Oil Tank Leaks or Oil Tank Failure Causes - oil tank leaks are caused by corrosion, damage, soil conditions, other factors InspectAPedia® -
Causes of leaks or other failures in above ground or buried oil storage tanks
Oil tank smells & odors, sources of heating oil odors in or at buildings
Our site offers impartial, unbiased advice without conflicts of interest.
We will block advertisements which we discover or readers inform us are associated with bad business practices,
false-advertising, or junk science. Our contact info is at
InspectAPedia.com/appointment.htm.
This document explains the common reasons for oil tank leaks in or from home heating oil storage tanks. Both underground tank leaks and above ground storage
tank leak causes are discussed. Oil tank leaks are caused by corrosion, mechanical damage, soil conditions, other factors which are explained here.
See OIL TANK LEAK ADVICE for our detailed advice on handling leaky oil tanks as well as links to oil tank leak regulations for U.S. states and Canadian provinces. Readers should also see BOILER NOISE SMOKE ODORS for a discussion of flue gas leaks, smells, and hazards from the combustion products of oil burning heating appliances.
OIL TANK FAILURE MECHANISMS - Fuel or Heating Oil Storage Tank Leak Failure Mechanisms
Oil tank leaks, depending on the location and size of the leak, can lead to costly environmental contamination and cleanup costs outdoors or indoors in buildings. In addition, oil tank leak smells or fumes from indoor leaks or oil spills are a source of building occupant complaints that need to be addressed.
External oil tank rust, unless very heavy, isn't highly correlated with internal rust, corrosion,
and tank leaks. Most oil tank failures are due to rust perforation from the inside
of the tank. This means that if you see any indications of even a pinhole or
leak on an oil tank, be careful! The steel may be quite thin and can be easily punctured
even though from outside it may look pretty good.
OIL TANK RUST PERFORATION - Usual Reasons for Oil Storage Tank Leaks - Rust Perforation
Underground fuel storage tanks usually fail from rust
perforation from the inside of the tank, due to several effects of water inside the tank including, in the
case of heating oil, combination of water with sulphur in the fuel.
So if a test shows that there is a lot of water in a buried oil tank one would be more
pessimistic about its remaining life.
Water in home heating oil joins with sulphur in this case to become acidic
and corrosive. It causes tank failure by rust penetration from the inside.
Also, there may be a bacteria living in tanks, existing at the water/oil
interface, digesting organics and excreting acids.
The corrosiveness of this activity is often most significant at the
water-oil interface in the tank, which explains why some tank leaks
will develop not at the very bottom of the tank (but look there too) but
instead, a few inches up, along the side of the tank.
The height of this
corrosion line along the sides of the inside of the oil storage tank depends on the amount of water in the tank and thus
the location of the water/oil interface line on the side of the tank.
HOW WATER GETS IN to OIL TANKS - How water gets into an oil storage tank
Bad oil tank filler location
Water, enters a heating or fuel oil tank from a poorly sealed fill box which is flush
with the ground or which is located below a roof edge, from missing fill pipe
or vent pipe caps, from loose pipe fittings, and less
commonly, from water delivered with fuel from an improperly maintained bulk
storage facility.
Condensation inside oil tanks and groundwater leaks into oil tanks
In outside above-ground tanks water also often enters the fuel oil tank from
condensation as temperatures change, particularly when the tank is not kept
filled.
Above ground tanks in cold climates may be exposed to temperature
variations drawing and expelling air from a partly-empty tank. When warm moist outdoor air is
drawn into a steel tank, moisture in the air may condense and accumulate in the tank.
Water can also leak into a tank from ground water
when the oil level is low if the tank is damaged. [R.W.
Beckett Corporation, Technical Information Bulletin, October 15, 1990.]
Delivery of bad oil
Most oil delivery companies store their product in very large
storage tanks near a rail or waterway delivery point. Large oil storage facilities may deliberately
keep water in the bottom of those tanks so that if the large (above ground oil storage depot tank)
begins to leak, water will leak out first and thus be observed before there is a large oil spill.
An oil truck which is filled when oil has just been delivered to the oil depot tank might in
unusual circumstances pick up excessive amounts of water in the oil it obtains, thus potentially
delivering it to its customers. Equipment is often used to attempt to trap and filter water in oil and
other fuel delivery systems to reduce this risk.
