OIL STORAGE TANKS

ABANDONING OIL TANKS
ABOVE GROUND OIL TANK INSPECTIONS
  INSPECT VISIBLE OIL TANKS
  OIL FILL & VENT
  OIL TANK SUPPORT
  ABANDONED INDOORS
  ABOVEGROUND OUTDOORS
    Indoor Tanks Used Outside
    How Water Enters Oil Tanks
    Problems of Water in Oil Tanks
    Additives for Outdoor Oil Tanks
  OIL TANK HISTORY REVIEW
  OIL TANK CHECKLIST
AFUE DEFINITION, RATINGS
AGE of OIL TANK
ANODES & DIP TUBES on WATER HEATERS

BIOGAS PRODUCTION & USE
BOILERS, HEATING

BURIED OIL TANK ADVICE
BURIED OIL TANKS, FINDING

COMBUSTION PRODUCTS & IAQ

DEFINITION of Heating & Cooling Terms
DIAGNOSE & FIX HEATING PROBLEMS-BOILER
DIAGNOSE & FIX HEATING PROBLEMS-FURNACE

FILTERS, OIL on HEATING EQUIPMENT
FIRE SAFETY CONTROLS
FLAME COLOR, BLUE vs YELLOW COMBUSTION
FLOATING UP OIL STORAGE or SEPTIC TANKS
FLOODED HEATING EQUIPMENT REPAIR
FLOODED WATER HEATER REPAIR
FUEL OIL TYPES & CHARACTERISTICS
FUEL UNIT, HEAING OIL PUMPS

GALVANIC SCALE & METAL CORROSION
GAUGES ON HEATING EQUIPMENT

HEAT LOSS in buildings
HEAT TAPES, Heat, Insulation prevent Freeze-Up

HEATING COST FUEL & BTU Cost Table
HEATING COST SAVINGS METHODS

HEATING OIL CLOUD WAX GEL POINT
HEATING OIL EXPOSURE HAZARDS, LIMITS
HEATING OIL - OLD, USEABLE?
HEATING OIL PIPING TROUBLES
HEATING OIL SHELF LIFE
HEATING OIL SLUDGE
HEATING OIL TANKS
HEATING OIL USAGE RATE

HEATING SYSTEM INSPECT DIAGNOSE REPAIR
HEATING SYSTEM NOISES

HOME BUYERS GUIDE TO OIL TANKS
HOT WATER HEATERS

NO HEAT - BOILER / FURNACE DIAGNOSIS
NOISE CONTROL for HEATING SYSTEMS
NOISES COMING FROM WATER HEATER

ODORS & SMELLS DIAGNOSIS & CURE
ODORS FROM HEATING SYSTEMS

OIL BURNERS
OIL BURNER INSPECTION GUIDE
OIL BURNER NOISE SMOKE ODORS
OIL BURNER SOOT & PUFFBACKS

OIL FILTERS on HEATING EQUIPMENT
OIL FILTER MISSING
OIL FUEL TYPES & CHARACTERISTICS

OIL LINE CLOGGING FIX
OIL LINE SAFETY VALVES
OIL ODORS, LEAKY OIL TANK PIPING
OIL PUMP FUEL UNIT

OIL SPILL CLEANUP / PREVENTION

OIL TANKS
OIL TANK ABANDONING PROCEDURE
OIL TANK AGE
OIL TANK, BURIED, ADVICE
OIL TANK, BURIED, FINDING

OIL TANK FAILURE CAUSES
OIL TANK FAILURE RATES
OIL TANK FLOATING UP

OIL TANK GAUGES
OIL TANK INSPECTION, ABOVE GROUND
OIL TANK INSPECTION REPORTS

OIL TANK LEAKS & SMELLS
  OIL TANK LEAK ENVIRONMENTAL ISSUES
  FREQUENCY of OIL TANK LEAKS
  HOME INSPECTOR OIL TANK REPORT
  OIL TANK LEAK IMPACTS
  OIL TANK LEAK CAUSES
  OIL TANK LEAK CLEANUP GUIDE
  OIL TANK LEAK REPORTING REGULATIONS - ALL
  OIL TANK REGULATIONS - CANADA
  OIL TANK LEAK REPORTING in NEW JERSEY
  OIL TANK LEAK & SIZE REPORTING REQUIREMENTS
  OIL TANK LEAK TESTING
  LEAKY OIL TANK FILL PIPES
  OIL TANK LEAK REPORTING BASICS
  WHAT IF AN OIL TANK IS LEAKING?

