Drive
West Conshohocken, PA 19428-2959
(610) 832-9500

Catalog of ASTM Standards

  • ASTM E 1430 Standard Guide for Using Release Detection Devices with Underground Storage Tanks
  • ASTM E 1526 Standard Practice for Evaluating the Performance of Release Detection Systems for Underground Storage Tank Systems
  • ASTM E 1599 Standard Guide for Corrective Action for Petroleum Releases
  • ASTM E 1739 Standard Guide for Risk-Based Corrective Action Applied at Petroleum Release Sites
  • ASTM E 1912 Standard Guide for Accelerated Site Characterization for Confirmed or Suspected Petroleum Releases
  • ASTM E 1943 Standard Guide for Remediation of Ground Water by Natural Attenuation at Petroleum Release Sites
  • ASTM E 1990 Standard Guide for Performing Evaluations of Underground Storage Tank Systems for Operational Conformance with 40 CFR, Part 280 Regulations

FTPI -- Fiberglass Tank and Pipe Institute
11150 S. Wilcrest Drive, Suite 101
Houston, TX 77099-4343
(281) 568-4100

  • FPTPI Recommended Practice T-95-02 Remanufacturing of Fiberglass Reinforced Underground Storage Tanks

KWA -- Ken Wilcox Associates, Inc.
1125 Valley Ridge Drive
Grain Valley, MO 64029
(816) 443-2494

  • KWA Recommended Practice for Inspecting Buried Lined Steel Tanks Using a Video Camera

NACE International (formerly the National Association of Corrosion Engineers)
Box 218340
Houston, TX 77218-8340
(713) 492-0535

Catalog of NACE Standards

  • NACE Standard RP 0169 Recommended Practice: Control of External Corrosion on Underground or Submerged Metallic Piping Systems
  • NACE Standard RP 0177 Recommended Practice: Mitigation of Alternating Current and Lightning Effects on Metallic Structures and Corrosion Control Systems
  • NACE Standard RP 0178 Recommended Practice: Design, Fabrication, and Surface Finish of Metal Tanks and Vessels to be Lined for Chemical Immersion Service
  • NACE Standard RP-0184 Recommended Practice: Repair of Lining Systems
  • NACE Standard RP 0285 Recommended Practice: Corrosion Control of Underground Storage Tank Systems by Cathodic Protection
  • NACE Standard RP0288 Recommended Practice: Inspection of Linings on Steel and Concrete
  • NACE Test Method TM 0101, "Measurement Techniques Related to Criteria for Cathodic Protection on Underground or Submerged Metallic Tank Systems"
  • NACE Test Method TM 0497 Measurement Techniques Related to Criteria for Cathodic Protection on Underground or Submerged Metallic Piping Systems

NFPA -- National Fire Protection Association
1 Batterymarch Park
Box 9101
Quincy, MA 02269-9101
(617) 770-3000

Catalog of NFPA Standards

  • NFPA 30 Flammable and Combustible Liquids Code
  • NFPA 30A Automotive and Marine Service Station Code
  • NFPA 326 Standard for the Safeguarding of Tanks and Containers for Entry, Cleaning, or Repair
  • NFPA 329 Recommended Practice for Handling Releases of Flammable and Combustible Liquids and Gases
  • NFPA 385 Standard for Tank Vehicles for Flammable and Combustible Liquids

NLPA -- National Leak Prevention Association
Phone: 815.301.2785
Fax: 240.757-0211
E-mail: info@nlpa-online.org

  • NLPA Standard 631 Entry, Cleaning, Interior Inspection, Repair, and Lining of Underground Storage Tanks

PEI -- Petroleum Equipment Institute
Box 2380
Tulsa, OK 74101-2380
(918) 494-9696

  • PEI RP100 Recommended Practices for Installation of Underground Liquid Storage Systems
  • PEI RP900 Recommended Practices for the Inspection and Maintenance of UST Systems

STI -- Steel Tank Institute

570 Oakwood Road
Lake Zurich, IL 60047
(708) 438-TANK [8265]

Catalog of STI Standards

  • STI R892 Recommended Practice for Corrosion Protection of Underground Piping Networks Associated with Liquid Storage and Dispensing Systems
  • STI-R922 Specification for Permatank
  • STI-R-972 Recommended Practice for the Installation of Supplemental Anodes for STI-P3 USTs
  • STI-P3 STI-P3 Specification and Manual for External Corrosion Protection of Underground Steel Storage Tanks
  • STI-F894 ACT-100 Specification for External Corrosion Protection of FRP Composite Steel Underground Storage Tanks
  • STI-F961 ACT-100-U Specification for External Corrosion Protection of Composite Steel Underground Storage Tanks

UL -- Underwriters Laboratories Inc.
333 Pfingsten Road
Northbrook, IL 60062-2096
(847) 272-8800

Catalog of UL Standards

  • UL 58 Standard for Safety: Steel Underground Tanks for Flammable and Combustible Liquids
  • UL 971 Standard for Safety: Non-Metallic Underground Piping for Flammable Liquids
  • UL 1316 Standard for Safety: Glass-Fiber-Reinforced Plastic Underground Storage Tanks for Petroleum Products
  • UL 1746 Standard for Safety: External Corrosion Protection Systems for Steel Underground Storage Tanks

WFCA -- Western Fire Chiefs Association
5360 S. Workman Mill Road
Whittier, CA 90601
(213) 699-0541

Questions & Answers regarding this article

.

Ask a Question or Search InspectAPedia

HTML Comment Box is loading comments...

Share this Article      

...

Technical Reviewers & References

  • InspectAPedia.com® - Daniel Friedman - Publisher & Editor.
  • InspectAPedia Bookstore lists recommended books, organized by topic & available for purchase. Most of our articles also list books on the specific article topic as well as other references, and information sources.
  • Critique, contributions wanted: Contact Us to suggest corrections or additions to articles at this website, and if you wish, to receive online listing and credit as a contributor. Particular thanks are due to the many experts and also consumers who read and critique technical articles at InspectAPedia.com.
  • Additional technical contributors & reference sources for this article are listed below.

Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

OIL TANK STANDARDS
OIL TANK STANDARDS
- Detailed List

  • U.S. EPA original source page: http://www.epa.gov/oust/cmplastc/standard.htm
  • The distance requirements for oil tanks to be set back from wells, property lines, etc. can be read at WELL CLEARANCES
  • Oil Tank Abandonment Regulations and Procedures for the abandonment of oil storage tanks, from which some of the above text was paraphrased, are discussed in detail at TANK ABANDONMENT - "Abandoning Commercial vs. Residential Underground Oil Storage Tanks (UST) - Procedures & Regulations
  • Thanks to Denise Adjutant, DOIT Web Support Division 271-8173, for New Hampshire oil tank regulations link update 6/22/09 Denise.Adjutant@doit.nh.gov
  • Canadian oil tank regulations sources include the individual provincial government websites and the Canadian Technical Standards and Safety Authority, 14th Floor, Centre Tower, 3300 Bloor Street West, Toronto, Ontario M8X 2X4 - http://www.tssa.org/ Contact the Canadian TSSA toll free at 1-877-682-TSSA (8772) or 416-734-3300 for the Toronto area. The Technical Standards and Safety Authority (TSSA) is an independent, not-for-profit organization responsible for the delivery of a range of safety services. This includes the administration of Ontario’s Technical Standards & Safety Act, 2000 within various industry sectors and the delivery of safety programs to the public.