IMPROPER OIL TANK INSTALLATION - Improper oil tank installation can cause leaks
Placing a tank in cinders or ash or acidic soil: tanks set in beds of cinders or ashes cause outside-in
corrosion and leaks.
Tanks may also be damaged by being dropped or pushed into
the excavated hole rather than being carefully lowered by a rope.
Burying an indoor-rated tank: That an installer would bury an indoor-rated 275-gallon tank outdoors may come as a
surprise to some readers but I've been surprised at how often we've found either
completely or partially buried indoor-tanks.
At least on older oil tanks (perhaps before 2000), the UL label affixed to the
tank explicitly says "indoor use only" right there for the installer to read. I contacted
a few manufacturers and wrote to UL to ask if it was a building code violation to
bury a tank with this indoor use rating. I haven't received a reply, but interestingly,
newer 275-gallon steel oil storage tank UL rating labels simply dropped the wording
that indicated where the tank could be used. Our concern was that an indoor-rated tank may lack
the thickness of steel or an anti-corrosion coating that a buried tank needs.
Placing an indoor-rated tank outside with no weather protection also risks water
entry in the tank (from roof spillage or condensation), gelling of the oil and loss
of heat in cold climates, and perhaps extra corrosion.
MECHANICAL DAMAGE - Mechanical damage to oil storage tanks
oil tanks may be damaged during their installation, such
as being dropped or gouged against a rock or other item which scratches or dents the tank,
increasing its vulnerability to outside corrosion.
While it's speculative (we have no field data on this item) tanks or tank piping may be
damaged by vehicle traffic in some locations as well.
IMPROPER OIL TANK PIPING - Improper oil piping can cause leaks
Oil tank piping materials or connections can lead to oil leaks. If you didn't know, residential oil tanks
are usually filled under pressure. The oil filler nozzle is actually linked to the top of the inlet pipe
and the truck pumps into the tank at pressure - most-likely to speed the delivery process. This fill-pressure
can be considerable and can cause leakage or even catastrophic tank failure and leaks into a building
if the tank piping is improper or if the tank is damaged.
At an above-ground or indoor oil storage tank a small amount of seepage around the oil filler pipe is normal - having installed oil
piping the author testifies that it requires very good workmanship to avoid this seepage as
the tank top thread tapping and 2" steel pipe thread tapping can be a bit crude. If oil is running
down the tank onto the floor or causing an odor problem this connection needs to be re-made. Because
the work can be troublesome (a filler pipe disassembly may require demolition at a house wall) it
should not be done unless really needed.
At a buried oil storage tank loose or improper oil filler connections at the top of a buried
tank or anywhere in the piping run can leak onto outdoor soil (luckily usually not deep underground)
or indoors in a building.
Under-sized oil storage tank fill or vent piping can cause very serious oil leaks inside the building or outside, including catastrophic oil leaks
if a (plastic) pipe breaks.
The most catastrophic in-building oil storage tank leaks are not from rust perforation itself as
such leaks are usually slow drips. Extreme indoor oil contamination occurs in more unusual
and very serious circumstances when indoor oil tank has been removed from a building, for example on
conversion from oil to gas heat, but the oil filler pipe was left outside and through the house wall,
though no longer connected to a tank inside.
In an instance in Ulster County, New York, the contractor
left plywood outside nailed against the building to prevent access to the old filler pipe pending its removal.
But a neighbor called her oil company with an out-of-oil "no heat" condition in very cold weather. The oil
delivery driver, intending to assist in an urgent case, went to the wrong house, removed the plywood, and
pumped hundreds of gallons of oil directly into the home's basement.
OIL TANK SOIL CONDITIONS - Soil conditions as a contributor to buried oil tank failure
If a soil is acidic and particularly in areas where there is also
a lot of groundwater or surface or roof runoff around a buried oil tank, the corrosivitiy of the
soil may be a factor in oil tank external corrosion and ultimate leakage
Manufacturing defects: such as defects in the coating of a steel tank to be buried or
poorly-welded seams may result in underground oil leakage. I have not seen reports of
this occurrence - this may be a theoretical rather than a significant risk.