OIL TANK LEGAL ISSUES
OIL TANK LIFE

OIL TANK PIPING & PIPING DEFECTS
  CAULK OIL PIPE ENTRANCES
  FIRE SAFETY CONTROLS
  HEAT TAPE HAZARD ON OIL TANK
  OIL FILL & VENT
  OIL FILL PIPE EXPOSED
  OIL FILL / VENT PIPE CAP LOST
  OIL FILL & VENT PIPES UNDERSIZED
  OIL FILTERS on HEATING EQUIPMENT
  OIL FILTER MISSING
  OIL LINE SAFETY VALVES
  OIL LINE CLOGGING FIX
  OIL LINE EXPOSED
  OIL LINE SINGLE, UP HIGH
  OIL LINE SINGLE ON BURIED TANK
  OIL ODORS, LEAKY OIL TANK PIPING
  DUAL OIL LINE 2 VALVES
  DUAL OIL TANKS - PIPING
  OIL LINE LEAKS
  OIL LINE SAFETY VALVES
  OIL TANK FILL & VENT LINES APART
  OIL TANK GAUGES
  OIL TANK VENT PIPE MISSING

OIL TANK PRESSURE

OIL TANK REGULATIONS
OIL TANK REMOVAL COs
OIL TANK REMOVAL FINANCIAL AID
OIL TANK REPORT LANGUAGE

OIL TANK SAFETY
OIL TANK SLUDGE
OIL TANK STANDARDS
OIL TANK STANDARDS - Detailed List
OIL TANK SPILL CLEANUP / PREVENTION
OIL TANK SUPPORT

OIL TANK TESTING
OIL TANK TESTING COs

OIL TANK WATER CONTAMINATION
  Water in Oil Tanks, Problems
  How Water Gets in Buried Oil Tanks
  How Water Gets in Above-Ground Oil Tanks
  How to Keep Water Out of Oil Tanks
  How to Measure Oil Tank Water Contamination
  How to Remove Water from an Oil Tank
OIL TANK WATER REMOVAL

SOOT on OIL FIRED HEATING EQUIPMENT

STAIN DIAGNOSIS on BUILDING INTERIORS

WATER HEATERS


More Information

Photograph of a residential outdoor above ground oil tank - was this tank intended for outdoor use? Photo courtesy Arlene Puentes, Kingston NY

Guide to Above Ground Outdoor Home Heating Oil Storage Tanks
InspectAPedia®  -    

  • Above ground outside oil tanks: inspections, leaks, troubleshooting
  • Water in oil tanks - sources, problems
  • Heating oil additives and chemicals for outdoor oil tanks to deal with water, icing, and waxing in outdoor oil storage tanks
  • Questions & answers about installing, using, & maintaining an outdoor aboveground heating oil storage tank

AST inspections outdoors: How to inspect above ground oil storage tanks (ASTs) when they are installed above ground outdoors: This article discusses the risks of heat loss or leaks when above-ground outdoor oil storage tanks are used outside. It explains how water gets into oil storage tanks no matter where they are located, above ground oil tanks, buried oil tanks, or even possibly indoor oil tanks

InspectAPedia offers impartial, unbiased advice without conflicts of interest. We will block advertisements which we discover or readers inform us are associated with bad business practices, false-advertising, or junk science. Our contact info is at InspectAPedia.com/Contact.htm.

Photograph at page top courtesy of Arlene Puentes. Also see OIL TANK WATER CONTAMINATION.

© Copyright 2012 InspectAPedia.com, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use page top links to major topics or use links at the left of each page to navigate within topics and documents at this website. Green links show where you are in a document series or at this website.

Guide to Issues with Indoor-rated Oil Storage Tanks Used Outdoors

Aboveground outdoor oil tank (C) Carson DunlopThe article explains the problems caused by water in oil tanks and also the problems faced by owners of above ground oil storage tanks located in cold climates. This article is a sub-chapter of OIL TANK INSPECTIONS

This article, sketchs, and photographs give advice and example photos for the visual inspection of above ground oil tanks for leaks and damage including damaged or leaky oil storage tanks, improper oil tank piping, valves, and indoor-type oil tanks located outdoors. Sketch of an above ground outdoor oil storage tank is courtesy of Carson Dunlop.

Here are a some important indicators of tank condition that any home inspector can include when an oil storage tank is visible and accessible inside or at a building. Readers whose heating system uses an above-ground outdoor oil storage tank should be sure to also read HEATING OIL CLOUD WAX GEL POINT and OIL TANK SLUDGE.

Oil tank label tagOil Tank Size and Rating for indoor use but Used Outdoors: If you find a 250g or 275g oil storage tank above ground outside, check its label and UL rating to see if that location was permitted.

