Underground Storage of Flammable and Combustible Liquids - Tank Removal, Abandonment or Placing Temporarily Out of Service in New Jersey - 1988 InspectAPedia® -
Underground Storage of Flammable and Combustible Liquids - Tank Removal, Abandonment or Placing Temporarily Out of Service-1988 regulations
Our site offers impartial, unbiased advice without conflicts of interest.
We will block advertisements which we discover or readers inform us are associated with bad business practices,
false-advertising, or junk science. Our contact info is at
InspectAPedia.com/appointment.htm.
State of New Jersey
Department of Community Affairs
Division of Codes and Standards
Construction Code Element
CN816
Trenton, NJ 08625-0816
609-530-8820
Date: January 1988
Subject: Underground Storage of Flammable and Combustible
Liquids - Tank Removal, Abandonment or Placing Temporarily Out
of Service
Reference: N.J.A.C. 5:23-3.6 and 2.32
BOCA National Building Code/1987, Section 619.0
BOCA National Fire Prevention Code/1987,
Section F-2804.6
National Fire Protection Association's
Flammable and Combustible Liquids Code/1984
(NFiPA30)
The Bureau of Construction Code Enforcement wants to clarify the Building and
Fire Protection Subcode Official's responsibility relating to the underground
storage of flammable and combustible liquids.
In accordance with N.J.A.C. 5:23-2-32 "Unsafe structures," underground
flammable and combustible liquid storage tanks which have been abandoned or
placed temporarily out of service and are considered unsafe are to be removed
or made safe.
Building Subcode section 619.0, "Flammable and Combustible Liquids" is
applicable to the construction and installation of storage systems containing
these liquids.
However, neither the subcodes nor the regulations contain
appropriate specific provisions for the placing temporarily out of service,
abandonment or removal of tanks.
Therefore, in accordance with N.J.A.C.
5:23-3.6, the specifications and standards listed in each sub code or its
appendix shall represent accepted engineering practice.
Appendix A of the
Building Sub codes references the BOCA, National Fire Prevention Code/1987 (BOCA,
F.P.C./1987) and the National Fire Protection Association's Flammable and
Combustible Liquids Code/1984 (NFIPA 30/1984).
a)BOCA F.P.C/1987 - Section F-2804.6 contains requirements to remove, abandon,
place temporarily out of service or otherwise dispose of any flammable or
combustible liquid underground storage tank.
b)NFIPA 30/1984 - Additional guidance may be found in Appendix B, "Abandonment
or Removal of Underground Tanks."
Although P-2804.6 was deleted from the State Uniform Fire Code at N.J.A.C.
5:18-3.2(a)28.vi, It still remains as a reference to the Building Subcode of
the Uniform Construction Code. Therefore, enforcement of P-2804.6 remains
within the jurisdiction of the Building and Fire Protection Subcode Officials.
DCA BULLETIN No. 88-3.
#########
Critique, contributions wanted: Contact Us to suggest corrections or additions to articles at this website, and if you wish, to receive online listing and credit as a contributor. Particular thanks are due to the many experts and also consumers who read and critique technical articles at InspectAPedia.com.
Additional technical contributors & reference sources for this article are listed below.
Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.
Petroleum Bulk Storage J. Sibblies, NY State DEC, Advice to Home Owners and Home Inspectors about Oil Storage Tanks - summary from ASHI Chapter Seminar.
Septic Tank inspection, testing, diagnosis, repair
Indoor Environment Website Indoor Building Environmental Hazard Detection, Testing, Repair, & Prevention - Main Web Page
Web Link Exchange: Contact Us to list your website or contact information for oil tank testing, tank corrosion research, oil industry experts
InspectAPedia® Home & Site Map - Building & Environmental Inspection, Testing, Diagnosis, Repair, & Problem Prevention Advice: In-depth research & advice on diagnosing, testing, correcting, & preventing building defects & indoor environmental hazards. Unbiased information, no conflicts of interest.
The Mold Information Center: What to Do About Mold in Buildings, When and How to Inspect for Mold, Clean Up Mold, or Avoid Mold Problems
Environmental Inspection, Testing, & Diagnosis On-Site IAQ, Gas, Air Testing, Mold Investigation, Sick Building Diagnosis, Lab Services, & Remediation Plan Preparation - indoor air quality testing, problem source determination, supporting lab work, written remediation plan addressing removal of environmental and other hazards and prevention of their recurrence.