Health Hazards of Exposure to Heating Oil Fumes
OSHA's position is that heating oil fumes are a nuisance and may not pose a hazard to a healthy individual. Our field investigation experience as well as a review of oil spill guidelines from several sources provide anecdotal and other evidence that the elderly, infants, or people who are in fragile health, as well as people who suffer from multiple chemical sensitivity, allergies, asthma, and some other respiratory conditions may experience more serious symptoms including asthma attacks and other complaints.
A typical No. 2 home heating oil MSDS document includes the hazard identification information for home heating oil that we list below. The same document provides information about toxicity levels - the exposure necessary for serious medical effects to be at risk or to actually occur.
Eye contact with heating oil: Contact with eyes may cause mild irritation. Flush with clean water for at least 15 minutes.
Skin contact with heating oil: Practically non-toxic following a single acute exposure; may cause skin irritation with prolonged or repeated contact; liquid may be absorbed through the skin in toxic amounts if large areas of skin are repeatedly exposed. Remove contaminated clothing, wash with soap and water or waterless hand cleaner; seek medical attention of skin redness develops.
Inhalation of heating oil [presumably refers to liquid inhalation?]: excessive exposure may cause irritation of the nose, throat, lungs, and respiratory tract. Central nervous system (brain) effects may include headache, dizziness, loss of balance and coordination, unconsciousness, coma, respiratory failure, and death.
MOVE TO FRESH AIR - provide artificial respiration (CPR) if necessary - seek immediate medical help.
Ingestion of heating oil: major threat occurs from vomiting and breathing liquid drops into the lungs; aspiration [presumably of liquid heating oil drops] can lead to chemical pneumonia (fluid in the lungs), severe lung damage, respiratory failure, or death.
DO NOT INDUCE VOMITING - seek immediate medical help.
Ingestion of heating oil may also cause gastrointestinal disturbances, irritation, nausea, vomiting, diarrhea, central nervous system (brain) effects similar to alcohol intoxication, and in severe cases of heating oil ingestion, effects may lead to tremors, convulsions, loss of consciousness, coma, respiratory arrest, and death.
Flue gases produced by burning heating oil in an area without adequate ventilation [presumably also where a chimney is not venting properly] may result in hazardous levels of combustion products, including carbon monoxide, and inadequate oxygen levels that can cause unconsciousness, suffocation, and death.
Carcinogenicity of heating oil: [cancer risk from home heating oil exposure]: similar products have caused skin cancer and systemic toxicity in laboratory animals following repeated applications. The significance of these results to human exposure has not been determined.
Exposure Limits for No. 2 Home Heating Oil
The following workplace exposure limit for heating oil is quoted from ATSDR.
The Occupational Safety and Health Administration (OSHA) and the Air Force Office of Safety and Health (AFOSH) regulate levels of petroleum products in the private sector and Air Force workplaces, respectively.
The maximum allowable amount of petroleum products in the workroom air during an 8-hour workday, 40-hour workweek, is 400 parts of petroleum distillates (naphtha) per million parts of air, or more simply stated, 400 ppm.
Critique, contributions wanted: Contact Us to suggest corrections or additions to articles at this website, and if you wish, to receive online listing and credit as a contributor. Particular thanks are due to the many experts and also consumers who read and critique technical articles at InspectAPedia.com.
Additional technical contributors & reference sources for this article are listed below.
Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.
"Toxicological profile for fuel oils", U.S. Department of Health and Human Services, Public Health Service, Agency for Toxic Substances and Disease Registry (ATSDR) Atlanta, GA 1995. - http://www.atsdr.cdc.gov/toxprofiles/tp75.html
Public Health Statement for Fuel Oils, ATSDR, (the full document original source can be found at http://www.atsdr.cdc.gov/toxprofiles/phs75.html). An excerpt from this document is just below. ATSDR,
Division of Toxicology,
1600 Clifton Road NE, Mailstop F-32,
Atlanta, GA 30333 888-422-8737.