Similarly, if you learn that a buried oil tank is an older, small-capacity tank such as 250g or 275g, it is reasonable to assume that an "indoor use only" oil storage tank was buried outside, as we have not located a single instance of a 20 year old 250/275 gallon oil storage tank which was tested, UL-Labeled, and rated for outdoor use above ground nor underground.

An oil tank lacking a rating for outdoor or buried use may lack adequate corrosion resistance and strength, risking rust-through, leaks, and even a dangerous collapse hazard.

Oil tank labelSuch oil tanks often need to be replaced. Unfortunately so many indoor oil tanks have been used outside, above ground or buried, that their use has been so popular that UL standards for labeling and controlling oil tank use are a bit more confusing.

Modern oil tank labels might no longer indicate if the tank is intended for outdoor use or not, and modern oil tank manufacturers may have rated tanks which were previously labeled "indoors" as now suitable for outdoor use or even buried-use.

Check with the manufacturer of your oil tank before moving it, using it outdoors, or burying it.

Problems Faced by Above Ground Outdoor Oil Storage Tanks

Photograph of an open oil outdoor oil tank vent and an oil tank filler pipe exposed to roof spillage.

How Water Gets Into Oil Storage Tanks

Water can enter an oil storage tank by more than one means:

  • Water may collect in an oil storage tank, above ground or buried, or in some cases even indoors, when the oil is left at low levels in the tank for long periods, particularly in periods of cool weather or in periods of alternating warm humid and then cool weather. As temperatures change around and then in the oil tank, warm moist outside air is drawn into the oil storage tank through its vent. Moisture in the air condenses on the cool tank interior surface, and can accumulate in the tank.
  • Water may enter an oil delivery truck by the same means as just discussed above for oil tanks. From the oil delivery truck water, along with oil, may then be pumped into the property owners oil storage tank. Some oil companies are quite diligent to avoid these problems or to include water filters on their delivery trucks.
  • Water may enter an oil storage tank by delivery of a "bad" batch of oil from the oil delivery company. Those huge commercial oil storage depot tanks you may see, perhaps near a railroad line or a river, may be deliberately maintained with a few feet of water in the bottom of the tank so that if a leak occurs it can be discovered as escaping water before the actual oil leaks out.

    When an oil company truck is being filled from one of these tanks, in some conditions some of the larger tank's water can enter the oil delivery truck tank where under some circumstances it can also be pumped into the homeowner's oil tank.
  • Water may enter an outdoor oil storage tank from roof runoff (rain or melting snow) spillage onto or near the oil filler or vent line for an oil tank. I've seen this condition both at above ground tanks which were placed under the house eaves (right where roof spillage fell onto the tank) and also at buried tanks whose filler pipe was set flush with the ground.
Photograph of a half buried outdoor oil tank. Was this oil tank intended for this exposure? Was it intended for ground contact.

Problems Caused When Water Enters an Oil Storage Tank?

What happens when an oil tank is outdoors? Water can enter the oil storage tank where it causes possibly serious problems for the heating equipment.

Water in the fuel oil or simple exposure of the oil to cold temperatures can lead to loss of heat and resultant damage to a building by several means:

The photo shows an oil tank which is half buried outdoors under a deck. Was this tank intended for outdoor use at all? If so, was it intended for use when in contact with the ground? Probably not. The risk is tank rusting, water entry, oil leaks, and related problems we've already listed.

  • In cold climates, water in the oil tank, which will reside at the bottom of the tank, may freeze in the tank or in the oil line, particularly for installations at which the oil line is attached to the bottom of the tank.

  • In warm, moderate, or cold climates water in the oil storage tank can cause rusting which is pulled into the heating equipment where it clogs the filter, fuel pump, or oil burner nozzle

  • In some modern high efficiency systems a special filter is used which will stop flow completely (such as the "System 2000" heating boiler), shutting down the burner in response to water or debris buildup in the filter - a move to protect the equipment.

  • In cold climates, heating oil in an outside oil tank supply line may "Jell" and stop flowing at cold temperatures.

  • Fire risk: Outside above ground oil storage tanks in cold climates exposed to jelling of the heating fuel may be (in error) fitted with a heating tape in an attempt to avoid freeze-up in the oil line itself. This is a potential fire hazard. Heat tapes should not be used on heating oil lines.


Photograph of a dual use outdoor oil tank with leaks at the oil lines.

Outdoor oil tanks in cold climates risk loss of heat from freezing water or jelling fuel as we just cited. In the photo shown here the oil lines are taken off of the top of the oil tank so as to avoid picking up water that may be present in the tank, avoiding the icing problem.

Note that no heat tapes are in use on the oil lines (good, that reduces a fire risk). It looks as if there has been some seepage around these oil lines, that the tank is old, and that one tank is being used to serve two oil-fired devices (two sets of oil lines leaving the tank).