We know very little of the human health effects caused by fuel oils. Daily use of a kerosene stove for cooking should not cause any breathing problems for most people. People who use kerosene stoves to cook do not have more colds than people who have other types of stoves. Breathing moderate amounts of deodorized kerosene (fuel oil no. 1) has been shown to slightly affect the ability to smell and to cause a taste sensation. Numerous case-studies have reported accidental poisoning in children as the result of drinking kerosene. These accidents are probably much more frequent in areas where kerosene is commonly used for cooking and heating. Drinking kerosene may cause vomiting, diarrhea, swelling of the stomach, stomach cramps, coughing, drowsiness, restlessness, irritability, and unconsciousness; also, it may be difficult to breathe, and breathing may be painful. Coughing, pneumonia, and difficult or painful breathing after drinking kerosene suggest that kerosene has entered the lungs. In addition, drinking large amounts of kerosene can put you into a coma, cause convulsions, and may even cause death. When kerosene gets on your skin for short periods, it can make your skin itchy, red, and sore; sometimes blisters may occur and your skin may peel.
Breathing fuel oil no. 1 vapor for periods as short as 1 hour may make you feel nauseous, increase your blood pressure, be irritating to your eyes, or make your eyes bloodshot. Breathing kerosene or JP-5 vapors can also affect your nervous system. Some of the effects that have been noted in case studies include headache, light-headedness, anorexia (loss of appetite), poor coordination, and difficulty concentrating. Breathing diesel fuel vapors for a long time may damage your kidneys, increase your blood pressure, or lower your blood's ability to clot. Constant skin contact (for example, washing) with diesel fuel may also damage your kidneys.
It appears that repeated contact with fuel oils can cause skin cancer in mice and may cause liver cancer in mice. However, there is some conflicting information. Further, the fuel oils were tested only on mice. We do not know if fuel oils can cause cancer in humans. The International Agency for Research on Cancer (IARC) has determined that residual (heavy) fuel oils and marine diesel fuel are possibly carcinogenic to humans (Group 2B classification). In addition, IARC considers that there is not enough information (Group 3 classification) available to determine if distillate (light) fuel oils or distillate (light) diesel fuels cause cancer. They have also determined that occupational exposures to fuel oils during petroleum refining are probably carcinogenic to humans (Group 2A classification). We do not know if fuel oils can cause birth defects or if they affect reproduction.
Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair
Our recommended books about building design, inspection, and repair, and about indoor environment testing, diagnosis, and cleanup are at the InspectAPedia Bookstore.
More Information on Building Diagnostic Inspections and Repairs
Oil Tanks - The Oil Storage Tank Information Website: Buried or Above Ground Oil Tank Inspection, Testing, Cleanup, Abandonment of Oil Tanks
Abandon a Buried Oil Tank, How To - Abandoning Commercial Underground Tanks, Russ Brauksieck, ASHI Tech. Journal, Vol.3 No.1 Spring 1993, P. 40-41 [Reprint]
Petroleum Bulk Storage J. Sibblies, NY State DEC, Advice to Home Owners and Home Inspectors about Oil Storage Tanks - summary from ASHI Chapter Seminar.
Septic Tank inspection, testing, diagnosis, repair
OIL TANK FAILURE CAUSES - Oil Tank Failure Causes - oil tank leaks are caused by corrosion, damage, soil conditions, other factors
OIL TANK TESTING - - How Oil Tanks are Tested for Evidence Leaks, of Current or Previous Oil Spills
TANK FAILURE RATES - Oil Tank Failure Rates - Oil Tank Leak Probability as a Function of Tank Age, Location, Condition, Soil Conditions and Other Factors
Web Link Exchange: Contact Us to list your website or contact information for oil tank testing, tank corrosion research, oil industry experts
InspectAPedia® Home & Site Map - Building & Environmental Inspection, Testing, Diagnosis, Repair, & Problem Prevention Advice: In-depth research & advice on diagnosing, testing, correcting, & preventing building defects & indoor environmental hazards. Unbiased information, no conflicts of interest.
The Mold Information Center: What to Do About Mold in Buildings, When and How to Inspect for Mold, Clean Up Mold, or Avoid Mold Problems
Environmental Inspection, Testing, & Diagnosis On-Site IAQ, Gas, Air Testing, Mold Investigation, Sick Building Diagnosis, Lab Services, & Remediation Plan Preparation - indoor air quality testing, problem source determination, supporting lab work, written remediation plan addressing removal of environmental and other hazards and prevention of their recurrence.