Water in oil tanks also often leads to internal corrosion and leaks in the tank itself, regardless of the tank location, though buried tanks and indoor oil tanks are less prone to water accumulation due to in-tank condensation in response to temperature changes than a tank located above ground outside. Oil storage tanks usually fail from rust perforation due to combination of water inside the tank with sulphur in the fuel oil. External rust, unless very heavy, isn't highly correlated with internal rust. A new tank, when required, may cost more $2000. installed, including removal of the old oil tank.

When an outdoor tank is exposed to these conditions and even for an indoor tank which we suspect has had a dose of water and sludge, we recommend regular use of a fuel oil additive such as 4 in 1 Hot(TM) to absorb water and to help break up sludge. The best solution is to locate the tank indoors or to build a heated shelter over the outdoor tank.

Heating or Fuel Oil Additives for Outdoor Oil Tanks

In cold climates, heating or fuel oil additives for above-ground outdoor oil tanks can help prevent loss of heat by adding a pour point depressant which lowers the temperature at which the heating oil will form waxes or jell, and by adding a chemical, typically an alcohol, to remove [small amounts] of water from the oil. I've used a product called "4-in-One Hot" which contains both a sludge break-up chemical and alcohol to help remove water from the heating oil. Such additives may indeed help break up sludge which tends to clog old heating oil lines. But I'd cite two warnings about using heating oil additives and chemicals for outdoor oil tanks:

  1. No oil additive is going to remove a large quantity of water from an oil tank. Measure the amount of water present. If it's inches, your oil company can pump the water out (leaving the heating oil intact).

  2. Oil additives that break up sludge might in some circumstances precipitate frequent clogging of the oil filter installed at your heating boiler or furnace since an increased amount of debris is being freed and sent along the oil lines. If you find that your boiler stops working shortly after receiving an oil delivery, check to see if the problem was a clogged oil filter. That would suggest that your tank has a lot of debris and that the debris or sludge were being stirred up whenever oil was delivered. Discuss this concern with your heating service contractor.

Pour point depressants for heating oil tanks are about the same as similar products used by owners of diesel fuel powered automobiles and trucks in cold climates, but except in dire emergency I would not recommend substituting one for the other as there are some differences in these fuels and chemicals.

Note: these tips are not a complete oil tank installation guide. Proper installation must be done by trained service technicians and must comply with local building codes.

See HEATING OIL CLOUD WAX GEL POINT for details about heating oil waxing or jelling.

Questions & Answers regarding this article

.

Ask a Question or Search InspectAPedia

HTML Comment Box is loading comments...

Share this Article      

...

Technical Reviewers & References

  • InspectAPedia.com® - Daniel Friedman - Publisher & Editor.
  • InspectAPedia Bookstore lists recommended books, organized by topic & available for purchase. Most of our articles also include a list of recommended books for the specific article topic as well as other references, and information sources.
  • Critique, contributions wanted: Contact Us to suggest corrections or additions to articles at this website, and if you wish, to receive online listing and credit as a contributor. Particular thanks are due to the many experts and also consumers who read and critique technical articles at InspectAPedia.com.
  • Additional technical contributors & reference sources for this article are listed below.

Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

ABOVE GROUND OIL TANK INSPECTIONS
  INSPECT VISIBLE OIL TANKS
  OIL FILL & VENT
  OIL TANK SUPPORT
  ABANDONED INDOORS
  ABOVE GROUND OUTDOOR OIL TANKS
  OIL TANK HISTORY REVIEW
  OIL TANK CHECKLIST
  ABOVEGROUND OUTDOORS

  • LEAK CAUSES various causes of oil tank leaks
    LEAK TESTING alternative ways to test oil tanks for leakage
    WATER in OIL TANKS how it gets there, how to get it out, what problems it causes
    TESTING COs who can test oil tanks for leaks or soil for evidence of oil leakage in the past
    OIL TANK CHECKLIST This oil company's checklist they give to their delivery drivers and which is then completed and passed on to homeowners summarizes the oil industry's views of leaky oil tank warnings.
  • Arlene Puentes, an ASHI home inspector in Kingston, NY, contributed the example photograph of an outdoor aboveground oil tank. Ms. Puentes can be contacted at ap@octoberhome.com
  • Thanks to Alan Carson and Bob Dunlop, Carson Dunlop, Associates, Toronto, for permission to use illustrations from their publication, The Illustrated Home which illustrates construction details and building components. Carson Dunlop provides home inspection education, publications, report writing materials, and home inspection services. Alan Carson is a past president of ASHI, the American Society of Home Inspectors